Goodman CAPFA6030D3 CAPFA AlumaFin7 Coil 5 Ton R-32 Upflow/Downflow 24.5" Cabinet

Product's Documents

Below are documents related to this product, you can read online or download:
Installation Instruction Specification Other Documents
CAPFA6030D3 photo

Installation Manual

This is the main product document for model CAPFA6030D3. Additionally, the document applies to other Goodman models: CAPFA6030D3

The file format is pdf, 16 pages, you can download this manual here .

background
UPFLOW/DOWNFLOW
COILS INSTALLATION INSTRUCTIONS
1. Important Safety Instructions
The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards. It is
the owner’s and installer’s responsibility to read and comply
with all safety information and instructions accompanying
these symbols. Failure to heed safety information increases
the risk of personal injury, property damage, and/or product
damage.
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or
installing this unit. Multiple power sources
may be present. Failure to do so may cause
property damage, personal injury or death.
Only personnel that have been trained to install, adjust,
service, maintenance or repair (hereinafter, “service”)
the equipment specified in this manual should service the
equipment.
This equipment is not intended for use by persons
(including children) with reduced physical, sensory or
mental capacities, or lack of experience and knowledge,
unless they have been given supervision or instruction
concerning use of the appliance by a person responsible
for their safety.
Children should be supervised to ensure that they do not
play with the equipment.
The manufacturer will not be responsible for any injury
or property damage arising from improper supervision,
service or service procedures. If you service this unit, you
assume responsibility for any injury or property damage
which may result. In addition, in jurisdictions that require
one or more licenses to service the equipment specified in
this manual, only licensed personnel should service the
equipment. Improper supervision, installation, adjustment,
servicing, maintenance or repair of the equipment specified
in this manual, or attempting to install, adjust, service
or repair the equipment specified in this manual without
proper supervision or training may result in product
damage, property damage, personal injury or death.
WARNING
Do not bypass safety devices.
WARNING
If any hot work is to be conducted on the refrigerating
equipment or an associated parts, appropriate fire
extinguishing equipment shall be available on hand. Have
a dry powder or CO2 fire extinguisher adjacent to the
charging area.
Ensure that the area is in the open or that it is
adequately ventilated before breaking into the system
or conducting any hot work. A degree of ventilation
shall continue during the period that the work is carried
out. The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the
atmosphere.
WARNING
2. Shipping Inspection
This equipment is approved for use with R32 refrigerant
only. Upon receiving the product, inspect it for damage from
shipment. Shipping damage, and subsequent investigation
is the responsibility of the carrier. Verify the model number,
specications, and accessories are correct prior to
installation. The distributor or manufacturer will not accept
claims from dealers for transportation damage or installation
of incorrectly shipped units.
2.1 Handling
Use caution when transporting/carrying unit. Do not carry
unit with hooks or sharp object. The preferred method
of carrying the unit after arrival at the job site is to carry
by two-wheel hand truck from the back or sides or by
hand by carrying at the cabinet corners. Take proper
precautions when carrying unit to avoid any damage to
the piping.
3. Codes & Regulations
This product is designed and manufactured to comply with
national codes. The product shall be installed in accordance
with national wiring regulations. Installation in accordance
with such codes and/or prevailing local codes/regulations is
the responsibility of the installer. Compliance with national
gas regulations shall be observed. The manufacturer
assumes no responsibility for equipment installed in violation
of any codes or regulations.
The United States Environmental Protection Agency
(EPA) has issued various regulations regarding the
introduction and disposal of refrigerants. Failure to
follow these regulations may harm the environment and
19001 Kermier Rd., Waller, TX 77484
© 2023-2024 Daikin Comfort Technologies Manufacturing, L.P.
www.daikincomfort.com • www.goodmanmfg.com • www.amana-hac.com
IO-4012B
04/2024
® is a registered trademark of Maytag Corporation or its related companies and is used under
license. All rights reserved.
background
2
can lead to the imposition of substantial nes. Should
you have any questions please contact the local o󰀩ce of
the EPA.
4. Replacement Parts
Inspect the unit to verify all required components are present
and intact. Report any missing components immediately to
the manufacturer or to the distributor. Make sure to include
the full product model number and serial number when
reporting and/or obtaining service parts. Replacement parts
for this product are available through your contractor or
local distributor. For the location of your nearest distributor
consult the white business pages, the yellow page section of
the local telephone book or contact:
HOMEOWNER SUPPORT
DAIKIN COMFORT TECHNOLOGIES
MANUFACTURING, L.P.
19001 KERMIER ROAD
WALLER, TEXAS 77484
877-254-4729
5. Pre-Installation Instructions
The appliance shall be installed in accordance with national
wiring regulations. This product was tested at an external
static pressure of 0.66 WC. None of the components in this
product line are designed or approved to be suitable for
outdoor use.
Refrigerant lines must be routed depending on conguration
of unit to maintain the required 24” minimum clearance for
service.
The A2L Sensor must be installed and powered for service.
