Goodman GR9S960805CU GR9S96_U Gas Furnace 96% AFUE Single-Stage Upflow/Horizontal

Product's Documents

Below are documents related to this product, you can read online or download:
User Manual Installation Instruction Other Documents
GR9S960805CU photo

Manual

This is the main product document for model GR9S960805CU.

The file format is pdf, 34 pages, you can download this manual here .

background
Service and Troubleshooting
96% Single Stage Ultra-Low NOx Gas Furnaces
A/GR9S96*U*
RS6612302
January 2025
TABLE OF CONTENTS
IMPORTANT INFORMATION .......................................... 2
PRODUCT IDENTIFICATION ..........................................3
SYSTEM OPERATION .....................................................5
SCHEDULED MAINTENANCE .....................................16
SERVICING .....................................................................19
CHECKING VOLTAGE ..................................................23
CHECKING WIRING ...................................................23
CHECKING THERMOSTAT, WIRING ........................23
CHECKING TRANSFORMER AND CONTROL
CIRCUIT ....................................................................... 23
CHECKING AIR CIRCULATOR BLOWER MOTOR 24
CHECKING DUCT STATIC ........................................24
CHECKING TEMPERATURE RISE ...........................25
CHECKING PRIMARY LIMIT CONTROL .................25
CHECKING AUXILIARY LIMIT CONTROL ..............26
INDUCED DRAFT BLOWER MOTOR ......................26
CHECKING GAS VALVE (REDUNDANT) ................27
CHECKING GAS PRESSURE ...................................27
CHECKING HOT SURFACE IGNITER ......................29
CHECKING PRESSURE TRANSDUCER ................. 29
CHECKING FOR DELAYED IGNITION ....................30
CHECKING INTEGRATED IGNITION CONTROL
BOARDS ......................................................................30
CHECKING FLAME SENSOR ...................................30
TROUBLESHOOTING ...................................................31
WIRING DIAGRAM ........................................................34
Pride and workmanship go into every product to provide
our customers with quality products. It is possible, however,
that during its lifetime a product may require service.
Products should be serviced only by a qualied service
technician who is familiar with the safety procedures
required in the repair and who is equipped with the proper
tools, parts, testing instruments and the appropriate service
manual. REVIEW ALL SERVICE INFORMATION IN THE
APPROPRIATE SERVICE MANUAL BEFORE
BEGINNING REPAIRS.
Do not bypass safety devices.
WARNING
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL,
ADJUST, SERVICE, MAINTENANCE OR REPAIR
(HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN
THIS MANUAL SHOULD SERVICE THE EQUIPMENT.
THIS EQUIPMENT IS NOT INTENDED FOR USE BY
PERSONS (INCLUDING CHILDREN) WITH REDUCED
PHYSICAL, SENSORY OR MENTAL CAPABILITIES, OR LACK
OF EXPERIENCE AND KNOWLEDGE, UNLESS THEY HAVE
BEEN GIVEN SUPERVISION OR INSTRUCTION CONCERNING
USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR
THEIR SAFETY.
CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT
THEY DO NOT PLAY WITH THE EQUIPMENT.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR
ANY INJURY OR PROPERTY DAMAGE ARISING FROM
IMPROPER SUPERVISION, SERVICE OR SERVICE
PROCEDURES. IF YOU SERVICE THIS UNIT, YOU ASSUME
RESPONSIBILITY FOR ANY INJURY OR PROPERTY
DAMAGE WHICH MAY RESULT. IN ADDITION, IN
JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES
TO SERVICE THE EQUIPMENT SPECIFIED IN THIS
MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE
THE EQUIPMENT. IMPROPER SUPERVISION, INSTALLATION,
ADJUSTMENT, SERVICING, MAINTENANCE OR REPAIR OF
THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR
ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR
THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT
PROPER SUPERVISION OR TRAINING MAY RESULT IN
PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
WARNING
© 2025
19001 Kermier Rd. Waller, TX 77484
www.daikincomfort.com
is a registered trademark of Maytag Corporaon or its related companies and is used under license. All rights reserved.
background
IMPORTANT INFORMATION
2
OUTSIDE THE U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.) Your telephone company will bill you for the call.
B10259-216
CO can cause serious illness including permanent brain
damage or death.
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
B10259-216
El monóxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
Las emisiones de monóxido de carbono pueden circular a través
del aparato cuando se opera en cualquier modo.
B10259-216
RISQUE D'EMPOISONNEMENT AU
MONOXYDE DE CARBONE
Cette ventilation est nécessaire pour éviter le danger d'intoxication
au CO pouvant survenir si un appareil produisant du monoxyde
de carbone continue de fonctionner au sein de la zone confinée.
To prevent the risk of property damage, personal injury,
or death. Do not store combustible materials or use
gasoline or other flammable liquids or vapors in the
vicinity of this appliance.
WARNING
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
If the information in these instructions is not followed
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
- What to do if you smell gas:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING
Should overheating occur or the gas supply fail to shut
off, turn off the manual gas shutoff valve external to the
furnace before turning off the electrical supply.
WARNING
This unit should not be connected to, or used in
conjunction with, any devices that are not certified for
use with this unit or have not been tested and approved by
the manufacturer. Serious property damage or personal
injury , reduced unit performance and/or hazardous
conditions may result from the use of devices that have not
been approved or certified by the manufacturer.
WARNING
background
PRODUCT IDENTIFICATION
3
NOMENCLATURE
The model and manufacturing number are used for positive identication of component parts used in manufacturing.
Please use these numbers when requesting service or parts information.
G R 9 S 96 060 3 B U A A
1 2 3 4 5,6 7,8,9 10 11 12 13 14
Brand
G - Goodman
A - Amana® Brand
Configuration
M - Upflow/Horizontal R410A
C - Downflow/Horizontal R410A
R- Upflow/ Horizontal R32
D - Downflow/Horizontal R32
MOTOR
9 - Multi-Speed ECM (9 taps) / Non-Communicating
V - Variable-Speed ECM / Communicating
Gas Valve
S - Single Stage
T - Two Stage
AFUE
80 - 80% AFUE
92 - 92% AFUE
96 - 96% AFUE
97 - 97% AFUE
MBTU/h
040 - 40,000 BTU/h
060 - 60,000 BTU/h
080 - 80,000 BTU/h
B - 1st Revision
Minor Revision
A - Initial Release
B - 1st Revision
Major Revision
A - Initial Release
C - 21"
NOx
N - Natural Gas
≥ 40 NG/J NOx
N - Low NOx (90%+)
≤ 40 NG/J NOx
X - Low NOx (80%)
≤ 40 NG/J NOx
U - Ultra Low NOx
≤ 14 NG/J NOx
Cabinet Width
A - 14"
B - 17.5"
D - 24.5"
Maximum CFM
3 - 1200 CFM
4 - 1600 CFM
5 - 2000 CFM
A R 9 S 96 060 3 B U A A
1 2 3 4 5,6 7,8,9 10 11 12 13 14
Brand
G - Goodman
A - Amana® Brand
Configuration
M - Upflow/Horizontal R410A
C - Downflow/Horizontal R410A
R- Upflow/ Horizontal R32
D - Downflow/Horizontal R32
MOTOR
9 - Multi-Speed ECM (9 taps) / Non-Communicating
V - Variable-Speed ECM / Communicating
Gas Valve
S - Single Stage
T - Two Stage
AFUE
80 - 80% AFUE
92 - 92% AFUE
96 - 96% AFUE
97 - 97% AFUE
MBTU/h
040 - 40,000 BTU/h
060 - 60,000 BTU/h
080 - 80,000 BTU/h
B - 1st Revision
Minor Revision
A - Initial Release
B - 1st Revision
Major Revision
A - Initial Release
C - 21"
NOx
N - Natural Gas
≥ 40 NG/J NOx
N - Low NOx (90%+)
≤ 40 NG/J NOx
X - Low NOx (80%)
≤ 40 NG/J NOx
U - Ultra Low NOx
≤ 14 NG/J NOx
Cabinet Width
A - 14"
B - 17.5"
D - 24.5"
Maximum CFM
3 - 1200 CFM
4 - 1600 CFM
5 - 2000 CFM
background
PRODUCT IDENTIFICATION
4
MODEL # DESCRIPTION
AR9S960403BUA*
AR9S960603BUA*
AR9S960805CUA*
Amana
® Brand 96% Ultra-Low NOx Gas Furnace, This furnace
complies with the SCAQMD Rule 1111 14 ng/J NOx emission limit.
Upflow/Horizontal Installation, induced draft. Nine-speed ECM motor.
The furnace features a stainless steel tubular heat exchanger.Line
voltage EAC and HUM terminals.
GR9S960403BUA*
GR9S960603BUA*
GR9S960805CUA*
Goodman
® Brand 96% Ultra-Low NOx Gas Furnace, This furnace
complies with the SCAQMD Rule 1111 14 ng/J NOx emission limit.
Upflow/Horizontal Installation, induced draft. Nine-speed ECM motor.
The furnace features a stainless steel tubular heat exchanger.Line
voltage EAC and HUM terminals.
background
SYSTEM OPERATION
5
SAFETY
Please adhere to the following warnings and cautions when
installing, adjusting, altering, servicing, or operating the
furnace.
To prevent personal injury or death due to improper
installation, adjustment, alteration, service or
maintenance, refer to this manual. For additional
assistance or information, consult a qualified installer,
service agency or the gas supplier.
WARNING
To prevent possible property damage, personal injury or
death due to electrical shock, the furnace must be located
to protect the electrical components from water.
WARNING
CHARGE (ESD) PRECAUTIONS
NOTE: Discharge your body’s static electricity before
touching unit. An electrostatic discharge can adversely
a󰀨ect electrical components.
Use the following precautions during furnace installation
and servicing to protect the integrated control module
from damage. By putting the furnace, the control, and the
person at the same electrostatic potential, these steps
will help avoid exposing the integrated control module to
electrostatic discharge. This procedure is applicable to both
installed and uninstalled (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the
integrated control module or any wire connected to the
control prior to discharging your body’s electrostatic
charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the
furnace near the control. Any tools held in a person’s
hand during grounding will be discharged.
3. Service integrated control module or connecting
wiring following the discharge process in Step 2. Use
caution not to recharge your body with static electricity;
(i.e., do not move or shu󰀪e your feet, do not touch
ungrounded objects, etc.). If you come in contact with
an ungrounded object, repeat Step 2 before touching
control or wires.
4. Discharge any static electricity from your body to
ground before removing a new control from its
container. Follow Steps 1 through 3 if installing the
control on a furnace. Return any old or new controls
to their containers before touching any ungrounded
object.
Product Application
This product is designed for NATURAL GAS ONLY.
This product is designed for use as a residential home
gas furnace. It is not designed or certied for use in
mobile home, trailer, or recreational vehicle applications.
IMPORTANT NOTE: The 80% furnace cannot be
installed as a direct vent (i.e., sealed combustion)
furnace. The burner box is present only to help reduce
sound transmission from the burners to the occupied
space.
To ensure proper installation, operation and servicing,
thoroughly read the installation and service manuals
for specics pertaining to the installation, servicing and
application of this product.
Possible property damage, personal injury or death due to
fire, explosion, smoke, soot, condensation, electrical shock
or carbon monoxide may result from improper installation,
repair, operation or maintenance of this product.
WARNING
To prevent property damage, personal injury or death due
to fire, do not install this furnace in a mobile home, trailer,
or recreational vehicle.
WARNING
To ensure proper furnace operation, install, operate,
maintain and service the furnace in accordance with the
installation, operation and service instructions, all local
building codes and ordinances. In their absence, follow
the latest edition of the National Fuel Gas Code (NFPA 54/
ANSI Z223.1), and/or CAN/CGA B149 Installation Codes,
local plumbing or waste water codes, and other applicable
codes.
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE Guide” or “Manual
J-Load Calculations” published by the Air Conditioning
Contractors of America.
