Installation Instructions for *RVS96 & *DVS96
Ultra Low NOx Variable Speed Gas Furnace
(Type FSP CATEGORY IV Direct
or Non Direct Vent Air Furnace)
IOG-2042
04/2024
19001 Kermier Rd., Waller, TX 77484
www.goodmanmfg.com • www.amana-hac.com
© 2024 Daikin Comfort Technologies Manufacturing, L.P.
is a registered trademark of Maytag Corporation or its related companies and is
used under license. All rights reserved.
These furnaces comply with requirements embodied
in the American National Standard/National Standard
of Canada ANSI Z21.47•CSA-2.3 Gas Fired Central
Furnaces.
Installer:
Ax all manuals
adjacent to the unit.
As a professional installer you have an obligation to know
the product better than the customer. This includes all
safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself
with this Instruction Manual. Pay special attention to all
safety warnings. Often during installation or repair it is
possible to place yourself in a position which is more
hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product
safely and to know it well enough to be able to instruct a
customer in its safe use.
Safety is a matter of common sense...a matter of thinking
before acting. Most dealers have a list of specic good
safety practices...follow them.
The precautions listed in this Installation Manual are
intended as supplemental to existing practices. However,
if there is a direct conict between existing practices and
the content of this manual, the precautions listed here take
precedence.
RECOGNIZE THIS SYMBOL AS
A SAFETY PRECAUTION.
*NOTE: Please contact your distributor or our
website for the applicable Specification Sheet
referred to in this manual.
Do not bypass safety devices.
WARNING
Only personnel that have been trained to install, adjust,
service, maintenance or repair (hereinafter, “service”)
the equipment specified in this manual should service the
equipment.
This equipment is not intended for use by persons
(including children) with reduced physical, sensory or
mental capacities, or lack of experience and knowledge,
unless they have been given supervision or instruction
concerning use of the appliance by a person responsible
for their safety.
Children should be supervised to ensure that they do not
play with the equipment.
The manufacturer will not be responsible for any injury
or property damage arising from improper supervision,
service or service procedures. If you service this unit, you
assume responsibility for any injury or property damage
which may result. In addition, in jurisdictions that require
one or more licenses to service the equipment specified in
this manual, only licensed personnel should service the
equipment. Improper supervision, installation, adjustment,
servicing, maintenance or repair of the equipment specified
in this manual, or attempting to install, adjust, service
or repair the equipment specified in this manual without
proper supervision or training may result in product
damage, property damage, personal injury or death.
WARNING
WARNING
THIS FURNACE MAY BE PAIRED WITH A COOLING UNIT THAT
USES R-32 REFRIGERANT. IF THE COOLING UNIT PAIRED WITH
THIS FURNACE DOES NOT USE R-32, THE R-32 FUNCTION IN THE
FURNACE CONTROL BOARD NEEDS TO BE TURNED OFF. PLEASE
SEE THE ELECTRICAL AND THE R-32 SECTIONS FOR MORE DETAILS.
REFRIGERANT SYSTEMS OTHER THAN 410-A OR R-32 MAY REQUIRE
AN ADDITIONAL MITIGATION CONTROL BOARD. REFER TO THE
INSTALLATION MANUAL OF THE INDOOR EVAPORATOR COIL TO
DETERMINE INSTALLATION REQUIREMENTS FOR THAT SUPPLIER’S
REFRIGERANT DETECTION SYSTEM.

2
CONTENTS
Safety Considerations .................................................3
Product Application ......................................................5
Location Requirements & Considerations ................6
Combustion & Ventilation Air Requirements............8
Installation Positions ...................................................8
Horizontal Applications & Considerations ...............9
High Altitude Installation ..........................................10
Vent Pipe & Combustion Air Pipe ...............................10
Condensate Drain Lines & Drain Trap .....................17
Electrical Connections ..............................................22
R-32 Features ................................................................29
Startup Procedure & Adjustment .............................29
Gas Supply And Piping .................................................30
Circulating Air & Filters ...........................................33
Operational Checks Safety Circuit Description ...37
Troubleshooting ..........................................................38
Maintenance ..................................................................38
Filters .............................................................................38
Before Leaving An Installation .................................39
Repair And Replacement Parts..................................39
Menu Options .................................................................40
Status Codes ................................................................41
Troubleshooting Chart ..............................................42
Wiring Diagrams ...........................................................45
This device, which was assembled by Daikin Comfort Technologies
Manufacturing, L.P., contains a component that is classied as an
intentional radiator. This intentional radiator has been certied by the
FCC: FCC ID QOQBGM111. And this international radiator has an
Industry Canada ID: IC 5123A-BGM111.