Ensure that the grommet is installed through the access
panel knockout hole. Sensor bracket assemblies are
shipped with two zip ties, one of which is designed for strain
relief. The zip tie shown in Figure 1, detail A, must be kept
attached to the sensor bracket assy. Detail B highlights the
zip tie that must be cut during installation in order to release
the wire bundle.
B
A
Figure 1 - Isometric view of sensor bracket assy (back view)
Follow routing diagram as shown in Figures 6 or 7 depending
on orientation of install. This wiring is intended to be passed
through the access hole on the furnace. If a hole must be
cut into the furnace, ensure that the wiring is well protected
from mechanical damage and that the hole is free from burrs
or sharp edges. Utilize a protective coating for all exposed
metallic edges.
This appliance is equipped with a leak detection sensor
which must be wired through the connector on the furnace
PCB or Non-A2L Furnace Integration Kit.
Scenario 1: Amana / Goodman / Daikin Furnace PCB with
R32 sensor compatibility.
Verify that the A2L function is enabled on the furnace board
PCB. Refer to the furnace IO for further instruction on
how to toggle this function from disabled to enabled. The
A2L verication step as described on the furnace IO must
be completed before the unit is commissioned. If the test
is not successful, call 1-855-DAIKIN1, option 3, for further
assistance.
Scenario 2: Amana / Goodman / Daikin Furnace or Modular
Blower PCB with no R32 sensor compatibility.
The leak detection sensor must be wired directly to the
Non-A2L Furnace Integration Kit and installed as a
pass-through to the non-A2L furnace control board. For
instructions on how to correctly wire the Non-A2L Furnace
Integration Kit refer to the kit IO.
Scenario 3: All other OEM Furnaces.
The availability of mitigation mode, or equivalent, must be
checked through the furnace model manufacturer IO. Please
follow relevant instructions to disable mitigation mode, or
equivalent. Once this step is complete follow instructions of
scenario 2. If mitigation mode, or equivalent, is present but
can't be disabled the furnace must be replaced.
If mitigation mode, or equivalent, is not available follow the
instructions on scenario 2.
Under no circumstance should the system be charged with
refrigerant at a capacity greater than the refrigerant charge
listed on the serial plate. This value indicates refrigerant
charge at or above 30% GREATER than the intended
charge with the longest line-sets.
If additional charge is required, you must contact Daikin
Comfort’s Homeowner Support Line.
5.1 Preparation
Keep this document with the unit. Carefully read all
instructions for the installation prior to installing product.
Make sure each step or procedure is understood and
any special considerations are taken into account before
starting installation. Assemble all tools, hardware and
supplies needed to complete the installation. Some items
may need to be purchased locally. Make sure everything
needed to install the product is on hand before starting.
background
3
5.2 Clearances
Consult all appropriate regulatory codes prior to
determining nal clearances. In installations that may lead
to physical damage (i.e. a garage) it is advised to install a
protective barrier to prevent such damage. Always install
units such that a positive slope in condensate line (1/4” per
foot) is allowed.
Further, any joints made in the installation between
parts of the refrigerating system must be accessible for
maintenance purposes.
NOTE: Furnace application requires that the installer
MUST review and strictly follow ALL furnace installation
clearance guidelines. Failure to do so may result in
property / equipment damage, personal injury or death.
CONSULT ALL APPROPRIATE REGULATORY CODES
WHEN DETERMINING FINAL CLEARANCES.
When installed in a room with an area less than that
outlined in table 3, that room shall be without continuously
operating open flames (for example an operating gas
appliance) or other potential ignition sources (for example
an operating electric heater, hot surfaces).
WARNING
6. System Matches
The entire system (combination of indoor and outdoor
sections) must be manufacturer approved and Air Condi-
tioning, Heating, and Refrigeration Institute (AHRI) listed.
NOTE: Installation of unmatched systems is not
permitted. Damage or repairs due to installation of
unmatched systems is not covered under the warranty.
7. Application Information
Auxiliary devices which may be a potential ignition source
are not to be installed in the duct work. Such potential
ignition sources include hot surfaces with a temperature
exceeding 650°C and electric switching devices.
WARNING
WARNING
Only auxiliary devices approved by the appliance
manufacturer or declared suitable with the refrigerant
shall be installed in connecting ductwork.
Coils are designed for indoor installation only and must be
installed downstream (discharge air) of the furnace. The
CAPTA product line may be installed in upow or downow
orientations.
8. Condensate Drain Piping
In all cooling applications where condensate overow may
cause damage, a secondary drain pan must be provided by
the installer and placed under the entire unit with a separate
drain line properly sloped and terminated in an area visible
to the owner. This secondary drain pan can provide extra
protection to the area under the unit should the primary
drain plug up and overow. For coils with “A” cabinets (14”
wide), use oat switch if secondary drain line is not installed.
Refer to product nomenclature from product specication
literature to identify coil models with “A” cabinets. As
expressed in our product warranty, we will not be liable for
any damages, structural or otherwise due to the failure to
follow this installation requirement.
