Service and Troubleshooting
*RVS80*U
Single Stage Variable Speed Ultra-Low NOx Gas Furnaces and Accessories
Copyright © 2025 Daikin Comfort Technologies Manufacturing, Inc.
RS6621303r1
October 2025
TABLE OF CONTENTS
IMPORTANT INFORMATION ......................................... 2
PRODUCT IDENTIFICATION ......................................... 3
SYSTEM OPERATION .................................................... 5
SCHEDULED MAINTENANCE ...................................... 19
SERVICING ..................................................................... 21
CHECKING VOLTAGE ................................................. 22
CHECKING WIRING ..................................................... 22
CHECKING THERMOSTAT, WIRING .........................22
CHECKING TRANSFORMER AND CONTROL
CIRCUIT ........................................................................ 22
CHECKING AIR CIRCULATOR BLOWER MOTOR ... 23
CHECKING DUCT STATIC .......................................... 23
CHECKING TEMPERATURE RISE ............................. 24
CHECKING PRIMARY LIMIT CONTROL .................... 24
CHECKING AUXILIARY LIMIT CONTROL ................. 25
INDUCED DRAFT BLOWER MOTOR ......................... 25
CHECKING GAS VALVE (REDUNDANT) ................... 26
CHECKING GAS PRESSURE ..................................... 26
GAS MANIFOLD PRESSURE MEASUREMENT
AND ADJUSTMENT ..................................................... 27
CHECKING HOT SURFACE IGNITER ........................ 28
CHECKING PRESSURE TRANSDUCER (80% ULN) 28
CHECKING FOR DELAYED IGNITION ...................... 28
Pride and workmanship go into every product to provide
our customers with quality products. It is possible, however,
that during its lifetime a product may require service.
Products should be serviced only by a qualied service
technician who is familiar with the safety procedures
required in the repair and who is equipped with the proper
tools, parts, testing instruments and the appropriate service
manual. REVIEW ALL SERVICE INFORMATION IN THE
APPROPRIATE SERVICE MANUAL BEFORE
BEGINNING REPAIRS.
Do not bypass safety devices.
WARNING
This furnace may be paired with a cooling unit that uses
R-32 refrigerant. If the refrigeration unit paired with this
furnace does not use R-32, the R-32 function in the furnace
control board needs to be turned off. Please see the
electrical and the R-32 sections for more details.
Refrigerant systems other than 410A or R32 may require
an additional mitigation control board. Refer to the
installation manual of the indoor evaporator coil to
determine installation requirements for that supplier’s
refrigerant detection system.
WARNING
Only personnel that have been trained to install, adjust,
service, maintenance or repair (hereinafter, “service”)
the equipment specified in this manual should service the
equipment.
This equipment is not intended for use by persons
(including children) with reduced physical, sensory or
mental capacities, or lack of experience and knowledge,
unless they have been given supervision or instruction
concerning use of the appliance by a person responsible
for their safety.
Children should be supervised to ensure that they do not
play with the equipment.
The manufacturer will not be responsible for any injury
or property damage arising from improper supervision,
service or service procedures. If you service this unit, you
assume responsibility for any injury or property damage
which may result. In addition, in jurisdictions that require
one or more licenses to service the equipment specified in
this manual, only licensed personnel should service the
equipment. Improper supervision, installation, adjustment,
servicing, maintenance or repair of the equipment specified
in this manual, or attempting to install, adjust, service
or repair the equipment specified in this manual without
proper supervision or training may result in product
damage, property damage, personal injury or death.
WARNING
Brand
®
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.

IMPORTANT INFORMATION
2
CHECKING INTEGRATED IGNITION CONTROL
BOARDS ........................................................................ 28
CHECKING FLAME SENSOR ..................................... 29
TROUBLESHOOTING CHART ...................................... 30
WIRING DIAGRAMS ...................................................... 49
IMPORTANT NOTICES
RECOGNIZE SAFETY SYMBOLS, WORDS AND
LABELS
If the information in these instructions is not followed
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
- What to do if you smell gas:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING
Should overheating occur or the gas supply fail to shut
off, turn off the manual gas shutoff valve external to the
furnace before turning off the electrical supply.
WARNING
To prevent the risk of property damage, personal injury,
or death. Do not store combustible materials or use
gasoline or other flammable liquids or vapors in the
vicinity of this appliance.
WARNING
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
OUTSIDE THE U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.) Your telephone company will bill you for the call.
B10259-216
CO can cause serious illness including permanent brain
damage or death.
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
B10259-216
El monóxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
Las emisiones de monóxido de carbono pueden circular a través
del aparato cuando se opera en cualquier modo.
B10259-216
RISQUE D'EMPOISONNEMENT AU
MONOXYDE DE CARBONE
Cette ventilation est nécessaire pour éviter le danger d'intoxication
au CO pouvant survenir si un appareil produisant du monoxyde
de carbone continue de fonctionner au sein de la zone confinée.
This unit should not be connected to, or used in conjunction with, any devices that are not listed in the applicable product
specifications as acceptable for use with this unit or have not been tested and approved by the manufacturer. Serious
property damage or personal injury , reduced unit performance and/or hazardous conditions may result from the use of
devices that have not been approved or listed in the applicable product specifications as acceptable by the manufacturer.
WARNING

PRODUCT IDENTIFICATION
3
NOMENCLATURE
The model and manufacturing number are used for positive identication of component parts used in manufacturing.
Please use these numbers when requesting service or parts information.
G R V S 80 060 4 B U **
1 2 3 4 5,6 7,8,9 10 11 12 13,14
BRAND ENGINEERING
G - GOODMAN® BRAND Major / Minor Revisions
A - AMANA® BRAND
* Not used for inventory control
CONFIGURATION NOx
R - Upflow/Horizontal U - Ultra Low NOx
MOTOR CABINET WIDTH
V - Variable Spped ECM B - 17
1/2"
GAS VALVE MAXIMUM CFM
S - Single Stage 4 - 1600 CFM 5 - 2000 CFM
AFUE MBTU/H
80 - 80% AFUE 60 - 60,000 BTU/h
80 - 80,000 BTU/h
C - 21"

PRODUCT IDENTIFICATION
4
MODEL # MFG # DESCRIPTION
ARVS80*U
ARVS800604BU AA
ARVS800805CU AA
Amana ® Brand 80% Ultra-Low NOx Gas Furnace, Eligible for installaon in
California's South Coast Air Quality Management District (SCAQMD) and San
Joaquin Valley Air Polluon Control District (SJVUAPCD). This furnace complies with
the 14 ng/J NOx emission limit in SCAQMD Rule 1111 and SJVUAPCD Rule 4905.
This furnace is eligible for the SCAQMD Clean Air Furnace Rebate Program:
www.CleanAirFurnaceRebate.com. Up
flow/Horizontal Le and Right,
Induced Dra, Nidec variable speed ECM motor. Stainless Steel tubular heat
exchanger. 120 volt silicon nitride igniter. Le or right gas entry. Line voltage EAC
terminal
GRVS80*U
GRVS800604BU AA
GRVS800805CU AA
Goodman ® Brand 80% Ultra-Low NOx Gas Furnace, Eligible for installaon in
California's South Coast Air Quality Management District (SCAQMD) and San
Joaquin Valley Air Polluon Control District (SJVUAPCD). This furnace comp
lies with
the 14 ng/J NOx emission limit in SCAQMD Rule 1111 and SJVUAPCD Rule 4905.
This furnace is eligible for the SCAQMD Clean Air Furnace Rebate Program:
www.CleanAirFurnaceRebate.com. Up flow/Horizontal Le and Right,
Induced Dra, Nidec variable speed ECM motor. Stainless Steel tubular heat
exchanger. 120 volt silicon nitride igniter. Le or right gas entry. Line voltage EAC
terminal

SYSTEM OPERATION
5
Safety
Please adhere to the following warnings and cautions when
installing, adjusting, altering, servicing, or operating the
furnace.
To prevent personal injury or death due to improper
installation, adjustment, alteration, service or
maintenance, refer to this manual. For additional
assistance or information, consult a qualified installer,
service agency or the gas supplier.
WARNING
To prevent possible property damage, personal injury or
death due to electrical shock, the furnace must be located
to protect the electrical components from water.
WARNING
Charge (ESD) Precautions
NOTE: Discharge your body’s static electricity
before touching unit. An electrostatic discharge
can adversely affect electrical components.
Use the following precautions during furnace installation
and servicing to protect the integrated control module
from damage. By putting the furnace, the control, and the
person at the same electrostatic potential, these steps
will help avoid exposing the integrated control module to
electrostatic discharge. This procedure is applicable to both
installed and uninstalled (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch
the integrated control module or any wire connected
to the control prior to discharging your body’s
electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the
furnace near the control. Any tools held in a person’s
hand during grounding will be discharged.
3. Service integrated control module or connecting
wiring following the discharge process in Step 2.
Use caution not to recharge your body with static
electricity; (i.e., do not move or shue your feet, do
not touch ungrounded objects, etc.). If you come in
contact with an ungrounded object, repeat Step 2
before touching control or wires.
4. Discharge any static electricity from your body to
ground before removing a new control from its
container. Follow Steps 1 through 3 if installing the
control on a furnace. Return any old or new controls
to their containers before touching any ungrounded
object.
Product Application
This product is designed for use as a residential home gas
furnace. It is not designed or certied for use in mobile
home, trailer, or recreational vehicle applications.
In the U.S.A., this furnace can be used in the following
non-industrial commercial applications: Schools, Oce
buildings, Churches, Retail stores, Nursing homes, Hotels/
motels, Common or oce areas. In all applications, the
furnace must be installed per the installation instructions.
GRVS80*U, ARVS80*U, furnaces are ETL certied. All
*RVS80*U furnaces are built for use with Natural gas only
& may not be converted for use with LP gas.
To ensure proper installation, operation and servicing,
thoroughly read the installation and service manuals
for specics pertaining to the installation, servicing and
application of this product.
Possible property damage, personal injury or death due to
fire, explosion, smoke, soot, condensation, electrical shock
or carbon monoxide may result from improper installation,
repair, operation or maintenance of this product.
WARNING
To prevent property damage, personal injury or death due
to fire, do not install this furnace in a mobile home, trailer,
or recreational vehicle.
WARNING
To ensure proper furnace operation, install, operate,
maintain and service the furnace in accordance with the
installation, operation and service instructions, all local
building codes and ordinances. In their absence, follow
the latest edition of the National Fuel Gas Code (NFPA 54/
ANSI Z223.1), and/or CAN/CGA B149 Installation Codes,
local plumbing or waste water codes, and other applicable
codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1) can be obtained from any of the following:
American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley
Cleveland, OH 44131
A copy of the CAN/CGA B149 Installation Codes can be
obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W, 1R3

SYSTEM OPERATION
6
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE Guide” or “Manual
J-Load Calculations” published by the Air Conditioning
Contractors of America.
Do not operate the furnace with the rain cap removed as
recirculation of the flue gases may occur. Water may also
collect inside the larger combustion air pipe and flow to
the burner enclosure, Failure to follow this warning can
result in property damage, equipment damage, personal
injury or death.
WARNING
In upright upflow installations, the drain trap must be
mounted on the opposite side of the unit from the junction
box. This will reduce the risk of water reaching the junction
box in the even of a blocked drain condition. Failure to
follow these instructions cab result in possible property
damage, personal injury or death due to electrical shock.
WARNING
Quick Start Guide
NOTE: This furnace is equipped with a control
board that is capable of monitoring for R-32
refrigerant leaks in the indoor refrigeration unit.
Please verify that the R-32 sensor wire is plugged
in to the furnace control board before startup,
if applicable. If furnace is not paired with an R-32
Refrigeration system, the default settings in the
furnace control board will need to be changed.
Please see the R-32 section for additional
information.
R-32 Function
This furnace is equipped with a control board that is
capable of shutting o the gas heat and turning on the
blower fan in case of an R-32 refrigerant leak in the indoor
evaporator coil. If the cooling unit that is paired with this
furnace does not utilize R-32 as the refrigerant, the R-32
functionalities in the furnace control board will need to be
turned o for the furnace to run properly.
R-32 function on the control board is ON by default. The
R-32 function can be disabled through the furnace control
by entering the A2L Function Enabled menu and selecting
“no”. If A2L function is disabled, the furnace control will
ignore all A2L functions. If A2L function is enabled, the
control will monitor the R-32 sensor information.
To enter the A2L Function Enabled menu, press the left
or right button until LED displays “A2E”. Press the center
button and the LED will display the selected option (yes or
no). Press the left or right button to select one of the two
options and press the center button to conrm the option.
R-32 Sensor Wire Routing
IMPORTANT NOTE: Wiring routing must not
interfere with circulator blower operation, filter
removal or routine maintenance. Wire should
not be routed near hot surfaces and should be
protected from sharp edges. Extra precaution
should be taken to avoid routing near the outlet
flue pipe.
The R-32 Sensor wire coming from the indoor evaporator
coil will need to be routed into the furnace and connected
to the connection point on the furnace control board. This
wire should be routed alongside the thermostat wires
through the low voltage openings in the left or right side of
the furnace blower compartment. Please see the electrical
section for the location of the R-32 Sensor connection on
the control board.
The R-32 function on the furnace control board may need
to be enabled or disabled if any element of the installation
changes from the original setup. The specic scenario
will depend on each installation, so please refer to the
evaporator coil’s installation manual to verify what is
required for your setup. For example, if the furnace was
initially installed with an evaporator coil that utilized R-410A
refrigerant, and the coil is later replaced with one that uses
R-32 refrigerant, then R-32 function mode on the furnace
control board must be enabled, and the R-32 sensor wire
must be connected to the furnace control board.
Furnace Start-up
During furnace start up, the furnace control will identify the
connected R-32 sensor and will start monitoring the sensor
communication. A green LED located next to the sensor
connection will indicate if there is communication between
the furnace control and the R-32 sensor. The LED will be
ON during the duration of the startup and then will either
start blinking or turn OFF. The blinking LED signies that
communication with the R-32 sensor is present. The LED
OFF signies that there is no signal with the sensor.
If there are no alarms or faults, the furnace will go into
regular run mode after a warm up period. The furnace
control monitors the R-32 sensor once per second.
R-32 Refrigerant Leak
If the R-32 sensor on the indoor evaporator coil detects
a specied concentration of R-32 refrigerant, the furnace
will enter Mitigation Mode to dilute the refrigerant
concentrations in case of a leak. In Mitigation Mode, the
furnace will do the following:
1. Display the A2L Refrigerant Leakage error code
(EAL).
2. Shut down the gas operation.
3. Energize the optional ventilation and alarm outputs.
4. Run the fan at max CFM airow.

