Installation Instructions for
*R9S80 & *D9S80*
Gas Furnace
CATEGORY I
IOG-2035C
07/2025
19001 Kermier Rd. Waller, TX 77484
www.goodmanmfg.com • www.amana-hac.com
© 2025 Daikin Comfort Technologies Manufacturing, Inc.
is a registered trademark of Maytag Corporation or its related companies and is used under license.
All rights reserved.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
As a professional installer you have an obligation to know
the product better than the customer. This includes all
safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself
with this Instruction Manual. Pay special attention to all
safety warnings. Often during installation or repair it is
possible to place yourself in a position which is more
hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product
safely and to know it well enough to be able to instruct a
customer in its safe use.
Safety is a matter of common sense...a matter of thinking
before acting. Most dealers have a list of specic good
safety practices...follow them.
The precautions listed in this Installation Manual are
intended as supplemental to existing practices. However, if
there is a direct conict between existing practices and the
content of this manual, the precautions listed herein take
precedence.
*NOTE: Please contact your distributor or our website for the
applicable Specication Sheet referred to in this manual.
80% HEX
DO NOT LIFT
PRODUCT USING
HEAT EXCHANGER
Do not bypass safety devices.
WARNING
These furnaces comply with requirements embodied
in the American National Standard / National
Standard of Canada ANSI Z21.47·CSA-2.3 Gas Fired
Central Furnaces.
Installer:
Ax all manuals
adjacent to the unit.
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL,
ADJUST, SERVICE, MAINTENANCE OR REPAIR
(HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN
THIS MANUAL SHOULD SERVICE THE EQUIPMENT.
THIS EQUIPMENT IS NOT INTENDED FOR USE BY
PERSONS (INCLUDING CHILDREN) WITH REDUCED
PHYSICAL, SENSORY OR MENTAL CAPABILITIES, OR LACK
OF EXPERIENCE AND KNOWLEDGE, UNLESS THEY HAVE
BEEN GIVEN SUPERVISION OR INSTRUCTION CONCERNING
USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR
THEIR SAFETY.
CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT
THEY DO NOT PLAY WITH THE EQUIPMENT.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR
ANY INJURY OR PROPERTY DAMAGE ARISING FROM
IMPROPER SUPERVISION, SERVICE OR SERVICE
PROCEDURES. IF YOU SERVICE THIS UNIT, YOU ASSUME
RESPONSIBILITY FOR ANY INJURY OR PROPERTY
DAMAGE WHICH MAY RESULT. IN ADDITION, IN
JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES
TO SERVICE THE EQUIPMENT SPECIFIED IN THIS
MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE
THE EQUIPMENT. IMPROPER SUPERVISION, INSTALLATION,
ADJUSTMENT, SERVICING, MAINTENANCE OR REPAIR OF
THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR
ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR
THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT
PROPER SUPERVISION OR TRAINING MAY RESULT IN
PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
WARNING
background
2
SAFETY CONSIDERATIONS
Adhere to the following warnings and cautions when
installing,adjusting, altering, servicing, or operating the
furnace. To ensure proper installation and operation,
thoroughly read this manual for specics pertaining to the
installation and application of this product.
Failure to follow the safety warnings exactly could
result in serious injury, death or property damage.
Never test for gas leaks with an open flame.
Use a commercially available soap solution made
specifically for the detection of leaks to check all
connections. A fire or explosion may result causing
property damage, personal injury or loss of life.
WARNING
FIRE OR EXPLOSION HAZARD
This furnace is manufactured for use with natural gas. It
may be eld converted to operate on L.P. gas by using the
appropriate L.P. conversion kit listed in the PROPANE
GAS/HIGH ALTITUDE INSTALLATIONS section of this
manual.
Install this furnace only in a location and position
as specied in LOCATION REQUIREMENTS &
CONSIDERATIONS section and INSTALLATION
POSITIONS section of this manual.
Provide adequate combustion and ventilation air to the
furnace as specied in COMBUSTION & VENTILATION
AIR REQUIREMENTS section of this manual.
Combustion products must be discharged to the outdoors.
Connect this furnace to an approved vent system only, as
specied in Category 1 Venting section of this manual.
Never test for gas leaks with an open ame. Use a
commercially available soap solution made specically for
the detection of leaks to check all connections, as specied
in GAS SUPPLY AND PIPING section of this manual.
Always install a furnace to operate within the furnace’s
intended temperature-rise range with a duct system which
has external static pressure within the allowable range, as
specied on the furnace rating plate and OPERATIONAL
CHECKS section of these instructions.
When furnace duct(s) supply air outside the space
containing the furnace, a return air duct must terminate in
the same space as the supply duct and be sealed to the
furnace casing.
A gas-red furnace for installation in a residential
garage must be installed as specied in the LOCATION
REQUIREMENTS AND CONSIDERATIONS section of
this manual.
This furnace may be used as a construction site heater
only if certain conditions are met. These conditions are
listed in the PRODUCT APPLICATION section of this
manual.
WARNING
To prevent personal injury or death due to improper
installation, adjustment, alteration, service, or maintenance,
refer to this manual. For additional assistance or
information, consult a qualified installer, servicer agency
or the gas supplier.
WARNING
THIS FURNACE MAY BE PAIRED WITH A COOLING UNIT THAT
USES R-32 REFRIGERANT. IF THE COOLING UNIT PAIRED WITH
THIS FURNACE DOES NOT USE R-32, THE R-32 FUNCTION IN
THE FURNACE CONTROL BOARD NEEDS TO BE TURNED OFF.
PLEASE SEE THE ELECTRICAL AND R-32 SECTIONS FOR MORE
DETAILS. REFRIGERANT SYSTEMS OTHER THAN 410A OR
R-32 MAY REQUIRE AN ADDITIONAL MITIGATION CONTROL
BOARD. REFER TO THE INSTALLATION MANUAL OF THE
INDOOR EVAPORATOR COIL TO DETERMINE INSTALLATION
REQUIREMENTS FOR THAT SUPPLIER’S REFRIGERANT
DETECTION SYSTEM.
TABLE OF CONTENTS
Safety Considerations ..................................................2
Product Application ......................................................4
Location Requirements & Considerations ................5
Combustion & Ventilation Air Requirements............8
Electrical Connections ..............................................10
Gas Supply and Piping ................................................. 11
Circulating Air .............................................................15
Electrical ......................................................................17
R-32 Information ...........................................................23
Maintenance ..................................................................23
Media Air Filter or Electronic Air Cleaner
Removal ..........................................................................24
Before Leaving an Installation .................................24
Repair and Replacement Parts ..................................24
Airflow Tables .............................................................25
Status Codes .................................................................30
Troubleshooting Codes ..............................................32
Wiring Diagram .............................................................34
Start-Up Checklist .......................................................36
background
3
WARNING
If the information in these instructions is not followed
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
– Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
– What to do if you smell gas:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions. If you can
not reach your gas supplier, call the fire department.
– Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING
This product contains or produces a chemical or chemicals
which may cause serious illness or death and which are
known to the State of California to cause cancer, birth
defects or other reproductive harms.
WARNING
To prevent possible property damage, personal injury or
death due to electrical shock, the furnace must be located
to protect the electrical components from water.
WARNING
Heating unit should not be utilized without reasonable
routine, inspection, maintenance and supervision. In the event
that the building may be exposed to freezing temperatures
and will be vacant, all water-bearing pipes should be
drained. The building should be properly winterized and the
water source closed. In the event that the building may be
exposed to freezing temperatures and will be vacant, any
hydronic coil units should be drained as well and, in such
case, alternative heat sources should be utilized.
WARNING
Should overheating occur or the gas supply fail to shut
off, turn off the manual gas shutoff valve external to the
furnace before turning off the electrical supply.
WARNING
Possible property damage, personal injury or death due to
fire, explosion, smoke, soot, condensation, electrical shock,
or carbon monoxide may result from improper installation,
repair operation, or maintenance of this product.
WARNING
To prevent personal injury or death due to improper
installation, adjustment, alteration, service or maintenance,
refer to this manual. For additional assistance or
information, consult a qualified installer, servicer agency
or the gas supplier.
WARNING
To prevent personal injury or death due to asphyxiation,
this furnace must be Category I vented. Do not vent using
Category III Venting.
Provisions must be made for venting combustion products
outdoors through a proper venting system. This length of
flue pipe could be a limiting factor in locating the furnace.
B10259-216
CO can cause serious illness including permanent brain
damage or death.
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
B10259-216
El monóxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
Las emisiones de monóxido de carbono pueden circular a través
del aparato cuando se opera en cualquier modo.
B10259-216
RISQUE D'EMPOISONNEMENT AU
MONOXYDE DE CARBONE
Le monoxyde de
des
carbone peut causer des maladies graves telles que
dommages permanents au cerveau et meme la mort.
Ce�e ven�la�on est nécessaire pour éviter le danger d'intoxica�on
au CO pouvant survenir si un appareil produisant du monoxyde
de carbone con�nue de fonc�onner au sein de la zone confinée.
background
4
Additional Safety Considerations
• This furnace is approved for Category I Venting only.
• Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of ue pipe could be a limiting factor in
locating the furnace.
Shipping Inspection
All units are securely packed in shipping containers
tested according to International Safe Transit Association
specications. The carton must be checked upon arrival
for external damage. If damage is found, a request for
inspection by the carrier’s agent must be made in writing
immediately.
The furnace must be carefully inspected on arrival for
damage and bolts or screws which may have come loose
in transit. In the event of damage the consignee should:
1. Make a notation on delivery receipt of any visible
damage to shipment or container.
2. Notify the carrier promptly and request an inspection.
3. With concealed damage, the carrier must be notied
as soon as possible - preferably within ve days.
4. File the claim with the following support documents
within a nine month statute of limitations.
• Original or certied copy of the Bill of Lading, or
indemnity bond.
• Original paid freight bill or indemnity in lieu
thereof.
• Original or certied copy of the invoice, showing
trade and other discounts or reductions.
• Copy of the inspection report issued by the
carrier’s representative at the time damage is
reported to carrier.
The carrier is responsible for making prompt inspection of
damage and for a thorough investigation of each claim.
The distributor or manufacturer will not accept claims from
dealers for transportation damage.
Keep this literature in a safe place for future refer ence.
Electrostatic Discharge (ESD) Precautions
NOTE: Discharge body’s static electricity before
touching unit. An electrostatic discharge can
adversely affect electrical components.
Use the following precautions during furnace installation
and servicing to protect the integrated control module
from damage. By putting the furnace, the control, and the
person at the same electrostatic potential, these steps
will help avoid exposing the integrated control module to
electrostatic discharge. This procedure is applicable to both
installed and non-installed (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch
the integrated control module or any wire connected
to the control prior to discharging your body’s
electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the
furnace near the control. Any tools held in a person’s
hand during grounding will be discharged.
3. Service integrated control module or connecting
wiring following the discharge process in step 2.
Use caution not to recharge your body with static
electricity (i.e., do not move or shu󰀪e your feet, do
not touch ungrounded objects, etc.). If you come in
contact with an ungrounded object, repeat step 2
before touching control or wires.
4. Discharge your body to ground before removing
a new control from its container. Follow steps 1
through 3 if installing the control on a furnace. Return
any old or new controls to their containers before
touching any ungrounded object.
To The Installer
Before installing this unit, please read this manual
thoroughly to familiarize yourself with specic items which
must be adhered to, including but not limited to: unit
maximum external static pressure, gas pressures, BTU
input rating, proper electrical connections, circulating air
temperature rise, minimum or maximum CFM, and motor
speed connections, and venting. These furnaces are
designed for Category I venting only.
NOTE: This unit should be installed in a manner so
that it is not accessible to the public.
PRODUCT APPLICATION
This furnace is primarily designed for residential home-
heating applications. It is NOT designed or certied for
use in mobile homes, trailers or recreational vehicles.
Neither is it designed or certied for outdoor applications.
The furnace must be installed indoors (i.e., attic space,
crawl space, or garage area provided the garage area is
enclosed with an operating door).
This furnace can be used in the following non-industrial
commercial applications:
Schools, O󰀩ce Buildings, Churches, Retail Stores,
Nursing Homes, Hotels/Motels, Common or O󰀩ce Areas
In such applications, the furnace must be installed with the
following stipulations:
• It must be installed per the installation instructions
provided and per local and national codes.
• It must be installed indoors in a building constructed
on site.
• It must be part of a ducted system and not used in a
free air delivery application.
• It must not be used as a “make-up” air unit.
• All other warranty exclusions and restrictions apply.
This furnace may be used as a construction site heater
ONLY if all of the following conditions are met:
• The vent system is permanently installed per these
installation instructions.
background
5
• A room thermostat is used to control the furnace.
Fixed jumpers that provide continuous heating
CANNOT be used and can cause long term
equipment damage. Bi-metal thermostats, or any
thermostat a󰀨ected by vibration must not be used
during construction.
• Return air ducts are provided and sealed to the
furnace.
• A return air temperature range between 60ºF (16ºC)
and 80ºF (27ºC) is maintained.
• Air lters are installed in the system and replaced
daily during construction and upon completion of
construction.
• The input rate and temperature rise are set per the
furnace rating plate.
• 100% outside air must be used for combustion
during construction. Temporary ducting may be used
to supply outside air to the furnace for combustion –
do not connect this duct directly to the furnace. Size
this duct according to NFPA 54/ANSI Z223.1 section
for Combustion and Ventilation Air.
• The furnace heat exchanger, components, duct
system, air lters and evaporator coils are thoroughly
cleaned following nal construction clean up by a
qualied person.
• All furnace operating conditions (including ignition,
input rate, temperature rise and venting) are veried
by a qualied person according to these installation
instructions.
• Furnace doors must be in place on the furnace while
the furnace is operating in any mode.
• Damage or repairs due to failure to comply with
these requirements are not covered under the
warranty.
NOTE: The Commonwealth of Massachusetts
requires that the following additional
requirements must also be met:
• Gas furnaces must be installed by a licensed
plumber or gas tter.
• A T-handle gas cock must be used.
• If the unit is to be installed in an attic, the
passageway to and the service area around the unit
must have ooring.
WARNING
To prevent property damage, personal injury, or death due to
fire, do not install this furnace in a mobile home, trailer, or
recreational vehicle.
To ensure proper furnace operation, install, operate
and maintain the furnace in accordance with these
installation and operation instructions, all local
building codes and ordinances. In their absence, follow
the latest edition of the National Fuel Gas Code (NFPA 54/
ANSI Z223.1) and/or local plumbing or waste water codes,
and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1) can be obtained from any of the following:
American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley
Independence, OH 44131
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE Guide” or “Manual
J-Load Calculations” published by the Air Conditioning
Contractors of America.
In the USA, this furnace MUST be installed in accordance
with the latest edition of the ANSI Z223.1 booklet entitled
“National Fuel Gas Code” (NFPA 54), and the requirements
or codes of the local utility or other authority having
jurisdiction. Additional helpful publications available from
the NFPA are, NFPA 90A - Installation of Air Conditioning
and Ventilating System and NFPA 90B - Warm Air Heating
and Air Conditioning System.
All venting shall be in accordance with the National Fuel
Gas Code, ANSI Z223.1, or applicable local building and/or
air conditioning codes.
NOTE: Furnaces with NOx screens meet the
California NOx emission standards and California
seasonal efficiency standards. ANNUAL
inspections of the furnace and its vent system is
strongly recommended.
LOCATION REQUIREMENTS AND
CONSIDERATIONS
Your unit model type determines which installation
procedures must be used. For *R9S80 models, you must
follow instructions for Horizontal Left, Horizontal Right or
Upow installations only. These furnaces are not approved
for Downow installations.