Condensate drain connections are located in the drain
pan at the bottom of the coil/enclosure assembly. Use the
female (3/4” FPT) threaded tting that protrudes outside of
the enclosure for external connections. The connectors
required are 3/4” NPT male, either PVC or metal pipe, and
must be hand tightened to a torque of no more than 37
in-lbs. to prevent damage to the drain pan connection. An
insertion depth between .36 to .49 inches (3-5 turns) should
be expected at this torque. Insulate PVC drain lines/pipes
with high heat resistive tape within 1” furnace ue/vent pipe.
Foil-Mastic Sealant tape is the preferred wrapping material.
1. Ensure drain pan hole is NOT obstructed.
2. To prevent potential sweating and dripping on
nished space, it may be necessary to insulate the
condensate drain line located inside the building. Use
Armaex® or similar material.
A secondary condensate drain connection, now called for
by many building codes, has been provided. Pitch the drain
line 1/4” per foot to provide free drainage. Provide required
support to drain line to prevent bowing. Install a condensate
trap in the primary drain line to ensure proper drainage. If the
secondary drain line is required, run the line separately from
the primary drain and end it where condensate discharge
can be easily seen.
CAUTION
If secondary drain is not installed, the secondary access
must be plugged.
9. Plastic Drain Pan Application
WARNING
Do not use the coil pan shipped with the unit on oil furnaces
or any application where the temperature of the drain
pan may exceed 300°F. A high temperature drain pan such as
kits HTP-A, -B, -C, and -D for normal cabinet widths of 14,
17.5, 21 and 24.5 inches, respectively, should be used for
applications where the temperature exceeds 300°F and below
450°F. A field fabricated metal drain pan can also be used for
applications where temperature exceeds 300°F. Failure to
follow this warning may result in property damage and/pr
personal injury.
background
4
If the uncased coil is to be installed on top of a gas furnace,
allow enough space between the top to the furnace and the
bottom of the plastic coil drain pan to have a free ow of air.
A minimum of 2.0” distance from the top of the furnace and
the bottom of the coil pan is required.
NOTE: The coil must be installed with the line set and drain
openings to the front of the furnace.
Figure 2
NOTE: Water coming from the secondary line means the
coil primary drain is plugged and needs immediate attention.
Install a trap in the drain line below the bottom of the drain
pan (Figure 2). If using a copper drain line, solder a short
piece of pipe, minimum 6” length, to the connector before
installing a drain tting.
DO NOT over torque the 3/4” copper connector to the plastic
drain connection. Using a wet rag or heatsink material on
the short piece to protect the plastic drain pan, complete
the drain line installation. Use Figure 3 as a template for
typical drain pipe routing. This gure shows how to avoid
interference with vent piping.
2” MIN.
3” MIN.
Figure 3
The appliance shall be stored so as to prevent mechanical
damage from occurring.
A, B CHASSIS W
ITH 80%
C, D CHASSIS WITH 90%
C, D CHASSIS WITH 80%
A, B CHASSIS W
ITH 90%
Figure 4
9.1 Condensate Drain Pan Break-away Feature
The drain pan (0161D00116) possesses a break-away
feature on the lip located on the front-top and rear-top
of the drain pan. This feature is to be used for uncased
installations, as necessary. The force required to break
the lip is 18lbf uniformly distributed over the feature. A
force of 8lbf localized on the corner of the lip can also be
applied. (Applies only for A-size cabinet) See Figure 5.
4.
BREAK AWAY
Figure 5
background
5
10. Sensor and Accessory Wiring
Refer to Table 3 for minimum conditioned room area
requirements.
A2L sensor fault codes should be referenced through the
corresponding A2L equipped furnace or accessory IO
manuals. It is the installer’s responsibility to ensure that
mitigation mode is operational.
Sensor is not intended for service or repair. If the sensor is
not functioning properly, mitigation mode will engage and
the sensor must be replaced by removing the old sensor
from the bracket and re-installing with new push-pins and
a zip-tie. (Sensor replacement part can be determined
through the homeowner support line provided earlier in this
document.)
All wiring installed in the eld to be used in conjunction of
the sensor must meet the following minimum specication:
• 18 AWG
• 1.58mm insulation thickness or protected from
damage
If the sensor used in this unit must be routed through the
Non-A2L Furnace Integration Kit, then reference the Non-
A2L Furnace Integration Kit installation manual for further
instructions.
For any and all accessories which may become a potential
ignition source, they must be installed to an accessory
control board. Ensure that any additional wiring from the
cased coil is done so as to protect from damage and wear,
avoiding the ue pipe and any joints which may need to be
brazed or broken for service. If a zone control system is
installed in the ductwork attached to this system, the zone
controller must be powered through a zoning kit to ensure
that the zoning dampers actuate during mitigation mode.
Check that wiring will not be subject to wear, corrosion,
excessive pressure, vibration, sharp edges or any other
adverse environmental e󰀨ects. The check shall also take
into account the e󰀨ects of aging or continual vibration from
sources such as compressors or fans.
WIRE
Figure 6 - Upow Wire Routing
WIRE
Figure 7 - Downow Wire Routing
background
6
A2L Sensor Input
Typical Design for Refrigerant Detection Sensor connectors.
