User Manual Braeburn 229150 Digital Humidistat 24 VAC

Documents for Braeburn 229150

The following documents are available:
User Manual Specification
  • 229150 Specifications - (English) Download
Other Documents
  • Humidification Catalog - (English) Download
  • Humidification Tri-Fold - (English) Download
  • Humidification Counter Mat Insert - (English) Download
Photos
229150 photo
BASE WITH VENTS
(FOR WALL MOUNT)
MOUNTING
HOLES (2)
PUSH BASE
INTO 1”
HOLE IN
WALL
OPENING
FOR WIRES
VENTS
WALL
DUCT
MOUNTING
HOLES (2)
PLACE BASE
OVER 1”
HOLE IN
DUCT
OPENING
FOR WIRES
BASE WITHOUT VENTS
(FOR DUCT MOUNT)
NO
VENTS
229150
PRECAUTIONS
This Humidistat must be installed by a Qualified Technician. Always turn off power to the HVAC
system prior to installing or servicing the humidifier or humidistat. Improper operation can
result in over or under humidification. Over humidification can result in condensation, structural
damage or mold. Condensation within a building’s structure can cause a loss of structural
strength. Condensation can also enable mold and mildew growth resulting in personal injury
and damage to building structure and contents. Older and poorly insulated structures cannot
withstand the same humidity levels as newer well insulated buildings. Read these instructions
carefully. This humidistat requires a 24 volt, AC power supply. Improper voltage can cause
malfunction or damage to the control. The technical specifications for this product and the
contents of the user manual are subject to change without notice.
Before Installing or Operating,
PLEASE READ ALL INSTRUCTIONS
Specifications
Electrical Rating 18-30 VAC, 60Hz
Switching Load 1 amp max.
Outdoor Sensor 200 ft. max.
Auto Mode
Control Range 10%-60% RH
Manual Mode
Control Range 10%-75% RH
Automatic
Digital Humidistat
In Automatic Mode, the Braeburn 229150 Digital Humidistat
will adjust humidity based on the outdoor temperature,
lowering the humidity in cold weather to reduce
condensation. The humidistat can operate in Manual Mode
to control humidity to a specific relative Humidity. In most
dwellings, Automatic operation is preferred to reduce
condensation on windows and within the structure.
Manual mode is necessary where the outdoor temperature
sensor cannot be installed. Manual mode may be desirable where valuable artwork, instruments
or woodwork demand constant humidity. The LCD Display is backlit and easy to read. The
humidistat can be mounted on an interior wall or on the return duct of the HVAC System.
Outdoor Temp. -10˚F, (-23˚C) min
Accuracy RH 10%-90% +3% RH
Accuracy Indoor Temp. +1˚F, +1˚C
Accuracy Outdoor Temp. +1˚F, +1˚C
Resolution 1˚ or 1%
Duct Mount Installation
IMPORTANT: Use base without vents for
duct mount installation.
1. Choose an accessible location on the
main RETURN air duct at least 15 inches
from any duct bends.
2. Drill a 1 inch diameter hole in the center
of your desired mounting location.
3. Using the base as a template, mark
two mounting holes and rectangular
opening (for wires).
4. Using a 1/8 inch drill bit, drill two
mounting holes. Cut or drill out
rectangular opening for wires.
5. Secure base to the duct with supplied
sheet metal screws. Pull wires
through opening.
6. Connect wires (see “wiring”) and then
attach humidistat body to base.
Wall Mount Installation
IMPORTANT: Use base with vents for
wall mount installation.
1. Choose a location in the living area
that is clear of drafts or excessive
amounts of humidity. Avoid mounting
near air ducts, doors or windows.
Do not install in bathrooms or kitchens.
2. Drill a 1 inch diameter hole in the center
of your desired mounting location.
3. Using base as a template, mark the
two mounting holes and rectangular
opening (for wires).
4. Using a 3/8 inch drill bit, drill two
mounting holes and gently tap in
supplied anchors. Cut or drill out
rectangular opening for wires.
5. Secure base to the wall with supplied
plastic anchors and screws. Pull wires
through opening.
6. Connect wires (see “wiring”) and then
attach humidistat body to base.
Wiring
WIRING TO FAN POWER HUMIDIFIER
Remote Sensor Installation
IMPORTANT: Keep remote sensor wires at
least 6 inches from line voltage wires.
1. If installing the optional outdoor remote
sensor, choose a location on the north or
east wall of the structure. Install above
the snow line away from air intakes or
exhaust sources.
2. Run two wire (22 gauge minimum) cable
from the humidistat SNSR1 and SNSR2
terminals to the outdoor location. Attach
wire to sensor regardless of polarity. Wire run should not exceed 200 ft.
3. Install the metal hanging bracket with the screws provided. Insert sensor into large
opening of bracket and sensor wire into small opening of bracket.
4. Use non-hardening caulk to plug any wiring holes after verifying operation of sensor.
DROP Button: Scrolls through Manual, Automatic and Off modes
THERMOMETER Button: Scrolls through indoor humidity (default), indoor temperature
and outdoor temperature (if outdoor sensor is connected).
F˚ / C˚ F˚ / C Button: Used to select Fahrenheit or Celsius display mode.
DOWN and UP Buttons: Use to adjust settings up or down.
Buttons: Press the DOWN and UP buttons at the same time to enter OFFSET mode
(see”OFFSET”).
+
+
Buttons: Press the DROP and THERMOMETER buttons at the same time for 5 seconds.
The humidistat will enter the TEST mode. (see “Testing the System”)
Quick Reference
“House” Symbol: Indoor temperature indicator.
“Tree” Symbol: Outdoor temperature indicator.
“Bar” Symbol: Humidity index indicator (Automatic Mode Only).
SNSR
1
SNSR 2
HUM1
HUM
2
AC
N
AC L
Constant
24 Volts
Yellow
Yellow
120 Volts
Switched
w/Furnace
Operation
SNSR 1
SNSR
2
HUM1
HUM2
AC N
AC L
Constant
24 Volts
Outdoor Sensor
24 Volts
Switched
w/Furnace
Operation
WIRING TO 24 VAC HUMIDIFIER