This device complies with Part 15 of the FCC’s Rules. Operation of this
device is subject to two conditions:
(1) This device may not cause harmful interference; and
(2) This device must accept any interference received, including
interference that may cause undesirable operation.
And this device meets the applicable Industry Canada technical
specications.
The manufacturer of the intentional radiator (model no. BGM111) is
Silicon Laboratories Finland Oy, which can be contacted by calling 617-
951-0200. (www.silabs.com)
Daikin Comfort Technologies Manufacturing, L.P. may be contacted by
calling 713-861-2500, or at 19001 Kermier Rd., Waller TX 77484.
(www.GoodmanMFG.com)
This equipment complies with FCC radiation exposure limits. To ensure
compliance, human proximity to the antenna shall not be less than
20 cm during normal operations.
NOTE: This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment o and
on, the user is encouraged to try to correct the interference by one or
more of the following measures:
—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and
receiver.
—Connect the equipment into an outlet on a circuit dierent
from that to which the receiver is connected.
—Consult the dealer or an experienced radio/ TV technician
for help.

3
WARNING
Changes or modifications not expressly approved by the par-
ty responsible for compliance could void the user’s authori-
ty to operate the equipment.
SAFETY CONSIDERATIONS
IMPORTANT NOTE: This unit is designed to
meet the NOx requirement of 14Ng/J maximum
as required by the South Coast Air Quality
Management District and the San Joaquin Valley
Air Pollution Control District, both in the State
of California, and is intended for installation in
those districts only.
This unit has a control system that compensates for certain
installation and environmental conditions. This unit must:
• Be properly installed, operated, and maintained per
the instructions.
• Be serviced only by properly trained service
technicians.
Units that are not installed, maintained, or operated
properly may result in “noisy” operation during the heating
cycle. If this unit is making unusual or objectionable noises
during the heating cycle, turn the heat o at the thermostat
and contact a qualied service organization right away.
Adhere to the following warnings and cautions when
installing, adjusting, altering, servicing, or operating the
furnace. To ensure proper installation and operation,
thoroughly read this manual for specics pertaining to the
installation and application of this product.
This furnace is manufactured for use with natural gas only.
Install this furnace only in a location and position
as specied in LOCATION REQUIREMENTS &
CONSIDERATIONS section and INSTALLATION
POSITIONS section of this manual.
Provide adequate combustion and ventilation air to the
furnace as specied in COMBUSTION & VENTILATION
AIR REQUIREMENTS section of this manual.
Combustion products must be discharged to the outdoors.
Connect this furnace to an approved vent system only, as
specied in VENT/FLUE PIPE & COMBUSTION AIR PIPE
section of this manual.
Never test for gas leaks with an open ame. Use a
commercially available soap solution made specically for
the detection of leaks to check all connections, as specied
in GAS SUPPLY AND PIPING section of this manual.
Always install a furnace to operate within the furnace’s
intended temperature-rise range with a duct system which
has external static pressure within the allowable range,
as specied on the furnace rating plate and Operational
Checks section of these instructions.
When a furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace.
A gas-red furnace for installation in a residential
garage must be installed as specied in the LOCATION
REQUIREMENTS AND CONSIDERATIONS section of this
manual.
This furnace cannot be used as a construction site heater.
CAUTION
FROZEN AND BURST WATER PIPE HAZARD
Failure to protect against the risk of freezing may result in
property damage.
Special precautions MUST be made if installing furnace
in an area which may drop below freezing. This can cause
improper operation or damage to equipment. If the furnace
environment has the potential of freezing, the drain trap
and drain line must be protected. The use of accessory drain
trap heaters, electric heat tape and/or RV antifreeze is rec-
ommended for these installations.
