GE - General Electric RAK148F2 Two Fan Speed Digital Remote Thermostat

User Manual - Page 2

For RAK148F2.

PDF File Manual, 16 pages, Read Online | Download pdf file

RAK148F2 photo
Loading ...
2
Specifications.
WARNING
FIRE AND SHOCK HAZARD
Always turn off power at the main power supply
before installing, cleaning or removing the
thermostat. Failure to do so could result in
electrical shock hazard.
Do not use on voltages over 30 VAC. Higher
voltages will damage the thermostat and could cause
shock or fire hazard.
NOTICE
All wiring must conform to local and national
electrical and building codes.
Use this thermostat only as described in this
manual.
Electrical rating: 24 VAC (18–30 VAC)
1 amp maximum per terminal
4 amp maximum total load
Operating temperature range: 40°F–99°F (4°C–37°C)
Temperature set range: 60°F–85°F (15°C–29°C)
Accuracy: ± 1°F (± 0.5°C)
System configurations:
RAK148F2: 2-stage heat (heat pump/resistance heat), 1-stage
cool, 2-speed fan
RAK164F2: 1-stage heat (resistance heat), 1-stage cool,
2-speed fan
Terminations: R, C, W, Y, GH, GL, B (RAK148F2);
R, C, W, Y, GH, GL (RAK164F2)
Wiring:
Maximum wiring length is 66ft (20 meters) for
AWG18
Maximum wiring length is 60ft (18 meters) for
AWG20
IMPORTANT SAFETY INFORMATION