Figure 8
11. Refrigerant Lines
CAUTION
The coil is shipped under pressure with a dry nitrogen
mixture. Use appropriate service tools and follow these
instructions to prevent injury.
WARNING
A quenching cloth is strongly recommended to prevent
scorching or marring of the equipment finish when brazing
close to the painted surfaces. Use brazing alloy of 5%
minimum silver content.
NOTE: Refrigerant tubing must be routed to allow adequate
access for servicing and maintenance of the unit.
Do not handle coil assembly with manifold or owrator tubes.
Doing so may result in damage to the tubing joints. Always
use clean gloves for handling coil assemblies.
Installation of pipe-work must be kept to a minimum. Pipe-
work including piping material, pipe routing and installation
must be protected from physical damage and shall not
be installed in an unventilated space. Equipment piping
in any occupied space shall be installed in such a way to
protect against accidental damage in operation and service.
Precautions must be taken to avoid excessive vibration
or pulsation to refrigeration piping. Protection devices,
piping and ttings shall be protected as far as possible
against adverse environmental e󰀨ects, for example, the
danger of water collecting and freezing in relief pipes or the
accumulation of dirt and debris. Steel pipes and components
shall be protected against corrosion with a rustproof coating
before applying any insulation. Any solenoid valves and
piping in the refrigerant systems must be so designed
and installed to minimize the likelihood of hydraulic shock
damaging the system. Solenoid valves must not block in
liquid refrigerant unless adequate relief is provided to the
refrigerant system’s low pressure side. Provisions must be
made for expansion and contraction of long runs of piping.
Follow standards related to ASHRAE 15, ASHRAE 15.2,
IAPMO Uniform Mechanical Code, ICC International
Mechanical Code or CSA B52 during any installation. Piping
must be accessible for inspection prior to being covered or
enclosed in compliance with national and local codes.
Flexible pipe elements must be protected against mechanical
damage, excessive stress by torsion, or other forces. They
should be checked for mechanical damage annually. The
indoor equipment and pipes must be securely mounted and
guarded such that accidental rupture of equipment cannot
occur from such events as moving furniture or reconstruction
activities. Field-made refrigerant joints indoors shall be
tightness tested.
Field pipework must be pressure tested with an inert gas and
then vacuum tested prior to refrigerant charging according
to the following requirements:
The minimum test pressure for the low side of the system
shall be the low side design pressure and the minimum test
pressure for the high side of the system shall be the high
side design pressure. If the high side of the system cannot
be isolated from the low side of the system, the entire system
shall be pressure tested to the low side design pressure.
Field-made refrigerant joints indoors shall be tightness
tested. The test method shall have a sensitivity of 5 grams
per year of refrigerant or better under a pressure of at least
0,25 times the maximum allowable pressure. No leak shall
be detected (Should be leak tight).
11.1 Tubing Size/Length
For the correct tubing size, follow the specication for
the condenser/heat pump. Give special consideration
to minimizing the length of refrigerant tubing when
installing coils. Refer to Remote Cooling/Heat Pump
Technical Publication TP-110* Long Line Set Application
for guidelines for line lengths over 80’. Leave a minimum
3” straight in line set from braze joints before any bends.
11.2 Tubing Preparation
All cut ends are to be round, burr free, and cleaned. Any
other condition increases the chance of a refrigerant
leak. Use a pipe cutter to remove the closed end of the
spun closed suction line.
WARNING
This unit must be charged with R-32 refrigerant. Ensure that
sensor is installed correctly and is operational.
11.3 Brazing
Braze joints should be made only with the connections
provided external to the cabinet. Do not alter the cabinet
nor braze inside the cabinet. To avoid overheating after
brazing, quench all brazed joints with water or a wet rag.
background
7
This system must be charged with R32 refrigerant in
order to operate safely.
When breaking into the refrigerant circuit to make repairs
– or for any other purpose – conventional procedures
shall be used. However, for ammable refrigerants
it is important that best practice be followed, since
ammability is a consideration. The following procedure
shall be adhered to:
1. Safely remove refrigerant following local and national
regulations;
2. Evacuate;
3. Purge the circuit with inert gas;
4. Evacuate;
5. Continuously ush or purge with inert gas when
using ame to open circuit; and
6. Open the circuit.
The refrigerant charge shall be recovered into the correct
recovery cylinders if venting is not allowed by local and
national codes. For appliances containing ammable
refrigerants, the system shall be purged with oxygen-
free nitrogen to render the appliance safe for ammable
refrigerants. This process might need to be repeated
several times. Compressed air or oxygen shall not be
used for purging refrigerant systems.
For appliances containing ammable refrigerants,
refrigerants purging shall be achieved by breaking the
vacuum in the system with oxygen-free nitrogen and
continuing to ll until the working pressure is achieved,
then venting to atmosphere, and nally pulling down to a
vacuum (optional for A2L). This process shall be repeated
until no refrigerant is within the system (optional for A2L).
When the nal oxygen-free nitrogen charge is used, the
system shall be vented down to atmospheric pressure to
enable work to take place.