WARNING
To prevent personal injury or death due to improper instal-
lation, adjustment, alteration, service or maintenance, refer
to this manual. For additional assistance or information,
consult a qualified installer, servicer agency or the gas
supplier.

4
WARNING
If the information in these instructions is not followed
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
- do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions. If you
cannot reach your gas supplier, call the fire depart-
ment.
- Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING
Heating unit should not be utilized without reasonable, rou-
tine, inspection, maintenance and supervision. If the build-
ing in which any such device is located will be vacant, care
should be taken that such device is routinely inspected,
maintained and monitored. In the event that the building may-
be exposed to freezing temperatures and will be vacant, all
water-bearing pipes should be drained, the building should
be properly winterized, and the water source closed. In the
event that the building may be exposed to freezing tempera-
tures and will be vacant, any hydronic coil units should be
drained as well and, in such case, alternative heat sources
should be utilized.
WARNING
Possible property damage, personal injury or death due to
fire, explosion, smoke, soot, condensation, electrical shock
or carbon monoxide may result from improper installation,
repair operation, or maintenance of this product.
WARNING
Should overheating occur or the gas supply fail to shut off,
turn off the manual gas shutoff valve external to the fur-
nace before turning off the electrical supply.
CO can cause serious illness including permanent brain
damage or death.
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
El monóxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
Las emisiones de monóxido de carbono pueden circular a través
del aparato cuando se opera en cualquier modo.
RISQUE D'EMPOISONNEMENT AU
MONOXYDE DE CARBONE
Cette ventilation est nécessaire pour éviter le danger d'intoxication
au CO pouvant survenir si un appareil produisant du monoxyde
de carbone continue de fonctionner au sein de la zone confinée.

5
Shipping Inspection
All units are securely packed in shipping containers
tested according to International Safe Transit Association
specications. The carton must be checked upon arrival
for external damage. If damage is found, a request for
inspection by carrier’s agent must be made in writing
immediately.
The furnace must be carefully inspected on arrival for
damage and bolts or screws which may have come loose
in transit. In the event of damage the consignee should:
1. Make a notation on delivery receipt of any visible
damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. With concealed damage, carrier must be notied as
soon as possible - preferably within ve days.
4. File the claim with the following support documents
within a nine month statute of limitations.
• Original or certied copy of the Bill of Lading, or
indemnity bond.
• Original paid freight bill or indemnity in lieu thereof.
• Original or certied copy of the invoice, showing
trade and other discounts or reductions.
• Copy of the inspection report issued by carrier’s
representative at the time damage is reported to
carrier.
The carrier is responsible for making prompt inspection of
damage and for a thorough investigation of each claim.
The distributor or manufacturer will not accept claims from
dealers for transportation damage.
Electrostatic Discharge (ESD) Precautions
NOTE: Discharge your body’s static electricity
before touching unit. An electrostatic discharge
can adversely affect electrical components.
Use the following precautions during furnace installation
and servicing to protect the integrated control module
from damage. By putting the furnace, the control, and the
person at the same electrostatic potential, these steps
will help avoid exposing the integrated control module to
electrostatic discharge. This procedure is applicable to both
installed and non-installed (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch
the integrated control module or any wire connected
to the control prior to discharging your body’s
electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the
furnaces near the control. Any tools held in a person’s
hand during grounding will be discharged.
3. Service integrated control module or connecting
wiring following the discharge process in step 2.
Use caution not to recharge your body with static
electricity; (i.e., do not move or shue your feet, do
not touch ungrounded objects, etc.). If you come in
contact with an ungrounded object, repeat step 2
before touching control or wires.
4. Discharge your body to ground before removing a
new control from its container. Follow steps 1 through
3 if installing the control on a furnace. Return any old
or new controls to their containers before touching
any ungrounded object.
To The Installer
Before installing this unit, please read this manual
thoroughly to familiarize yourself with specic items which
must be adhered to, including but not limited to: unit
maximum external static pressure, gas pressures, BTU
input rating, proper electrical connections, circulating air
temperature rise, minimum or maximum CFM, and motor
speed connections.