Upon completion of the furnace installation, carefully
inspect the flue system both inside and outside the furnace
to assure it is properly sealed. Leaks in the flue system can
result in serious personal injury or death due to exposure
to flue products, including carbon monoxide.
WARNING
background
SYSTEM OPERATION
6
If the information in these instructions is not followed
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
- What to do if you smell gas:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in
your building.
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING
HIGH ALTITUDE DERATE
The furnace, as shipped, requires no change to run
between 0-4500 feet. At all altitudes the air temperature
rise must be within the range listed on the Specication
Sheet applicable to your model for the fuel used. Manifold
pressure adjustments and combustion analysis are
required for all installations above 4500 ft. Refer to “Gas
Supply Pressure Measurement” section for instruction
on how to properly measure and adjust manifold “outlet”
pressure. The furnace should operate for a minimum of 15
minutes before taking a combustion sample. Combustion
samples should be taken from beyond the furnace exhaust
and must be within provided CO2% range. See table below
for recommended manifold pressure adjustments and
proper CO2% range. Gas heating values can vary; further
pressure adjustment may be necessary to ensure furnace
operates within acceptable CO2 range.
2.5" w .c.
2.5" w .c.
2.5" w .c.
Manifold
Pressure
at 5000 ft
ELECTRICAL CONNECTIONS
WARNING
HIGH VOLTAGE!
To avoid personal injury or death due to
electrical shock, disconnect electrical power
before servicing or changing any electrical
wiring.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
WARNING
HIGH VOLTAGE!
To avoid risk of injury, electrical shock
or death, the furnace must be electrically
polarized and grounded in accordance with
local codes or in their absence, with the
latest edition of the National Electric Code.
WIRING HARNESS
The wiring harness is an integral part of this furnace. Field
alteration to comply with electrical codes should not be
required. Wires are color coded for identication purposes.
Refer to the wiring diagram for wire routings. If any of
the original wire as supplied with the furnace must be
replaced, it must be replaced with wiring material having
a temperature rating of at least 105°C. Any replacement
wiring must be a copper conductor.
120 VOLT LINE CONNECTIONS
Before proceeding with electrical connections, ensure
that the supply voltage, frequency, and phase correspond
to that specied on the unit rating plate. Power supply to
the furnace must be NEC Class 1, and must comply with
all applicable codes. The furnace must be electrically
grounded in accordance with local codes or, in their
absence, with the latest edition of The National Electric
Code, ANSI NFPA 70.
Use a separate branch electrical circuit containing properly
sized wire, and fuse or circuit breaker. The fuse or circuit
breaker must be sized in accordance with the maximum
overcurrent protection specied on the unit rating plate.
An electrical disconnect must be provided at the furnace
location.
Line voltage wiring must enter into the junction box
provided with the furnace. Connect hot, neutral and ground
wires as shown in the wiring diagram located on the unit’s
blower door. Metal conduit is not considered a substitute
for an actual ground wire to the unit.
Line polarity must be observed when making eld
connections. Line voltage connections can be made
through either the right or left side panel. To relocate the
junction box, follow the steps shown in the Junction Box
Relocation section.
IMPORTANT NOTE: To avoid possible equipment
malfunction, route the low voltage wires to avoid
interference with lter removal or other maintenance.
background
SYSTEM OPERATION
7
WARNING
HIGH VOLTAGE!
To avoid risk of injury, electrical shock
or death, the furnace must be electrically
polarized and grounded in accordance with
local codes or in their absence, with the
latest edition of the National Electric Code.
To ensure proper unit grounding, the ground wire should
run from the furnace ground screw located inside the
furnace junction box all the way back to the electrical panel.
NOTE: Do not use gas piping as an electrical ground. To
conrm proper unit grounding, turn o󰀨 the electrical power
and perform the following check.
1. Measure resistance between the neutral (white)
connection and the unpainted surface on the furnace.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock
switch which interrupts unit voltage when the blower door is
opened for servicing. Do not defeat this switch.
24 VOLT THERMOSTAT WIRING
NOTE: Wire routing must not interfere with
circulator blower operation, lter removal, or routine
maintenance.
Low voltage connections can be made through either the
right or left side panel. Thermostat wiring entrance holes
are located in the blower compartment. The following gure
shows connections for a “heat only” system and “heat/cool
system”.
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Single-Stage Cooli
ng)
24 VA C
Thermostat
Y1
Y2
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Two-Stage Cooling)
24 VA C
Thermostat
Y2
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VA C
Thermostat
Heat Pump
R
C
Y
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VA C
Thermostat
Two Stage
Heat Pump
R
C
Y
Y2
Y2
Y1
Y2
Y2
Non-communicating Single Stage A/C
Figure 6A
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Single-Stage Cooling)
24 VA C
Thermostat
Y1
Y2
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Two-Stage Cooling)
24 VA C
Thermostat
Y2
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VA C
Thermostat
Heat Pump
R
C
Y
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VA C
Thermostat
Two Stage
Heat Pump
R
C
Y
Y2
Y2
Y1
Y2
Y2
Non-communicating Two Stage A/C
Figure 6B
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Single-Stage Cooling)
24 VA C
Thermostat
Y1
Y2
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Two-Stage Cooling)
24 VA C
Thermostat
Y2
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VA C
Thermostat
Heat Pum
p
R
C
Y
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VA C
Thermostat
Two Stage
Heat Pump
R
C
Y
Y2
Y2
Y1
Y2
Y2
Non-Communicating Single Stage Heat Pump
Figure 6C
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Single-Stage Cooling)
24 VA C
Thermostat
Y1
Y2
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Two-Stage Cooling)
24 VA C
Thermostat
Y2
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VA C
Thermostat
Heat Pump
R
C
Y
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VA C
Thermostat
Two Stage
Heat Pum
p
R
C
Y
Y2
Y2
Y1
Y2
Y2
Non-Communicating Two Stage Heat Pump
Figure 6D
NOTE: Equipment type (Single-stage cooling, Two-
stage cooling, Single-stage heat pump, Two-stage heat
pump) MUST be setup through the OdS menu by the
installer for proper system operation. See Using Push-
Button Switches for instructions on how to navigate
the control menu.
This furnace is equipped with a 40 VA transformer to
facilitate use with most cooling equipment. Consult the
wiring diagram, located on the blower compartment door,
for further details of 120 Volt and 24 Volt wiring.
A single-stage thermostat with only one heating stage is
needed to control this furnace.
LOW VOLTAGE VENTILATION
The Ventilation connections provide a dry contact for
eld ventilator wiring connections. These connections are
normally open and energize during the R-32 fault/alarm
condition. A VENT IN and a VENT OUT connectors are
provided and are shown in the image below.
LOW VOLTAGE A2L ALARM
The A2L alarm connection provides 24VAC for eld alarm
wiring connections. These connections are normally open
and energize during the R-32 fault/alarm condition. An A2L
Alarm connector is provided and is shown in the image
below.
FIELD INSTALLED ACCESSORIES (DAUGHTER
BOARD)
Additional accessories that do not have dedicated terminals
on the furnace control board may require an additional
daughter board to be installed. Please refer to service
manual on your product for more information.
background
SYSTEM OPERATION
8
R-32 SENSOR
24 VOLT
VENTILATION
(OPTIONAL)
24 VOLT A2L ALARM
(OPTIONAL)
24 VAC Accessories - Accessories Wiring
Figure 7
120 VOLT LINE CONNECTION OF ACCESSORIES
HUMIDIFIER AND ELECTRONIC AIR CLEANER
WARNING
HIGH VOLTAGE!
To avoid personal injury or death due to
electrical shock, disconnect electrical power
before servicing or changing any electrical
wiring.
The furnace integrated control module is equipped with
dedicated ¼ inch EAC and HUM relay terminals for
controlling external power to an optional eld-supplied
humidier and/or electronic air cleaner. Additional line
voltage wiring to the inside of the furnace must conform to
all local codes and have a minimum temperature rating of
105°C. All line voltage wire splices must be made inside
the furnace.
When utilized, the HUM relay will be closed during normal
heating operation and the EAC relay will be closed during
fan operation. 120VAC must be present on the one terminal
from HUM or EAC to take advantage of the second
terminal.
115 VAC EAC
115 VAC
HUM
120 Volt Line Connection of Accessories Humidier
(HUM) & Electronic Air Cleaner (EAC)
Figure 8
FOSSIL FUEL APPLICATIONS
This furnace can be used in conjunction with a heat pump
in a fossil fuel application. A fossil fuel application refers to
a combined gas furnace and heat pump installation which
uses an outdoor temperature sensor to determine the
most cost e󰀩cient means of heating via heat pump or gas
furnace.
A heat pump thermostat with two stages of heat is required
to properly use a furnace in conjunction with a heat pump.
Refer to the fossil fuel kit installation instructions for
additional thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit
installation instructions. All furnace connections must be
made to the furnace integrated control module and the
FURNACE terminal strip on the fossil fuel control board.
NORMAL SEQUENCE OF OPERATION
POWER UP
• 120 VAC power applied to furnace.
• Integrated ignition control performs internal checks.
• Upon power-up of the control board, all Seven
segments will be illuminated displaying “8 8 8”. After
power-up the displays will show “I d L”, idle, or stand-
by mode.
• The control is now ready to receive demands from the
room thermostat. Refer to Status Menu in this manual
for interpretation of items displayed in the status menu.
GAS HEATING MODE
The normal operational sequence in gas heating mode is
as follows:
• R and W thermostat contacts close, initiating a call
for heat. The control will display heat mode in status
menu: - g h
• Integrated control module performs safety circuit
checks.
• Induced draft blower is energized for 30 second pre-
purge period causing pressure sensor contacts to
close.
• Igniter warm up begins after 30 second pre-purge
expires.
• Gas valve opens at end of igniter warm up period,
delivering gas to burners and establishing ame.
• Integrated control module monitors ame presence.
Gas valve will remain open only if ame is detected.
• Circulator blower is energized on user selected heat
speed following a xed thirty second blower on delay.
Electronic air cleaner terminal is energized at the same
time the circulator blower is energized.
• The 120V humidier terminal is energized whenever
the induced draft blower is energized.
• Furnace operates; integrated control module monitors
safety circuits continuously.
• R and W thermostat contacts open, completing the call
for heat.
• Gas valve closes, extinguishing ame.
background
SYSTEM OPERATION
9
• Induced draft blower is de-energized following a thirty
second post purge.
• HUM terminal relay is de-energized.
• Circulator blower continues running for selected heat
o󰀨 delay. If required this can be changed in the eld.
• Electronic air cleaner is de-energized.
• Furnace awaits the next call from thermostat.
COOLING MODE
The control board supports two stages of cooling. If this
furnace is installed with a single stage cooling unit or heat
pump, the Y1 terminal of the control board must be used.
A Y2 call on the control board will be ignored if a Y1 call is
not present.
COOLING MODE SEQUENCE OF OPERATION
1ST STAGE COOLING MODE SEQUENCE:
• On a call for low stage cooling, the Y1 or Y1 and G
thermostat contacts close signaling the furnace control
board with 24 vac. on Y1 or Y1 and G terminals.
• The 7-Segment will display: 1 A C
• The compressor and condenser fan are energized.
• The circulator fan is energized at low cool speed after
the cool on delay period. The electronic air cleaner
EAC relay will close the EAC contacts.
• After the thermostat is satised, the compressor is
de-energized and the Cool Mode Fan O󰀨 Delay period
begins.
• Following the Cool Mode Fan O󰀨 Delay period, the
indoor fan and air cleaner relays are de-energized
2ND STAGE COOLING MODE SEQUENCE:
NOTE: A Y1 call must be present or a Y2 call will be
ignored.
• On a call for 2nd stage cooling, the Y2 or Y2 and G
thermostat contacts close signaling the furnace control
board with 24 vac. on Y2 or Y2 and G terminals.
