Monoblock MTHP Series
INSTALLATION & OWNER’S MANUAL
Read this manual carefully before installation and keep it where
the operator can easily nd it for future reference.
Due to updates and constantly improving performance, the
information and instructions within this manual are subject to
change without notice.
Version Date: April 14, 2026
Please visit www.mrcool.com/documentation
to ensure you have the latest version of this manual.
This product utilizes R-32 refrigerant
MODELS:
MDM10115D

mrcool.com1
CONTENTS
SAFETY ................................................................................................................... 1
UNIT OVERVIEW .................................................................................................... 3
2.1 Features .................................................................................................... 3
2.2 Packing List .............................................................................................. 4
2.3 Tools Required .......................................................................................... 4
2.4 Product Overview .................................................................................... 5
INSTALLATION ...................................................................................................... 5
3.1 Installation Overview .............................................................................. 5
3.2 Installation Location ................................................................................ 5
3.3 Drill Wall Opening .................................................................................... 6
3.4 Sealing & Mounting .................................................................................. 7
OPERATION ........................................................................................................... 8
4.1 Controls ..................................................................................................... 8
4.2 Remote ...................................................................................................... 9
POST-INSTALLATION .......................................................................................... 10
5.1 App Connection ...................................................................................... 10
5.2 Troubleshooting ..................................................................................... 13
5.3 Error Codes ............................................................................................. 14
1
Contents
Incorrect usage may cause serious damage or injury.
The symbols below are used throughout this manual to indicate instructions that should be
followed closely or actions that should be avoided to prevent death, injury, and/or property
damage.
Safety Precautions
CAUTION
Indicates the possibility of personal injury or loss of life.
Indicates the possibility of property damage or serious
consequences.
Read Before Using
WARNING
2
3
4
This marking indicates that this product should not be disposed of with other household wastes throughout North America.
To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly
to promote the sustainable reuse of material resources. To return your used device, please use the return and collection
systems or contact the retailer where the product was purchased. They can take this product for environmental-safe recycling.
5

mrcool.com 2 2
Incorrect usage may cause serious damage or injury.
The symbols below are used throughout this manual to indicate instructions that should be
followed closely or actions that should be avoided to prevent death, injury, and/or property
damage.
WARNING FOR PRODUCT INSTALLATION
1. This unit is for indoor use only.
2. This unit must only be connected to a 115V/60Hz grounded outlet.
3. The installation must be in accordance with national and local regulations.
4. If you are in doubt of the suitability of your electrical supply, contact a qualied electrician.
5. This unit has been tested and is safe to use. However, as with any electrical device, take precautions and
use with care.
6. Disconnect the power from the appliance before dismantling, assembling, or cleaning.
7. Avoid touching any moving parts of the unit.
8. Do not insert ngers, pencils, or other objects through the guard.
9. This unit is not intended for use by persons (including children) with reduced physical sensory or mental
capabilities. It is also not intended for use by those lacking experience and knowledge, unless they have
been given proper supervision or instruction concerning the use of the appliance by a person responsible
for their safety.
10. Do not leave children unsupervised with this unit.
11. Do not clean the unit by spraying or immersing it in water.
12. Never connect the unit to an electrical outlet using an extension cord. If an outlet is not available, one
should be installed by a qualied electrician.
13. Do not operate the unit unless it has been fully installed following the guidance provided within this
manual.
14. Never operate this unit if the cord or plug is damaged. Ensure the power cord is not stretched or exposed
to sharp objects/edges.
15. If the supply cord is damaged, it must be replaced by MRCOOL®, distributors, or a qualied person to
avoid hazards.
16. Any service other than regular cleaning or lter replacement should be performed by qualied personnel.
Failure to comply can result in a voided warranty.
17. Do not use the appliance for any purpose other than its intended use.
18. Avoid restarting the unit after a cycle for 3 minutes to prevent damage to the compressor.
19. Never use the main plug as a switch to turn on or turn o the unit. Use the On/O button located on the
control panel.
20. The unit should not be installed in laundry or wet rooms.
21. The unit must be installed in a room without sources of ignition (for example: open ames, an operating
gas appliance, or an operating electric heater).
22. The unit must be installed on a solid vertical wall by a licensed technician. The power supply must only be
connected after installation is complete.
23. The unit contains about 19.4oz (550g) of R-32, GWP: 675, 0.607 tonnes CO2 equivalent.
24. Do not install or store in an unventilated space with an area smaller than 43ft
2
(4m
2
) per unit. The room
must meet these requirements to prevent the stagnation of possible refrigerant leaks that pose a danger
of re or explosion if the refrigerant comes into contact with electric heaters, stoves, or other sources of
ignition.
25. Refrigerant gas can be odorless.
26. Do not use the unit if damage has occurred which may have compromised the refrigerant system, contact
MRCOOL® at 270-366-0457 or at [email protected].
27. Any repairs or maintenance made on the unit must be carried out by a licensed technician.
28. The refrigerant in the system should not be perforated or punctured.
29. The unit must always be stored and transported upright, otherwise irreparable damage may be caused to
the compressor. If in doubt, wait at least 24 hours after installing the unit before operating.
30. Do not lean on the system when secured to the wall.
31. Avoid touching the coils when cleaning the air lter.
SAFETY
1