*D9S80 models may be installed in the Downow position
as well as Horizontal Left & Horizontal Right positions.
WARNING
To prevent possible equipment damage, property damage,
personal injury, or death, the following bullet points must
be observed when installing this unit.
background
6
Follow the instructions listed below when selecting a
furnace location. Refer also to the guidelines provided in
the Combustion and Ventilation Air Requirements.
• Centrally locate the furnace with respect to the
proposed or existing air distribution system.
• Ensure the temperature of the return air entering
the furnace is between 55°F and 100°F when the
furnace is heating.
• Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of ue pipe could be a limiting factor in
locating the furnace.
• Ensure adequate combustion air is available for
the furnace. Improper or insu󰀩cient combustion air
can expose building occupants to gas combustion
products that could include carbon monoxide. Refer
to Combustion and Ventilation Air Requirements
section.
• The furnace must be level. If the furnace is to be set
on a oor that may become wet or damp at times,
the furnace should be supported above the oor on a
concrete base sized approximately 1-½” larger than
the base of the furnace.
• Ensure upow or horizontal furnaces are not installed
directly on carpeting, or any other combustible
material. The only combustible material allowed is
wood.
• Exposure to contaminated combustion air will result
in safety and performance-related problems. Do
not install the furnace where the combustion air is
exposed to the following substances:
chlorinated waxes or cleaners
chlorine-based swimming pool chemicals
water softening chemicals
deicing salts or chemicals
carbon tetrachloride
halogen type refrigerants
cleaning solutions (such as perchloroethylene)
printing inks
paint removers
varnishes
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
and masonry acid washing materials
• If the furnace is used in connection with a cooling
unit, install the furnace upstream of the cooling
coil. Additionally, a coil installed above an upow
furnace or under a counterow furnace may be the
same width as the furnace or may be one size larger
than the furnace. Example: a “C” width coil may be
installed with a “B” width furnace.
• For all applications, the front of the coil and furnace
must face the same direction.
• If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition
source are located not less than 18 inches (457 mm)
above the oor. Protect the furnace from physical
damage by vehicles.
• If the furnace is installed horizontally, the furnace
access doors must be vertical so that the burners re
horizontally into the heat exchanger. Do not install
the unit with the access doors on the “up/top” or
“down/bottom” side of the furnace.
• Do not connect this furnace to a chimney ue that
serves a separate appliance designed to burn solid
fuel.
• Counterow installation over a noncombustible oor.
Before setting the furnace over the plenum opening,
ensure the surface around the opening is smooth
and level. A tight seal should be made between the
furnace base and oor by using a silicon rubber
caulking compound or cement grout.
• Counterow installation over a combustible oor.
If installation over a combustible oor becomes
necessary, use an accessory subbase (see
Specication Sheet applicable to your model for
details). A special accessory subbase must be used
for upright counterow unit installations over any
combustible material including wood. Follow the
instructions with the subbase for proper installations.
• Do not install the furnace directly on carpeting, tile, or
other combustible material other than wood ooring.
NOTE: The subbase will not be required if an air
conditioning coil is installed between the supply
air opening on the furnace and the oor. The air
conditioning coil must be downstream from the heat
exchanger of the furnace.
Top - 1"
Side
Clearance - 1"
Back - 0"
Front Clearance - 3"
Vent Pipe Clearance to Combustibles-
6" using Single Wall Connector or 1"
using B-1 vent.
Figure 1
• Adequate combustion/ventilation air must be
supplied to the closet.
• Furnace must be completely sealed to oor or
base. Combustion/ventilation air supply pipes must
terminate 12” from top of closet and 12” from oor
of closet. DO NOT remove solid base plate for side
return.
background
7
• Return air ducts must be completely sealed to
the furnace and terminate outside the enclosure
surfaces.
Clearances and Accessibility
Unobstructed front clearance of 24” for servicing is
recommended.
TOP
B1-VENT SINGLE
(PLENUM)
1" 6" 1" 3" 0" 1"
VENT
SIDES
FRONT
BACK
Top clearance for horizontal configuration - 1”
Installation Positions
*R9S80 model furnaces may be installed vertically
(upow) or horizontally with left or right side down. *D9S80
model furnaces may be installed vertically (downow)
or horizontally with left or right side down. Do not install
this furnace on its back. For vertically installed upow
furnaces, return air ductwork may be attached to the side
panel(s) and/or basepan. For upright counterow furnaces,
return air ductwork must be attached to the top end of
the blower compartment. For any horizontally installed
furnaces, return ductwork must be attached to the blower
compartment end of the furnace.
NOTE: Ductwork must never be attached to the
back of the furnace.
Horizontal Installation
Line contact to framing is permitted when installed in the
horizontal conguration. Line contact is dened as the
portion of the cabinet that is formed by the intersection of
the top and side. ACCESSIBILITY CLEARANCE, WHERE
GREATER, SHOULD TAKE PRECEDENCE OVER
MINIMUM FIRE PROTECTION CLEARANCE. A gas-
red furnace for installation in a residential garage must
be installed so that the ignition source and burners are
located not less than eighteen inches (18”) above the oor
and is protected or located to prevent physical damage by
vehicles. A gas furnace must not be installed directly on
carpeting, tile, or other combustible materials other than
wood ooring.
Furnace Suspension
If suspending the furnace from rafters or joist, use 3/8”
threaded rod and 2”x2”x3/8” angle iron as shown below.
The length of rod will depend on the application and the
clearances necessary.
Suspended Furnace
Figure 2
Auxiliary Drain Pan
An auxiliary/secondary drain pan should be installed
under a condensing furnace and/or indoor coil when any
potential leakage could cause damage to ceilings, oors
or other areas below the installation location. The auxiliary
drain pan should be at least 1-1/2 inches deep, 3 inches
larger than the unit and constructed of corrosion-resistant
material. The drain pan should have a drain line connected
to the pan and the drain line should be pitched downward
away from the pan a minimum of 1/8” per foot of drain line.
The drain line should terminate in a location where the
water dripping from the drain line will alert the occupant
that a problem exists. The auxiliary drain pan should also
be equipped with a water level detection device conforming
to UL 508 that will shut o󰀨 the equipment served prior to
overow of the pan.
background
8
For upow and horizontal installations, the furnace and/
or indoor coil should be installed so that the equipment is
at least 1-1/2 inches above the drain pan. Do not install
the furnace and/or indoor coil directly into the auxiliary/
secondary drain pan and do not use any wood product
in the drain pan to elevate the furnace. Bricks, 2-inch
concrete cap blocks, metal furnace stands, or furnace
blocks can be used to elevate the furnace. For an upow
furnace installation, seal the entire bottom of the furnace
before setting the furnace at least 1-1/2 inches above the
drain pan.
Failure to properly install an auxiliary/secondary drain pan
for a furnace and/or indoor coil can result in water damage
to components and the furnace’s metal cabinet.
Figure 3
Existing Furnace Removal
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed into
operation could result in carbon monoxide poisoning or
death.
The following steps shall be followed with each appliance
connected to the venting system placed in operation, while
any other appliances connected to the venting system are
not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required by the National Fuel
Gas Code, ANSI Z223.1 or the Natural Gas and Propane
Installation Code, CSA B149.1-15 and these instructions.
Determine that there is no blockage or restriction,
leakage, corrosion and other deficiencies which could
cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they shall operate at maximum speed.
Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously.
7. Test for spillage from draft hood appliances at the
draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the
above tests, the venting system must be corrected
in accordance with the National Fuel Gas Code ANSI
Z223.1/NFPA 54 and/or National Gas and Propane
Installation Code CSA B149.1-15.
9. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas
burning appliance to their previous conditions of use.
Corrections must be in accordance with the latest edition of
the National Fuel Gas Code NFPA 54/ANSI Z223.1 and/or
CAN/CSA B149 Installation Codes.
If resizing is required on any portion of the venting system,
use the appropriate table in the latest edition of the
National Fuel Gas Code ANSI Z223.1.
Thermostat Location
In an area having good air circulation, locate the thermostat
about ve feet high on a vibration-free inside wall. Do not
install the thermostat where it may be inuenced by any of
the following:
• Drafts, or dead spots behind doors, in corners, or
under cabinets.
• Hot or cold air from registers.
• Radiant heat from the sun.
• Light xtures or other appliances.
• Radiant heat from a replace.
background
9
• Concealed hot or cold water pipes, or chimneys.
• Unconditioned areas behind the thermostat, such as
an outside wall.
Consult the instructions packaged with the thermostat for
mounting instructions and further precautions.
COMBUSTION AND VENTILATION
AIR REQUIREMENTS
WARNING
To avoid property damage, personal injury or death,
sufficient fresh air for proper combustion and ventilation
of flue gas must be supplied. Most homes require outside air
be supplied into the furnace area.
Improved construction and additional insulation in buildings
have reduced heat loss by reducing air inltration and
escape around doors and windows. These changes have
helped in reducing heating/cooling costs but have created
a problem supplying combustion and ventilation air for
gas red and other fuel burning appliances. Appliances
that pull air out of the house (clothes dryers, exhaust
fans, replaces, etc.) increase the problem by starving
appliances for air.
House depressurization can cause back drafting or
improper combustion of gas-red appliances, thereby
exposing building occupants to gas combustion products
that could include carbon monoxide.
If this furnace is to be installed in the same space with
other gas appliances, such as a water heater, ensure
there is an adequate supply of combustion and ventilation
air for all appliances. Refer to the latest edition of the
National Fuel Gas Code NFPA 54/ANSI Z223.1 or CAN/
CSA B149 Installation Codes or applicable provisions of
the local building codes for determining the combustion air
requirements for the appliances.
This furnace must use indoor air for combustion. It cannot
be installed as a direct vent (i.e., sealed com bustion)
furnace.
Most homes will require outside air be supplied to the
furnace area by means of ventilation grilles or ducts
connecting directly to the outdoors or spaces open to the
outdoors such as attics or crawl spaces.
The *R9S80 and *D9S80 furnaces are provided with a
combustion air intake pipe kit which adds a combustion air
intake pipe instead of relying on the louvers for combustion
air. Please refer to the installation manual provided with the
kit for additional information and instructions.
Category I Venting (Vertical Venting)
WARNING
To prevent possible personal injury or death due to
asphyxiation, this furnace must be Category I vented. Do not
vent using Category III venting.
Category I Venting is venting at a non-positive pressure. A
furnace vented as Category I is considered a fan-assisted
appliance and the vent system does not have to be “gas
tight”. NOTE: Gas furnaces with induced draft blowers
draw products of combustion through a heat exchanger
allowing, in some instances, common venting with natural
draft appliances (i.e. water heaters). All installations must
be vented in accordance with National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest edition.
NOTE: The vertical height of the Category I
venting system must be at least as great as the
horizontal length of the venting system.
WARNING
To prevent possible personal injury or death due to
asphyxiation, common venting with other manufacturer’s
induced draft appliances is not allowed.
The minimum vent diameter for the Category I venting
system is as shown:
MODEL
MINIMUM VENT
UPFLOW COUNTER FLOW
040 3 inch 3 inch
060 4 inch 4 inch
080 4 inch 4 inch
100 5 inch 4 inch
120 5 inch N/A
Under some conditions, larger vents than those shown
above may be required or allowed. When an existing
furnace is removed from a venting system serving other
appliances, the venting system may be too large to
properly vent the remaining attached appliances.
Furnaces are shipped with the induced draft blower
discharging from the top of the furnace (“Top” is as viewed
for an upow installation.) The induced draft blower on
*R9S80 models can be rotated 90 degrees for Category
I venting. For furnaces installed vertically or horizontally,
a four-inch single wall pipe can be used to extend the
induced draft blower outlet ½” beyond the furnace cabinet.
background
10
On *R9S80 furnaces installed upow or horizontally
with left side down, the draft inducer may be rotated
to discharge from the right side of the cabinet. When
rotating the inducer a chimney transition bottom kit (part #
4053501S) is needed for proper alignment of the inducer
outlet and the vent exit hole in the side of the cabinet. The
inducer may NOT be rotated on *D9S80 model furnaces
regardless of installation position.
THIS PRODUCT IS NOT DESIGNED FOR
COUNTERCLOCKWISE INDUCED DRAFT BLOWER
ROTATION.
Vent the furnace in accordance with the National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition.
Venting
THIS FURNACE IS NOT CERTIFIED TO BE
HORIZONTALLY VENTED.
To rotate the induced draft blower clockwise, you will need
to purchase one (4053501S) chimney transition bottom kit.
1. Disconnect electrical power from the furnace.
2. Disconnect the induced draft blower power leads,
ue pipe, and pressure switch tubing.
3. Remove the round cutout from the right side of the
wrapper.
4. Remove and save the four screws that fasten the
induced draft blower to the ue collector box.
5. Remove and save the three screws that hold the
chimney assembly to the induced draft blower.
6. Remove and save the four screws that fasten the
chimney top to the chimney bottom.
7. Remove the chimney transition bottom from the
transition bottom kit.
8. Install the chimney top with the four screws retained
from step 6 onto the new chimney transition bottom
from the transition bottom kit.
9. Install chimney assembly with the three screws
retained from step 5 onto the induced draft blower.
10. Reinstall the induced draft blower rotating it
90 degrees clockwise from the original upow
conguration using the four screws retained in
step 3. Ensure the gasket located between the
induced draft blower and the collector box is rotated
accordingly.
11. Reconnect the induced draft blower power leads.
NOTE: If the wires are not long enough, pull extra
wire from the wire bundle in the blower compartment.
12. Reconnect the ue pipe, and the pressure switch
tubing. Ensure that all wires and the pressure switch
tubing is at least one inch from the ue pipe, or any
other hot surface.
13. Restore power to furnace.
Counterow units are shipped with the induced draft
blower discharging from the top of the furnace (“Top” as
viewed for a counterow installation).
Vent the furnace in accordance with the National Fuel Gas
Code NFPA54/ANSI Z223.1 - latest edition.
WARNING
Never allow the products of combustion, including carbon
monoxide, to enter the return ductwork or circulation air
supply.
MASONRY CHIMNEYS
WARNING
Possibility of property damage, personal injury, death or
damaging condensation can occur inside masonry chimneys
when a single fan-assisted Category I appliance (80% AFUE
furnace) is vented without adequate dilution air. Do not
connect an 80% furnace to a masonry chimney unless the
furnace is common vented with a draft hood equipped
appliance or the chimney is lined with a metal liner or Type
B metal vent. All installations using masonry chimneys must
be sized in accordance with appropriate venting tables. If an
80% furnace is common vented with a draft hood equipped
appliance, the potential for condensation damage may still
exist with extremely cold conditions, long vent connectors,
exterior chimneys, or any combination of these conditions.
The risk of condensation damages is best avoided by using
masonry chimney as a pathway for properly sized metal liner
or Type B metal vent.
Masonry Chimney Terminations
A masonry chimney used as a vent for gas red equipment
must extend at least three feet above the highest point
where it passes through the roof. It must extend at least
two feet higher than any portion of a building within a
horizontal distance of 10 feet. In addition, the chimney
must terminate at least three feet above any forced air inlet
located within 10 feet. The chimney must extend at least
ve feet above the highest connected equipment draft
hood outlet or ue collar.
ELECTRICAL CONNECTIONS
WARNING
HIGH VOLTAGE!
To avoid the risk of electrical shock, wiring to
the unit must be polarized and grounded.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
background
11
WARNING
HIGH VOLTAGE!
To avoid risk of injury, electrical shock or death,
the furnace must be electrically grounded in
accordance with local codes or in their absence,
with the latest edition of the National Electric
Code.
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a
precaution when removing hole plugs.
Wiring Harness
The wiring harness is an integral part of this furnace. Field
alteration to comply with electrical codes should not be
required. Wires are color coded for identication purposes.
