Mitsubishi MUYGL15NA-U1 M-Series 14,000 BTU Single Zone Outdoor Cooling Unit MUYGL15NA

Service Manual - Page 26

For MUYGL15NA-U1. Series: M-Series
Also, The document are for others Mitsubishi models: MUZ-GL09NA, MUZ-GL09NAH, MUY-GL09NA, MUZ-GL12NA, MUZ-GL12NAH, MUY-GL12NA, MUZ-GL15NA, MUZ-GL15NAH, MUY-GL15NA, MUZ-GL18NA, MUZ-GL18NAH, MUY-GL18NA, MUZ-GL24NA, MUZ-GL24NAH, MUY-GL24NA

PDF File Manual, 76 pages, Read Online | Download pdf file

MUYGL15NA-U1 photo
Loading ...
Loading ...
Loading ...
26
4) HEATING CAPACITY (MUZ)
Model
Indoor air
Outdoor intake air WB temperature (˚F)
IDB (˚F)
5 15 25 35 43 45 55
TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
MUZ-GL09NA
75 4.8 0.42 6.3 0.54 7.9 0.63 9.4 0.70 10.6 0.74 11.0 0.75 12.4 0.78
70 5.2 0.41 6.7 0.52 8.2 0.62 9.6 0.68 10.9 0.72 11.2 0.73 12.7 0.76
65 5.5 0.39 6.9 0.50 8.6 0.59 10.0 0.67 11.2 0.70 11.6 0.71 13.0 0.75
MUZ-GL09NAH
75 4.8 0.55 6.3 0.67 7.9 0.76 9.4 0.70 10.6 0.74 11.0 0.75 12.4 0.78
70 5.2 0.54 6.7 0.65 8.2 0.75 9.6 0.68 10.9 0.72 11.2 0.73 12.7 0.76
65 5.5 0.52 6.9 0.63 8.6 0.72 10.0 0.67 11.2 0.70 11.6 0.71 13.0 0.75
MUZ-GL12NA
75 6.3 0.65 8.4 0.82 10.4 0.96 12.5 1.07 14.0 1.13 14.5 1.14 16.4 1.19
70 6.8 0.62 8.9 0.79 10.8 0.94 12.7 1.05 14.4 1.10 14.8 1.12 16.8 1.17
65 7.2 0.59 9.1 0.76 11.3 0.91 13.2 1.02 14.8 1.07 15.3 1.09 17.1 1.14
MUZ-GL12NAH
75 6.3 0.78 8.4 0.95 10.4 1.09 12.5 1.07 14.0 1.13 14.5 1.14 16.4 1.19
70 6.8 0.75 8.9 0.92 10.8 1.07 12.7 1.05 14.4 1.10 14.8 1.12 16.8 1.17
65 7.2 0.72 9.1 0.89 11.3 1.04 13.2 1.02 14.8 1.07 15.3 1.09 17.1 1.14
MUZ-GL15NA
75 7.9 0.94 10.4 1.19 13.1 1.40 15.6 1.56 17.6 1.64 18.1 1.66 20.5 1.73
70 8.6 0.90 11.1 1.15 13.5 1.37 15.9 1.52 18.0 1.60 18.5 1.63 21.0 1.70
65 9.0 0.86 11.3 1.10 14.1 1.32 16.5 1.48 18.5 1.56 19.1 1.58 21.4 1.66
MUZ-GL15NAH
75 7.9 1.07 10.4 1.32 13.1 1.53 15.6 1.56 17.6 1.64 18.1 1.66 20.5 1.73
70 8.6 1.03 11.1 1.28 13.5 1.50 15.9 1.52 18.0 1.60 18.5 1.63 21.0 1.70
65 9.0 0.99 11.3 1.23 14.1 1.45 16.5 1.48 18.5 1.56 19.1 1.58 21.4 1.66
MUZ-GL18NA
75 9.5 0.99 12.5 1.25 15.7 1.47 18.7 1.64 21.1 1.72 21.7 1.75 24.6 1.81
70 10.3 0.95 13.3 1.21 16.2 1.44 19.1 1.60 21.6 1.68 22.2 1.71 25.2 1.78
65 10.8 0.91 13.6 1.16 17.0 1.39 19.8 1.55 22.2 1.64 22.9 1.66 25.7 1.75
MUZ-GL18NAH
75 9.5 1.12 12.5 1.38 15.7 1.60 18.7 1.64 21.1 1.72 21.7 1.75 24.6 1.81
70 10.3 1.08 13.3 1.34 16.2 1.57 19.1 1.60 21.6 1.68 22.2 1.71 25.2 1.78
65 10.8 1.04 13.6 1.29 17.0 1.52 19.8 1.55 22.2 1.64 22.9 1.66 25.7 1.75
MUZ-GL24NA
75 12.1 1.38 16.0 1.74 20.0 2.05 23.9 2.28 26.9 2.40 27.7 2.43 31.5 2.53
70 13.1 1.32 17.0 1.68 20.7 2.00 24.4 2.22 27.6 2.34 28.4 2.39 32.2 2.48
65 13.8 1.26 17.4 1.61 21.7 1.93 25.3 2.16 28.4 2.28 29.3 2.32 32.8 2.43
MUZ-GL24NAH
75 12.1 1.38 16.0 1.74 20.0 2.05 23.9 2.28 26.9 2.40 27.7 2.43 31.5 2.53
70 13.1 1.32 17.0 1.68 20.7 2.00 24.4 2.22 27.6 2.34 28.4 2.39 32.2 2.48
65 13.8 1.26 17.4 1.61 21.7 1.93 25.3 2.16 28.4 2.28 29.3 2.32 32.8 2.43
NOTE: 1. IDB : Intake air dry-bulb temperature
TC : Total Capacity (x10
3
Btu/h) TPC : Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL
mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch or press any button on the remote con-
troller.
OBH733J
Loading ...
Loading ...