The outlet for the vacuum pump shall not be close to
any potential ignition sources, and ventilation shall be
available.
CAUTION
Applying too much heat to any tube can melt the tube.
Torch heat required to braze tubes of various sizes must be
proportional to the size of the tube. Service personnel must
use the appropriate heat level for the size of the tube being
brazed.
11.4 Tubing Connections for TXV Version
WARNING
Field installed TXV Metering devices, including Piston kits
and EEV, must be housed within the cabinet. Do not install
external of the unit.
TXV models come with factory installed adjustable TXV
with the bulb permanently located on the suction tube.
1. Remove coil access panel and rubber grommets.
2. Remove access valve tting cap and depress the
valve stem in access tting to release pressure. No
pressure indicates possible leak.
3. Reinstall the Coil Access Panel & rubber grommets.
4. Remove the spin closure on both the liquid and
suction tubes using a tubing cutter. DO NOT USE
A CUTTING METHOD THAT WOULD RESULT IN
THE GENERATION OF COPPER SHAVINGS OR
COPPER DUST.
SUCTION
LINE SET
SUCTION
TUBE
RUBBER
GROMMET
Figure 9A
TORQUE 180-240 IN-LBS
ENSURE THAT SEAL
WASHERS STAY
IN POSITION
CC
Figure 9B
CAUTION
Excessive torque can cause the TXV retaining ring to weaken
& create a leak. This will make it difficult to re-install. The
proper torque settings should be configured as below when
adjusting. Oiled equalizer should be set to 10-12 ft/lbs.
Outlet and inlet chat fitting should be set to 15-20 ft/lbs.
LIQUID
LINE SET
LIQUID
LINE
RUBBER
GROMMET
Figure 9C
background
8
Suction Pressure
Saturated Suction
Temperature ºF
PSIG R32
50 0.57
52
2.06
54
3.51
56
4.94
58
6.33
60
7.69
62
9.03
64
10.34
66
11.62
68
12.88
70
14.12
72
15.34
74
16.53
76
17.70
78
18.86
80
19.99
85
22.75
90
25.41
95
27.97
100
30.44
110
35.16
120
39.59
130
43.79
140
47.76
150
51.55
160
55.17
170
58.64
Saturated Suction Pressure
Temperature Chart
Table 1
Suction Pressure
Saturated Liquid
Temperature ºF
PSIG R32
200 68.25
210
71.23
220
74.11
225
75.50
235
78.25
245
80.91
255
83.50
265
86.03
275
88.48
285
90.86
295
93.19
305
95.46
325
99.85
355
106.08
375
110.02
405
115.65
415
117.46
425
119.24
435
120.98
445
122.70
475
127.68
500
131.65
525
135.48
550
139.17
575
142.73
600
146.17
625
149.50
Saturated Liquid Pressure
Temperature Chart
Table 2
Cased Coil Mitigation Chart
Model
Maximum
Total
System
Refrigerant
Charge
(oz)
Maximum
Total
System
Refrigerant
Charge
(kg)
Minimum Air
Conditioned
Room Area
(m²)
Minimum Air
Conditioned
Room Area
(ft²)
Minimum
Mitigation
Airow
m
3
hr
Minimum
Mitigation
Airow
(CFM)
1.5T Match-up 157.90 4.48 13.26 142.68 437.43 257.46
2.0T Match-up 160.50 4.55 13.47 145.03 444.63 261.70
2.5T Match-up 172.20 4.88 14.46 155.60 477.05 280.78
3.0T Match-up 205.70 5.83 17.27 185.87 569.85 335.40
3.5T Match-up 225.20 6.38 18.91 203.49 623.87 367.20
4.0T Match-up 242.10 6.86 20.32 218.77 670.69 394.75
5.0T Match-up 248.60 7.05 20.87 224.64 688.70 405.35
It is the installer’s responsibility to verify that actuation of mitigation procedures are operational with minimum required
airow according to the chart.
Table 3
background
9
5. Insert liquid line set into liquid tube expansion and
slide grommet about 18” away from braze joint.
6. Insert suction line set into suction tube expansion and
slide insulation and grommet about 18” away from
braze joint.
7. Braze suction and liquid line joints.
11.5 Thermal Expansion Valve System Adjustment
The following information for the indoor unit should be
veried before attempting to charge system or adjust TXV
if necessary.
1. Total static pressure is .5” WC or less.
2. Airow is correct for installed unit.
3. Airow tables are in the installation manual and Spec
Sheet for Indoor Unit.
4. Complete airow tables and charging information are
in Service Manual RS6200006.
5. The outdoor temperature must be 60°F or higher.
6. Set the room thermostat to COOL, fan switch to AUTO
7. Set the temperature control well below room
temperature.
Superheat adjustments should not be made until indoor
ambient conditions have stabilized. This could take up to
24 hours depending on indoor temperature and humidity.
Before checking superheat run the unit in cooling for 10
minutes or until refrigerant pressures stabilize. Use the
following guidelines and methods to check unit operation
and ensure that the refrigerant charge is within limits. NOTE:
Charge two stage units on low stage.