WARNING
To prevent property damage, personal injury or death due to
fire, do not install this furnace in a mobile home, trailer, or
recreational vehicle.
PRODUCT APPLICATION
This furnace is primarily designed for residential home-
heating applications. It is not designed or certied for use in
mobile homes, trailers or recreational vehicles. Neither is it
designed or certied for outdoor applications. The furnace
must be installed indoors (i.e., attic space, crawl space, or
garage area provided the garage area is enclosed with an
operating door).
This furnace can be used in the following non-industrial
commercial applications:
Schools, Oce buildings, Churches, Retail stores,
Nursing homes, Hotels/motels, Common or oce
areas.
In such applications, the furnace must be installed with the
following stipulations:
• It must be installed per the installation instructions
provided and per local and national codes.
• It must be installed indoors in a building constructed
on site.
• It must be part of a ducted system and not used in a
free air delivery application.
• It must not be used as a “make-up” air unit.
• It must be installed as a two-pipe systems for
combustion air.
• All other warranty exclusions and restrictions apply
This furnace is an ETL certied appliance and is
appropriate for use with natural gas.
• Dual certication means that the combustion air inlet
pipe is optional and the furnace can be vented as a:
• Non-direct vent (single pipe) central forced air furnace
in which combustion air is taken from the installation
area or from air ducted from the outside or,

6
• Direct vent (dual pipe) central forced air furnace
in which all combustion air supplied directly to the
furnace burners through a special air intake system
outlined in these instructions.
NOTE: Meeting the following conditions is
a requirement when using this furnace as a
construction site heater:
• The furnace has a permanently installed venting
system per these installation instructions.
• A room thermostat is used to control the furnace.
Fixed jumpers that provide continuous heating
CANNOT be used and can cause long term
equipment damage. Bi-metal thermostats or any
thermostat aected by vibration must be avoided
during construction.
• The furnace is attached to permanent return air
ducting sealed to the furnace.
• A return air temperature range between 60ºF (16ºC)
and 80ºF (27ºC) is maintained.
• MERV 11 air lter(s) are installed in the system
and inspected daily and replaced as needed during
construction and upon completion of construction.
• The input rate and temperature rise settings are within
furnace rating plate guidelines.
• The furnace must be installed as a two-pipe system,
using 100% outside air for combustion during
construction.
• The furnace heat exchanger, components, duct
system, air lters, and evaporator coils are thoroughly
cleaned following nal construction clean up by a
qualied person.
• All furnace operating conditions, including ignition,
input rate, temperature rise, and venting, are veried
by a qualied person according to these installation
instructions.
• Furnace doors must be in place on the furnace while
the furnace is operating in any mode.
NOTE: Damage or repairs due to failure to comply
with these requirements is not covered by the
manufacturer’s warranty.
To ensure proper furnace operation, install, operate and
maintain the furnace in accordance with these installation
and operation instructions, all local building codes and
ordinances. In their absence, follow the latest edition of
the National Fuel Gas Code (NFPA 54/ANSI Z223.1),
Installation Codes, local plumbing or waste water codes,
and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1) can be obtained from any of the following:
American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Independence, OH 44131-5516
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE Guide” or “Manual
J-Load Calculations” published by the Air Conditioning
Contractors of America.
LOCATION REQUIREMENTS &
CONSIDERATIONS
WARNING
To prevent possible equipment damage, property damage, per-
sonal injury or death, the following bullet points must be
observed when installing this unit.
WARNING
Possible property damage, personal injury or death due to
fire, explosion, smoke, soot, condensation, electrical shock
or carbon monoxide may result from improper installation,
repair operation, or maintenance of this product.
Follow the instructions listed below and the guidelines
provided in the Combustion and Ventilation Air
Requirements section when selecting a furnace location.
• Centrally locate the furnace with respect to the
proposed or existing air distribution system.
• Ensure the temperature of the return air entering the
furnace is between 55°F and 100°F when the furnace
is heating.
• Provide provisions for venting combustion products
outdoors through a proper venting system. Special
consideration should be given to vent/ue pipe routing
and combustion air intake pipe when applicable.