SYSTEM OPERATION
7
Once the R-32 sensor stops detecting a leak, the fan will
continue to run for 5 minutes. After the 5 minutes, if there
are no other alarms or faults, the control will de-energize
the optional ventilation and alarm outputs and then go back
to the original operating mode per the thermostat.
A2L Verification
The A2L Function Verication menu allows the installer to
verify if the R-32 function operates properly. This menu
simulates the refrigerant leak process and is only able to
be used when there are no active alarms or faults. To verify
the R-32 functions, enter the A2L Function Verication
menu and select “YES”. To enter the A2L Function
Verication menu, press the left or right switch until LED
displays “A2u”. Press the center switch and the LED will
display the selected option (yes or no). Press the left or
right switch to select one of the two options and press
the middle switch to conrm the option. Once “YES” is
selected, the furnace will do the following:
1. Display the A2L Refrigerant Leakage code (EAL)
2. Shut down the gas operation
3. Energize the optional ventilation and alarm outputs.
4. Run the fan at max CFM airow
The control will exit the verication function if:
1. The 5 minute timeout expires or
2. An alarm or fault is detected or
3. The user turns OFF the A2L Function Verication.
NOTE: To verify gas heating operation shuts down,
give furnace a call for heat before entering into
A2L Function Verification.
1. Connect all necessary thermostat wires to the
thermostat connector on the furnace control (only
available connections on the furnace are R & C for
power, Y for Cooling Calls, W for Heating Calls, G
for Fan Calls, Dehum for Dehumidication Calls.
Furnace will control staging of indoor unit and
outdoor unit automatically based on these inputs).
2. Make sure thermostat is set to single stage heat /
single stage cool mode. When a cool call is given,
24VAC should be applied to the Y terminal (G will
have 24VAC as well if a G wire is installed). When
a heat call is given 24VAC should be applied to the
W terminal (G may have 24VAC as well if a G wire
is installed). Even if a heat pump is installed, do not
setup the thermostat in heat pump mode. Single
stage heat / single stage cool mode is all that is
required for all applications. See rest of manual for
any exceptions. Do not setup thermostat in multi
stage mode either, it is not necessary.
3. For communicating 2 stage AC/HP or inverter AC/
HP outdoor units, connect the 1&2 wires between
the indoor and outdoor unit. It is recommended for
2 stage applications that a separate transformer
be installed in the outdoor unit to provide 24VAC to
the outdoor control. R&C can be used between the
indoor and outdoor in 2 stage AC application but only
if there isn’t already a transformer installed in the
outdoor unit.
4. Turn on power to Indoor and Outdoor units
5. Charging outdoor unit: Provide a cooling call (Y
or Y+G) – this initial cooling call after the power is
turned on will run the outdoor unit at full capacity until
the call is removed. Use this mode for charging. If
system is running low stage cooling just cycle power
and provide a cool call again to ensure full capacity
cooling.
6. System Testing: Download the CoolCloudHVAC
phone application (see pages 31 and 32)and use it
to test all operations of both indoor and outdoor units.
7. Conrm thermostat heat (W or W+G) and cool (Y
or Y+G) function properly and the system is turning
on in the correct mode. The internal algorithms will
constantly be adjusting the staging times / cooling
capacities based on load changes to the space.
NOTE: If a heat pump is installed it will be treated
as a priority heat for a W call. To test gas heat only,
without waiting for the system to stage between the
heat pump and furnace, disconnect communications
between the indoor and outdoor unit before running
the heating test.
Control System – General Information
The furnace contains internal logic to control equipment
staging. An adjustable target runtime is available (range
from 1 to 240 minutes) and set through the appropriate
system menu. The system will constantly be adjusting
staging in an eort to satisfy the thermostat call for cooling
(Y only) or heating (W Only) as close to the set target
runtime as possible. See information below for setting
options.
Comfort Setting Menu (CFS): There are 6 options available
in the Comfort Setting Menu which impacts both the
System Target Runtime and Dual Fuel Operation. Dual
Fuel operation adjustments only apply if a communicating
heat pump is installed. Comfort Setting Options 1 – 5 have
set values for the System Target Runtime and option 6
enables additional menus to customize all comfort settings.
See list below for the System Target Runtimes associated
with the rst 5 Comfort Settings. These rst 5 options are
setup to help satisfy the thermostat slower or faster based
on the selection where option 1, with a 10 minute Target
Runtime, is attempting to satisfy much faster than option 5,
with a 30 minute Target Runtime.
System Target Runtime:
Comfort Setting Option 1) 10 Minute System Target
Runtime
Comfort Setting Option 2) 15 Minute System Target
Runtime
Comfort Setting Option 3) 20 Minute System Target
Runtime
Comfort Setting Option 4) 25 Minute System Target
Runtime
Comfort Setting Option 5) 30 Minute System Target
Runtime

SYSTEM OPERATION
8
Dual Fuel Adjustment: This system will automatically
determine if the heat pump is capable of satisfying the
thermostat in the selected System Target Runtime. If the
heat pump is unable to satisfy in the selected time, dual
fuel settings will determine how many attempts should be
given to the heat pump before temporarily locking it out and
using the furnace. These dual fuel settings also determine
at what time the system should remove the temporary heat
pump lockout and run the heat pump again.
There are four adjustable items associated with Dual Fuel
control. In the same way as the System Target Time, each
of these items have defaulted values for Comfort Settings 1
– 5. Only when Comfort Setting 6 is selected will each item
be available for full adjustment.
1. Stage Up Percent (7 segment menu SUP): This
is a value that determines how far past the target
runtime the system should continue running the
heat pump before transitioning to the furnace. For
example, assume this menu was set to 20% with a
target runtime of 20 minutes. If the thermostat did
not remove the heating call after 20 minutes, the
system would allow for an additional 20% heat pump
run (20% of the 20 minute target is an additional 4
minutes). In this case, the system would transition
to gas heat after 24 minutes if the thermostat call
was still present. Each time this occurs, the system
records this as a strike against the heat pump (the
strike is important when looking at the Over Target
Threshold).
2. Over Target Threshold (7 segment menu Ott): If
the heat pump has consecutively transitioned to gas
heat for the selected Over Target Threshold amount
of times, meaning for this many consecutive cycles
it has been unable to satisfy the target time by itself,
then the heat pump will be temporarily locked out
and the furnace will become the primary heat source.
3. Stage Down Percent (7 segment menu SdP): This
only applies when the heat pump is in a temporary
lockout condition. In this case, the system will be
trying to determine when the best time is to remove
the lockout and run the heat pump again. To
determine the best time to remove the heat pump
lockout the system looks at how easily the furnace
is able to satisfy the thermostat using Low Stage
Gas Heat Only. Assume this setting is 15% and the
target time is 20 minutes. If Low Stage Gas Heat
can satisfy the thermostat in less than 17 minutes
(20 minutes - 15% = 17 minutes) then the algorithm
records a strike against the gas furnace (This strike
is important when looking at the Under Target
Threshold).
4. Under Target Threshold (7 segment menu Utt):
If the furnace is able to satisfy the thermostat using
Low Stage Gas Heat Only for the selected number
of consecutive cycles the heat pump lockout will
be temporarily removed. The heat pump will then
be used during the next cycle. If the heat pump
can satisfy the thermostat in less than the System
Target Runtime the temporary heat pump hold will be
completely removed and the heat pump will become
the primary heat source again. if it fails to do so, the
strike count against the furnace will be reset and
the furnace will remain the temporary primary heat
source until the Under Target Threshold is reached
again.
The system will automatically make adjustments in an
attempt to satisfy the thermostat as close to this target
runtime as possible. After a power cycle or mode change
(cooling to heating or heating to cooling) the system will
run full capacity for the selected mode during the rst
thermostat call. Based on the selected target runtime and
how long the initial cycle takes to satisfy the thermostat,
the control algorithm will adjust the system stage times for
a 2 stage unit or the capacity demand percentage for an
inverter / modulating unit for the next cycle. NOTE: Actual
runtimes may change depending on variations of load
throughout the day.
The following table shows the default values for all
Comfort Setting Options (1 – 5)
Comfort
Setti ng
Opti on
Target
Ti me
(Minutes)
Stage Up
Percentage
(%)
Stage Down
Percentage
(%)
Over Target
Threshhold
(Strike Count)
Under Target
Threshhold
(Strike Count)
1 10 20 20 2 10
2 15 20 20 4 8
3 20 20 20 6 6
4 25 20 20 8 4
5 30 20 20 10 2
The following table shows the ranges for each of item when
the adjustable Comfort Setting Option 6 is selected. The
table shows the minimum value, the maximum value and
the defaulted value. All items can be adjusted up or down
by increments of 1 which provides full exibility for all items.
NOTE: It is critical that these numbers be set
properly. If Comfort Setting option 3 is desired
but a target time of 60 is preferred, select
Comfort Setting Option 6 to enable all the
adjustable menus, set the Target Time to 60 and
make sure the other menus are set to match that
of Comfort Setting Option 3.
Menu Minimum Value Maximum Value Default Value
Target Time (t9t) 1 minute 240 minutes 60 minutes
Stage Up Percent (SUP) 0% 100% 20%
Stage Down Percent (SdP) 0% 100% 20%
Over Target Threshold (Ott) 1 strike 254 strikes 20 strikes
Under Target Threshold (Utt) 1 strike 254 strikes 20 strikes
Circulator Blower Speed
The Airow quantity is displayed as a number on the three
7 segment displays, rounded to the nearest 100 CFM. The
display alternates airow amount and the system operating
status.

SYSTEM OPERATION
9
Each furnace has a “Maximum CFM” it is capable of
providing. All fan operations (Constant CFM, Cooling
Airow Proles, Low and High Stage gas heat airow,
outdoor Air Conditioner / Heat Pump Airow, etc.) are
based o of multipliers which are percentages of this
maximum CFM. Max CFM is as follows:
3 Ton Models 1400 CFM
4 Ton Models 1760 CFM
5 Ton Models 2200 CFM
Setup Furnace Airow: Adjust the Gas Heating
Airow menu (gAF) setting to the desired percentage
of maximum airow. In most cases the default gas heat
airow will provide a temperature rise near the middle of
the acceptable range. High Stage CFM can be calculated
by the following equation: CFM = Max CFM * Selected
Heating Airfow Percentage.
For Communicating Outdoor Units: Main airow
adjustment is not required. The Outdoor unit will determine
the appropriate amount of indoor airow to request. Airow
Trims can be made if desired.
For Non-Communicating outdoor units, determine the
proper airow (based o tonnage of) the outdoor unit. Most
cooling systems are designed to work with airow between
350 and 450 CFM per ton. 400 CFM/TON is the industry
standard. Once desired airow has been determined, see
Tonnage / Airow table to identify the Tonnage Selection
that is closest to the desired airow. This table is based on
400 CFM per ton where Airow = (400 CFM) x (Selected
Tonnage).
EXAMPLE: If 1520 CFM is the desired airow the Tonnage
Selection that matches this is 3.8.
Enter the Tonnage (ton) menu either by using the on board
push buttons or phone application and select the Tonnage
Selection you identied. NOTE: Trim is also available if
additional adjustment is required.
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
1 400
2.3 920 3.6 1440 4.9 1960
1.1 440 2.4 960 3.7 1480 5 2000
1.2 480 2.5 1000 3.8 1520 5.1 2040
1.3 520 2.6 1040 3.9 1560 5.2 2080
1.4 560 2.7 1080 4 1600 5.3 2120
1.5 600 2.8 1120 4.1 1640 5.4 2160
1.6 640 2.9 1160 4.2 1680 5.5 2200
1.7 680 3 1200 4.3 1720 5.6 2240
1.8 720 3.1 1240 4.4 1760 5.7 2280
1.9 760 3.2 1280 4.5 1800 5.8 2320
2 800 3.3 1320 4.6 1840 5.9 2360
2.1 840 3.4 1360 4.7 1880 6 2400
2.2 880 3.5 1400 4.8 1920
Cooling Airflow Ramping Profiles
The multi-circulator blower also oers several custom
ON/ OFF ramping proles. These proles may be used to
enhance cooling performance and increase comfort level.
The ramping proles are selected using the Cooling Airow
Prole menu (if push buttons are used, use the CAP menu
to select the desired prole). Refer to the bullet points
below for a description of each ramping prole.
OFF
100% CFM
Cooling Demand
100% CFM
1 min
OFF
• provides only an OFF delay of one (1) minute at 100% of the cooling demand Profile A(1)
Cooling Demand
50% CFM
1/2 min
100% CFM
100% CFM
1 min
OFF
OFF
• ramps up to full cooling demand airflow by first stepping up to 50% of the full
demand for 30 seconds. The motor then ramps to 100% of the required airflow. A one (1)
minute OFF delay at 100% of the cooling airflow is provided.
Profile B(2)
1 min
100% CFM85% CFM
7 1/2 min
Cooling Demand
100% CFM
OFF
OFF
• ramps up to 85% of the full cooling demand airflow and operates there for
approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile C
also has a one (1) minute 100% OFF delay.
Profile C(3)
85% CFM
7 1/2 min
100% CFM
50% CFM
1/2 min
50% CFM
Cooling Demand
1/2 min
OFF
OFF
• ramps up to 50% of the demand for 1/2 minute, then ramps to 85% of the full
cooling demand airflow and operates there for approximately 7 1/2 minutes. The motor
then steps up to the full demand airflow. Profile D has a 1/2 minute at 50% airflow OFF delay.
Profile D(4 or 5)
In general lower heating speeds will: reduce electrical
consumption, lower operating sound levels of the blower,
and increase the outlet air temperature delivered to the
home if heatmode is running. If cooling mode is running
the same airow adjustment will decrease the outlet air
temperature delivered to the home. The speeds available
allow the blower performance to be optimized for the
particular homeowner’s needs.
Low Voltage Wiring - General Information
The Furnace functions with any thermostat that can be
congured to provide 24VAC on Y for cooling calls and
24VAC on W for Heating calls. Based on these simple
inputs, internal algorithms will decide how to control two
stages of furnace heat in addition to any single or multi
stage outdoor heating / cooling operation (the algorithms
will handle dual fuel multi-stage systems as well). The
thermostat must be setup to provide only a Y call when
cooling is required and only a W call when heating is
required. This is generally accomplished by selecting single
stage heat / single stage cool mode during setup (if setup
is required). Do not set thermostat to heat pump operation
as system will not operate properly.
NOTE: The only exception is if a single stage
non-communicating Heat Pump is connected to
the furnace. Refer to Non-Communicating Single
Stage Heat Pump diagram for details.

SYSTEM OPERATION
10
Thermostat connections to the control board are R, C, G,
W, Y & Dehum. Provided the thermostat does not require a
common wire as few as two thermostat wires may be used
for heat only (R and W) or cool only (R and Y) systems. A
minimum three thermostat wires may be used for heating
and cooling systems (R, W and Y). Refer to thermostat
wiring diagrams below for your system conguration.
Low voltage connections can be made through either the
right or left side panel of the furnace. Thermostat wiring
entrance holes are located in the blower compartment.
120 VAC HUM
120 VAC EAC
120 VAC Accessories - Accessories Wiring
Figure 1
Low Voltage Ventilation
The Ventilation connections provide dry contact for eld
ventilator wiring connections. These connections are
normally open and energize during the R-32 fault/alarm
condition. A VT IN and a VT OUT connectors are provided
and are shown in the image below.
Low Voltage A2L Alarm
The A2L alarm connection provides 24VAC for eld alarm
wiring connections. These connections are normally open
and energize during the R-32 fault/alarm condition. An A2L
Alarm connector is provided and is shown in the image
below.
24 VOLT A2L
ALARAM
(OPTIONAL)
24 VOLT
VENTILATION
R-32
24 VAC Accessories - Accessories Wiring
Figure 2
For gas heat only operations (no outdoor unit installed)
the thermostat must be setup to provide a single stage W
call when heating is required. See Gas Heat Only wiring
diagram for wiring instructions.
R
C
G
W
Y
Dehum
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
W
Y
Dehum
24 VAC
Thermostat
1
2
R
C
Gas Heat Only
Figure 3
Low Voltage Wiring-Communicating Outdoor Unit
Internal logic will control staging of all multi stage
equipment (2 stage AC/HP units and Inverter AC/HP units).
The thermostat is only required to provide a single stage
heat / cool call and fan or dehumidication call during
operation.

