BUILT-IN, RECESSED, CLOSET AND ALCOVE
INSTALLATION
The Dryer may be installed in a built-in, recessed area, closet
or alcove.
The installation spacing is in inches and is the minimum
acceptable.
Other installation must use the minimum dimensions
indicated.
Minimum clearance between dryer cabinet and adjacent
walls are: 2" either side and 3" front and rear.
Minimum vertical space from floor to overhead cabinets,
etc. is 52" (132 cm).
Closet door must be louvered or otherwise ventilated and
must contain a minimum of 60 sq.in. of open area equally
distributed. If closet contains both a washer and a dryer,
doors must contain a minimum of 120 sq.in. of open area
equally distributed.
No other fuel-burning appliance shall be installed in the
same closet with the dryer.
Additional clearances for wall, door and floor moulding
may be required.
Additional space is needed when an external exhaust
elbow is used.
NOTE: If a door is installed that potentially encloses the unit
while running, the door must allow for a minimum of 20 square
inches of free air movement. There must also be a 1" additional
space in front of the unit to the closed door and 1" from back of
the unit to the wall. Additional spacing should be considered for
easy installation, servicing, and compliance with all applicable
local, state, and federal codes.