Refer to Vent/Flue Pipe and Combustion Air Pipe -
Termination Locations for appropriate termination
locations and to determine if the piping system from
furnace to termination can be accomplished within
the guidelines given. NOTE: The length of ue and/
or combustion air piping can be a limiting factor in the
location of the furnace.
• Locate the furnace so condensate ows downwards
to the drain. Do not locate the furnace or its
condensate drainage system in any area subject to
below freezing temperatures without proper freeze
protection. Refer to Condensate Drain Lines and Trap
for further details.
• Ensure adequate combustion air is available for
the furnace. Improper or insucient combustion air
can expose building occupants to gas combustion
products that could include carbon monoxide. Refer to
Combustion and Ventilation Air Requirements.

7
• Set the furnace on a level oor to enable proper
condensate drainage. If the oor becomes wet or
damp at times, place the furnace above the oor
on a concrete base sized approximately 1-1/2” larger
than the base of the furnace. Refer to the Horizontal
Applications and Considerations for leveling of
horizontal furnaces.
• Ensure upow or horizontal furnaces are not installed
directly on carpeting, or any other combustible
material. The only combustible material allowed is
wood.
• Exposure to contaminated combustion air will result
in safety and performance-related problems. Do
not install the furnace where the combustion air is
exposed to the following substances:
Permanent wave solutions
Chlorinated waxes or cleaners
Chlorine-based swimming pool chemicals
Carbon tetrachloride
Water softening chemicals
Swimming pool chemicals
Deicing salts or chemicals
Halogen type refrigerants
Printing inks
Cleaning solutions (such as perchloroethylene)
Paint removers
Varnishes
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
• Protect a non-direct vent furnace from airborne
contaminants. To ensure that the enclosed non-direct
vent furnace has an adequate supply of combustion
air, vent from a nearby uncontaminated room or from
outdoors. Refer to the Combustion and Ventilation Air
Requirements for details.
• If the furnace is used in connection with a cooling coil
unit, install the furnace upstream or in parallel with the
cooling coil unit. Premature heat exchanger failure
will result if the cooling unit is placed ahead of the
furnace.
For vertical (upow) applications, the minimum cooling
coil width shall not be less than furnace width minus 1”.
Additionally, a coil installed above an upow furnace may
be the same width as the furnace or may be one size
larger than the furnace. Example: A “C” width coil may be
installed with a “B” width furnace.
For upow applications, the front of the coil and furnace
must face the same direction.
• If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition
source are located not less than 18” above the oor.
Protect the furnace from physical damage by vehicles.
• If the furnace is installed horizontally, ensure the
access doors are not on the “up/top” or “down/bottom”
side of the furnace.
• Do not connect this furnace to a chimney ue that
serves a separate appliance designed to burn solid
fuel.
Clearances and Accessibility
NOTES:
• For servicing or cleaning, a 24” front clearance is
required.
• Unit connections (electrical, ue and drain) may
necessitate greater clearances than the minimum
clearances listed above.
• In all cases, accessibility clearance must take
precedence over clearances from the enclosure
where accessibility clearances are greater.
POSITION* SIDES REAR FRONT BOTTOM FLUE TOP
Upfl ow
0" 0" 3" C 0" 1"
Horizontal
(Upfl ow
Model s )
6" 0" 3" C 0" 6"
Downflow
0" 1" 0" 1" C 0"
Horizontal
(Downfl ow
Model s )
6" ALCOVE 0" 4" C 0"
C = If placed on combustible floor, floor MUST be wood only.
*RVS96/*DVS96 M INIM UM CLEARANCES
TO COMBUSTIBLE M ATERIALS (INCHES)
Table 1
Installations must adhere to the clearances to combustible
materials to which this furnace has been design certied.
The minimum clearance information for this furnace is
provided on the unit’s clearance label. These clearances
must be permanently maintained. Clearances must also
accommodate an installation’s gas, electrical, and drain
trap and drain line connections. If the alternate combustion
air intake or vent/ue connections are used additional
clearance must be provided to accommodate these
connections. Refer to Vent/Flue Pipe and Combustion Air
Pipe for details.
NOTE: In addition to the required clearances to
combustible materials, a minimum of 24” service
clearance must be available in front of the unit.