SYSTEM OPERATION
11
Two wires are required between the indoor unit and
outdoor unit on the 1 and 2 terminals. It is recommended to
install a separate transformer with all 2 stage outdoor units
to reduce the power draw on the indoor transformer.
4 wires (R,C for power and 1, 2 for communications) can
be used for AC applications. See wiring images for details.
Do not connect R & C between the indoor unit and the
outdoor unit if there is already a transformer installed in the
outdoor unit providing 24VAC to the outdoor control. In this
case, just use 1 and 2 terminals for communications.
R
C
G
W
Y
Dehum
Optional
Optional
Optional if
feature
supported by
thermostat
L1
L2
INDOOR
BOARD TERMINAL
CONNECTIONS
OUTDOOR
BOARD TERMINAL
CONNECTIONS
OUTDOOR
TRANSFORMER
24VAC
240V
GROUND RECOMMENDED
(FIELD PROVIDED)
1
2
R
C
R
C
G
W
Y
Dehum
1
2
R
C
Note: for 2 Stage Air Conditioners, R & C wires can
be used between the indoor and outdoor units provided
a transformer is not already installed in the outdoor unit.
For 2 stage heat pumps, a transformer is always required
in the outdoor unit (R & C connections cannot be used)
Communicating Two Stage Air Conditioner or Heat Pump
Figure 4
1
2
R
C
R
C
G
W
Y
Dehum
Optional
Optional
Optional if
feature
supported by
thermostat
INDOOR
BOARD TERMINAL
CONNECTIONS
OUTDOOR
BOARD TERMINAL
CONNECTIONS
1
2
R
C
R
C
G
W
Y
Dehum
24 VAC
Thermostat
Communicating Inverter Air Conditioner or Heat Pump
Figure 5
Low Voltage Wiring-Non-Communicating
Outdoor Unit
When using the furnace with a single stage non-
communicating air conditioner or heat pump use the wiring
methods shown. When using a single stage air conditioner,
the thermostat must be setup for single stage heating and
single stage cooling mode. When using a single stage heat
pump, the thermostat must be setup for dual fuel operation
where the reversing valve is energized in cooling mode
(see Non-Communicating Single Stage Heat Pump wiring
diagram). In both cases airow must be selected using
the tonnage menu where Airow = (400 CFM) x (Selected
Tonnage). Tonnage values range from 1 to 6 in 0.1
increments.
NOTE: Airflow will not go above the system Max
CFM. If the tonnage value selected generates an
airflow value above the Max CFM, the system will
cap this value and not provide any more airflow
than the Max CFM.
R
C
G
W
Y
Dehum
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
W
Y
Dehum
24 VAC
Thermostat
1
2
R
C
Heat Pump
Optional
R
C
W
Y
This is the only
case where setting the
thermostat to heat pump
mode is acceptable.
Non-Communicating Single Stage Heat Pump
Figure 6
R
C
G
W
Y
Dehum
Optional
Optional
Optional if
feature
supported by
thermostat
INDOOR
BOARD TERMINAL
CONNECTIONS
1
2
R
C
R
C
G
W
Y
Dehum
C
Y
Remote
Condensing Unit
(Single-Stage Cooling)
24 VAC
Thermostat
Non-Communicating Single Stage A/C
Figure 7
Dehumidification
The control board is equipped with a 24 volt dehum
input in the thermostat wiring connector to be used with
a thermostat or dehumidistat. Dehumidication mode
allows the air handler’s circulator blower to operate at a
slightly lower speed (85% of calculated speed) during a
combined thermostat call for cooling and thermostat call for
dehumidication or dehumidistat call for dehumidication.
This lower blower speed enhances dehumidication of the
conditioned air as it passes through the AC coil. If using the
dehum input with a thermostat, congure the thermostat
to energize this terminal when dehumidication is desired.
If using an external dehumidistat, connect it between the
R and Dehum terminals. The dehumidistat must operate
on 24 VAC and utilize a switch which closes on humidity
rise. Refer to the low voltage wiring diagrams for additional
wiring details.

SYSTEM OPERATION
12
R
C
G
Y
Dehum
Dehumidistat
(close on humidity rise)
Dehumidistat (Close on Humidity Rise)
Figure 8
Fossil Fuel Applications
This furnace can be used in conjunction with a heat pump
in a fossil fuel application. A fossil fuel application refers to
a combined gas furnace and heat pump installation which
uses an outdoor temperature sensor to determine when to
run the heat pump or gas furnace.
For non-communicating single stage heat pump
installations a fossil fuel kit can be used. Follow the wiring
guidelines in the fossil fuel kit installation instructions.
All furnace connections must be made to the furnace
integrated control module and the “FURNACE” terminal
strip on the fossil fuel control board.
For Fossil Fuel systems the heat pump is given priority
when a compressor balance point lockout condition is not
present. Transitions from primary heat pump heating to
backup gas heating will result in full capacity operation
during the rst thermostat call. The furnace PCB algorithms
will then continuously adjust the stage times or the percent
capacity after the initial call in an attempt to satisfy the
thermostat at the target runtime.
Automatic Fossil Fuel Adjustment: If both compressor
balance point and backup heat balance point lockouts are
not present, the furnace algorithms will determine if the
heat pump is capable of satisfying the thermostat in the
selected target runtime. If the heat pump is not capable
of this it will be locked out until the furnace can satisfy
the thermostat, under the target runtime, while running
completely in low stage. At that point, an attempt will be
given to the heat pump and a decision made to keep using
gas heat or to transition back to the heat pump.
120 Volt Line Connection of Electronic Air
Cleaner
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
The accessory load specications are as follows:
EAC 1.0 Amp maximum at 120 VAC
The furnace integrated control module is equipped with
a line voltage accessory terminal for controlling power
to an optional eld supplied electronic air cleaner or any
device required to operate in parallel with a circulating fan
demand.
To connect an electronic air cleaner using the line voltage
EAC terminal:
• Turn OFF power to the furnace before installing any
accessories.
• Follow the air cleaner manufacturers’ instructions
for locating, mounting, grounding, and controlling
accessories. Utilize 1/4” quick connect terminals to
make accessory wiring connections to the furnace
integrated control module.
• Connect the hot terminal utilized for accessory
operation to the EAC terminal and the neutral side
of power to NEUTRAL bus on the integrated furnace
control or the neutral connection in the furnace
junction box.
• All eld wiring must conform to applicable codes.
• Connections should be made as shown.
• If it is necessary for the installer to supply additional
line voltage wiring to the inside of the furnace, the
wiring must conform to all local codes, and have a
minimum temperature rating of 105°C.
• All line voltage wire splices must be made inside the
furnace junction box.
Auxiliary Alarm Switch:
The control is equipped with a 24VAC Aux Alarm to be
used for a condensate switch install (designated by
“Condensate” on the control). These contacts could also
be used with compatible CO2 sensors or Fire Alarms. By
default, an AUX switch is normally closed and opens when
the water level in the evaporator coil base pan reaches an
undesirable level. The control will respond by turning o
the outdoor condensing unit and display EEd. If the AUX
switch is detected closed for 30 seconds, normal operation
resumes and error messages are no longer displayed.

SYSTEM OPERATION
13
Key Mitigations:
1. Full featured TS (dehum & overcool)
2. Connect G and dehum wire correctly
3. Dehumidistat
Dehumidification Control Options
1) Install Dehum wire
and DO NOT install G
Wire
2) Install Dehumidistat
in living space or
return duct
Is there a setting in the
thermostat to enable
Dehum without fan? (G)
Yes
No
During a call for Dehum,
does the thermostat
provide 24V to Dehum, Y,
and G?
Yes
No
Choose that setting
Wire the system and test
functionality
Yes
No
Wire the system and
test functionality
Dehumidification Control Options
Dry Environment
Yes
No
Install any 24VAC
thermostat on the
market - Use Y, W, G
signals
Thermostat has a Dehum or
Configurable terminal with
Dehum option
Yes
No
Does your thermostat have a
whole house Dehumidifier
setting?
Install Dehumidistat in
living space or return
duct
If the Dehumidistat
opens on a rise on
humidity, then you
will set Dehum logic
to Low via Coolcloud
app or push buttons
If the Dehumidistat
closes on a rise in
humidity, then you
will set Dehum logic
to High via Coolcloud
app or push buttons
Thermostat only sends Dehum + G on a
call for Dehum
A Dehumidistat needs to be installed in
the living space or return duct
If the Dehumidistat opens
on a rise on humidity,
then you will set Dehum
logic to Low via Coolcloud
app or push buttons
If the Dehumidistat closes on
a rise in humidity, then you will
set Dehum logic to High via
Coolcloud app or push buttons

SYSTEM OPERATION
14
CoolCloudHVAC Phone Application – General
Information
Examples of CoolCloud HVAC Phone Application
Screens
NOTE: Actual screen may look different based on
the device being used.
This furnace is Bluetooth
®
ready and functions with
a custom phone application designed to improve the
setup / diagnostic experience of the installing contractor.
Users can see specic model information, review active
diagnostic error codes, observe system status during
operation, make system menu adjustments such as the
target runtime, add site visit notes and run system testing
of all operational modes (heat / cool / fan) directly from
the phone. The phone application is also capable of
directly updating the furnace software anytime updates are
available (the application will automatically notify the user
if updates are available). Software update time could take
approximately 15 minutes to complete. The phone must
remain within Bluetooth range for only the download step
of an update. The user will be notied once the download
is completed and installation begins. At this time the phone
can be removed from the Bluetooth range if necessary
(NOTE: if the phone is out of range, the user will not know
when the installation has completed or what the existing
status of the installation is).
The Bluetooth® word mark and logos are registered
trademarks owned by Bluetooth SIG, Inc., and any use of
such marks are under license.
Download the CoolCloud Phone Application and create an
account to get started. A Wi-Fi/Cellular connection will be
required for account setup.
Connecting Phone Application to Furnace
When in close proximity to the furnace, the phone
application will detect the Bluetooth Network being
broadcasted by the system. Once the Bluetooth network
is selected by the user, due to security reasons, the user
will be prompted for a 3 digit access code before system
information can be displayed. The 3 digit code will be
displayed on the three seven segment displays of the
furnace control board. A sightglass is located close to the
control board that can be used to see these digits. The
user must enter the access code into the phone application
when prompted to do so in order to gain access to system
information. 3 failed entry attempts will result in a new code
being displayed on the control. If all 3 digits are not visible
from the sight glass, the user has two options to connect.
Option 1) Perform thermostat task as instructed by the
phone application to gain access. The following steps will
explain what this task involves.
• Step 1, ensure the thermostat is in an idol state (no
cool, heat or fan calls). To do this, set the thermostat
fan mode to Auto (not ON) and then remove any
active heat / cool calls. This task needs to be
completed within 5 minutes of the process beginning.
• Step 2, provide any 24VAC call to the control from
the thermostat (cooling, heating or fan will work). This
task must occur within 8 minutes after the Step 1 is
complete.
• Step 3, remove the call that was provided during Step
2. This task must be completed within 1 minute after
the call is provided during Step 2.
If the phone remains within Bluetooth range during the
three steps, the user will be notied when each step has
been completed and informed about what to do next. If the
user is not within Bluetooth range during this process the
phone application will still provide instruction about what
tasks to complete. After all 3 steps have successfully been
completed, the user will have access to system information
once in range.
Option 2) Remove the furnace door, ensure the control has
power and then read the 3 digits. The code will temporarily
remain active after a power cycle so the door can put
back on before making the connection if desirable. NOTE:
power will be cycled to the control board with this option. If
it is not desirable to cycle power to the unit for diagnostic
purposes Option 1 may be a better method to connect.
At power-up, the furnace control will display the unit
address (a two digit number) on the 2nd and 3rd characters
of the three seven segment displays. After the furnace
control has completed its’ internal start-up routine, the
furnace control will display the Status Menu.

SYSTEM OPERATION
15
The control board will display “Id L” while in idle (stand-by)
mode waiting for a call from the thermostat. The furnace
control is now ready to receive inputs from the room
thermostat.
The furnace control board will detect any compatible
communicating outdoor unit connected to it. Items that
appear in the main menu will vary accordingly. Example,
you will not see heat pump specic menus unless a
compatible heat pump is detected by the furnace control.
Push Buttons
Three push-buttons on the control board may be used to
navigate menus and select options. The three buttons are
labeled Left, Center and Right. The center button is used
to enter into the option menu and make the selection, the
left and right buttons are used to browse the main menu
and option menus. When the center button is pressed in
the main menu, the furnace control will go to the option
menu and display the default or previously-selected
option. Pressing the left or right button will display the next
available option. When the next adjustable or selectable
option is displayed, the furnace control will ash the option
with ½ second ON and ½ second OFF indicating the option
has not yet been selected.
To select an option; press and release the center button to
stop the current option from ashing. When the option has
stopped ashing, press the center button again to select
that option.
While navigating through options; If no buttons are
pressed during a 30 second time period, the display will
time-out and return to the Status Menu. Simultaneously
pressing & releasing any two buttons will also return the
furnace control back to the Status Menu. If the previously
displayed option was not selected and a timeout occurs,
the displayed option will not be stored in control memory as
a selected option.
The Status Menu includes the following items:
• The operation mode
• Blower CFM (if blower is running)
• Humidication/Dehumidication mode (if active)
• Ventilator operation (if active)
• Any active fault codes
Menu items will appear in rotation as follows:
• Each item is ON for 2 seconds
• OFF for 1 second
• Then to the next item
Example of Menu Navigation & Option Change
This is an example for how to use the push buttons to
make a change to the constant fan speed.
Cool Cloud HVAC Phone Application
1. When looking at the Furnace Control, the three
7 Segment displays (located just above the push
buttons) will be displaying system status. System
status includes the current modes of operation,
airow and any active error codes.
2. Press and release the Right Button (This will cycle
through the menus in one direction. Pressing the
Left Button would cycle through the menus in the
opposite direction. For this example, the right button
will be used).
3. The screen will now display Menu F10 (Last 10
Faults).
4. Press and release the Center Button. The center
button is used to enter menus and make selections
within menus.
5. What will be displayed is the currently selected fan
only percentage. For this example the assumption
is that this currently selected fan only percentage is
25% and changing this to 45% is the objective.
6. Press and Release the Right button. The screen
will change to 35 and start ashing. The ashing
indicates the displayed option has not been selected
yet.
7. Press and Release the Right button again. The 7
segment displays will continue ashing but will now
display 45.

