R600 and HSRL Series LP-Gas Regulators
3
TYPE
TYPICAL SETPOINT
NOMINAL RELIEF VALVE
START-TO-DISCHARGE
MAXIMUM INLET PRESSURE TO NOT EXCEED OUTLET
PRESSURE WITH DISC REMOVED
Inlet Pressure Maximum Outlet Pressure
psig bar psig bar psig bar psig bar
HSRL
11 inches w.c. 27 mbar 1 69 mbar
15 1.0
2 0.14
R622 and R642
50 3.4
R652
R632A
(1)
250 17.2
R632E
(1)
2 0.14 3.5 0.24
250 17.2
5 0.34R622E
50 3.4
R652E
R622H 10 0.69 20 1.37 Not Applicable
1. For integral two-stage regulators, the second stage disc is removed.
Table 1. Relief Valve Specifications
Figure 2. Regulator with Vent Pointed Down
3
3 FEET /
0.91 meter
VENT POINTED DOWN
Integral Two-stage Regulator
The Type R632A integral two-stage regulator contains
a non-adjustable  rst stage regulator on the inlet. The
second stage provides 11-inches w.c. / 27 mbar outlet
pressure. The second stage portion has a high capacity
internal relief valve construction. The  rst stage does not
have an internal relief valve. The regulators are normally
painted GRAY with a BLACK CAP.
Integral Two psig Service Regulator
The Type R632E integral two psig service regulator
contains a non-adjustable  rst stage regulator on the
inlet. The second stage provides 2 psig / 0.14 bar
outlet pressure. The second stage portion has a high
capacity internal relief valve construction. The  rst stage
does not have an internal relief valve. The regulators
are normally painted GRAY with a WHITE CAP and
White 2-psig STICKER.
Installation
WARNING
!
All vents should be kept open to permit
free  ow of air in and out of the regulator.
Protect vent openings against the entrance
of rain, snow, ice formation, paint, mud,
insects, or any other foreign material that
could plug the vent or vent line.
LP-Gas may discharge to the atmosphere
through the vent. An obstructed vent
which limits air or gas  ow can cause
abnormally high pressure that could
result in personal injury or property
damage. Failure to use a vent line on
Indoor Installations can cause a hazardous
accumulation of gas which could result in
personal injury or property damage.
Never use a Type R622H, R622E, R632E,
or R652E (pounds-to-pounds) regulator
on low pressure (inches of water column)
service because personal injury or
property damage could occur. The
Types R622E and R652E are not suitable
for use as a “ rst stage” regulator.
General Installation Instructions
Before installing the regulator,
Check for damage, which might have occurred
in shipment.
Check for and remove any dirt or foreign material,
which may have accumulated in the regulator body.
T14446-A2