A furnace installed in a conned space (i.e., a closet or
utility room) must have two ventilation openings with a
total minimum free area of 0.25 square inches per 1,000
BTU/hr of furnace input rating. Refer to Specication
Sheet applicable to your model for minimum clearances
to combustible surfaces. One of the ventilation openings
must be within 12” of the top; the other opening must
be within 12” of the bottom of the conned space. In a
typical construction, the clearance between the door and
door frame is usually adequate to satisfy this ventilation
requirement.

8
Existing Furnace Removal
The following vent testing procedure is reproduced from
the American National Standard/National Standard of
Canada for Gas-Fired Central Furnaces ANSI Z21.47,
CSA-2.3 latest edition Section 1.23.1.
The following steps shall be followed with each appliance
connected to the venting system placed in operation, while
any other appliances connected to the venting system are
not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required by the National Fuel
Gas Code, ANSI Z223.1 instructions. Determine that
there is no blockage or restriction, leakage, corrosion
and other deciencies which could cause an unsafe
condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building.
4. Close replace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts,
so they shall operate at maximum speed. Do not
operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously.
7. If improper venting is observed during any of the
above tests, the venting system must be corrected in
accordance with the National Fuel Gas Code ANSI
Z223.1/NFPA 54.
8. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, replace dampers and any other gas
burning appliance to their previous conditions of use.
If resizing is required on any portion of the venting system,
use the appropriate table in Appendix G in the latest edition
of the National Fuel Gas Code ANSI Z223.1 Installation
Codes.
Thermostat Location
The thermostat should be placed approximately ve feet
from the oor on a vibration-free, inside wall in an area
having good air circulation. Do not install the thermostat
where it may be inuenced by any of the following:
• Drafts, or dead spots behind doors, in corners, or
under cabinets.
• Hot or cold air from registers.
• Radiant heat from the sun.
• Light xtures or other appliances.
• Radiant heat from a replace.
• Concealed hot or cold water pipes, or chimneys.
• Unconditioned areas behind the thermostat, such as
an outside wall.
Consult the instructions packaged with the thermostat for
mounting instructions and further precautions.
COMBUSTION & VENTILATION AIR
REQUIREMENTS
WARNING
To avoid property damage, personal injury or death, suffi-
cient fresh air for proper combustion and ventilation of
flue gases must be supplied. Most homes require outside air
be supplied into the furnace area.
Improved construction and additional insulation in buildings
have reduced heat loss by reducing air inltration and
escape around doors and windows. These changes have
helped in reducing heating/cooling costs but have created
a problem supplying combustion and ventilation air for
gas red and other fuel burning appliances. Appliances
that pull air out of the house (clothes dryers, exhaust
fans, replaces, etc.) increase the problem by starving
appliances for air.
House depressurization can cause back drafting or
improper combustion of gas-red appliances, thereby
exposing building occupants to gas combustion products
that could include carbon monoxide.
If this furnace is to be installed in the same space with
other gas appliances, such as a water heater, ensure there
is an adequate supply of combustion and ventilation air for
all appliances. Refer to the latest edition of the National
Fuel Gas Code NFPA 54/ANSI Z223.1 or applicable
provisions of the local building codes for determining the
combustion air requirements for the appliances.
Most homes will require outside air be supplied to the
furnace area by means of ventilation grilles or ducts
connecting directly to the outdoors or spaces open to the
outdoors such as attics or crawl spaces.
INSTALLATION POSITIONS
This furnace may be installed in an upright position or
horizontal on either the left or right side panel. Do not
install this furnace on its back. For upright upow furnaces,
return air ductwork may be attached to the side panel(s)
and/or basepan. For horizontal upow furnaces, return
air ductwork must be attached to the blower compartment
end of the furnace. For both upright or horizontal downow
furnaces, return ductwork must be attached to the basepan
(top end of the blower compartment). NOTE: Ductwork
must never be attached to the back of the furnace. Contact
your distributor for proper airow requirements and number
of required ductwork connections. Refer to “recommended
Installation Positions” gure for appropriate installation
positions, ductwork connections, and resulting airow
arrangements.