In addition to conventional charging procedures, the
following requirements shall be followed:
1. Ensure that contamination of di󰀨erent refrigerants
does not occur when using charging equipment.
Hoses or lines shall be as short as possible to
minimize the amount of refrigerant contained in them.
2. A2L refrigerant cylinders shall be kept in an
appropriate position according to the instructions.
3. Ensure that the refrigeration system is grounded prior
to charging the system with refrigerant.
4. Label the system when charging is complete (if not
already).
5. Extreme care shall be taken not to overll the
refrigerating system.
Prior to recharging the system, it shall be pressure-tested
with the appropriate purging gas. The system shall be leak-
tested on completion of charging but prior to commissioning.
A follow up leak test shall be carried out prior to leaving the
site.
1. Purge gauge lines. Connect service gauge manifold to
base-valve service ports.
2. Temporarily install a thermometer on the liquid
line at the liquid line service valve and 4-6” from
the compressor on the suction line. Ensure the
thermometer makes adequate contact and is insulated
for best possible readings. Use liquid line temperature
to determine subcooling and vapor temperature to
determine superheat.
3. For optimum system performance subcool and
superheat should be matched as specied in outdoor
installation manual with respective AHRI outdoor
matchup. Any other system matchup shall have
subcooling set to 8ºF ± 1ºF and superheat setting
12ºF ± 1ºF.
Superheat Adjustments (Only if necessary)
1. Attach a pipe clamp thermometer near the suction line
service valve at the outdoor unit.
a. Ensure the thermometer makes adequate
contact for the best possible readings.
2. Adjust Superheat by turning the TXV valve stem
clockwise to increase and counterclockwise to
decrease. Adjustments should be made opening or
closing the valve by no more than ¼ turn at a time.
Allow the system to stabilize 15 to 20 minutes before
making additional adjustments if necessary.
3. After adjustments are complete replace cap on
adjustment stem and tighten 1/6 turn.
4. Remove gauges and check the Schrader ports for
leaks and tighten valve cores if necessary. Install caps
nger tight.
NOTE: In situations where the TXV must be removed and
replaced or re-installed into the system, the TXV should be
hand tightened rst and then apply a half turn to fully set the
TXV. No more than 20 ft-lb torque should be applied to the
joints of the TXV.
NOTE: Do NOT adjust the charge based on suction pressure
unless there is a gross undercharge.
5. Disconnect manifold set, installation is complete.
NOTE: Check the Schrader ports for leaks and tighten valve
cores if necessary. Install caps nger-tight.
SUBCOOL FORMULA = SAT. LIQUID LINE TEMP. -
LIQUID LINE TEMP.
SUPERHEAT FORMULA = SUCT. LINE TEMP. - SAT.
SUCT. TEMP.
Under no circumstances shall potential sources of ignition
be used in the searching for or detection of refrigerant leaks.
A halide torch (or any other detector using a naked ame)
shall not be used. If a leak is suspected, all naked ames
shall be removed/extinguished. If a leakage of refrigerant is
found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut o󰀨
valves) in a part of the system remote from the leak.
The following leak detection methods have been deemed
acceptable, provided proper care is taken in their
implementation:
background
10
1. Electronic leak detectors rated for use with R32
refrigerant. Ensure the detection equipment is
calibrated in a refrigerant-free area and that the leak
detector itself is not a potential source of ignition.
Leak detection equipment shall be set at a value of no
more then 0.075 kg/m3.
2. Leak detection uids - such as the bubble method or
uorescent method. Ensure that the use of detergents
containing chlorine are avoided as the chlorine may
react with the refrigerant and corrode the pipe-work.
The cased coil mitigation requirements are calculated at
sea level. For altitudes higher then 800m, please adjust
the minimum room area by the corresponding altitude
adjustment factor shown below. This chart is provided as
reference.
Height in
Meters
Height in
Feet
Altitude
Adjustment
Factor
0 0 1.00
200 660 1.00
400 1320 1.00
600 1970 1.00
800 2630 1.02
1000 3290 1.05
1200 3940 1.07
1400 4600 1.10
1600 5250 1.12
1800 5910 1.15
2000 6570 1.18
2200 7220 1.21
2400 7880 1.25
2600 8540 1.28
2800 9190 1.32
3000 9850 1.36
3200 10500 1.40
Do not apply any permanent inductive or capacitance loads
to the circuit without ensuring that this will not exceed the
permissible voltage and current permitted for the equipment
in use.
Intrinsically safe components are the only types that can
be worked on while live in the presence of a ammable
atmosphere. The test apparatus shall be at the correct rating
Check that cabling (wiring) will not be subject to wear,
corrosion, excessive pressure, vibration, sharp edges or any
other adverse environmental e󰀨ects. The check shall also
take into account the e󰀨ects of aging or continual vibration
from sources such as compressors or fans.
11.6 Piston Charge Instructions
If the unit is not equipped with a TXV metering device
follow the steps below:
1. Ensure the piston size present on the unit is rated
for use with the outdoor matchup as shown on the
piston kit chart. If it does not match, replace the
provided piston with the piston size listed on the
piston kit chart.
