Mitsubishi SEZKD12NA4 Heat Pump

User Manual - Page 4

For SEZKD12NA4.

PDF File Manual, 25 pages, Read Online | Download pdf file

SEZKD12NA4 photo
Loading ...
Loading ...
Loading ...
4
6.5
B
J
O
N
F
Max. 300 mm [11-13/16 in]
[Fig. 6-10]
Correct piping
Wrong piping
A Insulation (9 mm [3/8 in] or more)
B Downward slope (1/100 or more)
C Support metal
K Air bleeder
L Raised
M Odor trap
Grouped piping
D O. D. ø32 mm [1-1/4 in] PVC TUBE
E Make it as large as possible. About 10 cm [3-15/16 in].
F Indoor unit
G Make the piping size large for grouped piping.
H Downward slope (1/100 or more)
I O. D. ø38 mm [1-1/2 in] PVC TUBE for grouped piping.
(9 mm [3/8 in] or more insulation)
J Up to 550 mm [21-21/32 in]
N Drain hose (accessory)
O Horizontal or slightly upward
[Fig.6-11]
C
B
A
L
D
D
D
E
K
M
B
H
I
Max. 20m [65 ft]
1.5-2 m [5 to 7 ft]
G
F
FF
B
C
DE E
H
G
K
J
F
I
A
25 [1] 25 [1]
35
[1-13/32]
A Indoor unit
B Pipe cover (60 mm [3/8 in]) (accessory)
C Tie band (accessory)
D Visible part
E Insertion margin
F Drain hose (accessory)
G Drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE, field supplied)
H Insulating material (field supplied)
I Tie band (accessory)
J Max.180 ± 5 mm [7-3/32 ± 7/32 in]
K No gap. The joint section of the insulation material must meet at the top.
(Unit: mm [in])
[Fig. 6-13]
6.6
A
B
F
C
D
E
A Insert pump's end 2 to 4 cm [13/16 to 1-19/32 in].
B Remove the water supply port.
C About 2 liters
D Water
E Filling port
F Screw
[Fig. 6-14]
<Indoor board>
SWE
[Fig.6-12]
A Indoor unit
B Pipe cover (30 mm [3/16 in]) (accessory)
C Tie band (accessory)
D Band fixing part
E Insertion margin
F Drain hose (accessory)
G Drain pipe (O.D. ø32 PVC TUBE, field supplied)