9
UPFLOW
UPRIGHT
Alternate Vent/Flue Location
Figure 1A
UPFLOW/DOWNFLOW HORIZONTAL
LEFT AIR DISCHARGE
Figure 1B
UPFLOW/DOWNFLOW HORIZONTAL
RIGHT AIR DISCHARGE
Figure 1C
DOWNFLOW
Figure 1D
Recommended Installation Positions
HORIZONTAL APPLICATIONS &
CONSIDERATIONS
When installing a furnace horizontally, additional
consideration must be given to the following:
Furnace Suspension
If suspending the furnace from rafters or joists, use 3/8”
threaded rod and 2”x2”x1/8” angle iron as shown in the
following diagram. The length of rod will depend on the
application and the clearances necessary.
If the furnace is installed in a crawl space it must be
suspended from the oor joist or supported by a concrete
pad. Never install the furnace on the ground or allow it to
be exposed to water.
Figure 2
Front Cover Pressure Switch Tube Location
When a furnace is installed horizontally with left side down,
the front cover pressure switch tube must be re-located to
the lower port of the collector box cover.
1. Remove tube from front cover pressure switch and
collector box cover.
2. Remove rubber plug from bottom collector box port
and install on top collector box port.
3. Locate 24” x 1/4” tube in bag assembly.
4. Install one end on front cover pressure switch.
5. Route tube to lower port on collector box cover and
cut o excess tubing.
Drain Trap and Lines
In horizontal applications the condensate drain trap is
secured to the furnace side panel, suspending it below the
furnace. A minimum clearance of 5.5” below the furnace
must be provided for the drain trap. Additionally, the
appropriate downward piping slope must be maintained
from the drain trap to the drain location. Refer to
Condensate Drain Trap and Lines for further details. If the
drain trap and drain line will be exposed to temperatures
near or below freezing, adequate measures must be taken
to prevent condensate from freezing.

10
Leveling
Leveling ensures proper condensate drainage from the
heat exchanger. For proper ue pipe drainage, the furnace
must be level lengthwise from end to end. The furnace
should have a slight tilt from back to front with the access
doors downhill from the back panel approximately 1/2” to
3/4”. The slight tilt allows the heat exchanger condensate,
generated in the recuperator coil, to ow forward to the
recuperator coil frontcover.
Alternate Electrical and Gas Line Connections
This furnace has provisions allowing for electrical and gas
line connections through either side panel. In horizontal
applications the connections can be made either through
the “top” or “bottom” of the furnace.
Drain Pan
A drain pan must be provided if the furnace is installed
above a conditioned area. The drain pan must cover the
entire area under the furnace (and air conditioning coil if
applicable).
Freeze Protection
Refer to Horizontal Applications and Conditions - Drain
Trap and Lines.
HIGH ALTITUDE INSTALLATION
The furnace, as shipped, requires no change to run
between 0-4500 feet. At all altitudes, the air temperature
rise must be within the range listed on the Specication
Sheet applicable to your model for the fuel used. All
installations above 4,500 feet require manifold pressure
adjustments and combustion analysis. Refer to the “Gas
Supply Pressure Measurement” section for instruction on
how to accurately measure and adjust manifold “outlet”
pressure. The furnace should operate for a minimum of 15
minutes before taking a combustion sample. Combustion
samples should be taken from beyond the furnace exhaust
and must be within provided CO2% range. See table 2
for recommended manifold pressure adjustments and
proper CO2% range. Gas heating values can vary; further
pressure adjustment may be necessary to ensure furnace
operates within acceptable CO2 range.
96% Model
Manifold
Pressure at
5000 ft
Manifold
Pressure at
7500 ft
CO2%
Natural
Gas
Max Allowable
Venting
(3 in only)
*RVS960603BU
100 ft
*RVS960805CU 80 ft
*DVS960603BU
100 ft
*DVS960805CU
80 ft
2.5" w.c.
2.4" w.c.
6.5 - 8.5
2.5" w.c.
2.4" w.c.
6.5 - 8.5
Table 2
VENT PIPE & COMBUSTION AIR PIPE
This manual will refer to the pipe that discharges products
of combustion to the outdoors as the “vent” pipe or
“ue” pipe. The pipe that supplies air for combustion
to the furnace will be referred to as the “intake” pipe or
“combustion air” pipe.