SYSTEM OPERATION
16
8. Press and Release the Center Button again. The 45
being displayed will stop ashing. To then complete
the selection process and make 45 the ocial fan
only setting Press and Release the Center Button for
the last time. This nal step will jump the user back to
the main menu list and FSd will be displayed again.
9. The constant fan multiplier has now been changed
from 25 to 45.
Airow Display
When the blower is running the CFM will be displayed in
Status Menu. The rst 7 segment character will display “A”.
The second & third characters will display the actual CFM
divided by 100. The actual CFM will display rounded up or
down to the nearest 100 CFM as follows:
• 550 to 649 CFM display as “A06”
• 1150 to 1249 CFM display as “A12”
Alarm Display
If an active alarm is present, the alarm code shall be report-
ed in Status Menu starting with “E” and following with the
appropriate two digit alarm code.
Clearing Faults
While in the Last 10 Faults option menu, push & hold the
center button for 5 seconds. This will clear all non-active
alarm(s) in the Last 10 Faults menu. The display will ash
three times to conrm faults have been cleared.
Learn Menu
Using this option resets the communicating network which
will cause the furnace to discover what devices are present
on ClimateTalk™ network. This menu will not appear when
the furnace control is connected to a Non-Comm OD unit.
Code Release Number Menu
This is a reference only menu to display the rmware
release revision numbers for each micro-controller.
Constant Fan Speed Menu
This menu allows for adjustment of the multiplier for
constant fan operation in 10% increments. Each furnace
has a “Maximum CFM” determined by motor HP. All fan
operations are based o of multipliers which are percentag-
es of this number. Max CFM is shown below. The default
constant fan multiplier is 25%.
Model Max CFM
3 Ton Models 1400
4 Ton Models 1760
5 Ton Models 2200
Gas Heat Airow Multiplier Menu
The menu is used to change the gas heat airow multiplier
for gas heat operation. In most cases the default gas heat
airow will provide a temperature rise near the middle of
the acceptable range. The multiplier will be expressed by
the 2nd & 3rd characters of the display as a percentage of
max CFM.
Gas Heat Fan O Delay Menu
The default setting is 90 seconds. The available adjustment
range is from 30 to 180 seconds in 30 second increments.
Gas Heat Fan On Delay Menu
The default setting is 30 seconds. The available adjustment
range is from 5 to 30 seconds in 5 second increments.
Gas Heat Trim Factor Option Menu
Gas Heat airow may be trimmed from -10% to +10% in
2% increments.
Gas Heat Stage Multiplier Menu (CFM)
This menu allows adjustment of the low re CFM multiplier.
The default CFM for low re is 70% of high re.
Gas Pressure Test Menu
This menu allows 100% ring rate be locked in to check
gas valve pressure.
CAUTION
To prevent unreliable operation or equipment damage, the
inlet gas supply pressure must be as specified on the unit
rating plate with all other household gas fired appliances
operating.
INLET GAS SUPPLY PRESSURE
Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c.
NORMAL SEQUENCE OF OPERATION
Power Up
• 120 VAC power applied to furnace.
• Integrated ignition control performs internal checks.
• The control board will display I D L. awaiting a call
from the thermostat.
• Integrated ignition control monitors safety circuit
continuously.
• Furnace awaits call from thermostat.

SYSTEM OPERATION
17
Heating Mode
The normal operational sequence in heating mode is as
follows:
• R and W thermostat contacts close, initiating a call for
heat.
• Integrated control module performs safety circuit
checks.
• Pressure Sensor Verication: The control operates
the inducer in a manner to verify the pressure sensor
null value and span operation are within specication.
If the system is operating correctly, this test takes
only a few seconds. If the system is not functioning
properly, the control times out after a maximum 90
seconds and display the proper fault code.
• Induced draft blower is energized for 30 second
prepurge.
• Igniter warm up begins after 30 second prepurge
expires.
• Gas valves open at end of igniter warm up period,
delivering gas to burners and establishing ame.
• Integrated control module monitors ame presence.
Gas valve will remain open only if ame is detected.
• Circulator blower is energized on high heat speed
following a xed 30 second blower on delay.
Electronic air cleaner terminal is energized with
circulator blower.
• Furnace operates; integrated control module monitors
safety circuits continuously.
• R and W thermostat contacts open, completing the
call for heat.
• Gas valve closes, extinguishing ame.
• Induced draft blower is de-energized following a thirty
second post purge.
• Circulator blower continues running for selected heat
o delay period factory set at 120 seconds. If required
this can be changed in the eld.
• Electronic air cleaner is de-energized.
• Furnace awaits the next call from thermostat.
Cooling Mode
The normal operational sequence in cooling mode is as
follows:
• R, Y and G thermostat contacts close, initiating a call
for cool.
• Integrated control module performs safety circuit
checks.
• Outdoor fan and compressor are energized.
• Circulator blower is energized on cool speed following
a xed six second on delay. If required this can be
changed in the eld to 45 seconds. Electronic air
cleaner terminal is energized with circulator blower.
• Furnace circulator blower and outdoor cooling unit
run, integrated control module monitors safety circuits
continuously.
• R, Y and G thermostat contacts open, completing the
call for cool.
• Outdoor fan and compressor are de-energized.
• Circulator blower is de-energized following a xed
forty ve second cool o delay period. Electronic air
cleaner terminal is de-energized.
• Furnace awaits the next call from thermostat.
Fan Only Mode
The normal operational sequence in Fan Only Mode is as
follows:
• R and G thermostat contacts close, initiating a call for
fan.
• Integrated control module performs safety circuit
checks.
• Circulator blower is energized on low heat speed.
Electronic air cleaner terminal is energized.
• Circulator blower runs, integrated control module
monitors safety circuits continuously.
Combustion Quality
Combustion quality can be aected by several factors.
Major factors are venting and draining.
Other Causes
1. Manifold Gas Pressure must be set within the range
stated on the furnace rating plate.
2. Remove Draft Inducer, Check the integrity of the
gasket between the inducer and the collector box
cover, any air leak here will have a negative eect
on combustion. Check the orice hole in the collector
box, it must be free of burrs on both sides.
3. Make sure the eld installed gas line is not binding
and causing distortion of burner assembly
4. Make sure there are no cabinet air leaks allowing
supply air to aect combustion
5. If heat exchanger integrity is uncertain, follow
procedures in Service Bulletin SF-041.

SCHEDULED MAINTENANCE
18
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
If you must handle the ignitor, handler with care. Touching
th ignitor body with bare fingers, rough handling, or
vibration could result in early ignitor failure. Only a
qualified servicer should ever handle the ignitor.
CAUTION
ANNUAL INSPECTION
The furnace should be inspected by a qualied installer, or
service agency at least once per year. This check should
be performed at the beginning of the heating season.
This will ensure that all furnace components are in proper
working order and that the heating system functions
appropriately. Pay particular attention to the following
items. Repair or service as necessary.
• Flue pipe system. Check for blockage and/or leakage.
Check the outside termination and the connections at
and internal to the furnace.
• Heat exchanger. Check for corrosion and/or buildup
within the heat exchanger passageways.
• Burners. Check for proper ignition and ame sense.
• Wiring. Verify that electrical connections are tight and
free from corrosion.
• Filters.
• R-32 Sensor Wire. Check R-32 sensor wire
connection for tightness and check wire for damage.
AIR FILTER
Never operate furnace without a filter installed as dust
and lint will build up on internal parts resulting in loss of
efficiency, equipment damage, and possible fire.
WARNING
Filters must be used with this furnace. Filters do not ship
with these furnaces but must be provided by the installer
for proper furnace operation.
Dirty lters are the most common cause of inadequate
heating or cooling performance.
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
MAINTENANCE
Improper lter maintenance is the most common cause of
inadequate heating or cooling performance. Filters should
be cleaned (permanent) or replaced (disposable) every two
months or as required.
HORIZONTAL UNIT FILTER REMOVAL
Filters in horizontal installations are located in the central
return register.
INDUCED DRAFT AND CIRCULATION BLOWERS
The bearings in the induced draft blower and circulator
blower motors are permanently lubricated by the
manufacturer. No further lubrication is required. Check
motor windings for accumulation of dust which may cause
overheating. Clean as necessary.
FLAME SENSOR (QUALIFIED SERVICER ONLY)
Under some conditions, the fuel or air supply can create a
nearly invisible coating on the ame sensor. This coating
acts as an insulator, causing a drop in the ame sensing
signal. If this occurs, a qualied servicer must carefully
clean the ame sensor with steel wool. After cleaning, the
ame sensor output should be as listed on the specication
sheet.
The following is a must for every service technician and
service shop.
1. Thermometers or thermocouple meter (optional) - To
measure temperatures.
2. Multi-Meter - To measure amperage and voltage, to
test continuity, capacitors, and motor windings.
3. Manometer - To measure static pressure, pressure
drop across coils, lters and draft, and to measure
in let and manifold gas pressures.
Other recording type instruments can be essential in
solving abnormal problems, however, in many instances
they may be rented from local sources.
Proper equipment promotes faster, more ecient service
and accurate repairs resulting in fewer call backs.
HEATING PERFORMANCE TEST
Before attempting to diagnose an operating fault code, run
a Heating Performance Test to determine if the heating
system is performing within 5% of the BTU input found
on the rating plate of the unit being tested. To conduct a
heating performance test, the BTU input to the unit must
be calculated (see Clocking a Gas Meter). Before clocking
a gas meter, contact your local utility to provide the caloric
value (BTU content) of the natural gas in the area.
It is also important to conrm the airow (CFM) is within
the temperature rise range (see Airow Data in spec sheet)
and external static pressure range (approximately 0.5”
water column). How-to instructions can be found in the
service manual under Checking External Static Pressure
and Checking Temperature Rise.

SCHEDULED MAINTENANCE
19
CLOCKING A GAS METER
1. Turn o all gas appliances in the home.
2. Turn on the furnace. Ensure the furnace is operating at a 100% ring rate on 2 stage and modulating furnace
product.
3. Once heating cycle is at a steady state (typically 15 minutes of operation), use a stopwatch to time how long it takes
the smallest unit of measure dial on the gas meter to make a full revolution. In Table 1, one cubic foot is selected.
The smallest unit of measure will vary depending on the gas meter.
CUBIC
FEET
1
1
One
In this example
we are using the
one cubic foot
dial on the gas
meter
TABLE 1
4. Using Table 2 below, nd the number of seconds it took for the dial to make a full revolution. To the right of that
number of seconds and below the Size of Test Dial (selected in step 3 and shown in Table 1) will be the Cubic Feet
per Hour (CFH).
1/4
cu/ft
1/2
cu/ft
1
cu/ft
2
cu/ft
5
cu/ft
1/4
cu/ft
1/2
cu/ft
1
cu/ft
2
cu/ft
5
cu/ft
10 90 180 360 720 1800 36 25 50 100 200 500
11 82 164 327 655 1636 37 -- -- 97 195 486
12 75 150 300 600 1500 38 23 47 95 189 474
13 69 138 277 555 1385 39 -- -- 92 185 462
14 64 129 257 514 1286 40 22 45 90 180 450
15 60 120 240 480 1200 41 -- -- -- 176 439
16 56 113 225 450 1125 42 21 43 86 172 429
17 53 106 212 424 1059 43 -- -- -- 167 419
18 50 100 200 400 1000 44 -- 41 82 164 409
19 47 95 189 379 947 45 20 40 80 160 400
20 45 90 180 360 900 46 -- -- 78 157 391
21 43 86 171 343 857 47 19 38 76 153 383
22 41 82 164 327 818 48 -- -- 75 150 375
23 39 78 157 313 783 49 -- -- -- 147 367
24 37 75 150 300 750 50 18 36 72 144 360
25 36 72 144 288 720 51 -- -- -- 141 355
26 34 69 138 277 692 52 -- -- 69 138 346
27 33 67 133 265 667 53 17 34 -- 136 340
28 32 64 129 257 643 54 -- -- 67 133 333
29 31 62 124 248 621 55 -- -- -- 131 327
30 30 60 120 240 600 56 16 32 64 129 321
31 -- -- 116 232 581 57 -- -- -- 126 316
32 28 56 113 225 563 58 -- 31 62 124 310
33 -- -- 109 218 545 59 -- -- -- 122 305
34 26 53 106 212 529 60 15 30 60 120 300
35 -- -- 103 206 514
GAS RATE -- CUBIC FEET PER HOUR
Seconds fo
r
One
Revolution
Size of Test Dial
Seconds fo
r
One
Revolution
Size of Test Dial
Locate 40 seconds for one
revolu�on in the chart below
Then locate the 1 cu � dial column and select the
corresponding CFH from the 40 seconds for one revolu�on row
TABLE 2

SCHEDULED MAINTENANCE
20
5. Use this formula to verify the Cubic Feet per Hour (CFH) input determined in step 4 is correct:
(3600 x Gas Meter Dial Size) / Time (seconds) = Cubic Feet per Hour (CFH)
3600 is used as there are 60 seconds in
a minute and 60 minutes in an hour.
60x60=3600
6. Check with your local utility for actual BTU content (caloric value) of natural gas in the area (the average is 1025
BTU’s).
7. Use this formula to calculate the BTU/HR input (See BTU/HR Calculation Example):
Cubic Feet per Hour (CFH) x BTU content of your natural gas = BTU/HR input
8. Should the gure you calculated not fall within ve (5) percent of the nameplate rating of the unit, adjust the gas
valve pressure regulator or resize orices. To adjust the pressure regulator on the gas valve, turn downward
(clockwise) to increase pressure and input, and upward (counterclockwise) to decrease pressure and input. A
properly operating unit must have the BTU per hour input and CFM of air, within the limits shown to prevent short
cycling of the equipment. As the external static pressure goes up, the temperature rise will also increase. Consult
the proper tables for temperature rise limitation.
BTU/HR Calculation Example:
The unit being tested takes 40 seconds for the 1 cubic foot dial to make one complete revolution. Using the chart, this
translates to 90 cubic feet per hour. Based upon the assumption that one cubic foot of natural gas has 1,025 BTU’s
(Check with your local utility for actual BTU content), the calculated input is 92,250 BTU’s per hour.
Furnace Nameplate Input in this example: 90,000 BTU/HR
Calculated Gas Input in this example: 92,250 BTU/HR
This example is within the 5% tolerance input and does not need adjustment.
Always connect a manometer to the outlet tap at the gas
valve before adjusting the pressure regulator. In no case
should the final manifold pressure vary more than plus or
minus .2 inches water column from 3 inches water column
for natural gas.
CAUTION
A properly operating unit must have the BTU per hour input and CFM of air, within the limits shown to prevent short cycling
of the equipment. As the external static pressure goes up, the temperature rise will also increase. Consult the proper
tables for temperature rise limitation.

SERVICING
21
CHECKING FOR PHASING - PRIMARY TO SECONDARY OF UNMARKED TRANSFORMERS*
If meter reads approximately 96 volts - the primary to secondary are in phase - if reads approximately 144 volts out of
phase - reverse low voltage wires.
*NOTE: For ame rectication the common side of the secondary voltage (24 V) is cabinet grounded. If you were to bench
test a transformer the primary neutral and secondary common must be connected together for testing purposes.
Some transformers will display phasing symbols as shown
in the illustration to the left to assist in determining proper
transformer phasing.
Checking for polarization and phasing should become a
habit in servicing. Let's start now.
TRANSFORMER
.
SECONDARY
PRIMARY
.
GND
C
R
LINE VOLTAGE
L1 (HOT)
LINE VOLTAGE
(NEUTRAL)
METER READS
24 VOLTS
METER READS
120 VOLTS
.
GND
C
R
N
L1
.
GND
C
R
N
L1
READS 96 VOLTS - IN PHASE
READS 144 VOLTS - OUT OF PHASE
.
120.00
0.00
GND
GND
THIS IS L1 OR THE
HOT POWER LEG
THIS IS THE COMMON
OR NEUTRAL LEG
INCOMING POWER
These then should be wired to the furnace accordingly.
C
R
G
N
D
NEUTRAL
L1
PHASING SYMBOL
24 V
120 V

SERVICING
22
CHECKING VOLTAGE
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
1. Remove the burner door to gain entry to the Junction
Box.
2. Remove cover from the Junction Box and gain
access to incoming power lines.
With Power ON:
Line voltage now present.
WARNING
3. Using a voltmeter, measure the voltage across the
hot and neutral connections.
NOTE: To energize the furnace, the Door Interlock Switch
must be engaged at this point.
4. No reading - indicates open wiring, open fuse, no
power, or faulty Door Interlock Switch from unit to
fused disconnect service. Repair as needed.
5. With ample voltage at line voltage connectors,
energize the furnace blower motor by jumpering
terminals R to G on the integrated ignition control.
6. With the blower motor in operation, the voltage
should be 120 volts ± 10 percent.
7. If the reading falls below the minimum voltage, check
the line wire size. Long runs of undersized wire can
cause low voltage. If wire size is adequate, notify the
local power company of the condition.
8. After completing check and/or repair, replace
Junction Box cover and reinstall the service panel
doors.
9. Turn on electrical power and verify proper unit
operation.
CHECKING WIRING
Disconnect ALL power before servicing.
WARNING
1. Check wiring visually for signs of overheating,
damaged insulation and loose connections.
2. Use an ohmmeter to check continuity of any
suspected open wires.
3. If any wires must be replaced, replace with AWM,
105°C. 2/64 thick insulation of the same gauge or its
equivalent.
CHECKING THERMOSTAT, WIRING
Disconnect ALL power before servicing.
WARNING
1. Remove the blower compartment door to gain
access to the thermostat low voltage wires located at
the furnace integrated control module terminals.
2. Remove the thermostat low voltage wires at the
furnace control panel terminal board.
3. Jumper terminals R to W on the integrated ignition
control.
With Power On (and Door Interlock Switch closed):
Line voltage now present.
WARNING
4. Induced Draft Motor must run and pull in pressure
switch.
5. If the hot surface ignitor heats and at the end of the
ignitor warm-up period the gas valve opens and the
burners ignite, the trouble is in the thermostat or
wiring.
6. With power o, check the continuity of the thermostat
and wiring. Repair or replace as necessary.
If checking the furnace in the air conditioning mode,
proceed as follows:
7. With power o, Jumper terminals R to Y to G.
8. Turn on the power.
9. If the furnace blower motor starts and the condensing
unit runs, then the trouble is in the thermostat or
wiring. Repair or replace as necessary.
10. After completing check and/or repair of wiring and
check and/or replacement of thermostat, reinstall
blower compartment door.
11. Turn on electrical power and verify proper unit
operation.
CHECKING TRANSFORMER AND CONTROL
CIRCUIT
A step-down transformer 120 volt primary to 24 volt
secondary, 40 VA (Heating and Cooling Models) supplies
ample capacity of power for either operation.