mrcool.com3
• Do not cover or restrict airow for the outlet or inlet grilles.
• Keep the lters clean. Under normal conditions lters should only need cleaning once every three weeks
(approximately). Since the lters remove airborne particles, more frequent cleaning may be necessary,
depending on the air quality.
• For the initial start-up, set the fan speed to maximum and the thermostat to 4-5 degrees lower than the
current temperature. After, set the fan speed to low and set the thermostat to your desired temperature.
• Note: Pictures and information may vary regarding the unit in your possession due to continual product
improvement.
TIPS
Symbols Displayed on Unit
DANGER
This symbol shows that this appliance uses a ammable refrigerant. If the refrigerant
leaks and is exposed to an external ignition source, there is a risk of re.
CAUTION This symbol shows the operation manual should be read carefully.
CAUTION
This symbol shows that service personnel should be handling this equipment in
reference to the installation manual.
CAUTION
This symbol shows that information is available in the operating or installation
manual.
2.1 Features
Designed for eortless integration into your living space, this wall-mounted air conditioner combines a sleek,
modern aesthetic with high-performance functionality. Operation is kept simple with a bright LED display that
clearly indicates temperature and mode, while the integrated Wi-Fi app control oers expanded customization
from your smartphone. To maximize eciency and comfort, the unit features an energy-saving self-evaporative
function, an adjustable On/O timer, and a silent running option specically designed for undisturbed sleep.
With three fan speeds and four versatile modes—Cooling, Heating, Fan, and Dry—this system provides a
comprehensive climate solution tailored to suit your every need.
UNIT OVERVIEW
2

mrcool.com 4
4
2.2 Packing List
This system comes with the following accessories. Use all installation parts and accessories when installing the
unit. Improper installation may result in water leakage, electrical shock and re, or cause the equipment to fail.
The items that are not included with the air conditioner must be purchased separately.
PART LOOKS LIKE QUANTITY
Manual 1
Unit 1
Wall
Template
1
Plastic
Ducting
Sheet
2
Wall
Bracket
1
Remote
Control
1
PART LOOKS LIKE QUANTITY
Vent Cover
Assembly
2 (Chain,
Indoor Ring,
and Outdoor
Cover)
Fixed Plate 1
Tapping
Screw
2 (4x10mm)
Screws 7 (5x60mm)
Wall Plugs 7 (8x40mm)
Sealing
Strip
1
2.3 Tools Required
PART LOOKS LIKE
Level
Tape Measure
Pencil
8in (20cm) Core
Bit
PART LOOKS LIKE
Drill
Knife
5/16in (8mm)
Masonry Drill
Bit
1in (25mm)
Masonry Drill
Bit
UNIT OVERVIEW
2