2. For optimum system performance, superheat should
be matched as specied in outdoor installation
manual with respective AHRI outdoor matchup.
12. Supply Duct Connection
1. Top anges can be bent for ease in installation to the
duct anges. (See Figure 10)
WARNING
All required ventilation openings must be clear of
obstruction and all ducts connected to the appliance free
of potential ignition sources.
For appliances using A2L REFRIGERANTS, connected via
an air duct system to one or more rooms, the supply and
return air shall be directly ducted to the space. Open areas
such as false ceilings shall not be used as a return air duct
The air extraction opening from the room shall be located
equal or below the refrigerant release point. For oor
mounted units, it shall be as low as practicable. The air
extraction openings shall be located in a su󰀩cient distance
from the air intake openings to prevent re-circulation to the
space.
FILLER PLATE
FLANGE BENT DOWN
FLANGE UNFOLDED UP
Figure 10
2. A duct ange kit can also be purchased from your
distributor. (See Figure 11)
• 14 inch chassis - CLDUCTFLGA
background
11
• 17.5 inch chassis - CLDUCTFLGB
• 21 inch chassis - CLDUCTFLGC
• 24.5 inch chassis - CLDUCTFLGD
Figure 11
13. Filler Plates
Filler plates are supplied on all 17.5, 21, & 24.5 inch chassis
to be used for adapting the unit to a furnace one size smaller.
If the plenum and furnace openings are the same size, the
ller plates must be removed. See Figure 10.
14. Return Ductwork
DO NOT TERMINATE THE RETURN DUCTWORK
IN AN AREA THAT CAN INTRODUCE TOXIC OR
OBJECTIONABLE FUMES/ODORS INTO THE
DUCTWORK.
15. Sealing Along The Panel Gap
IMPORTANT NOTE: To prevent cabinet sweating and
airow leak, apply eld provided insulation tape along all
joining surfaces between the coil, gas furnace, duct work
and panels. See Figure 10.
16. Removing Coil from Cabinet
In an event of removing taller coils from cabinet to service
or replace; remove access panel, remove top tie rail to allow
the coils to slide out of the cabinet.
After service or replacement slide the coil back in the cabinet
and secure the top tie rail and re-install access panel.
See Figure 12.
TOP TIE
PANEL
Figure 12
17. UV Accessory (optional)
Clean Comfort brand UV coil puriers also can be purchased
from distributor. Maximum UV lamp diameter to be used per
delta plate knockout design is 1.375” to reduce the possibility
of air leak.
The power source must be installed external of the unit.
Ensure that the wiring is routed through the access panel
knockout with the grommet included. The magnetic door
switch must be installed to avoid any accidental Ultraviolet
exposure during service.
Refer to UV coil puriers product specication and installation
manual for additional details.
UV-C Part Numbers
Models Lamp
UC18S15-24 UCP-16013
UC18S15-24B UCP-16012
APPLY INSULATION TAPE
Figure 13
background
12
18. Aluminum Indoor Coil Cleaning
(Qualied Servicer Only)
This unit is equipped with an aluminum tube evaporator coil.
The safest way to clean the evaporator coil is to simply ush
the coil with water. This cleaning practice remains as the
recommended cleaning method for both copper tube and
aluminum tube residential evaporator coils.
It has been determined that many coil cleaners and drain
pan tablets contain corrosive chemicals that can be harmful
to aluminum tube and n evaporator coils. Even a one-
time application of these corrosive chemicals can cause
premature aluminum evaporator coil failure. Any cleaners
that contain corrosive chemicals including, but not limited
to, chlorine and hydroxides, should not be used.
An alternate cleaning method is to use one of the products
listed in TP-109* to clean the coils. The cleaners listed are
the only agents deemed safe and approved for use to clean
round tube aluminum coils. TP-109 is also available on the
web site in Partner Link > Service Toolkit.
NOTE: Ensure coils are rinsed well after use of any chemical
cleaners.
WARNING
Do not use means to accelerate the defrosting process or to
clean, other than those recommended by the manufacturer.
The appliance shall be stored in a room without
continuously operating ignition sources (for example: open
flames, an operating gas appliance or an operating electric
heater). Do not pierce or burn. Be aware that refrigerants
may not contain an odor.
19. Start-Up Procedure
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or
installing this unit. Multiple power sources
may be present. Failure to do so may cause
property damage, personal injury or death.
• Prior to start-up, ensure that all electrical wires are
properly sized and all connections are properly
tightened.
• All panels must be in place and secured. For air tight
application, gasket must be positioned at prescribed
locations to achieve 1.4% leakage.
• Tubing must be leak free.
• Condensate line must be trapped and pitched to allow
for drainage.
• Low voltage wiring is properly connected.
• Auxilliary drain is installed when necessary and
pitched to allow for drainage.
• Unit is protected from vehicular or other physical
damage.
• Return air is not obtained from, nor are there any
return air duct joints that are unsealed in, areas where
there may be objectionable odors, ammable vapors
or products of combustion such as carbon monoxide
(CO), which may cause serious personal injury or
death.