Refer to the wiring diagram for wire routings. If any of
the original wire as supplied with the furnace must be
replaced, it must be replaced with wiring material having
a temperature rating of at least 105°C. Any replacement
wiring must be a copper conductor.
115 Volt Line Connections
Before proceeding with electrical connections, ensure
that the supply voltage, frequency, and phase correspond
to that specied on the unit rating plate. Power supply to
the furnace must be NEC Class 1, and must comply with
all applicable codes. The furnace must be electrically
grounded in accordance with local codes or, in their
absence, with the latest edition of The National Electric
Code, ANSI NFPA 70 and/or The Canadian Electric Code
CSA C22.1.
Use a separate fused branch electrical circuit containing
properly sized wire, and fuse or circuit breaker. The fuse
or circuit breaker must be sized in accordance with the
maximum overcurrent protection specied on the unit
rating plate. An electrical disconnect must be provided at
the furnace location.
Connect hot, neutral, and ground wires as shown in the
wiring diagram located on the unit’s blower door. Metal
conduit is not considered a substitute for an actual ground
wire to the unit.
Line polarity must be observed when making eld
connections. Line voltage connections can be made
through either the right or left side panel. The furnace is
shipped congured for a right side electrical connection
with the junction box located inside the burner
compartment (blower compartment for downows). To
make electrical connections through the opposite side of
the furnace, the junction box must be relocated to the other
side of the burner (or blower) compartment prior to making
electrical connections. To relocate the junction box, follow
the steps shown below.
NOTE: Wire routing must not interfere with
circulator blower operation, filter removal, or
routine maintenance.
Junction Box Relocation
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a
precaution when removing hole plugs.
WARNING
To prevent personal injury or death due to electric shock,
disconnect electrical power before installing or servicing
this unit.
1. Remove both doors from the furnace.
2. Remove and save the screws holding the junc tion
box to the right side of the furnace.
3. Attach the junction box to the left side of the fur nace,
using the screws removed in step 2.
4. Check the location of the wiring. Conrm that it
will not be damaged by heat from the burners or
by the rotation of the fan. Also conrm that wiring
location will not interfere with l ter removal or other
maintenance.
IMPORTANT NOTE: To avoid possible equipment
malfunction, route the low voltage wires to
avoid interference with filter removal or other
maintenance.
WARNING
HIGH VOLTAGE!
To avoid risk of injury, electrical shock or death,
the furnace must be electrically grounded in
accordance with local codes or in their absence,
with the latest edition of the National Electric
Code.
To ensure proper unit grounding, the ground wire should
run from the furnace ground screw located inside the
furnace junction box all the way back to the electrical
panel. NOTE: Do not use gas piping as an electrical
ground. To conrm proper unit grounding, turn o󰀨 the
electrical power and perform the following check.
1. Measure resistance between the neutral (white)
connection and one of the burners.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock
switch which interrupts unit voltage when the blower door
is opened for servicing. Do not defeat this switch.
background
12
GAS SUPPLY AND PIPING
The furnace rating plate includes the approved furnace gas
input rating and gas types. The furnace must be equipped
to operate on the type of gas applied. This includes any
conversion kits required for alternate fuels and/or high
altitude.
CAUTION
To prevent unreliable operation or equipment damage, the
inlet gas supply pressure must be as specified on the unit
rating plate with all other household gas fired appliances
operating.
Inlet gas supply pressures must be maintained within the
ranges specied in the following table. The supply pressure
must be constant and available with all other household
gas red appliances operating. The minimum gas supply
pressure must be maintained to prevent unreliable ignition.
The maximum must not be exceeded to prevent unit
overring.
NOTE: Do not remove the gas valve inlet plug
before the gas line is installed. Replace if water
or debris has been introduced.
INLET GAS SUPPLY PRESSURE
NOTE: Adjusting the minimum supply pressure
below the limits in the above table could lead to
unreliable ignition. Gas input to the burners must
not exceed the rated input shown on the rating
plate. Overfiring of the fur nace can result in
premature heat exchanger failure. Gas pressures
in excess of 13 inch es water column can also cause
permanent damage to the gas valve.
At all altitudes, the manifold pressure must be within
0.3 inches w.c. of that listed in the Specication Sheet
applicable to your model for the fuel used. At all altitudes
and with either fuel, the air tempera ture rise must be
within the range listed on the furnace nameplate. Should
this appliance be converted to LP, refer to the instructions
included in the factory authorized LP conversion kit.
High Altitude Derate
When this furnace is installed at high altitude, the
appropriate High Altitude orice kit must be applied. This is
required due to the natural reduction in the density of both
the gas fuel and combustion air as altitude increases. The
kit will provide the proper design certied input rate within
the specied altitude range.
High altitude kits are purchased according to the
installation altitude and usage of either natural or
propane gas. Consult the furnace Specication Sheet for
appropriate kits.
Do not derate the furnace by adjusting the manifold
pressure to a lower pressure than specied on the furnace
rating plate. The combination of the lower air density and a
lower manifold pressure will prohibit the burner orice from
drawing the proper amount of air into the burner. This may
cause incomplete combustion, ashback, and possible
yellow tipping.
In some areas the gas supplier may articially derate the
gas in an e󰀨ort to compensate for the e󰀨ects of altitude.
If the gas is articially derated, the appropriate orice size
must be determined based upon the BTU/ft
3
content of
the derated gas and the altitude. Refer to the National
Fuel Gas Code, NFPA 54/ANSI Z223.1, and information
provided by the gas supplier to determine the proper orice
size.
A di󰀨erent pressure switch may be required at high altitude
regardless of the BTU/ft
3
content of the fuel used. Consult
the furnace Specication Sheet for pressure switch.
Consult the furnace Specication Sheet for appropriate
manufacturer’s kits for propane gas and/or high altitude
installations. The indicated kits must be used to insure safe
and proper furnace operation. All conversions must be
performed by a qualied installer, or service agency.
Propane Gas Conversion
WARNING
Possible property damage, personal injury or death may
occur if the correct conversion kits are not installed. The
appropriate kits must be applied to ensure safe and proper
furnace operation. All conversions must be performed by a
qualified installer or service agency.
This unit is congured for natural gas. The appropriate
manufacturer’s propane gas conversion kit must be applied
for propane gas installations.
Altitude Gas Kit Orifice
Manifold
Pressure
Pressure
Switch
#55 10.0" w .c.
0 - 4500
Natural None #45 3.5" w .c.
None
Propane LPM-31
If converting to LP gas, it is recommended that an LPLP0*
kit also be installed. The use of this kit will prevent the
furnace from ring when the LP gas supply pressure is too
low to support proper combustion.
background
13
Gas Valve
This unit is equipped with a 24 volt gas valve controlled
during furnace operation by the integrated control
module. As shipped, the valve is congured for natural
gas. The valve is eld convertible for use with propane
gas by replacing the regulator spring with a propane gas
spring from an appropriate manufacturer’s propane gas
conversion kit. Taps for measuring the gas supply pressure
and manifold pressure are provided on the valve.
The gas valve has a manual ON/OFF control located on
the valve itself. This control may be set only to the “ON”
or “OFF” position. Refer to the lighting instructions label
or Startup Procedure & Adjustment for use of this control
during start up and shut down periods.
Gas Piping Connections
When sizing gas lines, be sure to include all appliances
which will operate simultaneously.
The gas piping supplying the furnace must be properly
sized based on the gas ow required, specic gravity of the
gas, and length of the run. The gas line installation must
comply with local codes, or in their absence, with the latest
edition of the National Fuel Gas Code, NFPA 54/ANSI
Z223.1.
Natural Gas Capacity of Pipe
In Cubic Feet of Gas Per Hour (CFH)
Length of Nominal Black Pipe Size
Pipe in Feet 1/2" 3/4" 1" 1 1/4" 1 1/2"
10 132 278 520 1050 1600
20 92 190 350 730 1100
30 73 152 285 590 980
40 63 130 245 500 760
50 56 115 215 440 670
60 50 105 195 400 610
70 46 96 180 370 560
80 43 90 170 350 530
90 40 84 160 320 490
100 38 79 150 305 460
(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specif ic Gravity Gas)
CFH =
BTUH Furnace Input
Heating Value of Gas (BTU/Cubic Foot)
To connect the furnace to the building’s gas piping, the
installer must supply a ground joint union, drip leg, manual
shuto󰀨 valve, and line and ttings to connect to gas valve.
In some cases, the installer may also need to supply a
transition piece from ½” pipe to a larger pipe size.
The following stipulations apply when connecting gas
piping.
• Gas piping must be supported external to the furnace
cabinet so that the weight of the gas line does not
distort the burner rack, manifold or gas valve.
• Use black iron or steel pipe and ttings for the
building piping.
• Use pipe joint compound on male threads only. Pipe
joint compound must be resistant to the action of the
fuel used.
• Use ground joint unions.
• Install a drip leg to trap dirt and moisture before
it can enter the gas valve. The drip leg must be a
minimum of three inches long.
• Use two pipe wrenches when making connection to
the gas valve to keep it from turning. The orientation
of the gas valve on the manifold must be maintained
as shipped from the factory.
• Install a manual shuto󰀨 valve between the gas
meter and unit within six feet of the unit. If a union
is installed, the union must be downstream of the
manual shuto󰀨 valve, between the shuto󰀨 valve and
the furnace.
• Tighten all joints securely.
• Connect the furnace to the building piping by one of
the following methods:
– Rigid metallic pipe and ttings.
– Semi-rigid metallic tubing and metallic ttings.
Aluminum alloy tubing must not be used in exterior
locations.
– Use listed gas appliance connectors in accordance
with their instructions. Connectors must be fully in
the same room as the furnace.
– Protect connectors and semi-rigid tubing against
physical and thermal damage when installed.
Ensure aluminum-alloy tubing and connectors are
coated to protect against external corrosion when
in contact with masonry, plaster, or insulation, or
subjected to repeated wetting by liquids such as
water (except rain water), detergents, or sewage.
Gas line
entrance
Right side
gas entrance
(alternate)
General Furnace Layout
Figure 4
When the gas piping enters through the side of the furnace,
the installer must supply the following t tings (starting from
the gas valve):
• Close nipple.
• 90 degree elbow.
• Straight pipe to reach the exterior of the furnace.
A ground joint union, drip leg, and manual shuto󰀨 valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from ½”
to another pipe size.
background
14
Gas Piping Checks
Before placing unit in operation, leak test the unit and gas
connections.
WARNING
To avoid the possibility of explosion or fire, never use a
match or open flame to test leaks.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector, or
other approved testing methods.
WARNING
To prevent property damage or personal injury due to fire,
the following instructions must be performed regarding gas
connections, pressure testing, location of shutoff valve and
installation of gas piping.
NOTE: Never exceed specified pressures for
testing. Higher pressure may cause gas valve
failure.
Disconnect this unit and shuto󰀨 valve from the gas supply
piping system before pressure testing the supply piping
system with pressures in excess of ½ psig (3.48 kPa).
This unit must be isolated from the gas supply system by
closing its manual shuto󰀨 valve before pressure testing of
gas supply piping system with test pressures equal to or
less than ½ psig (3.48 kPa).
Propane Gas Tanks and Piping
A gas detecting warning system is the only reliable way to
detect a propane gas leak. Rust can reduce the level of
odorant in propane gas. Do not rely on your sense of smell.
Contact a local propane gas supplier about installing a
gas detecting warning system. If the presence of gas is
suspected, follow the instructions on Page 3 of this manual.
All propane gas equipment must conform to the safety
standards of the National Fire Protection Association,
NFPA 58
For satisfactory operation, propane gas pressure must be
10 inch WC at the furnace manifold with all gas appli ances
in operation. Maintaining proper gas pressure depends on
three main factors:
1. Vaporization rate, depending on temperature of the
liquid, and “wetted surface” area of the con tainer or
containers.
2. Proper pressure regulation (Two-stage regulation is
recommended for both cost and e󰀩ciency).
3. Pressure drop in lines between regulators, and
between second stage regulator and the appliance.
Pipe size will depend on length of pipe run and total
load of all appliances.
Complete information regarding tank sizing for vaporiza-
tion, recommended regulator settings, and pipe sizing is
available from most regulator manufacturers and propane
gas suppliers.
Use a pipe thread compound that is approved for natural
gas and LP Gas.
Refer to the following illustration for typical propane gas
installations and piping.
200 PSIG
Maximum
5 to 15 PSIG
(20 PSIG Max.)
Continuous
11" W.C.
Second Stage
Regulator
First Stage
Regulator
Propane Gas Installation (Typ.)
Figure 5
Propane Gas Piping Charts
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4"
10 730 1,700 3,200 5,300 8,300 3,200 7,500
20 500 1,100 2,200 3,700 5,800 2,200 4,200
30 400 920 2,000 2,900 4,700 1,800 4,000
40 370 850 1,700 2,700 4,100 1,600 3,700
50 330 770 1,500 2,400 3,700 1,500 3,400
60 300 700 1,300 2,200 3,300 1,300 3,100
80 260 610 1,200 1,900 2,900 1,200 2,600
100 220 540 1,000 1,700 2,600 1,000 2,300
125 200 490 900 1,400 2,300 900 2,100
150 190 430 830 1,300 2,100 830 1,900
175 170 400 780 1,200 1,900 770 1,700
200 160 380 730 1,100 1,800 720 1,500
Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Nominal Pipe Size
Schedule 40
Tubing Size, O.D. Type L
Pipe or
Tubing
Length,
Feet
3/8" 1/2" 5/8" 3/4" 7/8" 1-1/8" 1/2" 3/4" 1" 1-1/4" 1-1/2"
10 39 92 199 329 501 935 275 567 1,071 2,205 3,307
20 26 62 131 216 346 630 189 393 732 1,496 2,299
30 21 50 107 181 277 500 152 315 590 1,212 1,858
40 19 41 90 145 233 427 129 267 504 1,039 1,559
50 18 37 79 131 198 376 114 237 448 910 1,417
60 16 35 72 121 187 340 103 217 409 834 1,275
80 13 29 62 104 155 289 89 185 346 724 1,066
100 11 26 55 90 138 255 78 162 307 630 976
125 10 24 48 81 122 224 69 146 275 567 866
150 9 21 43 72 109 202 63 132 252 511 787
200 8 19 39 66 100 187 54 112 209 439 665
250 8 17 36 60 93 172 48 100 185 390 590
Pipe or
Tubing
Length,
Feet
Nominal Pipe Size
Schedule 40
Tubing Size, O.D. Type L
Sizing Between Second Stage and Appliance Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
background
15
CIRCULATING AIR
WARNING
Never allow the products of combustion, including carbon
monoxide, to enter the return duct work or circulation air
supply.
Duct systems and register sizes must be properly designed
for the CFM and external static pressure rat ing of the
furnace. Ductwork should be designed in accor dance
with the recommended methods of “Air Conditioning
Contractors of America” Manual D.
A duct system must be installed in accordance with
Standards of the National Fire Protection Association,
NFPA 90A and 90B.
A closed return duct system must be used, with the
return duct connected to the furnace. NOTE: Ductwork
must never be attached to the back of the furnace. For
installations requiring more than 1600 CFM, use a bottom
return or two sided return to help reduce noise and provide
smoother airow for heating. Supply and return con-
nections to the furnace may be made with exible joints
to reduce noise transmission. To prevent the blower from
inter fering with combustion air or draft when a central
return is used, a connecting duct must be installed between
the unit and the utility room wall. A room, closet, or alcove
must not be used as a return air chamber.
When the furnace is used in connection with a cooling unit,
the furnace should be installed upstream of the cooling coil.