mrcool.com5
2.4 Product Overview
Front Back
3.1 Installation Overview
Before beginning the installation, please ensure you have all necessary equipment and fully understand the
requirements. If you are in doubt, contact a certied technician. The installer must verify that the installation
area is suitable and free of cables, pipes, or other obstructions within or on the wall that could present a hazard
or prevent the completion of the installation.
Step 1: Selecting the Location
Identify a suitable location on an exterior wall, as the unit is designed to vent
directly out of the rear. The mounting surface must be at, solid, and capable of
supporting the machine’s weight reliably over time.
Step 2: Ensuring Proper Clearance
To allow for unrestricted airow and safe operation, position the unit so that there
is a minimum of 4in (10cm) of open space on the left, right, and bottom sides.
Additionally, ensure there is at least 8in (20cm) of vertical clearance above the unit.
Step 3: Managing Surroundings
Carefully check the installation area to ensure the unit is not obstructed by or
in close proximity to curtains, plants, faucets, furniture, or other household
appliances. Proper spacing prevents overheating and protects your belongings from
the exhaust.
Step 4: Positioning the Template
Secure the supplied installation template onto the wall in your chosen position. Use
a spirit level to verify that the reference line is perfectly level before proceeding with
any drilling or mounting.
3.2 Installation Location
INSTALLATION
3
Louver
Air Inlet
Control Panel
Air Inlet
Back Panel
Air Outlet
Drain Pipe
Wall Hanging Mounts
Front Panel
4in (10cm)
4in (10cm)
8in (20cm)
4in (10cm)
CAUTION
Ensure the intake and outlet holes do not line up with the studs in wood-frame
housing.

mrcool.com 6
6
3.3 Drill Wall Opening
Step 1: Drill ventilation holes using an 8in (20cm) core
drill to create the two main ventilation holes. Align
these with the template and ensure they are drilled at
a minimum 5° downward angle toward the exterior to
prevent water from entering.
Step 3: Mount the hanging rail and mark the screw
positions using the template and a level. Drill holes
with a 5/16in (8 mm) bit, insert wall plugs, and secure
the rail rmly with the provided screws. Ensure the rail
is rock-solid to prevent the unit from tipping.
For wood frame installations, ensure access holes are
positioned within the wall cavity. Avoid drilling directly
into studs to maintain a clear pathway for routing.
Step 5: Attach the external vent covers into place by
placing the indoor xing ring onto the interior side,
folding the external cover in half, attaching the pull-
chains to both sides, and sliding them through the
hole. Expand the cover outside and pull the chains
tight to hook them to the indoor ring. Trim any excess
chain.
Step 2: Drill the drainage hole for the drain pipe
hole using a 1in (25mm) bit. This must also have a
minimum 5° downward angle to ensure condensation
drains correctly. Note: Best performance is achieved
on walls no thicker than 9.5in (240mm).
Step 4: Install the vent tubes by rolling the plastic vent
sheets into tubes and feeding them into the holes
from the inside until they are ush with the interior
wall. From the outside, trim any excess tubing with a
sharp knife for a neat nish.
INSTALLATION
2

mrcool.com7
3.4 Sealing & Mounting
Step 1: Apply the Sealing Strip
• Apply the included adhesive sealing strip along the entire rear
edge of the unit to create a full circle and ensure a proper seal
to prevent extra noise.
• Begin applying the strip from the bottom of the unit.
• Gradually peel the protective backing layer away while pressing
the strip into place.
• Follow the edge of the unit closely and pay special attention to
the corners.
• Trim any excess length once the unit is encapsulated.
Step 2: Mount the Unit Carefully
• Lift the unit and align the hanging holes on the back with the
hooks on the hanging rail.
• Carefully place the unit into its designated position.
• While lifting, simultaneously slide the drainage pipe through the
1in (25mm) hole that was previously drilled.
Step 3: Secure and Verify
• Wall Contact: Ensure the backside of the product is tightly
attached to the wall. A ush t is required to avoid additional
vibration and noise.
• Drainage: The end of the external drainage pipe must be placed
in an open space or a dedicated drain. Ensure the pipe is not
constricted or damaged so water can ow freely.
• Foot Pads: Note that the rubber foot pads are only intended
to protect the bottom of the unit from abrasions prior to
installation.
Step 4: Final Clearance Check
• Conrm the unit has the following clearances for optimal
airow.
• Sides and Base: At least 4in (10cm) of open space.
• Top: At least 8in (20cm) of open space.
• Obstructions: Ensure the unit is clear of curtains, plants,
faucets, furniture, and other appliances.
INSTALLATION
3