• The 7-Segment will display: 2 A C
• The compressor and condenser fan are energized.
• The circulator fan is energized at cool speed after a
cool on delay. The electronic air cleaner EAC relay will
close the EAC contacts.
• After the thermostat is satised, the compressor is
de-energized and the Cool Mode Fan O󰀨 Delay period
begins.
• Following the Cool Mode Fan O󰀨 Delay period, the
indoor fan and air cleaner relays are de-energized.
HEAT PUMP MODE
1ST STAGE HP HEATING MODE SEQUENCE:
• On a call for low stage HP Heating, the Y1 or Y1 and G
thermostat contacts close signaling the furnace control
board with 24 vac. on Y1 or Y1 and G terminals.
• The 7-Segment will display: 1 H P
• The compressor and condenser fan are energized.
• The circulator fan is energized at HP1 fan speed after
the HP on delay period. The electronic air cleaner,
EAC, and humidier, HUM, relays will close the
contacts.
• After the thermostat is satised, the compressor is
de-energized and the electronic air cleaner EAC and
humidier HUM relays de-energize. The HP Heat Mode
Fan O󰀨 Delay period begins.
• Following the HP Heat Mode Fan O󰀨 Delay period, the
indoor fan, EAC, & HUM relays are de-energized.
2ND STAGE HP HEATING MODE SEQUENCE:
NOTE: A Y1 call must be present or a Y2 call will be
ignored.
• On a call for 2nd stage HP Heating, the Y2 or Y2 and G
thermostat contacts close signaling the furnace control
board with 24 vac. on Y2 or Y2 and G terminals.
• The 7-Segment will display: 2 H P
• The compressor and condenser fan are energized.
• The circulator fan is energized at HP2 fan speed after
the HP on delay period. The electronic air cleaner EAC
and humidier HUM relays will close the contacts.
• After the thermostat is satised, the compressor is
de-energized and the electronic air cleaner EAC and
humidier HUM relays de-energize. The HP Heat Mode
Fan O󰀨 Delay period begins.
• Following the HP Heat Mode Fan O󰀨 Delay period, the
indoor fan, EAC, & HUM relays are de-energized.
FAN ONLY MODE
The normal operational sequence in fan only mode is as
follows:
• R and G thermostat contacts close, initiating a call for
fan.
• Integrated control module performs safety circuit
checks.
• Circulator blower is energized on user selected
fan speed. Electronic air cleaner terminal relay is
energized.
• Circulator blower runs, integrated control module
monitors safety circuits continuously.
• R and G thermostat contacts open, completing the call
for fan.
• Circulator blower is de-energized. Electronic air cleaner
terminal relay is de-energized.
• Furnace awaits the next call from thermostat.
background
SYSTEM OPERATION
10
DEFROST MODE
Defrost call can only be generated with heat pump outdoor
unit properly congured in the OdS menu.
• On a call for Defrost, the Y1 or Y1 with Y2 with/without
O contacts and W thermostat contacts close signaling
the furnace control board to enter defrost.
• If Y with O and W are present simultaneously, the
blower shall be energized at Cooling Speed after
COOL on delay, then, switch the blower speed to the
Greater of (Cooling Speed or Gas Heat speed) after
Gas Heat On Delay expired.
• If Y without O and W are present simultaneously, the
blower shall be energized at HP Heat Speed after HP
Heat On Delay, then, switch the blower speed to the
Greater of (HP Heat Speed or Gas Heat speed) after
Gas Heat On Delay expired.
• The 7-Segment will display: d F t
• The electronic air cleaner EAC and humidier HUM
relays will close the contacts.
• After the thermostat is satised, the gas valve will de-
energize. The Gas Heat Mode Fan O󰀨 Delay period
begins.
• Following the Gas Heat Mode Fan O󰀨 Delay period,
the indoor fan, EAC, & HUM relays are de-energized.
START-UP PROCEDURE AND ADJUSTMENT
NOTE: This furnace is equipped with a control board
that is capable of monitoring for R-32 refrigerant leaks
in the indoor refrigeration unit. Please verify that the
R-32 sensor wire is plugged in to the furnace control
board before startup, if applicable. If furnace is not
paired with an R-32 Refrigeration system, the default
settings in the furnace control board will need to be
changed. Please see the R-32 section for additional
information.
Furnace must have a 120 VAC power supply properly
connected and grounded. Proper polarity must be
maintained for correct operation. An interlock switch
prevents furnace oper ation if the blower door is not in
place. Keep the blower access door in place except for
inspection and maintenance.
The integrated furnace control board is equipped with two
push-button switches used to access & navigate menus for
furnace setup & settings. The 3 x Seven Segment Displays
on the control board will show the current selection.
Upon power-up of the control board, all Seven segments
will be illuminated displaying “8 8 8”. After power-up the
displays will show “I d L”, idle, or stand-by mode. The
control is now ready to receive demands from the room
thermostat. Refer to Status Menu in this manual for
interpretation of items displayed in the status menu.
QUICK START
Initial set up of outdoor systems are required to be
congured through the control board. Navigate to OdS
menu using the push buttons to properly congure the
outdoor system. Selections for AC1, AC2, HP1, HP2 must
be made to enable specic fan speeds and thermostat
signals to function.
NOTE: Equipment type (Single-stage cooling, Two-
stage cooling, Single-stage heat pump, Two-stage heat
pump) MUST be setup through the OdS menu by the
installer for proper system operation.
USING PUSH-BUTTONS
All user settings may be accessed by three push-buttons
on the control board. The buttons are identied as “LEFT”
“CENTER” & “RIGHT”. To enter the main menu, press
“LEFT” or “RIGHT” button. Each time LEFT or RIGHT
button is pressed the display will show the next available
item in the main menu.
While in the main menu, press the “CENTER” button to
scroll through available options corresponding to the main
menu item displayed. In the option menu, the default
option will be displayed rst. If the default option has been
changed to another option, the current option selection will
be displayed rst.
The option menu will display both adjustable &
nonadjustable options. When an adjustable option is
displayed, the display will ash continuously until a switch
is pressed. If a non-adjustable option is displayed (such as
Code Release Number) the display will not ash.
While navigating the option menus, press the CENTER
button to select the displayed option. The displayed
selection will stop ashing indicating the selection was
made. Press the CENTER button again to nalize the
selection and return to the corresponding main menu.
In the option menu, after the last option has been
displayed, the display will revert to the corresponding main
menu & display the default (or selected) option. If buttons
are not pressed for 30 seconds the display will revert to the
status menu.
background
SYSTEM OPERATION
11
Control Board Main Menu
SEGT
#1
SEGT
#2
SEGT
#3
SEGT
#1
SEGT
#2
SEGT
#3
Active Alaram menu
E r r E
x x Err
( xx: code numbers ) - See chart
for Alarm Code definition
Last 10 Faults
F 1 0 E
x x F10
( xx: code numbers ) - See chart
for Alarm Code definition
Code Release Number
C r
Cr
Code number
Shared data Revision
S r
Sr
Shared Data Number
Reset to Factory Default
r F d
rFd
PCB will revert back to factory
default if selected yes
Outdoor Setting Menu 0 d S OdS
OdS option is used to select
outdoor unit type ( 1 or 2 stage )
Blower Speed for
Continuous Fan Mode
F S d
FSd
( xx: Blower Speed Number F01,
F02.. )
Single-Stage Cooling Fan
Speed
A C
AC
( xx: Blower Speed Number F01,
F02.. )
Low-stage Cooling Blower
Speed, Two-Stage
A C 1
AC1
( xx: Blower Speed Number F01,
F02.. )
High-stage Cooling Fan
Speed, Two-Stage
A C 2
AC2
( xx: Blower Speed Number F01,
F02.. )
Cool On Delay
C n d
Cnd
Default set at 7 Secs,
Adjustments can be made in 7
Secs increments from 0 to 35
Secs
Cool Off Delay
C f d
Cfd
Default set at 65 Secs,
Adjustments can be made in 5
Secs increments from 0 to 120
Secs
Gas Heat fan Speed
g A F
gAF
( xx: Blower Speed Number F01,
F02.. )
Gas Heat On Delay
g n d
gnd
Default set at 30 Secs,
Adjustments can be made in 5
Secs increments from 5 to 30
Secs
Gas heat Off Delay
g F d
gFd
Default set at 90 Secs,
Adjustments can be made in 30
Secs increments from 30 to 180
Secs
Single-Stage HP Heat Fan
Speed
H P
HP
( xx: Blower Speed Number F01,
F02.. )
Low-stage HP Heat Fan
Speed, Two-Stage
H P 1
HP1
( xx: Blower Speed Number F01,
F02.. )
High-stage HP Heat Fan
Speed, Two-Stage
H P 2
HP2
( xx: Blower Speed Number F01,
F02.. )
HP Heat off Delay
H F d
HFd
Default set at 60 Secs,
Adjustments can be made in 5
Secs increments from 30 to 120
Secs
HP Heat on Delay
H n d
Hnd
Default set at 5 Secs,
Adjustments can be made in 5
Secs increments from 5 to 30
Secs
Automatic Heat Staging -
For Two Stage Control
A H S
AHS
Refer to Section " CHANGING
HEATING MODE SETTING"
A2L Function Verification A 2 u A2u
A2L Function Enabled A 2 E A2E
no, 10, 20,
30, 60, AUt
Refer to the R-32
Section
Refer to the R-32
Section
Fxx
Del ay, Seconds
Del ay, Seconds
Fxx
Fxx
Fxx
Del ay, Seconds
Del ay, Seconds
Fxx
Fxx
Fxx
Del ay, Seconds
Del ay, Seconds
Menu Description
None
yes, no
AC1 / AC2 /
HP1 / HP2 /
OFF
Fxx
Additional Info
Main Menu Option Menu
Displ
ay
Text
None
Control Board Status Menu
S EGT
#1
S EGT
#2
S EGT
#3
All segme nts illuminated =
control powering up
8 8 8
Control in Idle stage
I d l
Constant Fan
F A n
Single-Stage Cooling Fan
Speed
A C
Low Stage Cooling
1 A C
High Stage Cooling
2 A C
Gas Heat
g H
Low Stage HP
1 H P
High Stage HP
2 H P
Defrost
d F t
Main Menu
Description of System
Status
FURNACE OPERATION
Purge gas lines of air prior to start-up. Do not purge lines
into an enclosed burner compartment. Follow NFPA 54,
National Fuel Gas Code 8.1 for proper purging methods.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector, or
other approved method.
NOTE: An interlock switch prevents furnace oper ation
if the blower door is not in place. Keep the blower
access doors in place except for inspection and
maintenance.
R-32 FUNCTION
This furnace is equipped with a control board that is
capable of shutting o󰀨 the gas heat and turning on the
blower fan in case of an R-32 refrigerant leak in the indoor
evaporator coil. If the cooling unit that is paired with this
furnace does not utilize R-32 as the refrigerant, the R-32
functionalities in the furnace control board will need to be
turned o󰀨 for the furnace to run properly.
R-32 function on the control board is ON by default. The
R-32 function can be disabled through the furnace control
by entering the A2L Function Enabled menu and selecting
“no”. If A2L function is disabled, the furnace control will
ignore all A2L functions. If A2L function is enabled, the
control will monitor the R-32 sensor information.
To enter the A2L Function Enabled menu, press the left
or right button until LED displays “A2E”. Press the center
button and the LED will display the selected option (yes or
no). Press the left or right button to select one of the two
options and press the center button to conrm the option.
R-32 SENSOR WIRE ROUTING
NOTE: Wiring routing must not interfere
with circulator blower operation, lter removal
or routine maintenance. Wire should not be routed
near hot surfaces and should be protected from sharp
edges.
