INSTALLER MENU
To prevent changes that may aect system performance, this thermostat has an INSTALLER’S
MENU and a USER MENU. The INSTALLER’S MENU provides access to every option, while the
USER MENU provides access to items that will not aect system performance. To access the
INSTALLER’S MENU press the Menu button for 8 seconds. The display will show item 30 in the
table below. Use Next and Back to navigate through menu items. Press or to change a
menu setting.
Installer’s Menu #
(Hold Menu 8 Seconds)
Description
Default Setting
(ashing icons)
Settings
(Press or )
30
Heat Cycle Rate (how often
the heat will turn on)
MEd
SLO – slow
MEd – medium
FAS – fast
32
Aux Cycle Rate (how often the
auxiliary heat will turn on)
MEd
SLO – slow
MEd – medium
FAS – fast
35
Cool Cycle Rate (how often
the cooling will turn on)
MEd
SLO – slow
MEd – medium
FAS – fast
50
Compressor Lockout
(protects the compressor
from short cycling)
OFF
On5 minute delay
OFF – no delay
60
Duel Fuel Logic (turn On when using
gas as the auxiliary heat source)
OFF
On- gas auxiliary heat
OFF- electric auxiliary heat
65
Maximum Heat Limit
(maximum set point for heat mode)
99 47 to 99
66
Minimum Cool Limit
(minimum set point for cool mode)
45 45 to 97
74
Schedule Type (set as either 7-Day,
5-1-1 Day or Non-Programmable)
5
7 – 7 Day
5 – 5-1-1 Day
0 – Non Programmable
76
Early Start (starts heating or
cooling early so your programmed
temperature is reached by the
programmed time)
OFF
On – start early
OFF – start at program
period time
(Installer Menu continued on next page)
1.) W2/E Jumper Wire
This thermostat electrically connect the W2 and E terminals so that you do not need to do
this with a jumper wire. If your system has separate W2 and E wires, clip the W2/E jumper
located on the back of the thermostat. This will isolate both terminals so they can be used
independently.
2.) O/B Terminal Switch
The O/B switch on this thermostat is factory set to the O position. This will accommodate
the majority of heat pump applications, which require the changeover relay to be
energized in Cool. If the heat pump being installed requires a B terminal to energize the
changeover relay in Heat, the O/B switch must be moved to the B position.
Baery Locaon
Premium AA alkaline batteries
are required when C-wire is
not available. When C-wire is
available, the batteries provide
a back-up source of power (this
will maintain the clock in the
event of a power outage).
1
2
4
CAUTION
!
To prevent compressor and/or property damage, if the outdoor temperature is below 50°F,
DO NOT operate the cooling system.
Do not allow the compressor to run unless the compressor oil heaters have been operational
for 6 hours and the system has not been operational for at least 5 minutes.
TEST EQUIPMENT
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
1.) Move fan switch to On position. The blower should begin to operate.
2.) Move fan switch to Auto position. The blower should stop immediately.
Heating System
1.) Move System Switch to Heat position. If the auxiliary heating system has a standing
pilot, be sure to light it.
2.) Press to adjust thermostat setting to above room temperature. The heat pump
system should begin to operate and the thermostat will indicate Heat On.
3.) Press to adjust thermostat setting to 3° above room temperature. The auxiliary heat
should begin to operate and the thermostat will indicate Heat On Auxiliary.
4.) Press to adjust thermostat setting below room temperature. The heating system
should stop operating and the thermostat should indicate Heat.
Auxiliary System
1.) Move System Switch to Aux position. If the auxiliary heating system has a standing pilot,
be sure to light it.
2.) Press to adjust thermostat setting to above room temperature. The auxiliary heating
system should begin to operate and the thermostat will indicate Heat On Auxiliary.
3.) Press to adjust thermostat setting below room temperature. The auxiliary heating
system should stop operating and the thermostat should indicate Heat Auxiliary.
Cooling System
1.) Move System Switch to Cool position.
2.) Press to adjust thermostat setting below room temperature. The blower should
come on immediately on high speed, followed by cold air circulation. The thermostat will
indicate Cool On. There can be up to a 5 minute delay. (see INSTALLER MENU, item 50)
3.) Press to adjust thermostat setting to above room temperature. The cooling system
should stop operating and the thermostat will indicate Cool.
Note: If Starting Soon is shown on the display, the compressor lockout feature is operating.
There will be up to a 5 minute delay before the compressor turns on.(see INSTALLER MENU,
item 50)
Installer’s Menu #
(Hold Menu 8 Seconds)
Description
Default Setting
(ashing icons)
Settings
(Press or )
79
Fahrenheit or Celsius °F
°F – Fahrenheit
°C – Celsius
81
Temperature Display Adjustment
(adjust the displayed “Room
Temperature”)
0 -5 to +5
83
Continuous Display Light (keep
the backlight always on – “C” wire
required)
OFF
On – always on
OFF – momentarily
86
Change Air Filter (set up a monthly
reminder)
OFF
1 to 12 reminder time
(months)
OFF – no lter reminder
99
Keypad Lock (prevent unwanted
changes to the thermostat)
OFF
On – disable buttons
OFF – all buttons are active
INSTALLER MENU (C0ntinued)