When the furnace is installed without a cooling coil, it is
recommended that a removable access panel be provided
in the outlet air duct. This opening shall be accessible
when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for visual light
inspection or such that a sampling probe can be inserted
into the air stream. The access panel must be made to
prevent air leaks when the furnace is in operation.
When furnace duct(s) supply air outside the space
containing the furnace, a return air duct must terminate in
the same space as the supply duct and be sealed to the
furnace casing.
When the furnace is heating, the temperature of the return
air entering the furnace must be between 55°F and 100°F.
Checking Duct Static
Refer to your furnace rating plate for the maximum ESP
(external duct static) rating.
Total external static refers to static pressure created by all
components external to the furnace cabinet. Cooling coils,
lters, ducts, grilles, registers must all be considered when
reading your total external static pressure. The supply
duct pressure must be read between the furnace and the
cooling coil. This reading is usually taken by removing the
“A” shaped block o󰀨 plate from the end on the coil; drilling
a test hole in it and reinstalling the block o󰀨 plate. Take a
duct static reading at the test hole. Tape up the test hole
after your test is complete. The negative pressure must be
read between the lter and the furnace blower.
2"
NOTE:
RAISE FURNACE BY AT LEAST 2"
FROM THE MAX LEVEL OF OVER
FLOW WATER IN CONDENSATE
OVERFLOW DRAIN PAN.
RETURN AIR DUCT
PLEASE ENSURE THE
BOTTOM OF FURNACE
IS SEALED PROPERLY
IF SIDE RETURN
DUCTS ARE USED
DRAIN PIPE
CONDENSATE OVERFLOW
DRAIN PAN
BLOCK AT EACH CORNER
UNDERNEATH THE FURNACE
Figure 6
background
16
Too much external static pressure will result in insu󰀩cient
air that can cause excessive temperature rise. This can
cause limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed as
follows:
1. With clean lters in the furnace, use a manometer to
measure the static pressure of the return duct at the
inlet of the furnace (Negative Pressure).
2. Measure the static pressure of the supply duct
(Positive Pressure).
3. The di󰀨erence between the two numbers is the total
external static pressure.
EXAMPLE:
static reading from return duct = -.1” w.c.
static reading from supply duct = .3” w.c.
total external static pressure on this system = .4” w.c.
NOTE: Both readings may be taken simultaneously
and read directly on the manometer if so desired.
If an air conditioner coil or Electronic Air
Cleaner is used in conjunction with the furnace,
the readings must also include these components,
as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum
listed on the furnace rating plate, check for closed
dampers, registers, undersized or poorly laid out duct work.
Checking Static Pressure
Figure 7
Filters - Read This Section Before Installing The
Return Air Ductwork
Filters must be used with this furnace. Discuss lter
maintenance with the building owner. Filters do not ship
with this furnace, but must be provided by the installer.
Filters must comply with UL900 or CAN/ULCS111
standards. Damage or repairs due to the installation of the
furnace without lters is not covered under the warranty.
Upright Installations
Depending on the installation and/or customer preference,
di󰀨ering lter arrangements can be applied. Filters can
be installed in the central return register or a side panel
external lter rack kit (upows), or the ductwork above a
downow furnace. As an alternative, a media air lter or
electronic air cleaner can be used as the primary lter.
Horizontal Installations
Filters must be installed in either the central return register
or in the return air duct work.
Circulation Air Filters
One of the most common causes of a problem in a forced
air heating system is a blocked or dirty lter. Circulating air
lters must be inspected monthly for dirt accumulation and
replaced if necessary. Failure to maintain clean lters can
cause premature heat exchanger failure.
A new home may require more frequent replacement until
all construction dust and dirt is removed.
Upflow Models Minimum Recommended Filter Size
*0403A* 1 - 16 X 25 Side or 1 - 14 X 24 Bottom Return
*0603A* 1 - 16 X 25 Side or 14 X 24 Bottom Return
*0603B*
1 - 16 X 25 Side or Bottom Return
*0604B* 1 - 16 X 25 Side or Bottom Return
*0803B* 1 - 16 X 25 Side or Bottom Return
*0804B* 1 - 16 X 25 Side or Bottom Return
*0804C* 1 - 16 X 25 Side or Bottom Return
*0805C*
1 - 16 X 25 Side or Bottom Return¹
*1005C* 2 - 16 X 25 Side or 1 - 20 X 25 Bottom Return¹
*1205D* 2 - 16 X 25 Side or 1 - 24 X 24 Bottom Return¹
Downflow Models
*0403A* 2 - 10 X 20 or 1 - 14 X 25 Top Return
*0603A* 2 - 10 X 20 or 1 - 14 X 25 Top Return
*0804B* 2 - 14 X 20 or 1 - 16 X 25 Top Return
*0805C* 2 - 14 X 20 or 1 - 20 X 25 Top Return
*1005C* 2 - 14 X 20 or 1 - 20 X 25 Top Return
¹ = Use 2 - 16 X 25 filters and two side returns or 20 X 25 filter on
bottom return if furnace is connected to a cooling unit over 4 tons
nominal capacity
Larger filters may be used, filters may also be centrally located
A combination of one side & bottom may be used instead of both sides
ELECTRICAL
24 Volt Thermostat Wiring
Important Note: Wiring routing must not interfere
with circulator blower operation, filter removal
or routine maintenance.
Low voltage connections can be made through either the
right or left side panel. Thermostat wiring entrance holes
are located in the blower compartment. The following gure
shows connections for a “heat/cool system”.
This furnace is equipped with a 40 VA transformer to
facilitate use with most cooling equipment. Consult the
wiring diagram, located on the blower compartment door,
for further details of 115 Volt and 24 Volt wiring.
background
17
Thermostat Wiring Diagrams
Y
C
Y
C
G
R
W
Y2
Y/Y1
C
G
R
W
ROOM THERMOSTAT
INTEGRATED FURNACE
CONTROL MODULE
REMOTE COOLING UNIT
(SINGLE STAGE)
Thermostat - Single-Stage Heating with Single-Stage Cooling
Figure 8
Y1
C
Y1C
G
R
W
Y2
Y/Y1
C
G
R
W
ROOM THERMOSTAT
INTEGRATED
FURNACE
CONTROL MODULE
REMOTE COOLING UNIT
(TWO STAGE)
Y2
Y2
Thermostat - Single-Stage Heating with Two-Stage Cooling
Figure 9
Fossil Fuel Applications
This furnace can be used in conjunction with a heat pump
in a fossil fuel application. A fossil fuel application refers to
a combined gas furnace and heat pump installation which
uses an outdoor temperature sensor to determine the most
cost e󰀩cient means of heating (heat pump or gas furnace).
A heat pump thermostat is required to properly use a
single-stage furnace in conjunction with a heat pump. Refer
to the fossil fuel kit installation instructions for additional
thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit
installation instructions. All furnace connections must be
made to the furnace two-stage integrated control module
and the “FURNACE” terminal strip on the fossil fuel control
board.
Twinning
For Furnace Twinning information, please refer to the
Furnace Twinning installation manual IO-2001. Please
scan the QR code below to open the document.
WARNING
all accessories that may become a potential ignition source
if installed, such as electronic air cleaners, must only be
powered through a daikin accessory control board kit. if an
electronic air cleaner is already installed in the duct work
and not connected to the accessory control board, it will
have to be disabled or removed. ensure that any additional
wiring from the indoor unit to the accessory control
board is routed and protected from damage and wear,
avoiding the flue pipe and any joints that may need brazed or
disconnected for service. refer to the product specification
sheet for the accessory control board kit part number.
115 Volt Line Connection of Accessories
(Humidifier and Electronic Air Cleaner)
The furnace integrated control module is equipped with
line voltage accessory terminals for controlling power to
an optional eld-supplied humidier and/or electronic air
cleaner.
The accessory load specications are noted in the chart:
Humidifier
1.0 Amp maximum at 120 VAC
Electronic Air Cleaner
1.0 Amp maximum at 120 VAC
Turn OFF power to the furnace before installing any
accessories. Follow the humidier or air cleaner
manufacturers’ instructions for locating, mounting,
grounding, and controlling these accessories. Accessory
wiring connections are to be made through the 1/4” quick
connect terminals provided on the furnace integrated
control module. The humidier and electronic air cleaner
hot terminals are identied as HUM H and EAC H. The
humidier and electronic air cleaner neutral terminals are
identied as NEUTRAL. All eld wiring must conform to
applicable codes. Connections should be made as shown.
If it is necessary for the installer to supply additional line
voltage wiring to the inside of the furnace, the wiring
must conform to all local codes, and have a minimum
temperature rating of 105°C. All line voltage wire splices
must be made inside the furnace junction box.
The integrated control module humidier terminal (HUM
H) is energized with 115 volts whenever the induced
draft blower is energized. The integrated control module
electronic air cleaner terminal (EAC H) is energized with
115 volts whenever the circulator blower is energized. This
terminal can also be used to provide 115 volt power to a
humidier transformer. The remaining primary transformer
wire would be connected to the Line N on the control
board.
WARNING
HIGH VOLTAGE!
To avoid personal injury or death due to
electrical shock, disconnect electrical power
before servicing or changing any electrical
wiring.
background
18
115 VAC HUM
115 VAC EAC
Accessories - Accessories Wiring
Figure 10
Low Voltage Humidifier
The furnace integrated control module is equipped with
a low voltage terminal for providing power to an optional
eld-supplied 24 volt humidier. The 24V HUM terminal
is energized any time the draft inducer is powered. See
connection diagram below.
NOTE: This is a 24 volt circuit only, the common
connection must be on C terminal of the low
voltage terminal strip (where thermostat wires
are connected). Wiring for this circuit must NOT
be connected to the line N location where line
voltage neutral wires are connected.
Low Voltage Ventilation
The Ventilation connections provide a dry contact for
eld ventilator wiring connections. These connections are
normally open and energize during the R-32 fault/alarm
condition. VT IN and VT OUT connections are provided on
the control board and are shown in the image below.
Low Voltage A2L Alarm
The A2L alarm connection provides 24VAC for eld alarm
wiring connections. These connections are normally open
and energize during the R-32 fault/alarm condition. An A2L
Alarm connection is provided on the control board and is
shown in the image below.
Field Installed Accessories
Additional accessories that do not have dedicated
terminals on the furnace control board may require an
additional daughter board to be installed. Please refer to
service manual on your product for more information.
NOTE: This furnace is equipped with a control
board that is capable of monitoring for R-32
refrigerant leaks in the indoor evaporator coil.
Please verify that the R-32 sensor wire is plugged
in to the furnace control board before startup,
if applicable. If furnace is not paired with an R-32
Refirgeration system, the default settings in the
furnace control board will need to be changed.
Please see the R-32 section for additional
information.
Furnace Startup
1. Close the manual gas shuto󰀨 valve external to the
furnace.
2. Turn o󰀨 the electrical power to the furnace.
3. Set the room thermostat to the lowest possible
setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition
device which automatically lights the burner. Do
not try to light the burner by hand.
5. Move the furnace gas valve manual control to the
OFF position.
6. Wait ve minutes then smell for gas. Be sure check
near the oor as some types of gas are heavier than
air.
7. If you smell gas after ve minutes, immediately follow
the safety instructions in the Safety Considerations
on page 2 of this manual. If you do not smell gas
after ve minutes, move the furnace gas valve
manual control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shuto󰀨 valve external to the
furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room
temperature.
12. After the burners are lit, set the thermostat to desired
temperature.
background
19
Gas Heat Sequence of Operation
Call for Heat
• On a call for heat, the thermostat contacts close &
the control board receives 24 VAC on the W terminal.
• The control board microcomputer runs its self-check
routine.
• The control veries the limit switch is closed (24 VAC
on Pin 8 of the 12 Pin connector).
• The control veries that pressure switch circuit is
open (0 VAC on Pin 5).
• The control module performs a gas valve circuitry
check to verify gas valve relay state and presence of
no voltage at the valve.
• The system will energize the Induced draft blower.
• The pre-purge period begins once the pressure
switch is detected closed (24 VAC on Pin 5).
• After the completion of pre-purge, the control will
energize the igniter.
• After completion of the ignitor warm-up period:
• The gas valve is energized.
• The ignitor is de-energized as soon as ame is
sensed.
• After 30 seconds the indoor blower is energized on
heating speed.
• When the thermostat is satised:
• The gas valve is de-energized.
• The inducer remains energized for the post purge
period (15 seconds).
24 VOLT HUM.
& HUMIDISTAT
24 VOLT VENTILATION
(OPTIONAL)
24 VOLT A2L ALARM
(OPTIONAL))
R-32 SENSOR
24 Volt Humidifier Connection
Figure 11
• The indoor blower runs for the selected o󰀨 delay
period (90 seconds by default, adjustable from 30 –
180 seconds).
Heating Mode Speed Selection
To change the main blower speed in HEATING mode,
follow the following steps:
1. Press left or right button till LED displays “gA1” (for
single stage HEATING). Press center button and
LED will display the selected speed number as Fxx
(xx: Blower speed number).
2. The control shall rotate available speed number
every time Left / Right buttons are pressed. Table
below shows the available speeds for Low & High
heat mode.
3. When the center button is pressed, the current
displayed speed shall be selected, and control shall
apply the newly selected speed in next heating call.
NOTE: Always refer to the Heating Chart to
choose from available heating speeds
THERMOSTAT CALL AVAILABLE SPEEDS
W/W1
F01
F03
F04
F02 (DEFAULT)
Heating Speed Table for 1 Stage IFC
(Integrated Furnace Control)
background
20
Continuous Fan Mode Speed Selection
To change the main blower speed in circulation mode,
follow the following steps:
1. Press the left or right button until LED displays “FSd”.
Press the center button and LED will display the
selected speed number as Fxx (xx: Blower speed
number from 1 to 9). F01 is the default speed for
circulation.
2. The control will rotate available speed number every
time left/right buttons are pressed. All 9 speeds are
available for circulation.
3. When the center button is pressed, the current
displayed speed will be selected, and control will
immediately apply that speed setting.
THERMOSTAT
CALL
AVAILABLE
SPEEDS
G
F01
F02
F03
(DEFAULT)
F04
F05
F06
F07
F08
F09
Circulation Speed Table
Cooling Mode Sequence of Operation
Low Stage Cooling Mode Sequence:
On a call for low stage cooling, the Y/Y1 or Y/Y1 and G
thermostat contacts close signaling the furnace control
board with 24 VAC on Y/Y1 or Y/Y1 and G terminals.
• The 7-Segment will display the cool mode:1 A C.
• The compressor and condenser fan are energized.
• The circulator fan is energized at low cool speed
after a cool on delay. The electronic air cleaner will
also be energized.
• After the thermostat is satised, the compressor and
condenser fan are de-energized and the Cool Mode
Fan O󰀨 Delay period begins.
• Following the Cool Mode Fan O󰀨 Delay period,
the cool circulator and air cleaner relay are de-
energized.
2nd Stage Cooling Mode Sequence:
On a call for 2nd stage cooling, the Y2 or Y2 and G
thermostat contacts close signaling the furnace control
board with 24 VAC on Y2 or Y2 and G terminals.
• The 7-Segment will display the cool mode: 2 A C.
• The compressor and condenser fan are energized.
• The circulator fan is energized at cool speed after a
cool on delay. The electronic air cleaner will also be
energized.
• After the thermostat is satised, the compressor and
condenser fan are de-energized and the Cool Mode
Fan O󰀨 Delay period begins.
• Following the Cool Mode Fan O󰀨 Delay period,
the cool circulator and air cleaner relay are de-
energized.
Cooling Mode Speed Selection
To change the main blower speed in COOLING mode,
follow the following steps:
1. Press the left or right button until LED displays “AC1”
(for single stage COOLING) or “AC2” (for two-stage
COOLING). Press the center button and LED will
display the selected speed number as Fxx (xx:
Blower speed number from 1 to 9).
