Loading ...
Loading ...
Loading ...
39
ENGLISH
ARUM***CTE5
DIP switch
7 Segment
SW01C
(Automatic Addressing Setting)
Quick control Setting
In the factory setting, main PCB DIP switch setting is all “OFF”.
- Check and make sure that all the indoor unit model name are
ARNU******4.
- Change the main PCB DIP switch No. 3 “OFF ON” like below
picture.
- Push the reset button.
ARUM***B(D)TE5
7 segmentDIP Switch
Reset button
DIP switch
7-Segment
Reset button
• Initial display order
• Example) ARUM480BTE5
48 HP 208/230 V Heat Recovery system
(Master unit: 22 HP, Slave 1: 14 HP, Slave 2: 12 HP)
Order HP(Ton) Mean
8(6)~24(20) Master unit capacity
26(22)~44(36) Slave 1 unit capacity
46(38)~52(42) Slave 2 unit capacity
8(6)~52(42) Total capacity
3 Heat Recovery (Factory Setting)
46 460 V model
57 575 V model
22 208/230 V model
30 Full function
22 14 12 48 3 22 1
HP 8 10 12 14 18 20 22 24
TON 6 8 10 12 14 16 18 20
• Master Unit
h Heat Pump installation
Turn on the DIP s/w No 4.
The factory setting display is appeared “HR”.
Change “HR” into “HP” display pushing button and then push
confirm button.
Turn off the DIP s/w No 4. and Push reset button to restart the
system. (If you turn on the DIP s/w No 4, you can make sure “HR”
or “HP” display later.)
• Slave Unit
DIP switch
setting
ODU Setting
Slave 1
Slave 2
DIP switch
setting
ODU Setting
Heat Recovery
System (Factory
Setting)
DIP switch
setting
ODU Setting
Setting Heat pump
system or Heat Recovery
system (Installer Setting)
ARUM***CTE5
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 39
Loading ...
Loading ...
Loading ...