mrcool.com 8
8
OPERATION
4
4.1 Controls
Symbol Meaning
Press "Power" to turn the unit On/O.
Press to alternate between the 4 dierent modes. The display will show the symbol for the
currently selected mode.
The Cooling function allows the air conditioner to cool the room and also reduces air
humidity. The desired temperature can be adjusted using the up or down buttons
between 60°F (16°C) and 86°F (30°C). The fan speed can also be adjusted using the
speed button.
Dry mode will extract moisture from the air, which will be drained outside using the
installed drain pipe. The fan speed cannot be adjusted in Dry mode.
In fan mode the unit will recirculate the air within the room. It will not cool, heat or
dehumidify. The fan speed can be adjusted using the speed button, but the desired
temperature cannot be set.
The Heating function allows the air conditioner to heat the room. The desired
temperature can be adjusted using the up or down buttons between 86°F (16°C) and
86°F (30°C). The fan speed can also be adjusted using the speed button.
Silent mode can be activated from the app or the remote control. It can also be activated
by pressing " "+" " on the unit control panel at the same time. It will only operate in
cooling or heating modes, and the fan speed will change to low and the noise levels will
be lower.
Press to change the fan speed between Low, Medium and High. The fan speed cannot
be adjusted in Dry or Silent modes.

mrcool.com9
OPERATION
4
Symbol Meaning
The air conditioner contains a 24-hour timer, which can be used to either set a delayed start or
a set period of operation.
SHUTDOWN TIMER:
While the unit is running, press the Timer button and the display will ash “0” 5 times. After the
5th ash, use the up and down buttons to adjust the duration in 1-hour increments between 1
to 24 hours. When the timer has elapsed, the unit will shutdown automatically.
DELAYED START TIMER:
With the unit is in standby, press the Timer button and the display will ash “0” 5 times. After
the 5th ash, use the up and down buttons to adjust the duration in 1-hour increments
between 1 to 24 hours. After the timer has elapsed, the unit will start up in the same mode with
the same settings as when it was turned o.
Used within Cooling and Heating modes to adjust the desired temperature 60°F-86°F
(16°C-30°C). Also use while setting the timer to adjust the duration.
Swing Mode
After the machine turns on, press the “SWING” button and the louver will swing continuously up
and down; by pressing the button again, the movement will stop and the louver will remain in
that position. Swing mode can only be adjusted from the remote, and will initially be turned on
by default. The louver will close automatically once switch OFF the unit.
Compressor
Protection
There is a 3-minute delay when powered on. In order to protect the life of the compressor and
electronic components, please do not switch on the unit for at least 5 minutes after you have
turned the unit o.
4.2 Remote
Symbol Meaning
Power
Press the POWER button to turn the machine
On/O.
Mode
Press the MODE button to switch between
Cooling, Heating, Fan, and Dry modes.
Fan
Press the FAN button to change between High,
Medium. and Low fan speeds
LED
Press the LED button to turn the display lights
on or o. This can be useful when sleeping.
Press the UP button to increase the desired
temperature or timer duration.
Press the DOWN button to decrease the
desired temperature or timer duration
Silent
Press for Silent mode. In Silent mode, noise
will be lower, frequency is low , and the fan
works in low speed.
Swing
Press to turn the louver swing function On/O
(only activated by the remote control & app)
Timer
Press the TIMER button to set the automatic
switch On/O.
The unit can be controlled with the remote control. Two AAA-batteries are required.

mrcool.com 10
10
POST-INSTALLATION
5
5.1 App Connection
Before Starting Connection be Aware of the Following:
• Ensure your router provides a standard 2.4ghz connection.
• If your router is dual band ensure that both networks have dierent network names (SSID). The provider of
your router/internet service provider will be able to provide advice specic to your router.
• Try to have the router as close to the unit as possible during setup.
• Once your phone is connected to your router via WiFi, download the "MRCOOL® Connect" app to your
phone through the app store.
Register the App:
If you do not have an app account, register an account or sign in with a verication code by Email. The following
steps describe the registration process.
1. Press on the "Sign Up" button at the bottom of the screen.
2. The system will automatically recognize your country/area. You can also select your country code manually.
Enter you email address and tap "Get Verication Code".
3. If you choose the mobile number option, enter the verication code in the message that was sent to you by
email. Set a password as prompted and press "Done" to nish your registration.