2. The control will rotate available speed number every
time left/right buttons are pressed. All 9 speeds are
available for both Single and Two Stage cooling.
3. When the center button is pressed, the current
displayed speed will be selected, and control will
apply the newly selected speed in next cooling call.
THERMOSTATCALL AVAILABLESPEEDS
Y/Y1
F01
F02
F03
F04(DEFAULT)
F05
F06
F07
F08
F09

Single-Stage Cooling Speed Table for 2 Stage IFC
THERMOSTATCALL AVAILABLESPEEDS
Y2
F01
F02
F03
F04
F05(DEFAULT)
F06
F07
F08
F09
Two-Stage Cooling Speed Table for 2 Stage IFC
Furnace Shutdown
1. Set the thermostat to the lowest setting. The
integrated control will close the gas valve and
extinguish ame. Following a 15 second delay, the
induced draft blower will be de-energized. After
the blower o󰀨 delay time expires, the blower de-
energizes.
2. Remove the burner compartment door and move
the furnace gas valve manual control to the OFF
position.
3. Close the manual gas shuto󰀨 valve external to the
furnace.
background
21
4. Replace the burner compartment door.
Gas Supply Pressure Measurement
OUTLET
INLET
Gas Valve ON/OFF Selector Switch
Outlet Pressure
Inlet Pressure
Regulator
Cover Screw
White-Rogers Model 36J22Y-204
Figure 12
.
Regulator Cover
Screw
Mode
3.5
.
White-Rogers Model 36J22Y-204 Connected to Manometer
Figure 13
Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c.
Propane Gas Minimum: 11.0" w.c. Maximum: 13.0" w.c.
INLET GAS SUPPLY PRESSURE
CAUTION
To prevent unreliable operation or equipment damage, the gas
manifold pressure must be as specified on the unit rating plate
with all other household gas fired appliances operating.
The line pressure supplied to the gas valve must be within
the range specied below. The supply pressure can be
measured at the gas valve inlet pressure tap or at a hose
tting installed in the gas piping drip leg. The supply
pressure must be measured with the burners operating.
To measure the gas supply pressure, use the following
procedure.
1. Turn OFF gas to furnace at the manual gas shuto󰀨
valve external to the furnace.
2. Connect a calibrated manometer (or appropriate
gas pressure gauge) at either the gas valve inlet
pressure tap or the gas piping drip leg. See White-
Rodgers 36J gas valve (Figure 13) to locate the inlet
pressure tap.
NOTE: If using the inlet pressure tap on the White-
Rodgers 36J gas valve, then use the 36G/J Valve
Pressure Check Kit, Part No. 0151K00000S.
3. Turn ON the gas supply and operate the furnace and
all other gas consuming appliances on the same gas
supply line.
4. Measure furnace gas supply pressure with burners
ring. Supply pressure must be within the range
specied in the Inlet Gas Supply Pressure table.
If supply pressure di󰀨ers from table, make the necessary
adjustments to pressure regulator, gas piping size, etc.,
and/or consult with local gas utility.
5. Turn OFF gas to furnace at the manual shuto󰀨 valve
and disconnect manometer. Reinstall plug before
turning on gas to furnace.
6. Turn OFF any unnecessary gas appliances stated in
step three.
Gas Manifold Pressure Measurement and
Adjustment
Only small variations in gas pressure should be made by
adjusting the gas valve pressure regulator. The manifold
pressure must be measured with the burners operating.
To measure and adjust the manifold pressure, use the
following procedure.
1. Turn OFF gas to fur nace at the manual gas shuto󰀨
valve external to the furnace.
2. Turn o󰀨 all electrical power to the system.
3. Outlet pressure tap connections:
White-Rodgers 36J22 valve: Back outlet pressure
test screw (inlet/outlet pressure tap) out one turn
(counterclockwise, not more than one turn).
4. Attach a hose and manometer to the outlet pressure
tap (White-Rodgers valve).
5. Turn ON the gas supply.
6. Turn on power and close thermostat “R” and “W”
contacts to provide a call for heat.
7. Measure the gas manifold pressure with burners
ring. Adjust manifold pressure using the Manifold
Gas Pressure table shown on this page.
Manifold Gas Pressure
Gas Range Nominal
Natural 3.2-3.8"w.c. 3.5"w.c.
Propane 9.7-10.3"w.c. 10.0"w.c.
8. Remove regulator cover screw from the outlet
pressure regulator adjust tower and turn screw
clockwise to increase pressure or counterclockwise
to decrease pressure. Replace regulator cover
screw.
9. Turn o󰀨 all electrical power and gas supply to the
system.
10. Remove the manometer hose from the hose barb
tting or outlet pressure tap.
background
22
11. Replace outlet pressure tap: White-Rodgers 36J22
valve: Turn outlet pressure test screw in to seal
pressure port (clockwise, 7 in-lb minimum).
12. Turn on electrical power and gas supply to the
system.
13. Close thermostat contacts “R” and “W” to energize
the valve.
Using a leak detection solution or soap suds, check for
leaks at outlet or screw (White-Rodgers valve). Bubbles
forming indicate a leak. SHUT OFF GAS AND REPAIR ALL
LEAKS IMMEDIATELY!
NOTE: For gas to gas conversion, consult your
dealer for appropriate conversion.
R-32 INFORMATION
R-32 Function
This furnace is equipped with a control board that is
capable of shutting o󰀨 the gas heat and turning on the
blower fan in case of an R-32 refrigerant leak in the indoor
evaporator coil. If the cooling unit that is paired with this
furnace does not utilize R-32 as the refrigerant, the R-32
functionalities in the furnace control board will need to be
turned o󰀨 for the furnace to run properly.
R-32 function on the control board is ON by default. The
R-32 function can be disabled through the furnace control
by entering the A2L Function Enabled menu and selecting
“no”. If A2L function is disabled, the furnace control will
ignore all A2L functions. If A2L function is enabled, the
control will monitor the R-32 sensor information.
To enter the A2L Function Enabled menu, press the left
or right button until LED displays “A2E”. Press the center
button and the LED will display the selected option (yes or
no). Press the left or right button to select one of the two
options and press the center button to conrm the option.
“A2E” selected
Figure 14
“Yes” selected
Figure 15
“No” selected
Figure 16
R-32 Sensor Wire Routing
Important Note: Wiring routing must not interfere
with circulator blower operation, filter removal
or routine maintenance. Wire should not be
routed near hot surfaces and should be protected
from sharp edges. Extra precaution should be
taken to avoid routing near the outlet flue pipe.
The R-32 Sensor wire coming from the indoor refrigeration
unit will need to be routed into the furnace and connected
to the connection point on the furnace control board. This
wire should be routed alongside the thermostat wires
through the low voltage openings in the left or right side of
the furnace blower compartment. Please see the electrical
section for the location of the R-32 Sensor connection on
the control board.
The R-32 function on the furnace control board may need
to be enabled or disabled if any element of the installation
changes from the original setup. The specic scenario
will depend on each installation, so please refer to the
evaporator coil’s installation manual to verify what is
required for your setup. For example, if the furnace was
initially installed with an evaporator coil that utilized R-410A
refrigerant, and the coil is later replaced with one that uses
R-32 refrigerant, then R-32 function mode on the furnace
control board must be enabled, and the R-32 sensor wire
must be connected to the furnace control board.
Furnace Start Up
During furnace start up, the furnace control will identify the
connected R-32 sensor and will start monitoring the sensor
communication. A green LED located next to the sensor
connection will indicate if there is communication between
the furnace control and the R-32 sensor. The LED will be
ON during the duration of the startup and then will either
start blinking or turn OFF. The blinking LED signies that
communication with the R-32 sensor is present. The LED
OFF signies that there is no signal with the sensor.
If there are no alarms or faults, the furnace will go into
regular run mode after a warm up period. The furnace
control monitors the R-32 sensor once per second.
background
23
R-32 Refrigerant Leak
If the R-32 sensor on the indoor evaporator coil detects
a specied concentration of R-32 refrigerant, the furnace
will enter Mitigation Mode to dilute the refrigerant
concentrations in case of a leak. In Mitigation Mode, the
furnace will do the following:
1. Display the A2L Refrigerant Leakage error code
(EAL)
2. Shut down the gas operation
3. Energize the optional ventilation and alarm outputs.
4. Run the fan at max CFM airow
Once the R-32 sensor stops detecting a leak, the fan will
continue to run for 5 minutes. After the 5 minutes, if there
are no other alarms or faults, the control will de-energize
the optional ventilation and alarm outputs and then go back
to the original operating mode per the thermostat.
A2L Verification
The A2L Function Verication menu allows the installer to
verify if the R-32 function operates properly. This menu
simulates the refrigerant leak process and is only able to
be used when there are no active alarms or faults. To verify
the R-32 functions, enter the A2L Function Verication
menu and select “YES”. To enter the A2L Function
Verication menu, press the left or right button until LED
displays “A2u”. Press the center button and the LED will
display the selected option (yes or no). Press the left or
right button to select one of the two options and press
the center button to conrm the option. Once “YES” is
selected, the furnace will do the following:
1. Display the A2L Refrigerant Leakage code (EAL)
2. Shut down the gas operation
3. Energize the optional ventilation and alarm outputs.
4. Run the fan at max CFM airow
The control will exit the verication function if:
1. The 5 minute timeout expires or
2. An alarm or fault is detected or
3. The user turns OFF the A2L Function Verication.
NOTE: To verify gas heating operation shuts down,
give furnace a call for heat before entering into
A2L Function Verification.
MAINTENANCE
WARNING
To avoid electric shock, injury or death, disconnect
electrical power before performing any
maintenance. If you must handle the igniter, handle
with care. Touching the igniter element with bare
fingers, rough handling or vibration could damage
the igniter resulting in premature failure. Only a
qualified servicer should ever handle the igniter.
Annual Inspection
The furnace should be inspected by a qualied installer, or
service agency at least once per year. This check should be
performed at the beginning of the heating season. This will
ensure that all furnace components are in proper working
order and that the heating system functions appropriately.
Pay particular attention to the following items. Repair or
service as necessary.
• Flue pipe system. Check for blockage and/or
leakage. Check the outside termination and the
connections at and internal to the furnace.
• Heat exchanger. Check for corrosion and/or buildup
within the heat exchanger passageways.
• Burners. Check for proper ignition, burner ame, and
ame signal.
• Wiring. Check electrical connections for tightness
and/or corrosion. Check wires for damage.
• Filters.
• R-32 Sensor Wire. Check R-32 sensor wire
connection for tightness and check wire for damage.
Filters
CAUTION
To ensure proper unit performance, adhere to the filter
sizes given in the recommended Minimum Filter Size Table or
Specification Sheet applicable to your model.
Filter Maintenance
Improper lter maintenance is the most common cause
of inadequate heating or cooling performance. Filters
should be cleaned (permanent) or replaced (disposable) as
required.
Filter Removal
Depending on the installation, di󰀨ering lter arrangements
can be applied. Filters can be installed in either the central
return register or a side panel external lter rack (upow
only). A media air lter or electronic air cleaner can be used
as an alternate lter. Follow the lter sizes given in the
Recommended Minimum Filter size table to ensure proper
unit performance.
To remove lters from an external lter rack in an upright
upow installation, follow the directions provided with
external lter rack kit.
Horizontal Unit Filter Removal
Filters in horizontal installations are located in the central
return register or the ductwork near the furnace.
To remove:
1. Turn OFF electrical power to furnace.
2. Remove lter(s) from the central return register or
ductwork.
3. Replace lter(s) by reversing the procedure for
removal.
4. Turn ON electrical power to furnace.
background
24
MEDIA AIR FILTER OR ELECTRONIC
AIR CLEANER REMOVAL
Follow the manufacturer’s directions for service.
Burners
Visually inspect the burner ames periodically during the
heating season. Turn on the furnace at the thermostat and
allow several minutes for ames to stabilize, since any
dislodged dust will alter the ames normal appearance.
Flames should be stable, quiet, soft, and blue (dust may
cause orange tips but they must not be yellow). They
should extend directly outward from the burners without
curling, oating, or lifting o󰀨. Flames must not impinge on
the sides of the heat exchanger ring tubes.
Induced Draft and Circulator Blowers
The bearings in the induced draft blower and circulator
blower motors are permanently lubricated by the
manufacturer. No further lubrication is required. Check
motor windings for accumulation of dust which may cause
overheating. Clean as necessary.
Flame Sensor (Qualified Servicer Only)
Under some conditions, the fuel or air supply can create a
nearly invisible coating on the ame sensor. This coating
acts as an insulator causing a drop in the ame sense
signal. If the ame sense signal drops too low the furnace
will not sense ame and will lock out. The ame sensor
should be carefully cleaned by a qualied servicer using
steel wool. Following cleaning, the ame sense signal
should be as indicated in the Specications Sheet.
Flue Passages (Qualified Servicer Only)
The heat exchanger ue passageways should be inspected
at the beginning of each heating season.
BEFORE LEAVING AN INSTALLATION
• Cycle the heating, cooling and fan only operations to
verify each operation is working properly.
• Review the Owner’s Manual with the homeowner
and discuss proper furnace operation and
maintenance.
• Leave literature packet near furnace.
REPAIR AND REPLACEMENT PARTS
• When ordering any of the listed functional parts, be
sure to provide the furnace model, manufacturing,
and serial numbers with the order.
• Although only functional parts are shown in the parts
list, all sheet metal parts, doors, etc. may be ordered
by description.
• Parts are available from your distributor.
