4
IMPORTANT Please Read and Follow!
A GFI shall be used if required by NFPA-70 (National Electric Code), federal/state/local laws, or local
ordinances.
The required use of a GFI is normally related to the location of a receptacle with respect to
any signi cant sources of water or moisture.
Viking Range, LLC will NOT warranty any problems resulting from GFI outlets which are not
installed properly or do not meet the requirements below.
If the use of a GFI is required, it should be:
Of the receptacle type (breaker type or portable type NOT recommended)
Used with permanent wiring only (temporary or portable wiring NOT recommended)
On a dedicated circuit (no other receptacles, switches or loads in the circuit)
Connected to a standard breaker of appropriate size (GFI breaker of the same size NOT
recommended)
Rated for Class A (5 mA +/- 1 mA trip current) as per UL 943 standard)
In good condition and free from any loose- tting gaskets (if applicable in outdoor situations)
Protected from moisture (water, steam, high humidity) as much as reasonably possible