• Ensure that the equipped A2L sensor is wired to
the furnace PCB and that there are no sources of
potential ignition within the system.
IMPORTANT: The A2L verication step as described on
the furnace IO or the Non-A2L Integration Kit IO must be
completed.
20. Refrigerant Recovery
When removing refrigerant from a system, either for
servicing or decommissioning, it is recommended good
practice that all refrigerants are removed safely. When
transferring refrigerant into cylinders, ensure that only
appropriate refrigerant recovery cylinders are employed.
Ensure that the correct number of cylinders for holding the
total system charge are available. All cylinders to be used
are designated for the recovered refrigerant and labeled
for that refrigerant (i.e. special cylinders for the recovery of
refrigerant). Cylinders shall be complete with pressure-relief
valve and associated shut-o󰀨 valves in good working order.
Empty recovery cylinders are evacuated and, if possible,
cooled before recovery occurs.
The recovery equipment shall be in good working order
with a set of instructions concerning the equipment that
is at hand and shall be suitable for the recovery of the
ammable refrigerant. If in doubt, the manufacturer should
be consulted. In addition, a set of calibrated weighing scales
shall be available and in good working order. Hoses shall be
complete with leak-free disconnect couplings and in good
condition. The recovered refrigerant shall be processed
according to local legislation in the correct recovery cylinder,
and the relevant waste transfer note arranged. Do not mix
refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed,
ensure that they have been evacuated to an acceptable
level to make certain that ammable refrigerant does not
remain within the lubricant. The compressor body shall not
be heated by an open ame or other ignition sources to
accelerate this process. When oil is drained from a system,
it shall be carried out safely.
background
13
Air Handler / Coil
ELECTRICAL
Line Voltage (Measure L1 and L2 Voltage) L1 - L2
Secondary Voltage (Measure Transformer Output Voltage) R - C
Blower Amps
Heat Strip 1 - Amps
Heat Strip 2 - Amps
BLOWER EXTERNAL STATIC PRESSURE
Return Air Sta�c Pressure IN. W.C.
Supply Air Sta�c Pressure IN. W.C.
Total External Sta�c Pressure (Ignoring +/- from the reading above, add total here) IN. W.C.
TEMPERATURES
Return Air Temperature (Dry bulb / Wet bulb)
DB °F WB °F
DB °F WB °F
Hea�ng Supply Air Temperature DB °F
Temperature Rise DB °F
Delta T (Difference between Supply and Return Temperatures) DB °F
Air Handler / Coil - (Inverter Matched)
INVERTER AH / COIL ONLY
Check EEV and EEV wiring is secure (no adjustment required)
Addi�onal Checks
Check wire rou�ngs for any rubbing
Check product for proper draining
Check screw �ghtness on blower wheel
Check factory wiring and wire connec�ons
Check product for proper clearances as noted by installa�on instruc�ons
°F to °C formula: (°F - 32) divided by 1.8 = °C °C to °F formula: (°C mul�plied by 1.8) + 32 = °F
Model Number
Serial Number
Cooling Supply Air Temperature (Dry bulb / Wet bulb)
21. Start-Up Checklist
background
14
THIS PAGE LEFT INTENTIONALLY BLANK
background
15
THIS PAGE LEFT INTENTIONALLY BLANK
background
16
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE
CUSTOMER FEEDBACK
We are very interested in all product comments.
Please ll out the feedback form on one of the following links:
Daikin Products: (https://daikincomfort.com/contact-us)
Goodman
®
Brand Products: (http://www.goodmanmfg.com/about/contact-us).
Amana
®
Brand Products: (http://www.amana-hac.com/about-us/contact-us).
You can also scan the QR code on the right for the product brand you
purchased to be directed to the feedback page.
DAIKIN
AMANA
®
BRAND
GOODMAN
®
BRAND
19001 Kermier Rd., Waller, TX 77484
© 2023-2024 Daikin Comfort Technologies Manufacturing, L.P.
www.daikincomfort.com • www.goodmanmfg.com • www.amana-hac.com
®
is a registered trademark of Maytag Corporation or its related companies and is used
under license. All rights reserved.
DAIKIN
AMANA
®
BRAND
GOODMAN
®
BRAND
PRODUCT REGISTRATION
Thank you for your recent purchase. Though not required to get the
protection of the standard warranty, registering your product is a relatively
short process, and entitles you to additional warranty protection, except that
failure by California and Quebec residents to register their product does not
diminish their warranty rights. The duration of warranty coverages in Texas
and Florida di󰀨ers in some cases.
For Product Registration, please register as follows:
Daikin Products: (https://daikincomfort.com/owner-support/product-registration).
Goodman® Brand products: (https://www.goodmanmfg.com/product-registration).
Amana® Brand products: (http://www.amana-hac.com/product-registration).
You can also scan the QR code on the right for the product brand you purchased
to be directed to the Product Registration page.

Specifications

Indexed Terms: Evaporator Coil, R-32, Coil

Goodman CAPFA6030D3 Questions and Answers

Questions and Answers

Related Products