Functional Parts List
Gas Valve Blower Motor
Gas Manifold Blower Wheel
Natural Gas Orice Blower Mounting Bracket
Propane Gas Orice Blower Cuto󰀨
Igniter Blower Housing
Flame Sensor Inductor
Rollout Limit Switch Heat Exchanger
Primary Limit Switch Door Switch
Pressure Switch Integrated Control Module
Induced Draft Blower Transformer
background
25
AIRFLOW TABLES *R9S80
0.1
0.2
0.3
0.4
CFM
CFM CFM CFM CFM Watts CFM Watts CFM Watts CFM Watts
F01 658 585 545 495 444 83 390 88 332 94 151 49
F02 749 697 652 607 554 102 509 108 459 113 406 120
F03 925 881 840 800 760 150 721 157 681 162 645 169
F04^ 882 841 800 760 719 138 678 144 641 151 602 157
F05 1330 1295 1273 1251 1223 358 1195 366 1168 375 1142 385
F06 1130 1090 1059 1022 991 230 957 237 926 246 895 255
F07 1158 1113 1090 1057 1024 247 996 258 964 264 935 271
F08 1270 1235 1208 1179 1147 304 1119 312 1088 322 1060 329
F09 1417 1380 1359 1336 1314 408 1288 419 1261 430 1238 440
F01 659 599 542 490 437 89 383 95 320 102 N/A N/A
F02 1268 1221 1188 1154 1122 336 1091 344 1060 353 1029 361
F03 1087 1044 1008 973 938 234 905 242 871 249 841 257
F04^ 1118 1070 1033 997 963 243 929 251 896 260 865 267
F05 1308 1262 1224 1197 1167 332 1141 341 1117 352 1089 361
F06 868 823 780 741 699 148 662 154 624 160 584 167
F07 922 877 835 795 757 165 718 173 679 180 642 187
F08 1382 1341 1311 1291 1263 435 1234 443 1206 453 1177 464
F09 1492 1448 1409 1381 1354 460 1332 470 1310 481 1288 491
F01 720 660 614 542 468 81 413 87 359 94 313 99
F02 1289 1260 1232 1194 1161 257 1125 266 1087 275 1073 286
F03 1125 1089 1052 1013 973 184 947 196 909 202 863 213
F04^ 1252 1198 1153 1110 1069 230 1028 239 990 247 953 256
F05 922 872 830 786 736 122 683 130 616 139 565 146
F06 1146 1113 1076 1039 1002 192 969 204 933 212 891 222
F07 1370 1345 1317 1286 1260 299 1224 313 1187 320 1168 333
F08 1413 1386 1360 1330 1302 317 1270 333 1242 345 1211 354
F09 1544 1500 1459 1419 1387 379 1349 390 1317 402 1286 405
F01 764 695 630 559 485 95 415 102 358 109 N/A N/A
F02 1287 1235 1191 1147 1104 244 1062 252 1020 263 979 272
F03 1339 1301 1258 1217 1174 270
1131 279 1090 289 1048 299
F04^ 1396 1346 1298 1257 1217 289 1175 299 1135 308 1098 319
F05 1185 1135 1088 1040 992 203 947 211 901 219 855 227
F06 1500 1460 1420 1360 1380 337 1294 353 1256 365 1219 380
F07 1591 1539 1493 1454 1416 391 1379 402 1347 412 1311 424
F08 1675 1622 1583 1545 1510 447 1474 459 1440 473 1402 482
F09 1790 1741 1701 1668 1631 531 1599 546 1567 560 1532 570
F01 710 646 580 515 432 79 367 85 314 90 274 95
F02 1298 1255 1216 1178 1140 242 1102 253 1067 263 1028 273
F03 1209 1166 1124 1083 1045 208 1005 217 964 227 923 236
F04^ 1138 1091 1045 1001 959 181 920 188 876 197 832 208
F05 1391 1352 1314 1278 1241 288 1209 298 1175 311 1140 242
F06 977 931 880 836 785 135 734 142 683 151 626 158
F07 1036 985 940 895 848 150 799 158 751 167 705 175
F08 1456 1414 1376 1341 1302 315 1270 327 1238 337 1200 352
F09 1533 1488 1452 1415 1383 360 1350 370 1317 381 1286 393
F01 841 657 595 522 439 90 367 97 315 102 N/A N/A
F02 1141 1089 1045 1001 958 192 914 200 869 207 823 214
F03 1311 1267 1226 1189 1150 253 1114 264 1072 275 1034 283
F04^ 1395 1347 1309 1270 1233 291 1199 302 1164 312 1125 323
F05 1490 1447 1407 1373 1336 339 1303 351 1269 360 1237 373
F06 1553 1510 1469 1435 1401 372 1368 384 1335 395 1300 408
F07 1593 1548 1508 1474 1440 392 1409 405 1376 415 1343 429
F08 1776 1735 1695 1661 1628 514 1601 529 1570 542 1542 555
F09 1853 1812 1773 1739 1708 569 1679 585 1650 599 1623 614
*R9S800604B*
Y/Y1, Y2, G
*R9S800803B*
Y/Y1, Y2, G
*R9S800804B*
Y/Y1, Y2, G
*R9S800403A*
Y/Y1, Y2, G
*R9S800603A*
Y/Y1, Y2, G
*R9S800603B*
Y/Y1, Y2, G
FAN & COOLING AIFLOW
MODEL
THERMOSTAT
CALL
TAP #
EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
0.5
0.6
0.7
0.8
background
26
AIRFLOW TABLES *R9S80
0.1 0.2 0.3
0.4
CFM
CFM CFM CFM CFM Watts CFM Watts CFM Watts CFM Watts
F01 831 750 671 588 501 98 405 106 348 112 300 117
F02 1214 1158 1103 1045 989 184 936 194 883 205 823 215
F03 1303 1249 1191 1136 1081 212 1028 223 974 234 928 248
F04^ 1426 1375 1324 1277 1229 259 1177 270 1124 283 1078 295
F05 1518 1465 1418 1372 1328 293 1284 305 1237 318 1195 330
F06 1588 1539 1494 1447 1401 330 1358 349 1313 360 1267 373
F07 1710 1666 1632 1595 1554 397 1512 412 1473 427 1431 440
F08 1785 1751 1717 1675 1639 446 1596 453 1557 472 1516 483
F09 1845 1805 1771 1733 1695 476 1655 488 1618 507 1576 521
F01 837 752 671 576 501 100 426 107 361 113 315 119
F02 1316 1270 1218 1166 1114 217 1061 227 1000 238 962 251
F03 1353 1323 1286 1235 1183 242 1131 253 1085 263 1040 275
F04^ 1587 1544 1506 1459 1416 333 1372 345 1323 358 1281 369
F05 1731 1673 1632 1587 1546 398 1506 414 1463 426 1421 440
F06 1794 1744 1709 1671 1632 444 1591 459 1555 474 1513 489
F07 1861 1805 1761 1720 1681 481 1642 496 1603 509 1565 524
F08 1910 1873 1839 1798 1761 525 1723 545 1686 559 1648 574
F09 2110 2055 2035 2003 1973 700 1946 724 1907 731 1890 750
F01 802 724 637 551 468 87 389 95 342 100 294 106
F02 1405 1356 1308 1262 1210 241 1182 #N/A 1155 252 1102 264
F03 1574 1531 1484 1440 1392 320 1357 331 1306 342 1256 355
F04^ 1619 1575 1526 1489 1446 336 1404 352 1355 361 1313 374
F05 1688 1641 1600 1557 1513 367 1477 383 1428 398 1381 405
F06 1811 1769 1730 1686 1649 443 1610 456 1572 468 1525 482
F07 1857 1812 1774 1733 1697 475 1662 489 1622 505 1586 518
F08 1892 1850 1805 1774 1735 496 1692 511 1658 523 1621 537
F09 2116 2073 2039 2005 1981 675 1945 688 1909 707 1879 728
F01 851 774 692 615 535 105 470 111 411 118 359 124
F02 1677 1629 1583 1540 1498 408 1449 422 1399 436 1349 450
F03 1537 1489 1444 1404 1365 335
1322 348 1272 360 1211 372
F04^ 1416 1365 1315 1267 1220 277 1163 285 1106 296 1048 306
F05 1154 1098 1043 983 932 177 874 187 819 196 755 205
F06 1806 1764 1729 1688 1654 489 1615 503 1578 519 1535 535
F07 1869 1816 1773 1731 1693 521 1661 535 1629 548 1589 560
F08 1947 1903 1865 1833 1802 604 1769 621 1743 640 1708 654
F09 2107 2066 2030 1996 1963 734 1932 753 1899 772 1867 788
*R9S801205D*
Y/Y1, Y2, G
*R9S800804C*
Y/Y1, Y2, G
*R9S800805C*
Y/Y1, Y2, G
*R9S801005C*
Y/Y1, Y2, G
FAN & COOLING AIFLOW
MODEL
THERMOSTAT
CALL
TAP #
EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
0.5
0.6
0.7
0.8
NOTE:
FURNACE MODEL
Y2 Y1
*R9S800805C* F08 F02
*R9S801205D* F06 F05
RECOMMENDED AIRFLOW SPEEDS FOR
CONNECTION WITH 2 STAGE OUTDOOR
MODELS
1. F04 is Default Speed for Y/Y1
2. F05 is Default Speed for Y2
3. F01 is Default Speed for G
4. For a single-stage outdoor unit, the Y connection from the thermostat can be connected to the Y/Y1
or Y2 connection on the furnace control module. A call for cooling will energize that connection on the
furnace control module. The desired cooling fan speed should be adjusted for the furnace control
module connection used (Y1 or Y2) to provide the correct cooling airflow.
background
27
AIRFLOW TABLES * R9S80
0.6 0.7 0.8
CFM
RISE CFM
RISE
CFM RISE CFM RISE
CFM RISE
CFM
CFM CFM
F01^^ 658 N/A 585 N/A 545 N/A 495 N/A 444 N/A 390
332
151
F02^ 749 40 697 42 652 45 607 49 554 53 509 459
406
F03
925
32 881 34 840 35
800 37 760 39 721
681 645
F04 882 34 841
35
800 37
760 39
719
41 678 641 602
F01^^ 659
N/A 599
N/A
542 N/A 490 N/A
437 N/A
383
320
N/A
F02^ 1268
35 1221
36
1188 37 1154 38 1122 40 1091 1060
1029
F03 1087
41
1044
43 1008 44 973 46 938 47 905 871 841
F04 1118
40
1070
42 1033 43 997 45 963 46 929
896 865
F01^^ 720
N/A
660 N/A 614 N/A 542 N/A 468 N/A 413 359 313
F02^ 1289 34
1260 35 1232 36 1194 37 1161 38 1125 1087 1073
F03 1125 40 1089 41 1052 42 1013 44 973 46 947
909 863
F04 1252
36 1198 37 1153 39 1110 40 1069 42 1028
990 953
F01^^ 764
N/A
695
N/A 630
N/A 559 N/A
485
N/A 415 358 N/A
F02^ 1287 35 1235 36 1191 37 1147 39
1104
40 1062 1020 979
F03 1339 33 1301
34 1258 35 1217
37 1174 38 1131 1090 1048
F04 1396
32
1346 33 1298 34 1257 35
1217 37 1175 1135 1098
F01^^ 710
N/A 646 N/A 580 N/A 515 N/A 432 N/A 367 314 274
F02^
1298 46 1255 47 1216 49 1178 50
1140 52 1102 1067 1028
F03 1209
49 1166 51 1124 53 1083 55 1045 57 1005 964 923
F04 1138 52
1091 54 1045 57 1001 59 959 62 920 876 832
F01^^ 841 N/A
657 N/A 595 N/A 522 N/A 439 N/A 367 315 N/A
F02^ 1141 52 1089 54 1045 57 1001 59
958 62 914 869 823
F03 1311
45 1267 47
1226 48 1189 50 1150 52 1114 1072 1034
F04 1395 42 1347
44 1309 45 1270 47
1233
48 1199 1164 1125
F01^^ 831 N/A 750
N/A 671 N/A 588 N/A
501
N/A 405 348 300
F02^ 1214 49 1158 51 1103 54 1045
57 989 60 936 883 823
F03 1303 45 1249
47 1191 50 1136 52 1081
55 1028 974 928
F04
1426 42
1375 43 1324 45 1277
46 1229
48 1177 1124 1078
F01^^ 837 N/A 752 N/A
671 N/A 576 N/A
501 N/A
426 361 315
F02^ 1316 45 1270 47
1218 49 1166 51 1114 53 1061 1000 962
F03 1353 44 1323 45 1286 46 1235 48 1183 50
1131 1085 1040
F04
1587 37 1544
38
1506 39 1459 41 1416
42 1372 1323 1281
F01^^
802 N/A 724 N/A 637 N/A 551 N/A 468 N/A 389 342
294
F02^ 1405 53
1356 55 1308 57
1262 59 1210
61 1155 1102 1057
F03 1574 47
1531 48
1484 50 1440 51 1392 53 1357 1306 1256
F04 1619 46
1575 47 1526 49 1489 50 1446 51 1404 1355
1313
F01^^ 851 N/A
774 N/A 692 N/A 615 N/A 535 N/A 470 411 359
F02^ 1677 53 1629 55 1583 56 1540
58 1498
59 1449 1399
1349
F03 1537 58 1489 60 1444 62 1404 63 1365 65 1322 1272 1211
F04^^ 1416 N/A 1365 N/A 1315 N/A 1267 N/A 1220 N/A 1163 1106
1048
NOTE:
^DEFAULT & RECOMMENDED
^^NOT RECOMMENDED FOR HEATING
*R9S800603A*
W/W1
*R9S800403A*
*R9S801205D*
W/W1
*R9S800804B*
W/W1
*R9S800804C*
W/W1
25-55
MODEL
T.STAT
CALL
TAP #
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
TEMP
RANGE
0.1
0.2
0.3
20-50
*R9S800604B*
W/W1
20-50
*R9S800803B*
W/W1
35-65
40-70
35-65
HEATING AIFLOW
W/W1
35-65
*R9S800805C*
W/W1
35-65
0.4
0.5
*R9S801005C*
W/W1
35-65
20-50
*R9S800603B*
W/W1
background
28
AIRFLOW TABLES
*D9S80
0.1 0.2 0.3 0.4
CFM CFM CFM CFM CFM Watts CFM Watts CFM Watts CFM Watts
F01 712 663 610 559 514 86 462 94 395 102 337 108
F02 1120 1081 1053 1022 990 216 955 225 918 231 887 240
F03 929 891 858 815 772 142 737 150 699 157 664 165
F04^ 1073 1031 1003 969 922 191 891 200 854 207 822 217
F05 1212 1198 1161 1138 1103 262 1076 268 1037 280 1007 288
F06 871 830 789 743 702 123 665 131 628 139 583 146
F07 825 784 741 694 650 114 609 120 563 126 520 133
F08 1274 1252 1220 1195 1169 298 1145 307 1110 315 1084 324
F09 1362 1342 1307 1273 1252 353 1237 364 1211 378 1185 385
F01 706 655 604 555 505 87 455 92 395 98 328 105
F02 1035 991 951 913 876 182 844 189 807 197 770 203
F03 932 887 844 806 767 145 728 152 689 158 651 164
F04^ 897 851 808 764 725 134 686 140 646 146 603 151
F05 1123 1077 1041 1006 973 218 941 227 907 235 875 242
F06 1155 1113 1074 1039 1006 233 974 241 945 251 913 258
F07 1255 1214 1181 1147 1116 286 1087 296 1056 304 1028 313
F08 1388 1331 1298 1266 1235 355 1207 367 1179 375 1151 387
F09 1421 1380 1348 1318 1289 390 1262 401 1233 411 1207 421
F01 760 697 636 569 481 86 402 92 349 98 300 103
F02 1286 1238 1196 1157 1117 232 1077 240 1036 250 998 259
F03 1393 1348 1308 1270 1230 277 1196 289 1158 295 1123 306
F04^ 1459 1414 1371 1336 1297 310 1264 321 1229 333 1193 342
F05 1753 1713 1677 1642 1611 493 1576 508 1549 524 1518 533
F06 1309 1261 1218 1182 1142 239 1103 248 1064 258 1025 268
F07 1580 1534 1495 1459 1429 376 1390 388 1356 394 1324 409
F08 1523 1483 1438 1403 1370 351 1336 355 1299 366 1266 377
F09 1643 1599 1562 1525 1491 418 1462 430 1431 444 1394 450
F01 1022 813 674 585 511 101 431 109 334 119 282 124
F02 1453 1407 1332 1259 1190 244 1143 261 1064 273 1003 287
F03 1176 1105 1020 935 864 163
797 173 729 183 673 194
F04^ 1710 1660 1613 1560 1505 344 1424 359 1353 375 1296 392
F05 1843 1786 1747 1690 1643 420 1575 435 1497 445 1435 459
F06 1859 1819 1779 1734 1691 432 1641 450 1593 465 1520 481
F07 2028 1982 1946 1907 1861 536 1814 555 1749 564 1683 588
F08 2096 2045 2006 1974 1927 585 1882 599 1818 611 1765 629
F09 2203 2170 2138 2113 2074 689 2032 705 1990 723 1948 737
F01 956 777 675 587 468 100 377 107 324 112 296 117
F02 1460 1404 1350 1299 1251 252 1203 264 1150 276 1098 287
F03 1561 1499 1441 1385 1336 290 1289 302 1243 314 1197 325
F04^ 1628 1571 1521 1472 1425 317 1380 331 1337 343 1291 356
F05 1714 1659 1611 1564 1519 360 1473 371 1432 387 1387 397
F06 1833 1784 1735 1688 1645 420 1605 436 1562 450 1520 462
F07 1899 1853 1804 1761 1720 465 1681 479 1640 494 1602 510
F08 1926 1894 1849 1807 1764 487 1720 497 1683 514 1642 527
F09 2222 2174 2132 2090 2053 688 2013 702 1976 719 1944 737
*D9S800403A*
Y/Y1, Y2, G
*D9S800603A*
Y/Y1, Y2, G
*D9S800804B*
Y/Y1, Y2, G
*D9S800805C*
Y/Y1, Y2, G
*D9S801005C*
Y/Y1, Y2, G
FAN & COOLING AIFLOW
MODEL
THERMOSTAT
CALL
TAP #
EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
0.5
0.6
0.7
0.8
NOTE:
FURNGCE MODEL Y2 Y1
*D9S800805C* F08 F02
1. F04 is Default Speed for Y/Y1
2. F05 is Default Speed for Y2
3. F01 is Default Speed for G
4. For a single-stage outdoor unit, the Y connection from the thermostat can be connected to the Y/Y1 or Y2
connection on the furnGCe control module. A call for cooling will energize that connection on the furnGCe control
module. The desired cooling fan speed should be adjusted for the furnGCe control module connection used (Y1 or Y2)
to provide the correct cooling airflow.
