Exhaust air pipe
1 Air outlet to outdoors 2 Air outlet via an air shaft
The exhaust air line should be as short and straight as possible.
To avoid excessive noise or a reduced extraction capacity the diameter of the
exhaust air pipeline should not be less than 150 mm.
Use or form only large radius bends. Small radius bends reduce the extraction
capacity of the hood.
Use only smooth pipelines or  exible hoses of non- ammable materials for the
exhaust air pipeline
If the exhaust air pipeline is horizontally routed, there must be a minimum gradient
of 1 cm per metre or an inclination angle of 2°. (Fig. C) Otherwise condensation
water could run into the extractor hood motor.
If the exhaust air is directed into an exhaust air duct, the end of the entry tting must
be directed in the direction of  ow.
If the exhaust air pipeline is routed though cool rooms, loft s etc. there can be
a large temperature drop within the individual parts of the pipeline, resulting in
sweating or condensation water production. This renders outlet pipeline insulation
necessary.
In some cases a condensation water barrier must be installed in addition to
adequate insulation.