SERVICING
23
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
1. Remove blower compartment door to gain access
to the thermostat low voltage wires located at the
furnace integrated control module.
2. Remove the thermostat low voltage wires at the
furnace integrated control module terminals.
With Power On (and Door Interlock Switch closed):
Line voltage now present.
WARNING
3. Use a voltmeter, check voltage across terminals R
and C. Must read 24 VAC.
4. No voltage indicates faulty transformer, open fuse,
bad wiring, bad splice, or open door interlock switch.
5. Check transformer primary voltage at incoming line
voltage connections, fuse, splices, and blower door
interlock switch.
6. If line voltage is available to the primary side
of transformer and not at secondary side, the
transformer is inoperative. Replace.
7. After completing check and/or replacement of
transformer and check and/or repair of control circuit,
reinstall blower compartment door.
8. Turn on electrical power and verify proper unit
operation.
CHECKING AIR CIRCULATOR BLOWER MOTOR
Disconnect ALL power before servicing.
WARNING
1. Remove blower compartment door to gain access
to the circulator blower motor and integrated ignition
control.
2. Disconnect the motor wire leads from its connection
point at the integrated ignition control module and
capacitor if applicable.
3. Using a ohmmeter, test for continuity between each
of the motor leads.
4. Touch one probe of the ohmmeter to the motor frame
(ground) and the other probe in turn to each lead.
If the windings do not test continuous or a reading is
obtained to ground, replace the motor.
5. After completing check and/or replacement of
circulator blower motor or induced draft blower motor,
reinstall blower compartment door.
6. Turn on electrical power and verify proper unit
operation.
Disconnect ALL power before servicing.
WARNING
CHECKING DUCT STATIC
The maximum and minimum allowable external static
pressures are found in the specication section. These
tables also show the amount of air being delivered at a
given static by a given motor speed or pulley adjustment.
The furnace motor cannot deliver proper air quantities
(CFM) against statics other than those listed.
Too great of an external static pressure will result in
insucient air that can cause excessive temperature rise,
resulting in limit tripping, etc. Whereas not enough static
may result in motor overloading.
To determine proper air movement, proceed as follows:
1. With clean lters in the furnace, use a manometer to
measure the static pressure of the return duct at the
inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct.
(Positive Pressure)
3. Add the two (2) readings together for total external
static pressure.
NOTE: Both readings may be taken simultaneously
and read directly on the manometer if so
desired. If an air conditioner coil or Electronic
Air Cleaner is used in conjunction with the
furnace, the readings must also include theses
components, as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the minimum
or maximum allowable statics, check for closed dampers,
registers, undersized and/or oversized poorly laid out duct
work.

SERVICING
24
CUTAWAY OF DUCTWORK
TO EXPOSE COIL
DIGITAL
MANOMETER
RETURN
AIR
Mode
.
SUPPLY
AIR
Checking Static Pressure
CHECKING TEMPERATURE RISE
The more air (CFM) being delivered through a given
furnace, the less the rise will be; so the less air (CFM)
being delivered, the greater the rise. The temperature
rise should be adjusted in accordance to a given furnace
specications and its external static pressure. An incorrect
temperature rise may result in condensing in or overheating
of the heat exchanger. An airow and temperature rise
table is provided in the blower performance specication
section. Determine and adjust temperature rise as follows:
1. Operate furnace with burners ring for approximately
ten minutes. Check BTU input to furnace - do not
exceed input rating stamped on rating plate. Ensure
all registers are open and all duct dampers are in
their nal (fully or partially open) position.
2. Place thermometers in the return and supply ducts
as close to the furnace as possible. Thermometers
must not be inuenced by radiant heat by being able
to “see” the heat exchanger.
SUPPLY
AIR
RETURN
AIR
Checking Temperature Rise
3. Subtract the return air temperature from the supply
air temperature to determine the air temperature rise.
Allow adequate time for thermometer readings to
stabilize.
4. Adjust temperature rise by adjusting the circulator
blower speed. Increase blower speed to reduce
temperature rise. Decrease blower speed to increase
temperature rise. Refer to Circulator Blower Speed
section in the Product Design section of this manual
for speed changing details. Temperature rise is
related to the BTUH output of the furnace and
the amount of air (CFM) circulated over the heat
exchanger. Measure motor current draw to determine
that the motor is not overloaded during adjustments.
CHECKING PRIMARY LIMIT CONTROL
All use a nonadjustable, automatic reset, bi-metal type limit
control.
Style 1
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
1. Remove burner compartment door to gain access to
the primary limit.
2. Remove low voltage wires at limit control terminals.
3. With an ohmmeter, test between these two terminals
as shown in the following drawing. The ohmmeter
should read continuous unless heat exchanger
temperature is above limit control setting. If not as
above, replace the control.

SERVICING
25
COLOR
IDENTIFYING
TAB
Testing Primary Limit Control
CHECKING AUXILIARY LIMIT CONTROL
AUXILIARY LIMIT
CONTROL
AUXILIARY LIMIT
CONTROL
BLOWER HOUSING
Auxiliary Limit Control Location
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
RED
RESET
BUTTON
COLOR
IDENTIFYING
Testing Auxiliary Limit Control
To avoid possible fire, only reset the auxiliary limit control
once. If it should open a second time, a qualified servicer
must determine why the auxiliary limit opened before
resetting again.
WARNING
INDUCED DRAFT BLOWER MOTOR
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
The induced draft assembly uses a three phase motor to
draw ue gases through the heat exchanger. The inducer
uses ball bearings and is permanently lubricated. This
motor is driven at varying speeds by the VFD (variable
frequency drive) section of the IFC. The IFC takes typical
single phase power supplied to the furnace and converts
it to a three phase supply to operate the draft inducer
at the desired speed. The windings of the induced draft
motor will have equal resistance +/- 5%. Normal resistance
readings at room temperature will range from 14-17 ohms.
The voltage supplied by the IFC to drive the induced draft
blower will vary from 15-110 volts A/C between any two
windings. This would be read between any two of the three
power wires between the IFC and the induced draft blower.
This voltage to the IBD will vary between furnace models
and is dependent on what percentage of maximum re is
being called for. The power wires are colored red, white,
and black. A green colored ground wire is also present.

SERVICING
26
CHECKING GAS VALVE (REDUNDANT)
A combination redundant operator type gas valve which
provides all manual and automatic control functions
required for gas red heating equipment is used.
The valve provides control of main burner gas ow,
pressure regulation, and 100 percent safety shut-o.
Disconnect ALL power before servicing.
WARNING
Single stage gas valves should be tested on the furnace
with 24 VAC connected to the gas valve and manometers
reading supply line and manifold pressures.
Disconnect ALL Gas and Electrical Power Supply.
WARNING
Orices should be treated with care in order to prevent
damage. They should be removed and installed with a box-
end wrench in order to prevent distortion. In no instance
should an orice be peened over and redrilled. This will
change the angle or deection of the vacuum eect or
entraining of primary air, which will make it dicult to adjust
the ame properly. This same problem can occur if an
orice spud of a dierent length is substituted.
Disconnect ALL Gas and Electrical Power Supply.
WARNING
CHECKING GAS PRESSURE
Gas Supply Pressure Measurement
To prevent unreliable operation or equipment damage, the
inlet gas supply pressure must be as specified on the unit
rating plate with all other household gas fired appliances
operating.
CAUTION
Gas inlet and manifold pressures should be checked and
adjusted in accordance to the type of fuel being consumed.
The line pressure supplied to the gas valve must be within
the range specied below. The supply pressure can be
measured at the gas valve inlet pressure tap or at a hose
tting installed in the gas piping drip leg. The supply
pressure must be measured with the burners operating.
To measure the gas supply pressure, use the following
procedure.
Disconnect ALL Gas and Electrical Power Supply.
WARNING
1. After turning o gas to furnace at the manual gas
shuto valve external to the furnace, remove burner
compartment door to gain access to the gas valve.
2. Connect a calibrated water manometer (or
appropriate gas pressure gauge) at either the gas
valve inlet pressure tap or the gas piping drip leg as
shown in the following gures. Refer to Measuring
Gas Pressure: Single Stage Valves gure for single
stage valve inlet pressure tap connections.
NOTE: At either location, a hose fitting must be
installed prior to making the hose connection.
NOTE: Use adapter kit #0151K00000S to measure
gas pressure on White-Rodgers 36J22 gas valves.
Mode
10.0
Measuring Inlet Gas Pressure (Alternate Method)
3. Turn ON the gas and electrical power supply and
operate the furnace and all other gas consuming
appliances on the same gas supply line.
4. Measure furnace gas supply pressure with burners
ring. Supply pressure must be within the range
specied in the following table.
INLET GAS SUPPLY PRESSURE
Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c.
If supply pressure diers from above, make necessary
adjustments to pressure regulator, gas piping size, etc.,
and/or consult with local gas utility.

SERVICING
27
WARNING
High Voltage!
Disconnect all electrical power and shut off gas
supply before servicing or installing this unit.
Multiple power sources may be present. Failure to
do so may cause property damage, personal injury
or death.
5. Disconnect manometer after turning o gas at
manual shuto valve. Reinstall plug before turning on
gas to furnace.
6. Turn OFF any unnecessary gas appliances started in
step 3.
7. Turn on gas to furnace and check for leaks. If
leaks are found, repair and then reinstall burner
compartment door.
8. Turn on electrical power and verify proper unit
operation.
GAS MANIFOLD PRESSURE MEASUREMENT AND
ADJUSTMENT
To prevent unreliable operation or equipment damage,
the gas manifold pressure must be as specified on the unit
rating plate. Only minor adjustments should be made by
adjusting the gas valve pressure regulator.
CAUTION
NOTE: Use adapter kit #0151K00000S to measure
gas pressure on White-Rodgers 36J22 gas valves.
Only small variations in gas pressure should be made by
adjusting the gas valve pressure regulator. The manifold
pressure must be measured with the burners operating.
To measure and adjust the manifold pressure, use the
following procedure.
HIGH VOLTAGE
Disconnect ALL electrical power and shut off gas supply
before servicing or installing.
WARNING
1. After turning o gas to furnace at the manual gas
shuto valve external to the furnace, remove burner
compartment door to gain access to the gas valve.
2. Connect a calibrated water manometer (or
appropriate gas pressure gauge) at the gas valve
outlet pressure tap. Refer to Measuring Gas
Pressure: Single Stage Valves gure for single stage
valve outlet pressure tap connections.
Line voltage now present.
WARNING
3. Turn ON the gas and electrical power supply and
operate the furnace.
4. Measure gas manifold pressure with burners ring.
Adjust manifold pressure using the table below.
Manifold Gas Pressure
Natural Gas 2.8 -3.2" w.c.
The nal manifold pressure must not vary from the above
specied pressures. Any necessary major changes in
gas ow rate should be made by changing the size of the
burner orice.
5. White-Rodgers 36J22 Valves:
a. Back outlet pressure test screw (inlet/outlet
pressure boss) out one turn (counterclockwise,
not more than one turn).
b. Attach a hose and manometer to the outlet
pressure outlet pressure boss.
c. Turn ON the gas supply.
d. Turn on power and close thermostat “R” and “W”
contacts to provide a call for low stage heat.
e. Measure the gas manifold pressure with burners
ring. Adjust manifold pressure using the Manifold
Gas Pressure table shown below.
f. Remove regulator cover screw from the
outlet pressure regulator adjust tower and
turn screw clockwise to increase pressure or
counterclockwise to decrease pressure. Replace
regulator cover screw.
g. Turn o all electrical power and gas supply to the
system.
h. Remove the manometer hose from the hose barb
tting or outlet pressure boss.
i. Turn outlet pressure test screw in to seal pressure
port (clockwise, 7 in-lb minimum).
WARNING
High Voltage!
Disconnect all electrical power and shut off gas
supply before servicing or installing this unit.
Multiple power sources may be present. Failure to
do so may cause property damage, personal injury
or death.
6. Turn on gas to furnace and check for leaks. If
leaks are found, repair and then reinstall burner
compartment door.
7. Turn on electrical power and verify proper unit
operation.

SERVICING
28
Pressure Regulator
Adjustment
(Under Cap Screw)
Gas Valve
On/Off
Selector
Switch
INLET
OUTLET
Inlet Pressure
Tap
Outlet Pressure
Tap
HIGH VOLTAGE
Disconnect ALL electrical power and shut off gas supply
before servicing or installing.
WARNING
Disconnect ALL power before servicing.
WARNING
CHECKING HOT SURFACE IGNITER
120V Silicon Nitride Igniter - ULN furnaces use a 120V
silicone nitride igniter, part #0130F00717. The normal
operating temperature is approximately 2156°F - 2678°F.
At room temperature the igniter ohm reading should be
from 20-100 ohms.
Line voltage now present.
WARNING
CHECKING PRESSURE TRANSDUCER (80% ULN)
The 80% ULN products utilize a pressure transducer (in
lieu of a pressure switch). The pressure transducer signals
the control board to modulate the heating cycle during a
call for heat by regulating the induced draft motor speed.
By regulating the speed of the induced draft motor, proper
air-fuel ratios are maintained.
Sensing range specication: 0.0 to -4.0 inches W.C.
Voltage specications:
• Steady State: 5.0 vDC from red to green wire
(transducer wiring harness input).
• With Inducer o: 0.5 vDC from black to green wire
(transducer wiring harness output).
• During operation: Output range equals 0.5 - 4.5 vDC.
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
CHECKING FOR DELAYED IGNITION
Delayed ignition is a delay in lighting a combustible mixture
of gas and air which has accumulated in the combustion
chamber.
Furnace design makes this extremely unlikely unless safety
controls have been by-passed or tampered with. Never by-
pass or alter furnace controls.
If delayed ignition should occur, the following should be
checked:
1. Improper gas pressure - adjust to proper pressure
(See CHECKING GAS PRESSURE).
CHECKING INTEGRATED IGNITION CONTROL
BOARDS
NOTE: Failure to earth ground the furnace,
reversing the neutral and hot wire connection to
the line (polarity), or a high resistance connection
in the neutral line may cause the control to
lockout due to failure to sense flame.
To avoid the risk of electrical shock, wiring to the unit
must be properly polarized and grounded. Disconnect
power before performing service listed below.
WARNING
The ground wire must run from the furnace all the way back
to the electrical panel. Proper grounding can be conrmed
by disconnecting the electrical power and measuring
resistance between the neutral (white) connection and the
burner closest to the ame sensor. Resistance should be
less than 10 ohms.
The ignition control is a combination electronic and
electromechanical device and is not eld repairable.
Complete unit must be replaced.