mrcool.com11
Connecting Using Bluetooth:
1. Before initiating the connection, make sure the unit is in standby mode.
2. Press the "Fan" button for 3 seconds, you will hear a chime and the WiFi indicator will ash.
3. Turn on and open the Bluetooth function on your phone to be able to pair to the unit.
4. When the device is powered on and ready to be connected, the connected Bluetooth device will show
automatically after opening the app. Click the "Add" button for connection.
5. Enter the WiFi information interface, then enter the password and click "Next" to continue.
POST-INSTALLATION
5
MRCOOL MTHP

mrcool.com 12
6. Enter the device connection interface after the progress bar is nished and the device will be connected
successfully.
POST-INSTALLATION
5
MRCOOL MTHP
MRCOOL MTHP
MRCOOL MTHP
MRCOOL MTHP
MRCOOL MTHP
MRCOOL MTHP
America/Chicago

mrcool.com13
5.2 Troubleshooting
Issue Possible Causes Solutions
The unit does
not work
There is no power.
Check that the unit is plugged in and the
outlet has power.
The ambient temperature is too low/high.
Only use the unit in a room with a
temperature between 45°F~95°F
(7°C~35°C).
In Cooling mode, the room temperature
is lower than the desired temperature. In
Heating mode, the room temperature is
higher than the desired temperature.
Adjust to the desired set point.
In dehumidication (Dry) mode, the
ambient temperature is low.
Make sure that the room temperature is
above 63°F (17°C).
There is direct sunlight.
Use curtains to reduce heat exposure
from the sun.
The cooling or heating
performance is poor
Doors or windows are open; there are a
lot of people in the space; or in Cooling
mode, there are other sources of heat.
Close doors and windows.
The lter is dirty. Clean the lter.
The air inlet or outlet is blocked.
Clear obstructions; make sure the unit is
installed as per the instructions.
The unit is leaking
The unit is not straight.
Use a level to check that the unit is
horizontal. If not, remove the unit from
the wall and straighten.
The drain pipe is blocked.
Check the drain pipe to ensure that it is
not blocked or constricted.
The compressor is not working Overheat protection is operating.
Wait for 3 minutes until the temperature
has lowered, then restart the machine.
The remote control is not working
The remote control is not aligned with the
direction of the remote control receiver.
Move the remote control closer to the
unit and make sure that the remote
directly faces the units remote control
receiver.
Dead batteries. Replace the batteries.
Note: If the recommended solutions do not work, please contact a technician or MRCOOL® at 270-366-0457 or at
POST-INSTALLATION
5

mrcool.com 14
5.3 Error Codes
Fault
Code
Description
Fault
Code
Description
F1 Compressor IPM error P8 Zero-crossing fault detection (indoor)
F2 PFC/IPM error PA Return air sensor temperature abnormal protection
F3 Compressor start error PC Coil tube overload protection (outdoor)
F4 Compressor running out of step PE Abnormal refrigerant circulation
F5 Location detection loop failure PH Exhaust temperature protection
F6 PCB communication error E0 Sensor on suction pipe error
F7 Coil sensor error (outdoor) E1 Temperature sensor error (indoor)
F8 Sensor on suction pipe error E2 Sensor error on indoor coil tube
FA Phase current overcurrent protection E3 DC fan feedback failure (indoor)
FE EE error (outdoor) E4 Communication error
FL Water-full protection E5 Water-splash motor error
P1 Overheat protection on top of the compressor E6 Temperature sensor error (outdoor)
P2 DC bus voltage undervoltage protection E7 Fan motor error (outdoor)
P3 AC input voltage protection E8 Fan feedback fault
P4 AC overcurrent EE EE error (indoor)
P5 AC undervoltage protection EA Reversing valve fault
P6 Coil tube overload protection (indoor) Eb Fluoride deciency protection
P7 Defrost protection on coil tube (indoor)
POST-INSTALLATION
5

Monoblock MTHP Series
The design and specications of this product and/or manual are subject to change without prior notice.
Consult with the sales agency or manufacturer for details.