26 New Wide Wired Remote Controller Owner’s & Installation Manual 27
ENGLISH
Installation instructionInstallation instruction
Installer Setting - Option Function Setting
Function Code Existing condition
Select existing condition
of each mode by pressing
button.
(00: not installed,
01 : installed)
3
Press button to save.
4
If pressing button long for 3
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
1
If pressing button repeatedly, it moves to
the selected option function code as picture
below.
2
Pressing button will exit settings mode.
❈ After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈ When exiting without pressing set button,
the manipulated value is not reflected.
5
Function
Plasma purification
Electric heater
Humidifier
Elevation grill
Ventilation kit
Auxiliary heater
Code
20
21
22
23
24
25
Setting feature for indoor unit when air cleaning / heater / humidifier / Up/down grill / Ventilation KIT
/Auxiliary Heater is newly installed, or installed unit is removed.
Move to Low Ambient Heating Operation
setting by pressing button.
4
Press button to setup Low
Ambient Heating Operation.
5
Press button to save.
8
Press button to exit or
system will automatically exit
after 25 seconds without any
input.
9
Move FAN Speed Setting during
Emergency Heater Operation by pressing
button.
6
Press button to setup FAN
Speed during Emergency Heater
Operation.
7
0 : not use
1 : use - compressor off(0℉/ -18℃) / compressor on(5℉ / -15℃)
2 : use - compressor off(5℉ / -15℃) / compressor on(10℉ / -12℃)
3 : use - compressor off(10℉/ -12℃) / compressor on(15℉ / -9℃)
0 : fan off
1 : fan on
ƓEmergency heater operation in Low Ambient temperature
- compressor off : Emergency heater enabled
- compressor on : Emergency heater disabled