SERVICING
29
Line voltage now present.
WARNING
These tests must be completed within a given time frame
due to the operation of the ignition control.
1. Check for 120 volts from Line 1 (Hot) to Line 2
(Neutral) at the ignition control. No voltage, check
the door switch connections and wire harness for
continuity.
2. Check for 24 volts from W to C terminal on the
ignition control. No voltage. Check transformer, room
thermostat, and wiring.
If you have 24 volts coming o the transformer but
receive approximately 13 volts on the terminal board
between (C) and (R), check for blown fuse.
3. Check for 120 volts to the induced draft blower by
measuring voltage between Pin 4 & 5 (black & white
wire on 5 pin connector.)
4. If voltage is present in Steps 1 through 3 and the
induced draft blower is operating, check for 120 volts
to the ignitor during the preheat cycle.
5. After the ignitor warmup time, begin checking for
24 volts to the gas valve. Voltage will be present
for seven seconds only if proof of ame has been
established.
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
CHECKING FLAME SENSOR
1. Disconnect the yellow ame sensor wire from the
sensor
2. Connect a micro-amp meter in series with this wire
and the sensor terminal.
3. Place the unit into a heating cycle.
Line voltage now present.
WARNING
4. As soon as ame is established a micro-amp reading
should be evident once proof of ame (micro-amp
reading) is established, the hot surface ignitor will be
de-energized.
5. The Integrated Ignition controls will have 3 to 8
micro-amps. If the micro-amp reading is less than 1,
check for high resistance wiring connections, sensor
to burner gap, dirty ame sensor, or poor grounding.
6. If absolutely no reading, check for continuity on all
components and if good - replace ignition control
module.
NOTE: Contaminated fuel or combustion air can
create a nearly invisible coating on the flame
sensor. This coating works as an insulator causing
a loss in the flame sense signal. If this situation
occurs the flame sensor must be cleaned with
steel wool.

MENU OPTIONS
LED
Display
Menu Description
ASE Aux (condensate switch enabled)
bSt
Enable or disable inverter boost operation. (compressor
speed may increase when this feature is on) (inverter only)
btt
Boost mode will operate above this selected temperature.
On = boost mode always on (default = 105°F) (inverter only)
CAP
Cooling Airow Prole setting (default = prole D shown as
4)
CbP
Heat Pump compressor lockout temperature. Furnace will
act as primary heat source below this temperature. (Default
= 45°F)
CdL
Compressor o delay at the beginning and end of a defrost
cycle.(default = 30 seconds)
CFd Cooling Airow O Delay Time. (default = 60 seconds)
CLr Resets all cooling settings to factory default.
Cnd Cooling Airow On Delay Time (default = 5 seconds)
Cr Control Firmware Revision Number
Cr9 Enable or disable inverter charge mode.
CrP
Select the range that includes the desired compressor RPS
for inverter cooling operation. See inverter manual for menu
options
CrS Maximum Compressor RPS for cooling mode. (inverter only)
CSt
Percentage of high stage cooling airow to run during low
stage operation. (default = 70%)
CtF Cooling Airow Trim (default 0%)
CtH
High Cooling Airow Trim for inverter units. See inverter
manual for menu options and defaults
CtI
Intermediate Cooling Airow Trim for inverter units. See
inverter manual for menu options and defaults
CtL
Low Cooling Airow Trim for inverter units. See inverter
manual for menu options and defaults
dF
Compressor run time between defrost cycles. (default = 30
minutes) (2 stage units)
dHE
Enables or disables dehumidication feature in the outdoor
unit. (default = Enabled)
DHL
Select “1” to enable dehumidication when the thermostat
DH terminal is energized. Select “0” to enable dehumidi-
cation when the thermostat DH terminal is de-energized.
(default = 1)
FCL
View 6 most recent fault codes and Clear Fault Codes if
desired (outdoor communicating units)
FdF Force system into a defrost cycle (inverter units)
FSd
Constant Fan Speed as percent of maximum airow. Default
= 25%
GFd Gas Heat Fan O Delay (default = 90 seconds)
GnD Gas Heat Fan On Delay (default = 30 seconds)
GSt
Percentage of high stage gas heating airow to run during
low stage gas heat operation (default = 70%)
9H Gas Heat
F10 Last 10 Faults
A2U A2L Function Verication
A2E A2L Function Enabled
LED
Display
Menu Description
GtF
Gas Heat Airow Trim (default = 0%)
HdI
Maximum Compressor Run Time Between Defrost Cycles
(default= 120 minutes)
HFd
Heat Pump Heating Airow O Delay Time (default = 60
seconds)
Hnd
Heat Pump Heating Airow On Delay Time (default = 5
seconds)
HrP
Select the range that includes the desired compressor RPS
for inverter heating operation. See inverter manual for menu
options
HrS
Maximum Compressor RPS for Heating Mode (inverter only)
Hrt
Reset all heat pump heating settings to factory default.
HSt
Percentage of high stage heat pump heating airow to run
during low stage operation. (default = 70%)
HtF
Heat Pump Indoor Airow Trim (default = 0%)
HtH
High Heating Airow Trim for Inverter Units. See inverter
manual for menu options and defaults
HtI
Intermediate Heating Airow Trim for Inverter Units. See
inverter manual for menu options and defaults
HtL
Low Heating Airow Trim for Inverter Units. See inverter
manual for menu options and defaults
Lrn
Restart communications between the indoor and outdoor
unit.
OdS
Select the number of stages for the non-communicating
outdoor unit. Default = OFF meaning no outdoor unit.
PPd
Enable Pump Down Mode
rFd
Resets furnace settings to factory defaults.
SCt
Maximum Current Option (system will limit capacity to per-
centage of maximum current) (default = 100%)
Sr
Control Shared Data Revision Number
Srt
Resets all outdoor unit settings to factory defaults.
SUt
System Verication Test (inverters only)
ton
Indoor Airow for non-communicating outdoor units. (values
based on 400CFM per ton) (default = 3.0 Ton)
Utr
Select Outdoor Unit Elevation (SL=same level, OL = outdoor
lower, IL = indoor lower) Default = Outdoor Lower
CFS
1 = system will try to satisfy the thermostat quickly.5 (de-
fault) = system will try to satisfy the thermostat more slowly.
t9t
Menu is enabled if the CFS menu is set to 6. Select the tar-
get time the system will attempt to satisfy the thermostat.
SUP
Menu is enabled if the CFS menu is set to 6. Select the per-
centage past the target time when the system will transition
to gas furnace operation during heat mode.
Ott
Menu is enabled if the CFS is set to 6. (the gas furnace will
run during the next heat call if the heat pump fails to satisfy
the custom target time for this number of consecutive cy-
cles) (default = 20 cycles)
Utt
Menu is enabled if the CFS menu is set to 6. (if low stage
gas heat is able to consecutively satisfy the thermostat un-
der the set target time for this number of cycles, the system
will transition to the heat pump for primary heating)
SdP
Menu is enabled if the CFS menu is set to 6. (this percent-
age will help determine when switching back to heat pump
operation is appropriate. Default = 20%. If target time = 20
minutes, low stage furnace operation must satisfy the ther-
mostat by less than 16 minutes. (target time - 20% default =
16 minutes).
TROUBLESHOOTING
30

TROUBLESHOOTING
31
STATUS CODES
LED
Display
Description of System Status
1AC Compressor Cooling, Low Stage (non-communicating units)
2AC Compressor Cooling, High Stage (non-communicating units)
1AC Compressor Heat, Low Stage (non-communicating units)
2AC Compressor Heat, High Stage (non-communicating units)
AC Compressor Cooling, Single-Stage (single stage non-comm. units)
AC1 Compressor Cooling, Low Stage (communicating units)
AC2 Compressor Cooling, High Stage (communicating units)
dHU Dehumidication
FAn Constant Fan
HP Compressor Heat, Single-Stage (single stage non-comm. units)
HP1 Compressor Heat, Low Stage (Communicating Units)
HP2 Compressor Heat, High Stage (Communicating Units)
IDL Idle
vAC Inverter Cooling
vHP Inverter Heating
dFt Defrost
gH Gas Heat

TROUBLESHOOTING
32
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Normal operation. IdL Idle • Normal operation. • None • Normal operation.
Furnace fails to
operate.
Integrated control
module LED dis-
play provides no
signal.
none
No 120v power to
furnace or no 24 volt
power to integrated
control module.
Blown fuse or
tripped circuit break-
er.
Integrated control
module is non-func-
tional.
• Manual disconnect
switch turned OFF,
vdoor switch open or
24 volt wire improperly
connected or loose.
• Furnace electrical
supply shared with
other devices.
• Integrated control
module is non-func-
tional.
• Check 120 volt power
to furnace and integrat-
ed control module.
• Check for possible
shorts in 120 volt circuit.
Repair as necessary.
• Replace non-func-
tional integrated control
module.
• Turn power OFF prior
to repair.
• Read precautions
in “Electrostatic Dis-
charge” section of
manual.
• Replace control with
correct replacement
part.
Furnace fails to
operate.
Eb0
Circulator blower
motor not running
when it should be
running.
• Loose wiring connec-
tion at circulator motor
power leads or circula-
tor motor power leads
disconnected.
• Failed circulator blow-
er motor.
• Tighten or correct wir-
ing connection.
• Check circulator
blower motor. Replace if
necessary.
• Turn power OFF prior
to repair.
• Replace circulator
motor with correct
replacement part.
Furnace fails to
operate.
Eb1
Integrated control
module has lost
communications with
circulator blower
motor.
• Loose wiring connec-
tion at circulator motor
power leads,
• Failed circulator blow-
er motor.
• Failed integrated
control module.
• Tighten or correct wir-
ing connection.
• Check circulator
blower motor. Replace if
necessary.
• Check integrated con-
trol module. Replace if
necessary.
• Turn power OFF prior
to repair.
• Replace circulator
motor with correct
replacement part.
• Replace integrated
control module with
correct replacement
part.
Furnace fails to
operate.
Eb2
Circulator blower
motor horse power
in shared data set
does not match cir-
culator blower motor
horse power.
• Incorrect circulator
blower motor in fur-
nace.
• Incorrect shared data
the in integrated con-
trol module.
• Verify circulator blower
if motor horsepower is
the same specied for
the specic model. Re-
place if necessary.
• Verify shared data set
is correct for the specic
model. Re-populate data
using the CoolCloud
HVAC App if required.
• Turn power OFF prior
to repair.
• Replace circulator
motor with correct
replacement part.
• Error code will be
cleared once shared
data and motor horse-
power match.

TROUBLESHOOTING
33
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Furnace operates
at reduced perfor-
mance.
Airow delivered is
less than expect-
ed.
Eb3
Circulator blower
motor is operating in
a power, tempera-
ture or speed limiting
condition.
• Blocked lters.
• Restrictive ductwork.
• Undersized ductwork.
• High ambient tem-
peratures.
• Check lters for block-
age. Clean lters or
remove obstruction.
• Check ductwork for
blockage. Remove
obstruction. Verify all
registers are fully open.
• Verify ductwork is
appropriately sized for
system. Resize/replace
ductwork if necessary.
• See “III. Product
Description” and “IV
Location Requirements
& Considerations” for
furnace installation
requirements.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
Eb4
Circulator blower
motor senses a loss
of rotor control.
Circulator blower
motor senses high
current.
• Abnormal motor load-
ing, sudden change
in speed or torque,
sudden blockage of
furnace air inlet/outlet.
• Check lters, lter
grilles, registers, duct
system and furnace air
inlet/outlet for blockag-
es.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
Eb5
Circulator blower
motor fails to start 10
consecutive times.
• Obstruction in circula-
tor blower housing.
• Seized circulator
blower motor bearings.
• Failed circulator blow-
er motor.
• Check circulator
blower for obstructions.
Remove and repair/re-
place wheel or motor if
necessary.
• Turn power OFF prior
to repair.
• Replace motor with
correct replacement
part.
• Replace wheel with
correct replacement
part.
Furnace fails to
operate.
Eb6
Circulator blower
motor shuts down
due to over or under
voltage condition.
Circulator blower
motor shuts down
due to over tempera-
ture condition on
power module.
• High AC line voltage
to furnace.
• Low AC line voltage
to furnace.
• High ambient tem-
peratures.
• Check power to fur-
nace. Verify line voltage
to furnace is within the
range specied on the
furnace rating plate.
See “III. Product De-
scription” and “IV
Location Requirements
& Considerations” for
furnace installation
requirements.
• Turn power OFF prior
to repair.
• Replace motor with
correct replacement
part.
• Re-populate data
using the CoolCloudH-
VAC App if required.
Furnace fails to
operate.
Eb7
Circulator blower
motor does not have
enough information
to operate properly.
Motor fails to start 40
consecutive times.
• Error with integrated
control module.
• Motor has a rotor
condition.
• Check integrated
control module. Verify
control is populated with
correct shared data set.
See data errors above
for details.
• Check for locked rotor
condition.
• Turn power OFF prior
to repair.

TROUBLESHOOTING
34
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Furnace operates
at reduced perfor-
mance or operates
on low stage when
high stage is ex-
pected.
Eb9
Airow is lower than
demanded.
• Blocked lters.
• Restrictive ductwork.
• Undersized ductwork.
• High ambient tem-
peratures.
• Check lters for block-
age. Clean lters or
remove obstruction.
• Check ductwork for
blockage. Remove
obstruction. Verify all
registers are fully open.
• Verify ductwork is
appropriately sized for
system. Resize/replace
ductwork if necessary.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
Ed0
Data not yet on
network.
• No network Data
• Populate shared data
set using the CoolCloud-
HVAC App.
• Turn power OFF prior
to repair.
• Use the CoolCloudH-
VAC App to download
the shared data set to
the furnace.
• Error code will be
cleared once data is
downloaded from the
CoolCloudHVAC App.
Operation dierent
than expected or
no operation.
Ed1 Invalid shared data.
• Shared data set is
invalid. Use the Cool-
CloudHVAC App to
download the shared
data to the furnace.
• Verify shared data set
is correct for the specif-
ic model. Re-populate
shared data set using
the CoolCloudHVAC
App.
• Turn power OFF prior
to repair.
• Error code will be
cleared once data is
downloaded from the
CoolCloudHVAC App.
Furnace fails to
operate.
EE0
Furnace lockout due
to excessive number
of ignition “retries” (3
total).
Failure to establish
ame.
Loss of ame after
establishment.
• Failure to establish
ame. Cause may be
no gas to burners, front
cover pressure switch
stuck open, bad igniter
or igniter alignment,
improper orices, or
coated/oxidized or
improperly connected
ame sensor.
• Loss of ame after
establishment. Cause
may be interrupted
gas supply, lazy burner
ames (improper gas
pressure or restriction
in ue and/or lack of
combustion air), or
improper induced draft
blower performance.
• Locate and correct gas
interruption.
• Replace or realign
igniter.
• Check ame sense
signal. Clean sensor if
coated and/or oxidized.
• Check ue piping for
blockage, proper length,
elbows and termination.
• Verify proper induced
draft blower perfor-
mance.
• Turn power OFF prior
to repair.
• Igniter is fragile, han-
dle with care.
• Clean ame sensor
with steel wool.
• See “Vent/Flue Pipe”
section for piping de-
tails.
Furnace fails to
operate.
EE1
Pressure switch
circuit closed at start
of heating cycle.
• Pressure switch con-
tacts sticking.
• Short in pressure
switch circuit wiring.
• Replace Pressure
switch.
• Repair short in wiring.
• Turn power OFF prior
to repair.
• Replace pressure
switch with proper
replacement part.