The R-32 Sensor wire coming from the indoor evaporator
coil will need to be routed into the furnace and connected
to the connection point on the furnace control board. This
wire should be routed alongside the thermostat wires
through the low voltage openings in the left or right side of
the furnace blower compartment. Please see the electrical
section for the location of the R-32 Sensor connection on
the control board.
background
SYSTEM OPERATION
12
FURNACE START-UP
During furnace start up, the furnace control will identify the
connected R-32 sensor and will start monitoring the sensor
communication. A green LED located next to the sensor
connection will indicate if there is communication between
the furnace control and the R-32 sensor. The LED will be
ON during the duration of the startup and then will either
start blinking or turn OFF. The blinking LED signies that
communication with the R-32 sensor is present. The LED
OFF signies that there is no signal with the sensor.
If there are no alarms or faults, the furnace will go into
regular run mode after a warm up period. The furnace
control monitors the R-32 sensor once per second.
R-32 REFRIGERANT LEAK
If the R-32 sensor on the indoor evaporator coil detects a
specied concentration of R-32 refrigerant, the furnace will
enter Mitigation Mode to dilute the refrigerant concentrations
in case of a leak. In Mitigation Mode, the furnace will do the
following:
1. Display the A2L Refrigerant Leakage error code (EAL)
2. Shut down the gas operation
3. Energize the optional ventilation and alarm outputs.
4. Run the fan at max CFM airow
Once the R-32 sensor stops detecting a leak, the fan will
continue to run for 5 minutes. After the 5 minutes, if there
are no other alarms or faults, the control will de-energize the
optional ventilation and alarm outputs and then go back to
the original operating mode per the thermostat.
A2L VERIFICATION
The A2L Function Verication menu allows the installer to
verify if the R-32 function operates properly. This menu
simulates the refrigerant leak process and is only able to
be used when there are no active alarms or faults. To verify
the R-32 functions, enter the A2L Function Verication menu
and select “YES”. To enter the A2L Function Verication
menu, press the left or right button until LED displays “A2u”.
Press the center button and the LED will display the selected
option (yes or no). Press the left or right button to select one
of the two options and press the center button to conrm
the option. Once “YES” is selected, the furnace will do the
following:
1. Display the A2L Refrigerant Leakage code (EAL)
2. Shut down the gas operation
3. Energize the optional ventilation and alarm outputs.
4. Run the fan at max CFM airow
The control will exit the verication function if:
1. The 5 minute timeout expires or
2. An alarm or fault is detected or
3. The user turns OFF the A2L Function Verication.
FURNACE START-UP
1. Close the manual gas shuto󰀨 valve external to the
furnace.
2. Turn o󰀨 the electrical power to the furnace.
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition device
which automatically lights the burner. Do not try to light
the burner by hand.
5. White-Rodgers valves: Push the switch to the OFF
position.
6. Wait ve minutes then smell for gas. Be sure to check
near the oor, as some types of gas are heavier than air.
7. If gas can be smelled following the ve minute waiting
peri od in Step 6, immediately follow the instructions on
Page 3 of this manual. If you do not smell gas after ve
minutes:
White-Rodgers valves: Push the switch to the ON
position.
8. Replace the door on the front of the furnace.
9. Open the manual gas valve external to the furnace.
10. Turn on the electrical power supply to the furnace.
11. Adjust the thermostat to a setting above room
temperature.
12. After the burners are lit, set the room thermostat to the
desired temperature.
NOTE: There will be a delay between thermostat
energizing and burner ring.
FURNACE SHUTDOWN
1. Set the thermostat to lowest setting. The integrated
control will close the gas valve and extinguish ame.
Following a 30 second delay, the induced draft blower
will be de-energized. The circulation blower will shut
down when the time delay expires. Time delay is
selectable on all models.
2. Turn o󰀨 the electrical power supply to the furnace.
3. Remove the burner compartment door.
4. White-Rodgers valve: Push switch to the OFF position.
5. Close manual gas shuto󰀨 valve external to the furnace.
6. Replace the door on the unit.
background
SYSTEM OPERATION
13
CIRCULATOR BLOWER SPEED ADJUSTMENT
WARNING
To avoid personal injury or death due to electrical shock,
turn OFF power to the furnace before changing speed taps.
This furnace is equipped with a multi-speed circulator
blower. This blower provides ease in adjusting blower
speeds. The Specication Sheet applicable to your model
provides an airow table, showing the relationship between
airow (CFM) and external static pressure (E.S.P.), for the
proper selection of heating and cooling speeds.
1. Determine the tonnage of the cooling system installed
with the furnace. If the cooling capacity is in BTU/hr
divide it by 12,000 to convert capacity to tons.
Example: Cooling Capacity of 30,000 BTU/hr.
30,000/12,000 = 2.5 Tons
2. Determine the proper air ow for the cooling system.
Most cooling systems are designed to work with air
volume between 350 and 450 CFM per ton. Most
manufacturers recommend an air ow of about 400
CFM per ton.
Example: 2.5 tons X 400 CFM per ton = 1000 CFM
3. Select the heating speed for your model from the heating
speed chart in the Specication Sheet. The selected
speed must provide a temperature rise within the rise
range listed with the particular model.
CONTINUOUS FAN MODE SPEED SELECTION
To change the main blower speed in circulation mode, see
the following steps:
1. Press left or right button until LED displays “FSd”. Press
center button and LED will display the currently selected
speed number as Fxx (xx: Blower speed number from
1 to 9).
2. The control shall cycle through available fan speeds
every time the left or right button is pressed. All 9 speeds
are available for circulation.
3. When the center button is pressed, the current displayed
speed shall stop ashing. Press the center button again
to select the option and the control shall immediately
apply that blower setting and return to the corresponding
main menu.
THERMOSTAT CALL
AVAILABLE SPEEDS
(FSd menu)
G
F01
F02
F03
F04
F05
F06
F07
F08
F09
Circulation Speed Table
COOLING MODE SPEED SELECTION
To change the main blower speed in COOLING mode,
follow the following steps:
NOTE: If Heat Pump system is congured in OdS menu
(HP1 or HP2) COOLING thermostat calls will include
“Y1”/Y2” + “O” terminals energized.
1. Press left or right button until LED displays “AC1”
(for single stage COOLING) or “AC2” (for Two stage
COOLING). Press center button and the LED will
display the currently selected speed number as Fxx
(xx: Blower speed number from 1 to 9).
2. The control shall cycle through available fan speeds
every time the left or right button is pressed. All 9
speeds are available for both Single and Two Stage
cooling.
3. When the center button is pressed, the current
displayed speed shall stop ashing. Press the center
button again to select the option and the control shall
immediately apply that blower setting and return to the
corresponding main menu.
THERMOSTAT CALL
(OdS: Terminal)
AVAILABLE SPEEDS
(AC1 menu)
1AC: Y1
1HP: Y1 + O
F01
F02
F03
F04
F05
F06
F07
F08
F09
Single Stage Cooling Speed Table
THERMOSTAT CALL
(OdS: Terminal)
AVAILABLE SPEEDS
(AC2 menu)
2AC: Y1 + Y2
2HP: Y1 + Y2 + O
F01
F02
F03
F04
F05
F06
F07
F08
F09
Two Stage Cooling Speed Table
background
SYSTEM OPERATION
14
GAS HEATING MODE SPEED SELECTION
To change the main blower speed in GAS HEATING mode,
see the following steps:
1. Press left or right button until LED displays “gAF”.
Press center button and LED will display the currently
selected fan speed as Fxx (xx: Blower speed number).
2. The control shall cycle through available speed number
every time the left or right button is pressed.
3. When the center button is pressed, the current
displayed speed shall stop ashing. Press the center
button again to select the option and the control shall
immediately apply that blower setting and return to the
corresponding main menu.
NOTE: Each furnace model contains di󰀨erent allowable
gas heating speeds. Allowable gas heating speeds will
be visible within gAF fan speed menu.
Heat Pump Heating Mode Speed Selection
To change the main blower speed in Heat Pump HEATING
mode, follow the following steps:
1. Press left or right button until LED displays “HP1” (for
single stage HP HEATING) or “HP2” (for Two stage
HP HEATING). Press center button and the LED will
display the currently selected speed number as Fxx
(xx: Blower speed number from 1 to 9).
2. The control shall cycle through available fan speeds
every time the left or right button is pressed. All 9
speeds are available for both Single and Two Stage HP
HEATING.
3. When the center button is pressed, the current
displayed speed shall be selected, and control shall
apply the newly selected speed in next HP HEATING
call.
THERMOSTAT CALL
(OdS: Terminal)
AVAILABLE SPEEDS
(HP1 menu)
1HP: Y1
F01
F02
F03
F04
F05
F06
F07
F08
F09
Single Stage HP Heating Speed Table
THERMOSTAT CALL
(OdS: Terminal)
AVAILABLE SPEEDS
(HP2 menu)
2HP: Y1 + Y2
F01
F02
F03
F04
F05
F06
F07
F08
F09
Two Stage HP Heating Speed Table
CIRCULATOR BLOWER FAN TIMING ADJUSTMENT
NOTE: Items in this section refer to the air circulator
blower fan, NOT to the induced draft blower.
The induced draft blower timing sequence is not
adjustable.
The integrated control module on all models provides
selectable fan on/o󰀨 delay adjustments.
ON/OFF FAN DELAY SELECTION
To change the fan on or o󰀨 delay for COOLING, HP
HEATING & GAS HEATING modes, see the following
steps:
1. Press left or right button until LED displays the desired
on/o󰀨 setting (See MAIN MENU section for selectable
blower on/o󰀨 delay options). Press center button
and LED will display the selected on/o󰀨 delay time in
seconds.
2. The control shall cycle through available on/o󰀨 delay
times every time the left or right button is pressed.
3. When the center button is pressed, the current
displayed on/o󰀨 delay shall stop ashing. Press the
center button again to select the option and the control
shall immediately apply that delay setting and return to
the corresponding main menu.
SAFETY CIRCUIT DESCRIPTION
GENERAL
WARNING
To avoid personal injury or death, do not remove
any internal compartment covers or attempt any
adjustment. Electrical components are contained in both
compartments. Contact a qualified service agent at once if
an abnormal operation should develop.
WARNING
Do not bypass safety devices.
background
SYSTEM OPERATION
15
A number of safety circuits are employed to ensure safe
and proper furnace operation. These circuits serve to
control any potential safety hazards and serve as inputs
in the monitoring and diagnosis of abnormal function.
These circuits are continuously monitored during furnace
operation by the integrated control module.
INTEGRATED CONTROL MODULE (IFC)
The integrated control module is an electronic device
which controls all furnace operations. Responding to
the thermostat, the module initiates and controls normal
furnace operation, and monitors and addresses all safety
circuits. If a potential safety concern is detected, the
module will take the necessary precautions and provide
diagnostic information through an LED.
PRIMARY LIMIT
The primary limit control is located on the partition panel
and monitors heat exchanger compartment temperatures.
It is a normally closed (electrically), automatic reset,
temperature activated sensor. The limit guards against the
overheating resulting from insu󰀩cient air passing over the
heat exchanger.
AIR BAFFLE LIMIT
The outlet air ba󰀪e limit is located on top of the heat
exchanger and monitors heat exchanger compartment
temperatures. It is a normally closed (electrically),
automatic reset, temperature activated sensor. The limit
guards against overheating resulting from insu󰀩cient air
passing over the heat exchanger.
AUXILIARY LIMIT
The auxiliary limit control is located either on or near
the circulator blower and monitors heat exchanger
compartment temperatures. The control is a normally
closed (electrically), automatic reset, temperature activated
sensor. It guards against overheating resulting from
insu󰀩cient air passing over the heat exchanger. The
auxiliary limit control is suitable for both horizontal right and
horizontal left installations. Regardless of airow direction,
it does not need to be relocated.
PRESSURE SWITCHES
The pressure switches are normally-open (closed during
operation) negative air pressure-activated switches. They
monitor the airow (combustion air and ue products)
through the heat exchanger via pressure taps located on
the induced draft blower and the coil front cover. These
switches guard against insu󰀩cient airow (combustion
air and ue products) through the heat exchanger and/or
blocked condensate drain conditions.
