VERTICAL DISCHARGE
(WP28M, WP29M, IP29M)
HORIZONTAL DISCHARGE
(WP28M & WP29M only)
INSTALLATION
1. Run power cable to installation location. Remove one knock-
out from rough-in plate wiring box.
BLACK TO BLACK
WHITE TO WHITE
GROUND WIRE
TO GROUND
SCREW
ROUGH-IN PLATE
2. Attach ROUGH-IN PLATE to MOUNTING STUDS at inside,
top of hood with (4) existing #10-32 HEX NUTS.
REMOVE ONE
ELECTRICAL
KNOCKOUT
3. Remove wiring cover.
4. Connect cable to wiring box using proper connector. Connect
BLACK TO BLACK (hot), WHITE TO WHITE (neutral) and
GREEN OR BARE WIRE (ground) under second ground
screw. Replace wiring cover.
5. Run 10” round steel duct to installation location.
6. Install 10” damper (Model 421, included) inside the vertical
ductwork that will be attached to the rough-in plate. Do not
install in a horizontal ductwork or directly on top of the adapter
or it will not open and close properly.
Remove shipping tape if present. Secure the damper to the
duct with 3 - #8 sheet metal screws (not provided). Ensure
the damper opens and closes freely. Seal all joints with metal
foil duct tape to eliminate air leaks.
NOTE: To optimize airflow and reduce noise, position the
damper at least 17” above the top of the rough-in plate - or
as far as the duct run will allow.
17” MIN.
MODEL 421
10-IN. DAMPER
(INCLUDED)