TROUBLESHOOTING
35
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Induced draft
blower runs con-
tinuously with no
further furnace
operation.
EE2
Pressure switch
circuit open.
• Pressure switch hose
blocked, pinched, or
connected improperly.
• Blocked ue pipe,
or weak induced draft
blower.
• Incorrect pressure
switch set point or
malfunctioning switch
contacts.
• Loose or improperly
connected wiring.
• Inspect pressure
switch hose. Repair/re-
place if necessary.
• Inspect ue piping for
blockage, proper length,
elbows and termination.
Correct as necessary.
• Correct pressure
switch set point or con-
tact motion.
• Tighten or correct wir-
ing connections.
• Turn power OFF prior
to repair.
• Replace pressure
switch with proper
replacement part.
• Replace induced draft
blower with proper
replacement part.
Circulator blower
runs continuously
with no furnace
operation.
EE3
Primary limit circuit
open.
• Insucient condi-
tioned air over the heat
exchanger.
• Blocked lters, re-
strictive ductwork.
• Improper circulator
blower speed or failed
circulator blower motor.
• Loose or improperly
connected wiring in
high limit circuit.
• Check lters and
ductwork for blockage.
Clean lters or remove
obstruction.
• Check circulator blow-
er speed and perfor-
mance. Correct speed
or replace blower motor
if necessary.
• Tighten or correct wir-
ing connections.
• Turn power OFF prior
to repair.
• See Specication
Sheet applicable for
your model for allow-
able temp rise range
and proper circulator
speed.
Induced draft blow-
er and circulator
blower run con-
tinuously with no
furnace operation.
EE4
Flame sensed with
no call for heat.
• Short to ground in
ame sense circuit.
• Lingering burner
ame.
• Slow closing gas
valve.
• Correct short at ame
sensor or in ame sen-
sor wiring.
• Check for lingering
ame.
• Verify proper operation
of gas valve.
• Turn power OFF prior
to repair.
No furnace oper-
ation.
EE5 Open fuse.
• Short in low voltage
wiring
• Locate and correct
short in low voltage
wiring.
• Turn power OFF prior
to repair.
• Replace fuse with
3-amp automotive type.
Normal furnace
operation with
weak ame signal.
EE6
Flame sense micro
amp signal is low.
• Flame sensor is coat-
ed/oxidized.
• Flame sensor incor-
rectly positioned in
burner ame.
• Lazy burner ame
due to improper gas
pressure or combus-
tion air.
• Clean ame sensor if
coated or oxidized.
• Inspect ame sensor
for proper alignment.
• Compare current gas
pressure to rating plate
and adjust as needed.
• Turn power OFF prior
to repair.
• Clean ame sensor
with steel wool.
• See “Vent/Flue Pipe”
section for piping de-
tails.
• See rating plate for
proper gas pressure.
Furnace fails to
operate.
EE7
Problem with igniter
circuit.
• Improperly connected
igniter.
• Shorted igniter.
• Poor furnace ground.
• Igniter relay fault
on integrated control
module.
• Check and correct
wiring from integrated
control module to igniter.
• Replace shorted
igniter.
• Check and correct fur-
nace ground wiring.
• Check igniter output
from control. Replace if
necessary.
• Turn power OFF prior
to repair.
• Replace igniter with
correct replacement
part.
• Replace control with
correct replacement
part.

TROUBLESHOOTING
36
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Furnace fails to
operate.
E10 Grounding fault
• Poor neutral connec-
tion.
• Verify neutral wire
connection to furnace
and continuity to ground
source.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
E11 Open rollout switch.
• Gas pressure too
high.
• Burners mis-aligned.
• Restricted heat ex-
changer or venting.
• Check and correct gas
pressure.
• Check and correct
burner alignment.
• Check and correct
restriction
• Turn power OFF prior
to repair.
Furnace fails to
operate.
E12
Redundant relay
open alarm.
• Replace integrated
control board.
• Turn power OFF prior
to repair.
• Replace the integrat-
ed control board with
proper replacement
part.
Furnace fails to
operate.
E13
Redundant relay
stuck closed alarm.
• Replace integrated
control board.
• Turn power OFF prior
to repair.
• Replace the integrat-
ed control board with
proper replacement
part.
E14 External Flash Fault
• Data error in storage
function (fault history,
system status, etc.)
• Replace integrated
control board if fault
code does not reset.
• Turn power OFF prior
to repair.
• Replace the integrat-
ed control board with
proper replacement
part.
External return air
temperature read-
ing not visible on
CoolCloud app
E15
Return Air Tempera-
ture Sensor Circuit is
Open (External)
NOTE: Allow time as
the control may take up
to 90 seconds to detect
sensors.
• Verify that the sensor
probe is plugged in all
the way
• Verify that the sensor
probe connector is prop-
erly crimped.
• Verify that resistance
across the sensor
probe is 10kΩ at 77°F.
Resistance is lower at
temperatures higher
than 77°F. Resistance is
higher at temperatures
lower than 77°F.
• Replace PCB
• Turn power OFF prior
to repair.

TROUBLESHOOTING
37
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
External return air
temperature read-
ing not visible on
CoolCloud app
E16
Return Air Tempera-
ture Sensor Circuit is
Shorted (External)
• Check sensor probe
terminals & conductors
for electrical short.
• Check PCB connector
for shorts if sensor short
error reported when
sensor probe is not
plugged in.
• Replace PCB
• Turn power OFF prior
to repair.
Supply air tem-
perature reading
not visible on
CoolCloud app
E17
Supply Air Tempera-
ture Sensor Circuit is
Open (External)
NOTE: Allow time as
the control may take up
to 90 seconds to detect
sensors.
• Verify that the sensor
probe is plugged in all
the way
• Verify that the sensor
probe connector is prop-
erly crimped.
• Verify that resistance
across the sensor
probe is 10kΩ at 77°F.
Resistance is lower at
temperatures higher
than 77°F. Resistance is
higher at temperatures
lower than 77°F.
• Replace PCB
• Turn power OFF prior
to repair.
Supply air tem-
perature reading
not visible on
CoolCloud app
E18
Supply Air Tempera-
ture Sensor Circuit is
Shorted (External)
• Check sensor probe
terminals & conductors
for electrical short.
• Check PCB connector
for shorts if sensor short
error reported when
sensor probe is not
plugged in.
• Replace PCB
• Turn power OFF prior
to repair.
Onboard return air
temperature read-
ing not visible on
CoolCloud app
E19
Onboard return air
temperature sensor
is unplugged
• Power cycle the fur-
nace, the control may
take up to 90 seconds to
detect sensors
• Check PCB for any
visible electrical or
mechanical damage to
onboard sensor (R311).
• Replace PCB
• Turn power OFF prior
to repair.

TROUBLESHOOTING
38
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Onboard return air
temperature read-
ing not visible on
CoolCloud app
E1A
Onboard return air
temperature sensor
is shorted.
• Power cycle the fur-
nace, the control may
take up to 90 seconds to
detect sensors
• Ensure there are no
foreign objects on the
PCB that could cause
an electrical short at
onboard sensor (R311).
• Replace PCB
• Turn power OFF prior
to repair.
Furnace fails to
operate.
E1b
Analog Pressure
Sensor reference
error.
• 5VDC reference
voltage out of range
(5.0 +/- 0.2 VDC for 5
seconds).
• Check Red, Black,
White harness and con-
nections to the inducer
and integrated control
board.
• Replace pressure
sensor.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
E1C
Analog Pressure
Sensor null error.
• Pressure Sensor volt-
age out of range when
inducer is o.
• Check Red, Black,
White harness and con-
nections to the inducer
and integrated control
board.
• Check pressure hoses
to pressure sensor and
pressure switch.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
E1d
Analog Pressure
Sensor span error.
• Pressure sensor out
of range when pres-
sure switch is closed.
• Pressure switch
opens and closes
outside of expected
pressure sensor range.
• Check Red, Black,
White harness and con-
nections to the inducer
and integrated control
board.
• Check pressure hoses
to pressure sensor and
pressure switch.
• Replace pressure
switch if error continues.
• Turn power OFF prior
to repair.
• Replace pressure
switch with proper
replacement part.
Furnace fails to
operate.
E1E
Analog Pressure
Sensor pressure
error.
• Inducer RPM has
reached its limit.
• Blocked ue pipe.
• Check Red, Black,
White harness and con-
nections to the inducer
and integrated control
board.
• Check ue piping for
blockage, proper length,
elbows and termination.
• Replace pressure sen-
sor if necessary.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
E1F
Analog Pressure
Sensor input error.
• Wrong pressure sen-
sor installed.
• Check Red, Black,
White harness and con-
nections to the inducer
and integrated control
board.
• Replace pressure
sensor.
• Turn power OFF prior
to repair.
• Replace pressure
sensor with proper
replacement part.

TROUBLESHOOTING
39
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Furnace fails to
operate.
EbF
Inducer communica-
tion alarm
• Loose wiring connec-
tions from the integrat-
ed control board to the
inducer.
• Check Red, Black,
White harness and con-
nections to the inducer
and integrated control
board.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
EEA
Polarity if 120 volt
AC is reversed.
• Polarity of 120 volt
AC power to furnace
or integrated control
module is reversed.
• Poor furnace ground.
• Review wiring diagram
to correct polarity.
• Verify proper ground.
Correct if necessary.
• Check and correct
wiring.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
EEb
Gas valve is not
energized when it
should be.
External gas valve
error.
• Miswired gas valve
circuit.
• Open gas valve
circuit.
• Gas valve relay on in-
tegrated control board
stuck open.
• Check wiring in gas
valve circuit.
• Replace integrated
control board.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
EEC
Gas valve is ener-
gized when it should
not be.
Internal gas valve
error.
• Miswired gas valve
circuit.
• Shorted gas valve
wiring.
• Gas valve relay on in-
tegrated control board
stuck open.
• Check wiring in gas
valve circuit.
• Replace integrated
control board.
• Turn power OFF prior
to repair.
Furnace fails to
operate.
EEd
Aux limit switch open
(blower compart-
ment).
• 120 volt power supply
was shut o during
heat cycle.
• Insucient condi-
tioned air over the heat
exchanger. Blocked
lters, restrictive
ductwork, improper cir-
culator blower speed or
failed circulator blower
motor.
• Check lters and
ductwork for blockage.
Clean lters or remove
obstruction.
• Check circulator blow-
er speed and perfor-
mance. Correct speed
or replace blower motor
if necessary.
• Tighten or correct wir-
ing connections.
• Turn power OFF prior
to repair.
• See Specication
Sheet applicable for
your model for allow-
able temp rise range
and proper circulator
speed.
Furnace fails to
operate.
EEF
AUX switch (conden-
sate switch) open.
• High water level in
evaporator coil drain
pan or auxiliary drain
pan
• Check evaporator coil
drain pan, piping and
auxiliary drain pan.
• Turn power OFF prior
to repair.
Furnace stops
heating and only
the fan is operat-
ing.
EAF
Furnace has lost
communication with
the R-32 sensor
and the furnace is in
mitigation mode.
Furnace may not
be paired with R-32
Cooling Unit. Refer to
the R-32 Information
Section.
• Loose or damaged
R-32 sensor wire.
• Verify wire connection
to R-32 sensor is not
loose.
• Verify the R-32 sensor
wire is not damaged.
• Replace R-32 sensor if
necessary.
• Turn power OFF prior
to repair.
• Replace R-32 sensor
with proper replace-
ment part.

TROUBLESHOOTING
40
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Furnace stops
heating and only
the fan is operat-
ing.
EA0
R-32 sensor has de-
tected a refrigerant
leak and furnace is
in mitigation mode.
• Investigate the indoor
coil for a refrigerant leak.
• Furnace will resume
normal operation once
a leak is not detected
and the 5 minute delay
period is over.
• Turn power OFF prior
to repair.
Furnace stops
heating and only
the fan is operat-
ing.
EA1
R-32 sensor has
detected a fault and
furnace is in mitiga-
tion mode.
• Investigate the R-32
sensor.
• Replace the R-32 sen-
sor if necessary.
• Turn power OFF prior
to repair.
• Replace R-32 sensor
with proper replace-
ment part.
Furnace stops
heating and only
the fan is operat-
ing.
EA2
A2L relay in the fur-
nace control board
has detected a fault
and furnace is in
mitigation mode.
• Investigate the A2L
relay.
• Cycle power to the
furnace.
• Replace the integrated
control board if neces-
sary.
• Turn power OFF prior
to repair.
• Replace the integrat-
ed control board with
proper replacement
part.
Fault Code Recall
Accessing the furnace’s diagnostic menu provides access to the last ten faults detected by the furnace. Faults are stored
most recent to least recent, Any consecutively repeated fault is stored a maximum of three times. Example: A clogged re-
turn air lter causes the furnace limit to trip repeatedly. The control will only store this fault the rst three consecutive times
the fault occurs. NOTE: It is highly recommended that the fault history be cleared when performing maintenance or
servicing the furnace.

41
Troubleshooting 80% Heating (ULN - Communicating)
No Heat
Yes
No
Does furnace 7
segment LED
display show
IdL
Check furnace breaker, switch, door
switch, 120 VAC at Line H & Line N on
control board, 120 VAC at transformer
primary, 24 VAC at transformer
secondary
If all check ok replace control
board
Yes
Verify 24v from W to C
Is thermostat calling
for heat and furnace
LED display show
gH
No
No
Replace pressure transducer
Is inducer
motor running
Replace inducer motor
Yes
No
Replace PS
Is pressure
switch
closed
No
Does igniter
warm up at
all
Yes
Replace igniter
Igniter relay on control board is
faulty, replace board
Yes
Does igniter
stay on for 17
second warm up
Yes
No
Pressure switch is not staying
closed
Igniter
resistance
20-100 ohms
at room
temperature
Yes
No
No
Is negative
pressure
enough to
close PS
Yes
Check for vent obstruction or
excessive vent length / elbows
Are inlet and
manifold
pressures within
range per IO
If inlet gas pressure is between
4.5”-10.0”W.C. and manifold
pressures is between
2.8”-3.2”W.C., repalce gas vlave
No
Yes
Do burners stay
on more than 4
seconds
Check for flame signal of 2-4
microamps, check furnace and
control board earth ground
No
Yes
Does blower
motor come on
following 30
second delay
No
Check for fault code displayed
and make corrective action
based on fault code. Use
UTT-01 to diagnose motor
Check pressure trasducer for proper
operation. Check power at wire
harness. Between Red & Green wires
should be 5 VDC. Between Black &
Green should be 0.25 VDC at 0’ W.C.
If voltage between Green &
Black is below 0.5 VDC
If voltage between Red &
Black is 0.8 VDC or greater.
Check power at the wire harness.
Between White & Black wires should
read 120 VAC. Between Yellow &
Brown wires should be between 5-7
VAC. Between Orange & Brown wires
should be 2.2 VAC.
No
Check wiring harness between
board & inducer motor, if wiring
ok, replace board
Yes
Is 24 VAC
present at gas
valve
No
Check wire harness connection
at gas valve and 15-pin wire
harness on PCB. Verify proper
ground to furnace
Yes
Does actual temp
rise fall within the
range specified
on furnace rating
plate
Yes
No
Yes
Correct condition causing rise
to be out of range

42
Troubleshooting 80% Heating (ULN - Communicating)
Completed
Does burner
stay on to satisfy
thermostat
Yes
Check for fault code on 7
segment LED display
No
Yes

43
Troubleshooting Error Codes - (B0 & B1)
Board flashes
B0 & B1
No
Yes
Check wiring
harnesses and wiring
connections.
Correct loose wiring
issue.
Ohm motor for open
or shorted circuit. Is
motor open or
shorted?
Test control voltage at the
control board. Replace
integrated control board if
necessary.
Test ECM motor and controller
with ECM tester. Replace motor
and/or controller if necessary
Replace motor if open or
shorted.
Correct power supply if out of
range. Replace motor if
necessary
Check for primary
voltage to blower motor.
Is the power supply
voltage between 104 &
127 vAC (115vAC +
10%)? (Typically
115-127vAC)
Yes
Check control
voltage between
pins 1 & 4. Voltage
should be between
3-15 vDC (Typically
9-15 vDC)
Yes
No
No
Error Code:
B0 - Circulator blower motor not
running when it should be running.
B1 - Integrated control module has
lost communications with
circulator blower motor.
Applicable Models:
(for Goodman Amana Brand)
*RVS-U, *DVT, *RVT, *DVM,
*RVM
(for Daikin)
DR**SC-U, *DD**VT, *DR**VT,
DD97MC, DR97MC
Method of Error Detection:
B0 - High voltage to the motor,
no DC voltage to the motor or no
communication to blower motor.
B1 - Bad ground or no
communication to blower motor.
Error Decision Conditions:
Primary voltage to blower motor
out of range.
Missing DC voltage between pins
1 and 4.