RECOMMENDED AIRFLOW SPEEDS FOR
CONNECTION WITH 2 STAGE OUTDOOR MODELS
background
29
AIRFLOW TABLES
*D9S80
0.6 0.7 0.8
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
F01^^ 712 N/A 663 N/A 610 N/A 559 N/A 514 N/A 462 395 337
F02^ 1120 26 1081 27 1053 28 1022 29 990 30 955 918 887
F03 929 32 891 33 858 35 815 36 772 38 737 699 664
F04 1073 28 1031 29 1003 30 969 31 922 32 891 854 822
F01^^ 706 N/A 655 N/A 604 N/A 555 N/A 505 N/A 455 395 328
F02^ 1035 43 991 45 951 47 913 49 876 51 844 807 770
F03 932 48 887 50 844 53 806 55 767 58 728 689 651
F04^^ 897 N/A 851 N/A 808 N/A 764 N/A 725 N/A 686 646 603
F01^^ 760 N/A 697 N/A 636 N/A 569 N/A 481 N/A 402 349 300
F02^ 1286 46 1238 48 1196 50 1157 51 1117 53 1077 1036 998
F03 1393 43 1348 44 1308 45 1270 47 1230 48 1196 1158 1123
F04 1459 41 1414 42 1371 43 1336 44 1297 46 1264 1229 1193
F01^^ 1022 N/A 813 N/A 674 N/A 585 N/A 511 N/A 431 334 282
F02^ 1453 41 1407 42 1332 45 1259 47 1190 50 1143 1064 1003
F03^^ 1176 N/A 1105 N/A 1020 N/A 935 N/A 864 N/A 797 729 673
F04 1710 35 1660 36 1613 37 1560 38 1505 39 1424 1353 1296
F01^^ 956 N/A 777 N/A 675 N/A 587 N/A 468 N/A 377 324 296
F02^ 1460 51 1404 53 1350 55 1299 57 1251 59 1203 1150 1098
F03 1561 47 1499 49 1441 51 1385 53 1336 55 1289 1243 1197
F04 1628 46 1571 47 1521 49 1472 50 1425 52 1380 1337 1291
NOTE:
^DEFAULT & RECOMMENDED
^^NOT RECOMMENDED FOR HEATING
MODEL
T.STAT
CALL
TAP #
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
TEMP
RANGE
0.1
0.2
0.3
0.4
0.5
HEATING AIFLOW
*D9S801005C*
W/W1
40-70
*D9S800804B*
W/W1
35-65
*D9S800805C*
W/W1
35-65
*D9S800403A*
W/W1
25-55
*D9S800603A*
W/W1
30-60
background
30
1 STAGE STATUS CODES
Main
Menu
Option Menu
Active Alarm menu
Er r Exx
( xx: code numbers )
Last 10 Faults
F10 Exx
( xx: code numbers )
Code Release Number
Cr
CR Number
Reset to Factory Default
r Fd yes, no
Blower Speed for Continous Fan Mode
FSd Fxx
( xx: Blower Speed Number
F01, F02.. )
Blower Speed for 1st Stage
Compressor Mode
AC1 Fxx
( xx: Blower Speed Number
F01, F02.. )
Blower Speed for 2nd Stage
Compressor Mode
AC2 Fxx
( xx: Blower Speed Number
F01, F02.. )
Cool On Delay
Cnd
Delay, Seconds
Default set at 7 Secs,
Adjustments can be made in
7 Secs increments from 0 to
35 Secs
Cool Off Delay
Cf d
Delay, Seconds
Default set at 65 Secs,
Adjustments can be made in
5 Secs increments from 0 to
120 Secs
Blower Speed for Gas Heat Mode
gAF Fxx
( xx: Blower Speed Number
F01, F02.. )
Gas Heat On Delay
gnd
Delay, Seconds
Default set at 30 Secs,
Adjustments can be made in
5 Secs increments from 5 to
30 Secs
Gas heat Off Delay
gFd
Delay, Seconds
Default set at 90 Secs,
Adjustments can be made in
30 Secs increments from 30 to
180 Secs
Automatic Heat Staging - For Two
Stage Control
AHS
no, 10, 20, 30,
60, AUt
Refer to Section "
CHANGING HEATING
MODE SETTING"
A2L Function Verification
A2u yes, no
Refer to the R-32 Information
Section
A2L Function Enabled
A2E yes, no
Refer to the R-32 Information
Section
Menu Description
LED Display
Notes
Idle
I dL
Continous Fan
FAn
Compressor Cooling, Low
Stage
1 AC
Compressor Cooling, High
Stage
2 AC
Gas heat - Single Stage
Control
gH
OEM test Mode
EOL
Mode
Main
Menu
background
31
1 STAGE TROUBLESHOOTING CODES
To View & Clear Fault Codes
• Press either the Left or Right button until F10 is displayed.
• Press the center button to view stored faults.
• Press and hold the center button for 5 to 30 seconds.
• All stored faults will be erased, and the display will ash - - - three times and return to F10.
Symptom LED Status Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Normal operation. IdL Idle • Normal operation. • None • Normal operation.
Furnace fails to operate.
Integrated control
module LED display
provides no signal.
nonE
No 115v power to
furnace or no 24 volt
power to integrated
control module.
Blown fuse or tripped
circuit breaker.
Integrated control mod-
ule is non-functional.
• Manual disconnect
switch turned OFF,
door switch open or
24 volt wire improperly
connected or loose.
• Furnace electrical sup-
ply shared with other
devices.
• Integrated control
module is non-func-
tional.
• Check 115 volt power
to furnace and integrat-
ed control module.
• Check for possible
shorts in 115 volt circuit.
Repair as necessary.
• Replace non-func-
tional integrated control
module.
• Turn power OFF prior
to repair.
• Read precautions in
""Electrostatic Dis-
charge"" section of
manual.
• Replace control with
correct replacement
part.
Furnace fails to operate
and goes into a hard
lockout.
EbL
Circulator blower motor
current after heat ON
delay is lower than
expected value.
• Loose wiring connec-
tions to and from the
blower motor.
• Circulator blower
motor 115 volt L1 wire
is not plugged into the
CIRC-H connection on
the integrated control
board.
• Circulator blower
motor failure.
• Check for loose wiring
connections to and from
the circulator blower
motor.
• Check 115 volt L1
wire from blower motor
is plugged into the
CIRC-H connection on
the integrated control
board.
• Check circulator blow-
er motor operation.
Replace blower motor if
necessary.
• Turn power OFF prior
to repair.
• Replace blower motor
with correct replace-
ment part.
Furnace fails to operate
and goes into a hard
lockout.
EbU
Circulator blower motor
current during inducer
pre-purge is higher than
expected value.
• Circulator blower
motor power wiring
reversed on integrated
control board.
• Check for loose wiring
connections to and from
the circulator blower
motor.
• Check for miswired
connections on the inte-
grated control board.
• Turn power OFF prior
to repair.
Furnace fails to operate. Ed8
Invalid Call (check ODS
setting)
• ODS setting does not
match outdoor unit.
• Setup ODS to match
outdoor unit.
• Setup TON airow to
match outdoor unit.
• Set system to IdL
before setting ODS and
TON
Furnace fails to operate. EE0
Furnace lockout due
to excessive number
of ignition ""retries"" (3
total).
Failure to establish
ame.
Loss of ame after
establishment.
• Failure to establish
ame. Cause may be
no gas to burners, bad
igniter or igniter align-
ment, improper orices,
or coated/oxidized or
improperly connected
ame sensor.
• Loss of ame after
establshment. Cause
may be interrupted
gas supply, lazy burner
ames (improper gas
pressure or restriction in
ue and/or lack of com-
bustion air), or improper
induced draft blower
performance.
• Locate and correct gas
interruption.
• Replace or realign
igniter.
• Check ame sense
signal. Clean sensor if
coated and/or oxidized.
• Check ue piping for
blockage, proper length,
elbows and termination.
• Verify proper induced
draft blower perfor-
mance.
• Turn power OFF prior
to repair.
• Igniter is fragile, han-
dle with care.
• Clean ame sensor
with steel wool.
• See ""Vent/Flue
Pipe"" section for piping
details.
Furnace fails to operate. EE1
Pressure switch circuit
closed at start of heat-
ing cycle.
• Pressure switch con-
tacts sticking.
• Short in pressure
switch circuit wiring.
• Replace pressure
switch.
• Repair short in wiring.
• Turn power OFF prior
to repair.
• Replace pressure
switch with proper
replacement part.
background
32
1 STAGE TROUBLESHOOTING CODES
Symptom LED Status Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Induced draft blower
runs continuously with
no further furnace
operation.
EE2
Pressure switch circuit
open.
• Pressure switch hose
blocked, pinched, or
connected improperly.
• Blocked ue pipe,
or weak induced draft
blower.
• Incorrect pressure
switch set point or
malfunctioning switch
contacts.
• Loose or improperly
connected wiring.
• Inspect pressure
switch hose. Repair/
replace if necessary.
• Inspect ue piping for
blockage, proper length,
elbows and termination.
Correct as necessary.
• Check induced draft
blower performance.
Correct as necessary.
• Check pressure switch
operation. Replace as
needed.
• Tighten or correct
wiring connections.
• Turn power OFF prior
to repair.
• Replace pressure
switch with proper
replacement part.
• Replace induced draft
blower with proper
replacement part.
Circulator blower runs
continuously with no
furnace operation.
EE3
Primary limit circuit
open.
• Insu󰀩cient condi-
tioned air over the heat
exchanger.
• Blocked lters, restric-
tive ductwork.
• Inproper circulator
blower speed or failed
circulator blower motor.
• Loose or improperly
connected wiring in high
limit circuit.
• Check lters and
ductwork for blockage.
Clean lters or remove
obstruction.
• Check circulator blow-
er speed and perfor-
mance. Correct speed
or replace blower motor
if necessary.
• Tighten or correct
wiring connections.
• Turn power OFF prior
to repair.
• See Specication
Sheet applicable for
your model for allow-
able temp rise range
and proper circulator
speed.
Induced draft blower
and circulator blower
run continuously with no
furnace operation.
EE4
Flame sensed with no
call for heat.
• Short to ground in
ame sense circuit.
• Lingering burner
ame.
• Slow closing gas
valve.
• Correct short at ame
sensor or in ame sen-
sor wiring.
• Check for lingering
ame.
• Verify proper operation
of gas valve.
• Turn power OFF prior
to repair.
No furnace operation. EE5 Open fuse.
• Short in low voltage
wiring
• Back of control board
is touching mounting
panel because stando󰀨s
are missing.
• Locate and correct
short in low voltage
wiring.
• Replace the missing
stando󰀨s.
• Turn power OFF prior
to repair.
• Replace fuse with
3-amp automotive type.
Normal furnace oper-
ation with weak ame
signal.
EE6
Flame sense micro amp
signal is low.
• Flame sensor is coat-
ed/oxidized.
• Flame sensor incor-
rectly positioned in
burner ame.
• Lazy burner ame due
to improper gas pres-
sure or combution air.
• Clean ame sensor if
coated or oxidized.
• Inspect ame sensor
for proper alignment.
• Compare current gas
pressure to rating plate
and adjust as needed.
• Turn power OFF prior
to repair.
• Clean ame sensor
with steel wool.
• See ""Vent/Flue
Pipe"" section for piping
details.
• See rating plate for
proper gas pressure.
Furnace fails to operate. E10 Grounding fault
• Poor neutral connec-
tion.
• Verify neutral wire
connection to furnace
and continuity to ground
source.
• Turn power OFF prior
to repair.
Furnace fails to operate. E11 Open rollout switch.
• Gas pressure too high.
• Burners mis-aligned.
• Restricted heat ex-
changer or venting.
• Check and correct gas
pressure.
• Check and correct
burner alignment.
• Check and correct
restriction
• Turn power OFF prior
to repair.
Furnace fails to operate. EEA
Polarity if 115 volt AC is
reversed.
• Polarity of 115 volt AC
power to furnace or in-
tegrated control module
is reversed.
• Poor furnace ground.
• Review wiring diagram
to correct polarity.
• Verify proper ground.
Correct if necessary.
• Check and correct
wiring.
• Turn power OFF prior
to repair.
background
33
Symptom LED Status Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Furnace fails to operate. EEb
Gas valve is not ener-
gized when it should be.
External gas valve error.
• Miswired gas valve
circuit.
• Open gas valve circuit.
• Gas valve relay on
integrated control board
stuck open.
• Check wiring in gas
valve circuit.
• Replace integrated
control board.
• Turn power OFF prior
to repair.
Furnace fails to operate. EEC
Gas valve is energized
when it should not be.
Internal gas valve error.
• Miswired gas valve
circuit.
• Shorted gas valve
wiring.
• Gas valve relay on
integrated control board
stuck open.
• Check wiring in gas
valve circuit.
• Replace integrated
control board.
• Turn power OFF prior
to repair.
Furnace fails to operate. EEE
Internal Faults or IRQ
Loss in integrated con-
trol board.
• Replace integrated
control board.
• Turn power OFF prior
to repair.
Twinning feature not
working.
EEH TWIN error.
• Both furnaces not on
the same 115 volt power
from breaker.
• Low voltage wiring
error or loose wiring
connections.
• Verify 115 volt power
to each furnace.
• Check wiring connec-
tions.
• Replace integrated
control board if neces-
sary.
• Turn power OFF prior
to repair.
Furnace fails to operate. EEJ Inducer relay error.
• Replace integrated
control board
• Turn power OFF prior
to repair.
• Replace the integrated
control board with prop-
er replacement part.
Furnace fails to operate. EEL
Problem with igniter
circuit.
• Improperly connected
igniter.
• Shorted igniter.
• Poor furnace ground.
• Igniter relay fault
on integrated control
module.
• Check and correct
wiring from integrated
control board to igniter.
• Replace shorted
igniter.
• Check and correct
furnace ground wiring.
• Check igniter output
from control. Replace if
necessary.
• Turn power OFF prior
to repair.
• Replace igniter with
correct replacement
part.
• Replace control with
correct replacement
part.
Furnace fails to operate. EEn Igniter open.
• Loose or incorrect
wiring from integrated
control board to igniter.
• Damaged igniter.
• Check and correct
wiring from integrated
control board to igniter.
• Replace igniter if
necessary.
• Turn power OFF prior
to repair.
• Replace igniter with
correct replacement
part.
Furnace stops heating
and only the fan is
operating.
EAF
Furnace has lost
communication with the
R-32 sensor and the
furnace is in mitigation
mode.