BURNER TEMPERATURE SWITCH
The burner temperature switch is mounted on the burner
assembly to monitor the burner box temperature. It is
normally closed (electrically), auto-reset sensor. This switch
guards against the burner ames not being properly drawn
into the heat exchanger.
PRESSURE SENSOR
The pressure sensor is mounted near induced draft blower.
Its function is to regulate the induced draft blower’s speed
in order to maintain proper air-fuel ratio for clean and
reliable combustion. The pressure sensor also guards
against insu󰀩cient airow (combustion air and ue
products) through the heat exchanger.
FLAME SENSOR
The ame sensor is a probe mounted near the burner
assembly which uses the principle of ame rectication to
determine the presence or absence of ame.
TROUBLESHOOTING
DIAGNOSTIC CHART
Refer to the troubleshooting chart for assistance in
determining the source of unit operational problems. The
3 digit diagnostic display provides alarm codes to assist in
troubleshooting the unit.
FAULT CODE RETRIEVAL
The ignition control is equipped with push buttons that can
be used to see the last ten faults detected by the control.
Press the left or right button to navigate to F10. Press the
center button to select this option.
CLEAR FAULT MEMORY
To clear all alarm codes, navigate to the last ten faults menu,
F10, and hold the option button down for 5 seconds.
RESETTING FROM LOCKOUT
Furnace lockout results when a furnace is unable to
achieve ignition after three attempts. It is characterized
by a non-functioning furnace and a fault code will be
displayed. If the furnace is in “lockout”, it will (or can be)
reset in any of the following ways.
1. Automatic reset. The integrated control module will
automatically reset itself and attempt to resume normal
operations following a one hour lockout period.
2. Manual power interruption. Interrupt 120 volt power to
the furnace.
NOTE: If the condition which originally caused the
lockout still exists, the control will return to lockout.
Refer to the Diagnostic Chart for aid in determining the
cause.
background
SCHEDULED MAINTENANCE
16
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
If you must handle the ignitor, handler with care. Touching
the ignitor body with bare fingers, rough handling, or
vibration could result in early ignitor failure. Only a
qualified servicer should ever handle the ignitor.
CAUTION
ANNUAL INSPECTION
The furnace should be inspected by a qualied installer, or
service agency at least once per year. This check should
be performed at the beginning of the heating season.
This will ensure that all furnace components are in proper
working order and that the heating system functions
appropriately. Pay particular attention to the following
items. Repair or service as necessary.
• Flue pipe system. Check for blockage and/or leakage.
Check the outside termination and the connections at
and internal to the furnace.
• Heat exchanger. Check for corrosion and/or buildup
within the heat exchanger passageways.
• Burners. Check for proper ignition and ame sense.
• Wiring. Verify that electrical connections are tight and
free from corrosion.
• Filters.
AIR FILTER
Never operate furnace without a filter installed as dust
and lint will build up on internal parts resulting in loss of
efficiency, equipment damage, and possible fire.
WARNING
Filters must be used with this furnace. Filters do not ship
with these furnaces but must be provided by the installer
for proper furnace operation.
Dirty lters are the most common cause of inadequate
heating or cooling performance.
MAINTENANCE
Improper lter maintenance is the most common cause of
inadequate heating or cooling performance. Filters should
be cleaned (permanent) or replaced (disposable) every two
months or as required.
HORIZONTAL UNIT FILTER REMOVAL
Filters in horizontal installations are located in the central
return register.
INDUCED DRAFT AND CIRCULATION BLOWERS
The bearings in the induced draft blower and circulator
blower motors are permanently lubricated by the
manufacturer. No further lubrication is required. Check
motor windings for accumulation of dust which may cause
overheating. Clean as necessary.
FLAME SENSOR (QUALIFIED SERVICER ONLY)
Under some conditions, the fuel or air supply can create a
nearly invisible coating on the ame sensor. This coating
acts as an insulator, causing a drop in the ame sensing
signal. If this occurs, a qualied servicer must carefully
clean the ame sensor with steel wool. After cleaning, the
ame sensor output should be as listed on the specication
sheet.
The following is a must for every service technician and
service shop.
1. Dial type thermometers or thermocouple meter
(optional) - to measure dry bulb temperature.
2. Volt-Ohm Meter - to measure amperage and voltage
and to test continuity, capacitors and motor windings.
3. Manometer - to measure static pressure, pressure drop
across coils, lters and draft and to test gas inlet and
manifold pressure.
Other recording type instruments can be essential in
solving abnormal problems, however, in many instances
they may be rented from local sources.
Proper equipment promotes faster, more e󰀩cient service
and accurate repairs resulting in fewer call backs.
HEATING PERFORMANCE TEST
Before attempting to diagnose an operating fault code, run
a Heating Performance Test to determine if the heating
system is performing within 5% of the BTU input found
on the rating plate of the unit being tested. To conduct a
heating performance test, the BTU input to the unit must
be calculated (see Clocking a Gas Meter). Before clocking
a gas meter, contact your local utility to obtain the caloric
value (BTU content) of the natural gas in the area.
It is also important to conrm the airow (CFM) is within
the temperature rise range (see Airow Data in spec sheet)
and external static pressure range (approximately 0.5”
water column). How-to instructions can be found in the
service manual under Checking External Static Pressure
and Checking Temperature Rise.
background
SCHEDULED MAINTENANCE
17
CLOCKING A GAS METER
1. Turn o󰀨 all gas appliances in the home.
2. Turn on the furnace. Ensure the furnace is operating at a 100% ring rate on 2 stage and modulating furnace product.
3. Once heating cycle is at a steady state (typically 15 minutes of operation), use a stopwatch to time how long it takes
the smallest unit of measure dial on the gas meter to make a full revolution. In Table 1, one cubic foot is selected. The
smallest unit of measure will vary depending on the gas meter.
CUBIC
FEET
1
1
One
In this example
we are using the
one cubic foot
dial on the gas
meter
TABLE 1
4. Using Table 2 below, nd the number of seconds it took for the dial to make a full revolution. To the right of that
number of seconds and below the Size of Test Dial (selected in step 3 and shown in Table 1) will be the Cubic Feet
per Hour (CFH).
1/4
cu/ft
1/2
cu/ft
1
cu/ft
2
cu/ft
5
cu/ft
1/4
cu/ft
1/2
cu/ft
1
cu/ft
2
cu/ft
5
cu/ft
10 90 180 360 720 1800 36 25 50 100 200 500
11 82 164 327 655 1636 37 -- -- 97 195 486
12 75 150 300 600 1500 38 23 47 95 189 474
13 69 138 277 555 1385 39 -- -- 92 185 462
14 64 129 257 514 1286 40 22 45 90 180 450
15 60 120 240 480 1200 41 -- -- -- 176 439
16 56 113 225 450 1125 42 21 43 86 172 429
17 53 106 212 424 1059 43 -- -- -- 167 419
18 50 100 200 400 1000 44 -- 41 82 164 409
19 47 95 189 379 947 45 20 40 80 160 400
20 45 90 180 360 900 46 -- -- 78 157 391
21 43 86 171 343 857 47 19 38 76 153 383
22 41 82 164 327 818 48 -- -- 75 150 375
23 39 78 157 313 783 49 -- -- -- 147 367
24 37 75 150 300 750 50 18 36 72 144 360
25 36 72 144 288 720 51 -- -- -- 141 355
26 34 69 138 277 692 52 -- -- 69 138 346
27 33 67 133 265 667 53 17 34 -- 136 340
28 32 64 129 257 643 54 -- -- 67 133 333
29 31 62 124 248 621 55 -- -- -- 131 327
30 30 60 120 240 600 56 16 32 64 129 321
31 -- -- 116 232 581 57 -- -- -- 126 316
32 28 56 113 225 563 58 -- 31 62 124 310
33 -- -- 109 218 545 59 -- -- -- 122 305
34 26 53 106 212 529 60 15 30 60 120 300
35 -- -- 103 206 514
GAS RATE -- CUBIC FEET PER HOUR
Seconds fo
r
One
Revolution
Size of Test Dial
Seconds fo
r
One
Revolution
Size of Test Dial
Locate 40 seconds for one
revolu�on in the chart below
Then locate the 1 cu � dial column and select the
corresponding CFH from the 40 seconds for one revolu�on row
TABLE 2
background
SCHEDULED MAINTENANCE
18
5. Use this formula to verify the Cubic Feet per Hour (CFH) input determined in step 4 is correct:
(3600 x Gas Meter Dial Size) / Time (seconds) = Cubic Feet per Hour (CFH)
3600 is used as there are 60 seconds in
a minute and 60 minutes in an hour.
60x60=3600
6. Check with your local utility for actual BTU content (caloric value) of natural gas in the area (the average is 1025
BTU’s).
7. Use this formula to calculate the BTU/HR input (See BTU/HR Calculation Example):
Cubic Feet per Hour (CFH) x BTU content of your natural gas = BTU/HR input
8. Should the gure you calculated not fall within ve (5) percent of the nameplate rating of the unit, adjust the gas
valve pressure regulator. To adjust the pressure regulator on the gas valve, turn downward (clockwise) to increase
pressure and input, and upward (counterclockwise) to decrease pressure and input. A properly operating unit must
have the BTU per hour input and CFM of air, within the limits shown to prevent short cycling of the equipment. As the
external static pressure goes up, the temperature rise will also increase. Consult the proper tables for temperature
rise limitation.
BTU/HR Calculation Example:
The unit being tested takes 40 seconds for the 1 cubic foot dial to make one complete revolution. Using the chart, this
translates to 90 cubic feet per hour. Based upon the assumption that one cubic foot of natural gas has 1,025 BTU’s
(Check with your local utility for actual BTU content), the calculated input is 92,250 BTU’s per hour.
Furnace Nameplate Input in this example: 90,000 BTU/HR
Calculated Gas Input in this example: 92,250 BTU/HR
This example is within the 5% tolerance input and does not need adjustment.
Always connect a manometer to the outlet tap at the gas
valve before adjusting the pressure regulator. In no case
should the final manifold pressure vary more than plus or
minus .2 inches water column from 3 inches water column
for natural gas.
CAUTION
A properly operating unit must have the BTU per hour input and CFM of air, within the limits shown to prevent short cycling
of the equipment. As the external static pressure goes up, the temperature rise will also increase. Consult the proper
tables for temperature rise limitation.
background
SERVICING
19
GAS VALVE
BURNER ASSEMBLY
PRESSURE TRANSDUCER
INTEGRATED
CONTROL BOARD
CONTROL TRANSFORMER
PRESSURE SWITCHES
VENT PIPE CONNECTION
COMBUSTION AIR CONNECTION
DRAFT INDUCER
Component I.D.
background
SERVICING
20
FLAME SENSOR
BURNER LIMIT
AUXILIARY LIMIT
AUXILIARY LIMIT
background
SERVICING
21
OUTLET AIR
BAFFLE LIMIT
PRIMARY LIMIT
background
SERVICING
22
As more and more electronics are introduced to the Heating
Trade, Polarization of incoming power and phasing of primary
to secondary voltage on transformers becomes more import-
ant.
Polarization has been apparent in the Appliance industry since
the introduction of the three prong plug, however, the Heating
Industry does not use a plug for incoming power, but is hard
wired.
Some of the electronic boards being used today, with ame
rectication, will not function properly and/or at all without
polarization of incoming power. Some also require phasing
between the primary and secondary sides of step-down trans-
formers.
We recommend that these two items be checked during nor-
mal installation and/or service calls. See as follows:
CHECKING FOR PHASING - PRIMARY TO SECONDARY OF UNMARKED TRANSFORMERS*
If meter reads approximately 96 volts - the primary to secondary are in phase - if reads approximately 144 volts out of
phase - reverse low voltage wires.