44
Troubleshooting Error Code - (B2-B6, B9)
Board flashes
B2,B3,B4,B5,B6, or B9
No
Yes
Does the
furnace have the
correct blower
motor?
Verify shared data set is correct
for specific model. Repopulate
shared data if required
Correct power supply if out of
range
Replace motor if necessary.
Verify correct motor horsepower.
Replace if necessary
Check for blocked
filters, restrictive
ductwork, undersized
ductwork. Does the
furnace have any of
these conditions?
Yes
Is the furnace
operating in a high
ambient condition
outside of the
temperature range
specified?
Yes
No
No
Does the
furnace have
the correct
shared data?
Check primary
voltage to blower
motor. Is the power
supply voltage
between 104 & 127
vAC (115vAC
+10%)?
Address high ambient condition
if necessary.
Check filters, remove
obstructions, verify registers are
fully open and RA grills are not
blocked. Verify duckwork is
appropriately sized. Resize/
replace ductwork if necessary.
No
No
Yes
Yes
Error Code:
B2 - Circulator blower motor HP in
shared data set does not match
circulator blower motor HP.
B3 - Circulator blower motor is
operating in a power, temperature
or speed limiting condition.
B4 - Circulator blower motor
senses a loss of rotor control or
high current.
B5 - Circulator blower motor fails
to start 10 consecutive times.
B6 - Circulator blower motor shuts
down due to over or under voltage
condition, or over temperature
condition.
B9 - Airflow is lower than
demanded.
Applicable Models:
(for Goodman/Amana Brand)
*RVS80-U, *RVS96-U, *DVT,
*RVT, *DVM97, *RVM97
(for Daikin)
DR**SC-U
Method of Error Detection:
Wrong horsepower blower motor,
primary voltage to motor is out of
range, high temperature, high amp
draw blower motor failure.
Error Decision Conditions:
Wrong horsepower blower motor,
primary voltage to motor is out of
range, high temperature, high amp
draw blower motor failure.

45
Troubleshooting Error Codes - (E0 - 80%)
Board flashes
E0
No
Yes
Are burners
firing up?
Check gas valve On/Off switch
is turned to On position and 24V
present at gas valve? Check
wire harness connection on gas
valve.
Check flame sense signal.
Clean flame sensor if coated
and/or oxidized.
Check manifold gas pressure is
remaining constant and not
dropping below required range
Verify 120VAC present at ignitor.
Replace if voltage is present
Is hot surface
ignitor
glowing?
Yes
Is supply gas present
and manifold gas
pressure within
range. (Nat. Gas 3.2"
to 3.8" W.C, LP 9.7" -
10.3" W.C)
Yes
No
No
Error Code:
E0 - Lockout due to an excessive
number of ignition retries (3 total)
Applicable Models:
All 80% models
Method of Error Detection:
Furnace fails to ignite after 3
retires
Error Decision Conditions:
No gas or low gas pressure at
manifold. Bad hot surface ignitor -
not glowing, dirty flame sensor
Are burners
staying lit?
Yes
No
Verify low fire pressure switch is
remaining close. Replace if
needed

46
Troubleshooting Error Codes - (E3)
Board flashes E3
No
Yes
Check for blocked
filters, restrictive
ductwork, undersized
ductwork. Does the
furnace have any of
these conditions?
Correct blower speed to
maintain temperature rise within
the specifications.
Correct any wiring issues
Correct power supply if out of
range
Replace blower motor or
controller as needed.
Check primary voltage
to blower motor. Is the
power supply voltage
between 104 and 127
vAC (115vAC + 10%)?
Is the circulator
blower speed set
to the correct
speed for heating
airflow
No
No
Does the blower motor
have any loose or
improperly connected
wiring in the primary
limit circuit or to the
blower motor from the
control board?
Replace primary limit
Clean filters, remove
obstructions, verify registers are
fully open and RA grills are not
blocked. Verify ductwork is
appropriately sized. Resize/
replace ductwork if necessary.
No
Yes
Yes
Error Code:
E3 - Primary limit circuit is open.
Applicable Models:
All furnace models
Method of Error Detection:
Temperature across primary limit
during heating operation.
Error Decision Conditions:
During heating operation, primary
limit break temperature has
opened the primary limit circuit.
Is the primary
limit stuck open
or shorted?
No
Yes
No
No
Yes
Check the
performace of the
blower motor. Is
the blower motor
operating
properly?
Yes
Check gas inlet
and manifold
pressure. Are both
of these withing
specifications?
Yes
Adjust inlet and/or manifold
pressure to specification.
Perform combustion analysis to
determine other possible issues.

47
Troubleshooting Fault Codes - (E4 & E6)
Board flashes
E4 or E6
No
Does the furnace
have an actual
ground wire from
the furnace to the
breaker panel
ground bar?
Correct short at flame sensor or
in flame sensor wiring.
Check for lingering flame. Verify
proper operation of gas valve.
Yes
Correct furnace wiring - install
ground wire to breaker
Does the furnace
have a lingering
burner flame or a
slow closing gas
valve?
Yes
Check flame
sense micro
amp signal. Is
the micro amp
reading 1 or
lower?
Yes
No
No
Check flame sense
circuit to ground. Does
flame sense circuit
have a short to
ground?
No
Yes
Clean flame sensor with steel
wool (never use sand paper). If
flame sensor rod is pitted or
damaged - replace as needed.
Inspect for proper flame sensor
alignment.
Check gas inlet and manifold
pressures to rating plate and
adjust as needed.
If flame sense micro amp signal
to control board is more than 1
(typical range of 2 to 4), replace
control board as needed.
Error Code:
E4 - Flame sensed with no call for
heat.
E6 - Flame sense micro amp
signal is minimal.
Applicable Models:
All furnace models
Method of Error Detection:
Micro amp signal from flame
sensor.
Error Decision Conditions:
Micro amp reading with no call for
heat.
Low micro amp reading after
furnace ignition.

48
Troubleshooting Error Code - (Eb & EC)
Board flashes
Eb or EC
No
Check gas valve
wiring circuit. Is
wiring to gas valve
correct?
Integrated
control board
stuck closed.
Replace
integrated
control board.
Remove wiring connections
to the gas valve and check
for voltage at these
connections. If voltage is
present, check gas valve for
short to ground or loose
connection. Repair loose
connection or replace gas
valve as needed.
Verify voltage to gas valve is
the same as transformer
voltage. If voltage is not the
same, check for grounding
issue, If voltage is the same,
replace gas valve as needed.
Yes
Correct miswiring to gas
valve.
Yes
Yes
No
No
Is gas valve
shorted?
Yes
With no call for
heat, do you
have voltage to
gas valve?
With a call for heat and
the igniter on, do you
have voltage between
M & Common on the
gas valve?
No
Using the
wiring
diagram,
locate the MV
(MVL) and
Common
wires in the
wiring harness
connection on
the integrated
control board.
With a call for heat
and the igniter on,
do you have
voltage between
these 2 pins?
Integrated control board
stuck closed. Replace
integrated control board.
Replace gas valve as
needed.
Error Code:
Eb - Gas valve is not energized
when it should be. External Gas
Valve Error.
EC - Gas valve is energized when
it should not be. Internal Gas
Valve Error.
Applicable Models:
(for Goodman/Amana Brand)
All furnace models
(for Daikin)
All furnace models, except Daikin
modulating furnaces
Method of Error Detection:
No voltage to gas valve when
voltage should be present.
Voltage to gas valve with no call
for heat.
Error Decision Conditions:
No voltage reading at gas valve
with a call for heat.
Voltage reading at gas valve with
no call for heat.
Remove wires on
gas valve and check
gas valve for
shorted to ground.
No
Yes

TROUBLESHOOTING
49
MODEL/TEMP RISE RANGE
(MID-RISE)
*RVS800604BU
20-50 (35)
*RVS800805CU
35-65 (50)
CFM RISE CFM RISE
Recommended CFM for Heat &
Expected Temperature Rise
1270 35 1200 50
Lowest Recommended Heating CFM &
Expected Temperature Rise
1140 40 1080 55
NOTE: To Set Heating CFM Using Push Buttons;
1. Scroll using Left or Right push buttons until gTF appears on the 7 segment display.
2. Press & release center button & display will show current heating airow trim expressed as a percentage of max CFM.
3. Press & release Left or Right button until desired percentage appears.
4. Press & release center button once more to select the displayed percentage.
5. * in front of model name represents Amana/Goodman brand.
*RVS800604BU
COOLING SPEED
(@ 0.1” - 0.8” w.c. ESP)
Tons
High-Stage
Cfm
Low-Stage
CFM
2 800 560
2.5 1,000 700
3 1,200 840
4 1,600 1,120
MAX 1,760
*RVS800805CU
COOLING SPEED
(@ 0.1” - 0.8” w.c. ESP)
Tons
High-Stage
Cfm
Low-Stage
CFM
2 800 560
3 1,200 840
4 1,600 1,120
5 2.000 1,400
MAX 2,200

WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
50
RD
0140F20068-A
RD
YL
WH
PK
BK
BK
BL
YL
PK
RD
RD
RD
9
8
12
1
15
11
14
7
2
5
4
13
3
6
10
MODULE
CONTROL
INTEGRATED
TWO-STAGE
EAC
FS
BK
2
LIMIT CONTROL
AUXILIARY
AUTO RESET
WARNING:DISCONNECT
TRANSFORMER
40 VA
N
NO
3
YL
1
FLAME SENSOR
GR
C
VAC
TO UNIT MUST BE
1
PU
AND GROUNDED.
1
115
SWITCH (PRESSURE)
FIELD SPLICE
FIELD
GND
LOW VOLTAGE FIELD
LIMIT CONTROL
AUTO RESET PRIMARY
WH
1
AUTO RESET BURNER BOX
LIMIT
WH
L
NOTES:
1. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.
2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED,
IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF
AT LEAST 105
°
C. USE COPPER CONDUCTORS ONLY.
3. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C. AND LOCAL CODES.
4. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS SWITCH
FOR MORE THAN 2 SECONDS WHILE IN STANDBY (NO THERMOSTAT INPUTS)
5. HUMIDIFIER INSTALLATION OPTIONS: USE HUM TERMINAL TO RUN HUMIDIFIER DURING
HEAT CALL (COMMUNICATING OR LEGACY MODES). USE HUM-IN AND HUM-OUT
TERMINALS TO RUN HUMIDIFIER DURING HEAT CALL (COMMUNICATING MODE OR
LEGACY MODE) OR INDEPENDENTLY FROM HEAT CALL (COMMUNICATING MODE ONLY -
SETUP IS DONE WITHIN COMMUNICATING THERMOSTAT)
6. WHEN THIS FURNACE IS PAIRED WITH NON R-32 REFRIGERANT SYSTEMS, DEFAULT SETTINGS
WILL NEED TO BE CHANGED. REFER TO INSTALLATION MANUAL FOR FURTHER INSTRUCTIONS.
7. FERRITE CORE INSTALLED AT THIS LOCATION. ONLY APPLICABLE TO SOME MODELS.
PK
BK
5
YL
SERVICING. WIRING
EQUIPMENT GND
INTERNAL TO
PROT. DEVICE
INTEGRATED
CONTROL
PK
RD
PLUG
CONNECTION
2
4
BK
DOOR OPEN)
(OPEN WHEN
DOOR SWITCH
COMPARTMENT
BLOWER
SWITCH
(TEMPERATURE)
C
BLOWER
CIRCULATOR
JUNCTION
Ø /60 HZ
DISCONNECT
OVERCURRENT
HI VOLTAGE (115V)
LOW VOLTAGE (24V)
GND
VAC
CHASSIS
GROUND
2
3
4
IGNITER
SURFACE
HOT
2
GND
M
BLOWER
DRAFT (ID)
INDUCED
BK
24
BLOWER COMPARTMENT
115 VAC/ 1
OVERCURRENT
3
HI VOLTAGE FIELD
HARNESS
ECM MTR
TERMINAL
POWER BEFORE
IGNITER
RD
BK
TO
RD
POWER SUPPLY WITH
BURNER COMPARTMENT
PROTECTION DEVICE
PROPERLY POLARIZED
WH
BK
JUNCTION BOX
RG
IGN
IND
-HI
IND
-LO
IND
-N
IGN
-N
AUX
IN
AUX
OUT
3A
FUSE
1
2
R
C
BIAS
BIAS
BIAS
BIAS
TERM
R
C
G W Y
DH
Y2
SAT
GND
GND
NA
RAT
TERM
CT
BREAK
OFF
TABS
DATA AC
BREAK
OFF TABS
LEFT
CENTER
RIGHT
STATUS
CODE
PU
PU
PK
U
V
W
LINE
NEUTRAL
BL
GY
BK
RD
YL
WH
RD
BK
BK
WH
WH
WH
GND
TX
RX
YL
RD
WH
WH
WH
RD
GR
GR
BL
BR
GY
VDD
GY
YL
BR
GR
PK
YL
GY
BR
YL
BR
GY
GND
PRESSURE
TRANSDUCER
RD
BK
GR
BR
GY
RD
EMI LINE FILTER
BK
GY
BL
GND
PK
ID BLOWER
PRESSURE SWITCH
2 CIRCUIT
CONNECTOR
GAS VALVE
WIRE
CODES:
BLACK
BLUE
BROWN
GREEN
GRAY
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
TAN
VIOLET
COLOR
DESIGNATION
BK
BL
BR
GR
GY
OR
PK
PU
RD
WH
YL
TN
VT
GND
1
2
5V
A2L SENSOR
CONNECTOR
A2L MODE IS ENABLED BY
DEFAULT
REFER TO INSTALLATION MANUAL
FOR FURTHER INSTRUCTIONS.
GND
PI
5V
MOB_PE
E34
GND
GROUND WIRE
CONNECTED
TO CONTROL
MOUNTING
PANEL
RD
BK
GR
GR
GR
E28
SEE NOTE 7
A/GRVS80*UAA