LG Electronics ARWB096DA2

User Manual - Page 8

For ARWB096DA2.

PDF File Manual, 89 pages, Download pdf file

Loading ...
Loading ...
Loading ...
Outside units Information
Power Supply: Outside Unit (3Ø, 208/230V, 60Hz)
n Heat Recovery
• Ratio of the running Indoor Units to the Outside: Within 10 ~ 100%
• A combination operation over 100% cause to reduce each indoor unit capacity.
n Combination Ration(Minimum : 50%)
Notes:
* We can guarantee the operation only within 130% Combination.
System Capacity HP(Ton)
Model Name
Product Refrigerant Charge lb(kg)
CF(Correction Factor) lb(kg)
Maximum Connectable No. of Indoor Units
Net Weight lb
kg
Dimension(W×H×D) inch
mm
Refrigerant Liquid inch(mm)
Connecting Low Pressure Gas inch(mm)
Pipes High Pressure Gas inch(mm)
Water Inlet mm
Connecting Outlet mm
Pipes Drain Outlet inch(mm)
8(6.5) 16(12.5) 24(19.0)
ARWB072BA2 ARWB144BA2 ARWB216BA2
16.1(7.3) 19.4(8.8) 19.4(8.8) + 16.1(7.3)
3.3(1.5) 6.6(3.0) 9.9(4.5)
16 32 49
(339.5)×1 (491.6)×1 (491.6)×1 + (339.5)×1
(154)×1 (223)×1 (223)×1+(154)×1
(30-13/32×44-3/32×21-1/2)×1 (30-13/32×44-3/32×21-1/2)×1 (30-13/32×44-3/32×21-1/2)×2
(772×1,120×547)×1 (772×1,120×547)×1 (772×1,120×547)×2
3/8(9.52) 1/2(12.7) 3/4(19.05)
7/8(22.2) 1-1/8(28.58) 1-3/8(34.9)
3/4(19.05) 7/8(22.2) 1-1/8(28.58)
PT32A (Female) PT40A (Female) PT40A + PT32A (Female)
PT32A (Female) PT40A (Female) PT40A + PT32A (Female)
3/4(22) (Female) 3/4(22) (Female) 3/4(22) (Female)
Outside units Information
8 Outside Unit
Number of outside units
Connection Capacity
3Ø, 208/230V, 60Hz 3Ø, 480V, 60Hz
Single outside unit 130% 130%
Double outside units 130% 130%
Triple outside units 130% 130%
Loading ...
Loading ...
Loading ...