*NOTE: For ame rectication the common side of the secondary voltage (24 V) is cabinet grounded. If you were to bench
test a transformer the primary neutral and secondary common must be connected together for testing purposes.
These then should be wired to the furnace accordingly.
Some transformers will display phasing symbols as shown
in the illustration to the left to assist in determining proper
transformer phasing.
Checking for polarization and phasing should become a
habit in servicing. Lets start now.
background
SERVICING
23
CHECKING VOLTAGE
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
1. Remove the burner door to gain entry to the Junction
Box.
2. Remove cover from the Junction Box and gain access
to incoming power lines.
With Power ON:
Line voltage now present.
WARNING
3. Using a voltmeter, measure the voltage across the hot
and neutral connections.
NOTE: To energize the furnace, the Door Interlock Switch
must be engaged at this point.
4. No reading - indicates open wiring, open fuse, no
power, or faulty Door Interlock Switch from unit to fused
disconnect service. Repair as needed.
5. With ample voltage at line voltage connectors, energize
the furnace blower motor by jumpering terminals R to
G on the integrated ignition control.
6. With the blower motor in operation, the voltage should
be 115 volts ± 10 percent.
7. If the reading falls below the minimum voltage, check
the line wire size. Long runs of undersized wire can
cause low voltage. If wire size is adequate, notify the
local power company of the condition.
8. After completing check and/or repair, replace Junction
Box cover and reinstall the service panel doors.
9. Turn on electrical power and verify proper unit
operation.
CHECKING WIRING
Disconnect ALL power before servicing.
WARNING
1. Check wiring visually for signs of overheating,
damaged insulation and loose connections.
2. Use an ohmmeter to check continuity of any suspected
open wires.
3. If any wires must be replaced, replace with AWM,
105°C. 2/64 inch thick insulation of the same gauge or
its equivalent.
THERMOSTAT AND WIRING
Disconnect ALL power before servicing.
WARNING
1. Remove the blower compartment door to gain access
to the thermostat low voltage wires located at the
furnace integrated control module terminals.
2. Remove the thermostat low voltage wires at the
furnace control panel terminal board.
3. Jumper terminals R to W on the integrated ignition
control.
With Power On (and Door Interlock Switch closed):
Line voltage now present.
WARNING
4. Induced Draft Motor must run and pull in pressure
switch.
5. If the hot surface ignitor heats and at the end of the
ignitor warm-up period the gas valve opens and the
burners ignite, the trouble is in the thermostat or wiring.
6. With power o󰀨, check the continuity of the thermostat
and wiring. Repair or replace as necessary.
If checking the furnace in the air conditioning mode,
proceed as follows.
7. With power o󰀨, Jumper terminals R to Y to G.
8. Turn on the power.
9. If the furnace blower motor starts and the condensing
unit runs, then the trouble is in the thermostat or wiring.
Repair or replace as necessary.
10. After completing check and/or repair of wiring and
check and/or replacement of thermostat, reinstall
blower compartment door.
11. Turn on electrical power and verify proper unit
operation.
CHECKING TRANSFORMER AND CONTROL
CIRCUIT
A step-down transformer 120 volt primary to 24 volt
secondary, 40 VA (Heating and Cooling Models) supplies
ample capacity of power for either operation.
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
background
SERVICING
24
1. Remove blower compartment door to gain access to
the thermostat low voltage wires located at the furnace
integrated control module.
2. Remove the thermostat low voltage wires at the
furnace integrated control module terminals.
With Power On (and Door Interlock Switch closed):
Line voltage now present.
WARNING
3. Use a voltmeter, check voltage across terminals R and
C. Must read 24 VAC.
4. No voltage indicates faulty transformer, open fuse, bad
wiring, bad splice, or open door interlock switch.
5. Check transformer primary voltage at incoming line
voltage connections, fuse, splices, and blower door
interlock switch.
6. If line voltage is available to the primary side of
transformer and not at secondary side, the transformer
is inoperative. Replace.
7. After completing check and/or replacement of
transformer and check and/or repair of control circuit,
reinstall blower compartment door.
8. Turn on electrical power and verify proper unit
operation.
CHECKING AIR CIRCULATOR BLOWER MOTOR
Disconnect ALL power before servicing.
WARNING
1. Remove blower compartment door to gain access
to the circulator blower motor and integrated ignition
control.
2. Check for any obstruction that would keep the fan
wheel / fan motor from turning.
3. The multi-speed ECM motor requires a line voltage
power supply (black connected to CIRC H or Current
Sensor and white connected to neutral on the control
board) as well as a signal on one or two of the speed
taps (T1-T5). The speed tap voltage is 6-17 vDC and
can vary based on the tap or taps that are energized.
The voltage reading from any one of the speed taps is
referenced between the female COM terminal next to
the speed taps on the control board.
CONNECTOR
ID
DESCRIPTION
CONNECTOR VOLTAGE
(REFERENCE)
L
LINE, L1
LINE, L1
G
GROUND
CHASSIS GROUND
N
LINE, L2
LINE, L2
C
SIGNAL COMMON
COMMON
1
TAP 1
6 - 17 VDC
2
TAP 2
6 - 17 VDC
3
TAP 3
6 - 17 VDC
4
TAP 4
6 - 17 VDC
5
TAP 5
6 - 17 VDC
Speed
9-Tap Mode (Energized Tap Signal)
1
2
3
4
5
1
ON
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
3
OFF
x
ON
OFF
OFF
4
OFF
x
x
ON
OFF
5
OFF
x
x
x
ON
6
ON
ON
OFF
OFF
OFF
7
ON
x
ON
OFF
OFF
8
ON
x
x
ON
OFF
9
ON
x
x
x
ON
ON = The tap is energized (6 - 17vDC)
OFF = The tap is not energized
x = The tap can be either ON or OFF
Disconnect ALL power before servicing.
WARNING
CHECKING DUCT STATIC
The maximum and minimum allowable external static
pressures are found in the specication section. These
tables also show the amount of air being delivered at a
given static by a given motor speed. The furnace motor
cannot deliver proper air quantities (CFM) against statics
other than those listed.
Too great of an external static pressure will result in
insu󰀩cient air that can cause excessive temperature rise,
resulting in limit tripping, etc. Whereas not enough static
may result in motor overloading.
background
SERVICING
25
To determine proper air movement, proceed as follows:
1. With clean lters in the furnace, use a manometer to
measure the static pressure of the return duct at the
inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct.
(Positive Pressure)
3. Add the two (2) readings together for total external
static pressure.
EXAMPLE:
Static reading from return duct = -.1” w.c.
Static reading from supply duct = .3” w.c.
Total external static pressure on this system = .4” w.c.
NOTE: Both readings may be taken simultaneously
and read directly on the manometer if so desired. If an
air conditioner coil or Electronic Air Cleaner is used in
conjunction with the furnace, the readings must also
include theses components, as shown in the following
drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the minimum
or maximum allowable statics, check for closed dampers,
registers, undersized and/or oversized poorly laid out duct
work.
CUTAWAY OF DUCTWORK
TO EXPOSE COIL
DIGITAL
MANOMETER
RETURN
AIR
Mode
.
SUPPLY
AIR
Checking Static Pressure
CHECKING TEMPERATURE RISE
The more air (CFM) being delivered through a given
furnace, the less the rise will be; so the less air (CFM)
being delivered, the greater the rise. The temperature
rise should be adjusted in accordance to a given furnace
specications and its external static pressure. An incorrect
temperature rise may result in condensing in or overheating
of the heat exchanger. An airow and temperature rise
table is provided in the blower performance specication
section. Determine and adjust temperature rise as follows:
1. Operate furnace with burners ring for approximately
ten minutes. Check BTU input to furnace - do not
exceed input rating stamped on rating plate. Ensure
all registers are open and all duct dampers are in their
nal (fully or partially open) position.
2. Place thermometers in the return and supply ducts as
close to the furnace as possible. Thermometers must
not be inuenced by radiant heat by being able to “see”
the heat exchanger.
SUPPLY
AIR
RETURN
AIR
Checking Temperature Rise
3. Subtract the return air temperature from the supply
air temperature to determine the air temperature rise.
Allow adequate time for thermometer readings to
stabilize.
4. Adjust temperature rise by adjusting the circulator
blower speed. Increase blower speed to reduce
temperature rise. Decrease blower speed to increase
temperature rise. Refer to Circulator Blower Speed
section in the Product Design section of this manual
for speed changing details. Temperature rise is related
to the BTUH output of the furnace and the amount of
air (CFM) circulated over the heat exchanger. Measure
motor current draw to determine that the motor is not
overloaded during adjustments.
CHECKING PRIMARY LIMIT CONTROL
All use a nonadjustable, automatic reset, bi-metal type limit
control.
Style 1 drawing illustrates the Primary Limit used on the
80% furnaces.
Style 1
background
SERVICING
26
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
1. Remove burner compartment door to gain access to
the primary limit.
2. Remove low voltage wires at limit control terminals.
3. With an ohmmeter, test between these two terminals
as shown in the following drawing. The ohmmeter
should read continuous unless heat exchanger
temperature is above limit control setting. If not as
above, replace the control.
COLOR
IDENTIFYING
TAB
Testing Primary Limit Control
CHECKING AUXILIARY LIMIT CONTROL
BLOWER HOUSING
AUXILIARY LIMIT CONTROL
Auxiliary Limit Control Location
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
RED
RESET
BUTTON
COLOR
IDENTIFYING
Testing Auxiliary Limit Control
To avoid possible fire, only reset the auxiliary limit control
once. If it should open a second time, a qualified servicer
must determine why the auxiliary limit opened before
resetting again.
WARNING
INDUCED DRAFT BLOWER MOTOR
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
background
SERVICING
27
R9S96*U
The induced draft assembly uses a three phase motor to
draw ue gases through the heat exchanger. The inducer
uses ball bearing and is permanently lubricated. This motor
is driven at varying speeds by the VFD (variable frequency
drive) section of the Integrated Furnace Control (IFC).
The IFC take typical single phase power supplied to the
furnace and converts it to a three phase supply to operate
the draft inducer at the desired speed. The windings of
the induced draft motor will have equal resistance +/- 5%.
Normal resistance readings at room temperature will range
from 14-17 ohms. The voltage supplied by the IFC to drive
the induced draft blower will vary from 15-110 volts A/C
between any two windings. This would be read between
any two of the three power wires between the IFC and
the induced draft blower. This voltage to the Induced Draft
Blower (IBD) will vary between furnace models and is
dependent on what percentage of maximum re is being
called for. The power wires are colored red, white, and
black. A green colored ground wire is also present.
CHECKING GAS VALVE (REDUNDANT)
A combination redundant operator type gas valve which
provides all manual and automatic control functions
required for gas red heating equipment is used.
The valve provides control of main burner gas ow,
pressure regulation, and 100 percent safety shut-o󰀨.
Disconnect ALL power before servicing.
WARNING
Single stage gas valves should be tested on the furnace
with 24 VAC connected to the gas valve and manometers
reading supply line and manifold pressures.
Disconnect ALL Gas and Electrical Power Supply.
WARNING
Orices should be treated with care in order to prevent
damage. They should be removed and installed with a box-
end wrench in order to prevent distortion. In no instance
should an orice be peened over and re-drilled. This will
change the angle or deection of the vacuum e󰀨ect or
entraining of primary air, which will make it di󰀩cult to adjust
the ame properly. This same problem can occur if an
orice spud of a di󰀨erent length is substituted.
Disconnect ALL Gas and Electrical Power Supply.
WARNING
CHECKING GAS PRESSURE
GAS SUPPLY PRESSURE MEASUREMENT
To prevent unreliable operation or equipment damage, the
inlet gas supply pressure must be as specified on the unit
rating plate with all other household gas fired appliances
operating.
CAUTION
Gas inlet and manifold pressures should be checked and
adjusted in accordance to the type of fuel being consumed.