• Furnace may not
be paired with R-32
Cooling Unit. Refer to
the R-32 Information
Section.
• Loose or damaged
R-32 sensor wire.
• Verify wire connection
to R-32 sensor is not
loose.
• Verify the R-32 sensor
wire is not damaged.
• Replace R-32 sensor if
necessary.
• Turn power OFF prior
to repair.
• Replace R-32 sensor
with proper replacement
part.
Furnace stops heating
and only the fan is
operating.
EAL
R-32 sensor has
detected a refrigerant
leak and furnace is in
mitigation mode.
• Investigate the indoor
coil for a refrigerant
leak.
• Furnace will resume
normal operation once
a leak is no longer de-
tected and the 5-minute
delay period is over.
• Turn power OFF prior
to repair.
Furnace stops heating
and only the fan is
operating.
EAS
R-32 sensor has detect-
ed a fault and furnace is
in mitigation mode.
• Investigate the R-32
sensor.
• Replace the R-32
sensor if necessary.
• Turn power OFF prior
to repair.
• Replace R-32 sensor
with proper replacement
part.
Furnace stops heating
and only the fan is
operating.
EAr
A2L relay in the furnace
control board has
detected a fault and
furnace is in mitigation
mode.
• Investigate the A2L
relay.
• Cycle power to the
furnace.
• Replace the integrated
control board if neces-
sary.
• Turn power OFF prior
to repair.
• Replace the integrated
control board with prop-
er replacement part.
1 STAGE TROUBLESHOOTING CODES
background
34
WIRING DIAGRAM
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple
power sources may be present. Failure to do so may cause property
damage, personal injury or death.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
ERROR CODE STATUS
READ CODES FROM LEFT TO RIGHT
SEVEN SEGMENT DISPLAY
Seg#3 Seg#2 Seg#1
INTERNAL FAULTS OR IRQ LOSS
E E E
LOCKOUT DUE TO EXCESSIVE RETRIES RECYCLE E E 0
PRESSURE SWITCH STUCK CLOSED E E 1
PRESSURE SWITCH OPEN E E 2
OPEN HIGH LIMIT SWITCH E E 3
FLAME DETECTED WHEN NO FLAME SHOULD BE PRESENT E E 4
OPEN FUSE E E 5
LOW FLAME SIGNAL E E 6
IGNITOR RELAY FAULT E E L
REVERSED LINE POLARITY OR GROUNDING ERROR E E A
INTERNAL GAS VALVE ERROR E E b
EXTERNAL GAS VALVE ERROR E E C
OPEN ROLLOUT SWITCH E 1 1
IGNITOR OPEN E E n
INDUCER RELAY ERROR E E J
TWIN ERROR E E H
LOW CIRCULATOR CURRENT E bL
ERROR CODE STATUS
READ CODES FROM LEFT TO RIGHT
SEVEN SEGMENT DISPLAY
Seg#3 Seg#2 Seg#1
CIRCULATOR CURRENT UNEXPECTED EbU
A2L COMMUNICATION ALARM EAF
A2L LEAKAGE ALARM EAL
A2L INTERNAL ALARM EAS
A2L RELAY ALARM EAr
0140F20001-B
GR
GND
RD
GR
24
VAC
115
VAC
GND
BK
BR
WH
PK
RD
LIMIT
CONTROL
AUXILIARY
AUTO RESET
PK
40 VA
TRANSFORMER
N
G
C
SENSOR
FLAME
1 ROLL OUT SWITCH
SOME UNITS MAY HAVE
PU
BK
JUNCTION
BOX
WH
YL
LIMIT CONTROL
AUTO RESET PRIMARY
WH
1
L
BK
ID BLOWER
PRESSURE SWITCH
PK
RD
L
N
DOOR OPEN)
(OPEN WHEN
DOOR SWITCH
COMPARTMENT
BLOWER
BLOWER
CIRCULATOR
DISCONNECT
CONNECTOR
2 CIRCUIT
WH
IGNITER
SURFACE
HOT
2
BLOWER
DRAFT
INDUCED
BK
BLOWER COMPARTMENT
BK
ECM MOTOR
HARNESS
BK
BURNER COMPARTMENT
1
2
3
4
5
6
7
8
9
10
11
12
EAC-H
XFMR-H
LINE-H
E20
E2
E1
E15
E8
E5
E4
E3
E7
E6
LEFT
CENTER
RIGHT
SW331313SW1
R223
SW2
6
R226
YL
RD
YL
YL
BK
BK
WH
WH
WH
GY
BL
GR
PU
PU
NEUT2
NEUT1
CIRC-N
EAC-N
HUM-N
XFMR-N
LINE-N
RD
1
2
BK
BK
BK
WH
WH
WH
WH
5
2
1
4
3
RD
BK
OR
BL
YL
RD
BL
OR
BK
YL
T1
T2
T3
T4
T5
COM
RD
GND
TWIN
24V HUM
E21
E24
W/W1
R
Y/Y1
GC
Y2
GND
RD
YL
A2L
ALARM
SPARE
VT-
OUT
VT-
IN
GND
1
2
5V
GY
NO
C
GAS
VALVE
BR
GY
C
HI
A2L MODE IS ENABLED BY
DEFAULT
REFER TO INSTALLATION MANUAL
FOR FURTHER INSTRUCTIONS.
TO 115 VAC/ 1
/60 HZ
POWER SUPPLY WITH
OVERCURRENT
PROTECTION DEVICE
NOTES:
1. MANUFACTURER'S SPECIFIED REPLACEMENT
PARTS MUST BE USED WHEN SERVICING.
2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED
WITH THE FURNACE MUST BE REPLACED IT MUST
BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST
105
˚
C. USE COPPER CONDUCTORS ONLY.
3. UNIT MUST BE PERMANENTLY GROUNDED AND
CONFORM TO N.E.C. AND LOCAL CODES.
4. TO RECALL THE LAST 6 FAULTS, MOST RECENT
TO LEAST RECENT, DEPRESS SWITCH FOR MORE
THAN 2 SECONDS WHILE IN STANDBY
(NO THERMOSTAT INPUTS)
5. WHEN THIS FURNACE IS PAIRED WITH NON R-32
REFRIGERANT SYSTEMS, DEFAULT SETTINGS
WILL NEED TO BE CHANGED. REFER TO
INSTALLATION MANUAL FOR FURTHER
INSTRUCTIONS.
WIRE
COLOR:
YL
WH
BL
BK
RD
OR
PK
GY
TN
GR
BR
YELLOW
WHITE
BLUE
BLACK
RED
ORANGE
BROWN
PINK
GRAY
TAN
GREEN
PURPLE
VIOLET
COLOR
DESIGNATION:
PU
VT
SWITCH (PRESSURE)
FIELD SPLICE
FIELD GROUND
EQUIPMENT GROUND
PROTECTION DEVICE
PLUG CONNECTION
SWITCH (TEMPERATURE)
JUNCTION
OVERCURRENT
TERMINAL
IGNITER
HIGH VOLTAGE (115V)
HIGH VOLTAGE FIELD
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
WARNING: DISCONNECT
POWER BEFORE
SERVICING. WIRING
TO UNIT MUST BE
PROPERLY POLARIZED
AND GROUNDED
A2L SENSOR
CONNECTOR
CIRC-H
E39
BK
A/G*9S80*****AA
background
35
WIRING DIAGRAM
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple
power sources may be present. Failure to do so may cause property
damage, personal injury or death.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
ERROR CODE STATUS
READ CODES FROM LEFT TO RIGHT
SEVEN SEGMENT DISPLAY
Seg#3 Seg#2 Seg#1
INTERNAL FAULTS OR IRQ LOSS
E E E
LOCKOUT DUE TO EXCESSIVE RETRIES RECYCLE E E 0
PRESSURE SWITCH STUCK CLOSED E E 1
PRESSURE SWITCH OPEN E E 2
OPEN HIGH LIMIT SWITCH E E 3
FLAME DETECTED WHEN NO FLAME SHOULD BE PRESENTE E 4
OPEN FUSE E E 5
LOW FLAME SIGNAL E E 6
IGNITOR RELAY FAULT E E L
REVERSED LINE POLARITY OR GROUNDING ERROR E E A
INTERNAL GAS VALVE ERROR E E b
EXTERNAL GAS VALVE ERROR E E C
OPEN ROLLOUT SWITCH E 1 1
IGNITOR OPEN E E n
INDUCER RELAY ERROR E E J
TWIN ERROR E E H
LOW CIRCULATOR CURRENT E bL
ERROR CODE STATUS
READ CODES FROM LEFT TO RIGHT
SEVEN SEGMENT DISPLAY
Seg#3 Seg#2 Seg#1
CIRCULATOR CURRENT UNEXPECTEDE
bU
A2L COMMUNICATION ALARM EAF
A2L LEAKAGE ALARM EAL
A2L INTERNAL ALARM EAS
A2L RELAY ALARM EAr
0140F20077-A
WITH OVERCURRENT
115 VAC/ 1
/60 HZ
TO
POWER SUPPLY
PROTECTION DEVICE
GR
GND
RD
GR
24
VAC
115
VAC
GND
BK
BR
WH
RD
RD
PK
40 VA
TRANSFORMER
N
G
C
SENSOR
FLAME
1 ROLL OUT SWITCH
SOME UNITS MAY HAVE
PU
BK
JUNCTION
BOX
WH
YL
LIMIT CONTROL
AUTO RESET PRIMARY
WH
1
L
BK
ID BLOWER
PRESSURE SWITCH
RD
L
N
DOOR OPEN)
(OPEN WHEN
DOOR SWITCH
COMPARTMENT
BLOWER
BLOWER
CIRCULATOR
DISCONNECT
2 CIRCUIT
CONNECTOR
WH
IGNITER
SURFACE
HOT
2
BLOWER
DRAFT
INDUCED
BK
BLOWER COMPARTMENT
BK
ECM MOTOR
HARNESS
BK
BURNER COMPARTMENT
1
2
3
4
5
6
7
8
9
10
11
12
EAC-H
XFMR-H
LINE-H
E20
E2
E1
E15
E8
E5
E4
E3
E7
E6
LEFT
CENTER
RIGHT
133WS313SW1
R223
SW2
6
R226
YL
RD
YL
YL
BK
BK
WH
WH
WH
GY
BL
GR
PU
PU
NEUT2
NEUT1
CIRC-N
EAC-N
HUM-N
XFMR-N
LINE-N
1
2
BK
BK
BK
WH
WH
WH
WH
5
2
1
4
3
RD
BK
OR
BL
YL
RD
BL
OR
BK
YL
T1
T2
T3
T4
T5
COM
RD
GND
TWIN
24V HUM
E21
E24
W/W1
R
Y/Y1
GC
Y2
GND
RD
YL
A2L
ALARM
SPARE
VT-
OUT
VT-
IN
GND
1
2
5V
GY
NO
C
GAS
VALVE
BR
GY
C
HI
A2L MODE IS ENABLED BY
DEFAULT
REFER TO INSTALLATION MANUAL
FOR FURTHER INSTRUCTIONS.
NOTES:
1. MANUFACTURER'S SPECIFIED REPLACEMENT
PARTS MUST BE USED WHEN SERVICING.
2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED
WITH THE FURNACE MUST BE REPLACED IT MUST
BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST
105
˚
C. USE COPPER CONDUCTORS ONLY.
3. UNIT MUST BE PERMANENTLY GROUNDED AND
CONFORM TO N.E.C. AND LOCAL CODES.
4. TO RECALL THE LAST 6 FAULTS, MOST RECENT
O LEAST RECENT, DEPRESS SWITCH FOR MORE
THAN 2 SECONDS WHILE IN STANDBY
(NO THERMOSTAT INPUTS)
5. WHEN THIS FURNACE IS PAIRED WITH NON R-32
REFRIGERANT SYSTEMS, DEFAULT SETTINGS
WILL NEED TO BE CHANGED. REFER TO
INSTALLATION MANUAL FOR FURTHER
INSTRUCTIONS.
WIRE
COLOR:
YL
WH
BL
BK
RD
OR
PK
GY
TN
GR
BR
YELLOW
WHITE
BLUE
BLACK
RED
ORANGE
BROWN
PINK
GRAY
TAN
GREEN
PURPLE
VIOLET
COLOR
DESIGNATION:
PU
VT
SWITCH (PRESSURE)
FIELD SPLICE
FIELD GROUND
EQUIPMENT GROUND
PROTECTION DEVICE
PLUG CONNECTION
SWITCH (TEMPERATURE)
JUNCTION
OVERCURRENT
TERMINAL
IGNITER
HIGH VOLTAGE (115V)
HIGH VOLTAGE FIELD
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
WARNING: DISCONNECT
POWER BEFORE
SERVICING. WIRING
TO UNIT MUST BE
PROPERLY POLARIZED
AND GROUNDED
A2L SENSOR
CONNECTOR
CIRC-H
E39
BK
A/G*9S80*****AB
background
36
START-UP CHECKLIST
Furnace
ELECTRICAL
LineVoltage(MeasureL1toNandNtoGroundVoltage)
L‐N
N‐G
SecondaryVoltage(MeasureTransformerOutputVoltage) R‐C
BlowerAmps
BLOWEREXTERNALSTATICPRESSURE
ReturnAirStaticPressure IN.W.C.
SupplyAirStaticPressure IN.W.C.
TotalExternalStaticPressure(Ignoring+/‐fromthereadingabove,addtotalhere) IN.W.C.
TEMPERATURES
ReturnAirTemperature(Drybulb/Wetbulb) DB°F WB°F
DB°F WB°F
HeatingSupplyAirTemperature DB°F
TemperatureRise DB°F
DeltaT(DifferencebetweenSupplyandReturnTemperatures) DB°F
GASPRESSURES
GasInletPressure
IN.W.C.
GasManifoldPressure(LowFire) IN.W.C.
GasManifoldPressure(HighFire) IN.W.C.
GasType(NG)=NaturalGas/(LP)=LiquidPropane
AdditionalChecks
Checkwireroutingsforanyrubbing
Checkforkinkedpressureswitchtubing.
Checkflueelbowforalignmentandclamptightness.
Checkscrewtightnessonblowerwheel.
Checkfactorywiringandwireconnections.
Checkproductforproperclearancesasnotedbyinstalltioninstructions
CheckR‐32sensorwireisconnectedproperly(ifapplicable)
°Fto°Cformula:(°F‐32)dividedby1.8=°C°Cto°Fformula:(°Cmultipliedby1.8)+32=°F
CoolingSupplyAirTemperature(Drybulb/Wetbulb)
ModelNumber
SerialNumber
background
37
THIS PAGE IS INTENTIONALLY LEFT BLANK
background
38
THIS PAGE IS INTENTIONALLY LEFT BLANK
background
39
THIS PAGE IS INTENTIONALLY LEFT BLANK
background
40
Our continuing commitment to quality products may mean a change in specications without notice.
© 2025 Daikin Comfort Technologies Manufacturing, Inc.
19001 Kermier Rd., Waller, TX 77484
www.goodmanmfg.com • www.amana-hac.com
is a registered trademark of Maytag Corporation or its related companies and is used under license.
All rights reserved.
CUSTOMER FEEDBACK
We are very interested in all product comments.
Please ll out the feedback form on one of the following links:
Goodman
®
Brand Products: (http://www.goodmanmfg.com/about/contact-us).
Amana
®
Brand Products: (http://www.amana-hac.com/about-us/contact-us).
You can also scan the QR code on the right for the product brand
you purchased to be directed to the feedback page.
GOODMAN
®
BRAND
AMANA
®
BRAND

Specifications

Indexed Terms: Gas Furnace, 80% AFUE

Goodman GD9S800804BX Questions and Answers

Questions and Answers

Related Products