The line pressure supplied to the gas valve must be within
the range specied below. The supply pressure can be
measured at the gas valve inlet pressure tap or at a hose
tting installed in the gas piping drip leg. The supply
pressure must be measured with the burners operating.
To measure the gas supply pressure, use the following
procedure.
Disconnect electrical power and shut off gas supply.
WARNING
1. After turning o󰀨 gas to furnace at the manual gas
shuto󰀨 valve external to the furnace, remove burner
compartment door to gain access to the gas valve.
2. Connect a calibrated manometer (or appropriate gas
pressure gauge) at either the gas valve inlet pressure
tap or the gas piping drip leg as shown in the following
gures. Refer to Measuring Gas Pressure: Single
Stage Valves gure for single stage valve inlet pressure
tap connections.
NOTE: At either location, a hose tting must be
installed prior to making the hose connection.
NOTE: Use adapter kit #0151K00000S to measure gas
pressure on White-Rodgers 36J22 gas valves.
background
SERVICING
28
Mode
10.0
Measuring Inlet Gas Pressure
(Alternate Method)
3. Turn ON the gas and electrical power supply and
operate the furnace and all other gas consuming
appliances on the same gas supply line.
4. Measure furnace gas supply pressure with burners
ring. Supply pressure must be within the range
specied in the following table.
INLET GAS SUPPLY PRESSURE
Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c.
If supply pressure di󰀨ers from above, make necessary
adjustments to pressure regulator, gas piping size, etc.,
and/or consult with local gas utility.
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
5. Disconnect manometer after turning o󰀨 gas at manual
shuto󰀨 valve. Reinstall plug before turning on gas to
furnace.
6. Turn OFF any unnecessary gas appliances started in
step 3.
7. Turn on gas to furnace and check for leaks. If leaks are
found, repair and then reinstall burner compartment
door.
8. Turn on electrical power and verify proper unit
operation.
GAS MANIFOLD PRESSURE MEASUREMENT AND
ADJUSTMENT
To prevent unreliable operation or equipment damage,
the gas manifold pressure must be as specified on the unit
rating plate. Only minor adjustments should be made by
adjusting the gas valve pressure regulator.
CAUTION
NOTE: Use adapter kit #0151K00000S to measure gas
pressure on White-Rodgers 36J22 gas valves.
Only small variations in gas pressure should be made by
adjusting the gas valve pressure regulator. The manifold
pressure must be measured with the burners operating.
To measure and adjust the manifold pressure, use the
following procedure.
HIGH VOLTAGE
Disconnect ALL electrical power and shut off gas supply
before servicing or installing.
WARNING
1. After turning o󰀨 gas to furnace at the manual gas
shuto󰀨 valve external to the furnace, remove burner
compartment door to gain access to the gas valve.
2. Connect a calibrated manometer (or appropriate gas
pressure gauge) at the gas valve outlet pressure
tap. Refer to Measuring Gas Pressure: Single Stage
Valves gure for single stage valve outlet pressure tap
connections.
Line voltage now present.
WARNING
3. Turn ON the gas and electrical power supply and
operate the furnace.
4. Measure gas manifold pressure with burners ring.
Adjust manifold pressure using the table below.
Manifold Gas Pressure
Natural Gas 2.8 -3.2" w.c.
The nal manifold pressure must not vary from the above
specied pressures. Any necessary major changes in
gas ow rate should be made by changing the size of the
burner orice.
background
SERVICING
29
5. White-Rodgers 36G22 Valves:
a. Back outlet pressure test screw (inlet/outlet
pressure boss) out one turn (counterclockwise, not
more than one turn).
b. Attach a hose and manometer to the outlet
pressure boss.
c. Turn ON the gas supply.
d. Turn on power and close thermostat “R” and “W”
contacts to provide a call for low stage heat.
e. Measure the gas manifold pressure with burners
ring. Adjust manifold pressure using the Manifold
Gas Pressure table shown below.
f. Remove regulator cover screw from the outlet
pressure regulator adjust tower and turn screw
clockwise to increase pressure or counterclockwise
to decrease pressure. Replace regulator cover
screw.
g. Turn o󰀨 all electrical power and gas supply to the
system.
h. Remove the manometer hose from the hose barb
tting or outlet pressure boss.
i. Turn outlet pressure test screw in to seal pressure
port (clockwise, 7 in-lb minimum).
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
6. Turn on gas to furnace and check for leaks. If leaks are
found, repair and then reinstall burner compartment
door.
7. Turn on electrical power and verify proper unit
operation.
Pressure Regulator
Adjustment
(Under Cap Screw)
Gas Valve
On/Off
Selector
Switch
INLET
OUTLET
Inlet Pressure
Tap
Outlet Pressure
Tap
HIGH VOLTAGE
Disconnect ALL electrical power and shut off gas supply
before servicing or installing.
WARNING
Disconnect ALL power before servicing.
WARNING
CHECKING HOT SURFACE IGNITER
120V Silicon Nitride Igniter - ULN furnaces use a 120V
silicone nitride igniter, part #0130F00717. The normal
operating temperature is approximately 2156°F - 2678°F.
At room temperature the igniter ohm reading should be
from 20-100 ohms.
Line voltage now present.
WARNING
CHECKING PRESSURE TRANSDUCER (96% ULN)
The 96% ULN products utilize a pressure transducer (in
lieu of a pressure switch). The pressure transducer signals
the control board to modulate the heating cycle during a
call for heat by regulating the induced draft motor speed.
By regulating the speed of the induced draft motor, proper
air-fuel ratios are maintained.
Sensing range specication:0.0-4.0 inches W.C.
Voltage specications:
• Steady State: 5.0 vDC from red to green wire
(transducer wiring harness input).
• With Inducer o󰀨: 0.25 vDC from black to green wire
(transducer wiring harness output).
• During operation: Output range equals 0.25 - 4.0 vDC.
Potential errors:
1. Control board does not receive 0.25 vDC for inducer
motor with motor o󰀨.
a. Will result in E1C error code on the control board.
2. Control board does not receive the required voltage
change (0.25 - 4.0 vDC) during inducer motor
operation.
a. Will result in E1d error code on the control board.
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
background
SYSTEM OPERATION
30
CHECKING FOR DELAYED IGNITION
Delayed ignition is a delay in lighting a combustible mixture
of gas and air which has accumulated in the combustion
chamber.
Furnace design makes this extremely unlikely unless safety
controls have been by-passed or tampered with. Never by-
pass or alter furnace controls.
If delayed ignition should occur, the following should be
checked:
1. Improper gas pressure - adjust to proper pressure (See
CHECKING GAS PRESSURE).
CHECKING INTEGRATED IGNITION CONTROL
BOARDS
NOTE: Failure to earth ground the furnace, reversing
the neutral and hot wire connection to the line
(polarity), or a high resistance connection in the
neutral line may cause the control to lockout due to
failure to sense ame.
To avoid the risk of electrical shock, wiring to the unit
must be properly polarized and grounded. Disconnect
power before performing service listed below.
WARNING
The ground wire must run from the furnace all the way back
to the electrical panel. Proper grounding can be conrmed
by disconnecting the electrical power and measuring
resistance between the neutral (white) connection and the
burner closest to the ame sensor. Resistance should be
less than 10 ohms.
The ignition control is a combination electronic and
electromechanical device and is not eld repairable.
Complete unit must be replaced.
Line voltage now present.
WARNING
These tests must be completed within a given time frame
due to the operation of the ignition control.
1. Check for 120 volts from Line 1 (Hot) to Line 2
(Neutral) at the ignition control. No voltage, check
the door switch connections and wire harness for
continuity.
2. Check for 24 volts from W to C terminal on the
ignition control. No voltage. Check transformer, room
thermostat, and wiring.
If you have 24 volts coming o󰀨 the transformer but
receive approximately 13 volts on the terminal board
between (C) and (R), check for blown fuse.
3. Check for 120 volts to the induced draft blower by
measuring voltage between Pin 1 & 3 (black & white
wire on 3 pin connector.)
4. If voltage is present in Steps 1 through 3 and the
induced draft blower is operating, check for 120 volts to
the ignitor during the preheat cycle.
5. After the ignitor warmup time, begin checking for 24
volts to the gas valve. Voltage will be present for seven
seconds only if proof of ame has been established.
NOTE: For R9S96*U models, refer to the Induced Draft
Blower Motor information on page 24 to complete step
3 above.
CHECKING FLAME SENSOR
WARNING
High Voltage!
Disconnect all power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
1. Disconnect the yellow ame sensor wire from the
sensor
2. Connect a micro-amp meter in series with this wire and
the sensor terminal.
3. Place the unit into a heating cycle.
Line voltage now present.
WARNING
4. As soon as ame is established a micro-amp reading
should be evident once proof of ame (micro-amp
reading) is established, the hot surface ignitor will be
de-energized.
5. The Integrated Ignition controls will have 3 to 8 micro-
amps. If the micro-amp reading is less than 1, check
for high resistance wiring connections, sensor to burner
gap, dirty ame sensor, or poor grounding.
6. If absolutely no reading, check for continuity on all
components and if good - replace ignition control
module.
NOTE: Contaminated fuel or combustion air can create
a nearly invisible coating on the ame sensor. This
coating works as an insulator causing a loss in the
ame sense signal. If this situation occurs the ame
sensor must be cleaned with steel wool.
background
Symptom
LED
Status
Fault Description Corrective Actions
Normal operation
I dL
Normal operation None
Furnace fails to
operate
EEE
Internal Faults or IRQ Loss in Control
Board
Replace integrated control board
Locate and correct gas interruption
Check front cover pressure switch operation and verify
proper drainage (hose, wiring, contact operation),
correct if necessary
Replace or realign igniter
Check flame sense signal, clean sensor if coated or
oxidized
Check flue piping for blockage, proper length, elbows,
and termination
Verify proper induced draft blower performance
Pressure switch circuit is closed at start
of heating cycle
Pressure switch contacts sticking
Short in pressure switch circuit wiring
Pressure switch circuit is not closed
Pressure switch hose blocked pinched,
or connected improperly
Inspect flue and/or inlet air piping for blockage, proper
length, elbows, and termination
Check drain system, correct as necessary
Check induced draft blower performance, correct as
necessary
Incorrect pressure switch set point or
malfunctioning switch contacts
Check pressure switch operation, replace as needed
Loose or improperly connected wiring Tighten or correct wiring connection
Primary limit circuit is open
Check filters and ductwork for blockage Clean filters or
remove obstruction
Insufficient conditioned air over the heat
exchanger
Check circulator blower speed and performance
Blocked filters, restrictive ductwork,
improper circulator blower speed, or
failed circulator blower motor
Correct speed or replace blower motor if necessary
Loose or improperly connected wiring in
high limit circuit
Tighten or correct wiring connection
Flame sensed with no call for heat Correct short at flame sensor or in flame sensor wiring
Short to ground in flame sense circuit
Lingering burner flame Slow closing gas
valve
Open fuse Replace fuse
Short in low voltage wiring Locate and correct short in low voltage wiring
No furnace operation
EE5
Induced draft blower
runs continuously with
no furnace operation
EE2
Inspect pressure switch hose, repair/replace if
necessary
Blocked flue and/or inlet air pipe, blocked
drain system or weak induced draft
blower
Circulator blower runs
continuously
No furnace operation
EE3
Induced draft blower
and circulator blower
runs continuously
No furnace operation
EE4
Check for lingering or lazy flame Verify proper operation
of gas valve
Furnace fails to
operate
EE0
Furnace lockout due to an excessive
number of ignition “retries” (3 total)
Failure to establish flame
Loss of flame after establishment
Furnace fails to
operate
EE1
Replace low stage pressure switch
Repair short in wiring
TROUBLESHOOTING
31
background
Symptom
LED
Status
Fault Description Corrective Actions
Flame sense micro amp signal is
minimal
Flame sensor is coated/oxidized
Flame sensor incorrectly positioned in
burner fame
Check inlet air piping for blockage, proper length,
elbows, and termination
Compare current gas pressure to rating plate and adjust
as needed
Polarity of 115 volt AC is reversed Correct polarity, check and correct wiring if necessary
Poor unit ground Verify proper ground, correct if necessary
Furnace fails to
operate
E10
Grounding fault
Poor neutral connection
Verify neutral wire connection to furnace & continuity to
ground source
Check for correct gas pressure
Check for correct burner alignment
Check for and correct burner restriction
Check burner temperature switch, replace if necessary
Furnace fails to
operate
E12
Reduntent relay open alarm Replace integrated control board
Furnace fails to
operate
E13
Reduntent relay stuck closed alarm Replace integrated control board
Gas valve is not energized when it
should be
Check wiring in gas valve circuit
External Gas Valve Error Replace integrated control board
Gas valve is energized when it should
not be
Check wiring in gas valve circuit
Internal gas valve error Replace integrated control board
Auxiliary limit circuit is open
Check filters and ductwork for blockage Clean filters or
remove obstruction
Blocked filters, restrictive ductwork,
improper circulator blower speed, or
failed circulator blower motor
Correct speed or replace blower motor if necessary
Loose or improperly connected wiring in
high limit circuit
Tighten or correct wiring connection
Furnace fails to
operate
EbF
Inducer communication alarm
Check Red, Black, White harness & connections to
inducer & control board
Furnace fails to
operate
E1b
APS reference error
Check Red, Black, White harness & connections to
inducer & control board
Replace pressure sensor
Furnace fails to
operate
E1C
APS null error
Check Red, Black, White harness & connections to
inducer & control board
Check pressure hoses to pressure sensor and pressure
switch
Normal furnace
operation
EE6
Clean flame sensor if coated or oxidized Inspect for
proper flame sensor alignment
Lazy burner flame due to improper gas
pressure or combustion air
Furnace fails to
operate
EEA
Furnace fails to
operate
E11
Furnace fails to
operate
EEb
Furnace fails to
operate
EEC
Circulator blower runs
continuously
No furnace operation
EEd
Burner limit switch circuit is Open
TROUBLESHOOTING
32
background
Symptom
LED
Status
Fault Description Corrective Actions
Furnace fails to
operate
E1d
APS span error
Check Red, Black, White harness & connections to
inducer & control board
Check pressure hoses to pressure sensor and pressure
switch
Furnace fails to
operate
E1E
APS pressure error
Check Red, Black, White harness & connections to
inducer & control board
Replace pressure sensor
Furnace fails to
operate
E1F
APS input error
Check Red, Black, White harness & connections to
inducer & control board
Replace pressure sensor
Twinning feature not
working
EEH
TWIN Error
Check for wiring connections.
Replace integrated control board
Furnace fails to
operate and goes
to hard lockout
EbL
Main blower motor is consuming
very little current after heat on
delay, below an expected value
Check for loose motor wiring connections.
Verify if the blower motor is burnt, replace
blower motor if found burnt
Furnace fails to
operate and goes
to hard lockout
EbU
Main blower motor is consuming
too much current during inducer
pre-purge, above an expected
value.
Verify wiring connections to and from motor
are not loose.
Verify that line voltage wires to the control
and the main blower motor are not reversed
at the control.
Furnace fails to
operate
Ed0
No Shared data Populate shared data set using BTPIM01
Furnace stops heating
and only the fan is
operating
EAF
Furnace has lost communication with the
R-32 sensor and the furnace is in
mitigation mode.
Verify wire connection to R-32 sensor is not loose.
Verify that the R-32 sensor wire is not damaged.
Replace R-32 Sensor.
Furnace stops heating
and only the fan is
operating
EAL
R-32 sensor has detected a refrigerant
leak and furnace is in mitigation mode.
Investigate the indoor coil for a refrigerant leak.
Furnace will resume normal operation once a leak is not
detected and the 5 minute delay period is over.
Furnace stops heating
and only the fan is
operating
EAS
R-32 sensor has detected a fault and the
furnace is in mitigation mode.
Investigate the R-32 sensor.
Replace the R-32 sensor.
Furnace stops heating
and only the fan is
operating
Ear
A2L relay in the furnace control board
has detected a fault and the furnace is in
mitigation mode.
Investigate A2L relay.
Cycle power on the furnace.
Replace integrated control board.
Furnace fails to
operate.
No 115 power to furnace or no 24 volt
power to integrated control module.
Restore high voltage power to furnace and integrated
control module.
Blown fuse or tripped circuit breaker
Correct condition which caused fuse to open, replace
fuse
Integrated control module is non-
functional
Replace non-functional integrated control module.
None
Integrated control
module LED display
provides no signal
TROUBLESHOOTING
33
background
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
34
GR
GND
JUNCTION
BOX
WARNING:DISCONNECT
N
TO UNIT MUST BE
AND GROUNDED.
L
SERVICING. WIRING
DISCONNECT
GND
WH
BK
POWER BEFORE
PROPERLY POLARIZED
0140F20035-A
Ø /60 HZ
OVERCURRENT
115 VAC/ 1
TO
POWER SUPPLY WITH
PROTECTION
DEVICE
BURNER COMPARTMENT
BLOWER
COMPARTMENT
DOOR-SWITCH
(OPEN WHEN
DOOR OPEN)
RD
ECM MTR
HARNESS
BK
RD
GR
BK
BK
YL
FLAME SENSOR
GY
1
2
M
C
BLOWER COMPARTMENT
AUTO RESET AUXILIARY
LIMIT CONTROL
RD
RD
AUTO RESET
PRIMARY
LIMIT CONTROL
BK
GND
BLOWER
DRAFT (ID)
INDUCED
1
2
3
RD
WH
BK
RD
WH
2 CIRCUIT
CONNECTOR
HOT
SURFACE
IGNITER
WH
PK
BK
RD
WH
2
1
WH
WH
BL
YL
BK
OR
RD
BL
WH
BK
BK
NOTE 5
NOTE 6
CR48
E28
E5
E22
E47
W11
BLW
E32
YL
WH
E4
PK
PU
AUTO RESET
BAFFLE
LIMIT
GAS VALVE
BR
NO
C
PU
PU
AUTO RESET
BURNER BOX
LIMIT
AUTO RESET
AUXILIARY
LIMIT
CONTROL
PK
YL
PU
PK
TAP1
E23
NEUTRAL
E46
E25
E26
E19
W12
WH
MOB_PE
TAP2
TAP3
TAP4
TAP5
GND
FS
E39
E41
U
V
W
LINE
N
H
FUSE
GY
YL
NO
C
ID BLOWER
PRESSURE
SWITCH
YL
PRESSURE TRANSDUCER
BK
RD
GR
2
1
3
4
UNUSED
5V
GND
PI
A2L MODE IS ENABLED BY DEFAULT
REFER TO INSTALLATION MANUAL FOR FURTHER
INSTRUCTIONS.
SW1
SW2
E35
IN
OUT
E42
EAC
W2
W1
B\C
R
G
Y1
TWIN
Y2
PSO
BLI
MVH
MVL
GND
HLI
TH
MVC
HLO
PS1
TR
ALI
GND
PI
5V
E18
A2L
A2L
ALARM
HUM
VENT
0
PK
PK
GY
RD
GR
BR
PU
YL
COLLECTOR BOX
PRESSURE SWITC
H
YL
1
12
NOTES :
1. MANUFACTUR'S SPECIFIED REPLACEMENT
PARTS MUST BE USED WHEN SERVICING.
2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED
WITH THE FURNACE MUST BE REPLACED, IT
MUST BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST
105
C. USE COPPER CONDUCTORS ONLY.
3. BLOWER SPEEDS SHOULD BE ADJUSTED BY
INSTALLER TO MATCH THE INSTALLATION
REQUIREMENTS SO AS TO PROVIDE
THE CORRECT HEATING TEMPRATURE
RISE AND THE CORRECT COOLING CFM.
4. UNIT MUST BE PERMANENTLY GROUNDED
AND CONFORM TO N.E.C. AND LOCAL CODES.
5. EAC. NORMALLY OPEN CONTACTS FOR OPTIONAL
ELECTRONIC AIR CLEANER USE. CONTACTS
CLOSE
WHEN INDOOR BLOWER IS RUNNING. TERMINALS
ARE NOT INTERNALLY POWERED
6. HUM. NORMALLY OPEN CONTACTS FOR OPTIONAL
HUMIDIFIER USE. CONTACTS CLOSE WHEN DRAFT
INDUCER IS RUNNING. TERMINALS ARE NOT
INTERNALLY POWERED
7. WHEN THIS FURNACE IS PAIRED WITH NON R-32
REFRIGERANT SYSTEMS, DEFAULT SETTINGS WILL
NEED TO BE CHANGED. REFER TO INSTALLATIONS
MANUAL FOR FURTHER INSTRUCTIONS.
PK
COLOR CODES:
RD
GY
WH
PU
OR
YL
BL
BR
BK
GR
BLUE
BROWN
BLACK
GREEN
PINK
GRAY
PURPLE
ORANGE
RED
WHITE
YELLOW
SWITCH (PRESSURE)
FIELD SPLICE
FIELD GROUND
EQUIPMENT GROUND
INTERNAL TO
PROTECTION DEVICE
INTEGRATED CONTROL
PLUG CONNECTION
SWITCH (TEMPERATURE)
JUNCTION
OVERCURRENT
TERMINAL
IGNITER
HIGH VOLTAGE (115V)
HIGH VOLTAGE FIELD
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
NO
C
STATUS & FAULT
(SEE INSTALLATION MANUAL FOR COMPLETE LIST OF FAULTS)
SEVEN SEGMENT DISPLAY
Seg. 1 Seg. 2 Seg. 3
IDLE I d L
CONTINIOUS FAN F A n
LOW STAGE COOLING 1 A C
HIGH STAGE COOLING 2 A C
GAS HEAT g H
HEAT PUMP HEAT, LOW STAGE 1 H P
HEAT PUMP HEAT, HIGH STAGE 2 H P
DEFROST d F t
LOCKOUT DUE TO EXCESSIVE RETRIES RECYCLE E E 0
PRESSURE SWITCH CLOSED WHEN ECPECTED TO BE OPEN E E 1
PRESSURE SWITCH OPEN WHEN EXPECTED TO BE CLOSED E E 2
OPEN HIGH LIMIT SWITCH E E 3
FLAME DETECTED WHEN NO FLAME SHOULD BE PRESENT E E 4
OPEN FUSE E E 5
LOW FLAME SIGNAL E E 6
IGNITOR FAULT OR IGNITOR RELAY FAULT E E 7
REVERSED LINE POLARITY E E A
GROUNDING ERROR E 1 0
INTERNAL GAS VALVE ERROR E E b
EXTERNAL GAS VALVE ERROR E E C
STATUS & FAULT
(SEE INSTALLATION MANUAL FOR COMPLETE LIST OF FAULTS)
SEVEN SEGMENT DISPLAY
Seg. 1 Seg. 2 Seg. 3
AUXILLIARY LIMIT SWITCH OPEN E E d
BURNER LIMIT SWITCH OPEN E 1 I
LOW CIRCULATOR CURRENT E b L
CIRCULATOR CURRENT UNEXPECTED E b U
A2L COMMUNICATION ALARM E A F
A2L LEAKAGE ALARM E A L
A2L INTERNAL ALARM E A S
A2L RELAY ALARM E A r
RD
BLOWER
CIRCULATOR
BK
GR
RD
3
1
WH
2
4
BL
5 4 3
2 1
RD
OR
BK
YL
24
VAC
WH
40 VA
TRANS-
FORMER
115
VAC
BK
GND
GROUND WIRE
CONNECTED
TO CONTROL
MOUNTING PANEL
*R9S96*U

Specifications

Indexed Terms: Gas Furnace, 96% AFUE