This furnace is dual certied and may be installed as a
non-direct vent (single pipe) or direct vent (dual pipe)
appliance.
WARNING
Upon completion of the furnace installation, carefully
inspect the entire flue system both inside and outside of the
furnace to assure it is properly sealed. Leaks in the flue
system can result in serious personal injury or death due to
exposure to flue products, including carbon monoxide.
WARNING
Failure to follow these instructions can result in bodily
injury or death. Carefully read and follow all instructions
given in this section.
WARNING
To avoid bodily injury, fire or explosion, solvent cements
must be kept away from all ignition sources (i.e. sparks,
open flames, and excessive heat) as they are combustible
liquids. Avoid breathing cement vapors or contact with skin
and/or eyes.
Materials
PVC, CPVC, or ABS pipe & ttings are typically used as
venting and intake pipe materials. All 90° elbows must
be medium or long radius types. A medium radius elbow
should measure ~3-1/16” minimum from the plane of
one opening to the center line of the other opening for 2”
diameter pipe, and ~4-9/16” minimum for 3” pipe.
In addition to these materials, Innoue® by Centrotherm
Eco Systems is also an approved vent and combustion
air materials for installations in the U.S.A. Manufacturers
Installation instructions for these products must be
followed. These products have specic instructions for
installing, joining and terminating. Do not mix materials
or components of one manufacturer with materials or
components of another manufacturer. Refer to the following
chart for plastic pipe & ttings specications

11
Table 3
Installation
This furnace is manufactured with 2” CPVC vent & intake
couplings. Use transition cement to connect PVC or ABS
pipe to these ttings. For furnaces requiring installation
of 3” pipe, the transition from 2” to 3” should be made as
close to the furnace as possible, and only when the piping
is sloped enough to prevent condensation from collecting.
This furnace must not be connected to Type B, BW, or
L vent or vent connector, and must not be vented into
masonry chimney. A masonry chimney may be used as
a chase or passage way for approved venting materials
providing the masonry chimney is not also being used to
vent products of combustion. Never common vent this
appliance with another appliance. Never use a vent which
is used by a solid fuel appliance.
Piping may run vertically or horizontally and must be
adequately supported to prevent strain on joints, sagging,
separation, and detachment from the furnace. Horizontal
runs of piping must be supported every three to ve
feet. Condensation within the furnace secondary heat
exchanger and in the vent pipe is a normal occurrence.
Vent pipe must be installed to maintain a minimum 1/4 inch
per foot downward slope toward the furnace to return
condensate to the furnace’s drain system. Condensation
may also occur in the intake pipe. This commonly takes
place during the summer months when humid air enters
an intake pipe that runs through a cool basement or other
conditioned space.
Precautions should be taken to prevent condensate from
freezing inside the ue/vent pipe, combustion air intake
pipe and/or at the pipe terminations. All ue/vent and/
or combustion air piping exposed to temperatures below
35°F for extended periods of time should be insulated with
1/2” thick closed cell foam. All vent/ue piping exposed
to outdoors in excess of the terminations permitted as
described in the provided installation manual should be
insulated with 1/2” thick closed cell foam. Inspect piping
for leaks prior to installing insulation. If the combustion air
intake or ue vent pipe is to be installed above a nished
ceiling or other area where dripping of condensate will
be objectionable, insulating the combustion air pipe may
be necessary. Use 1/2” thick closed cell foam insulation
where required. Refer to vent & intake options for using the
RF000142 kit and managing condensation.
WARNING
To avoid bodily injury, fire or explosion, solvent cements
must be kept away from all ignition sources (i.e. sparks,
open flames, and excessive heat) as they are combustible
liquids. Avoid breathing cement vapors or contact with skin
and/or eyes.
PREFERRED
Figure 3
TRANSITION NO LESS
THAN 45 TO HORIZONTAL
PLANE TO AVOID CREATING
A WATER TRAP IN VENT
PIPING.
°
ACCEPTABLE
Figure 4
PVC
ASTM
STANDARD
SCHEDULE 40 PIPE D1785
SDR
21
or
26 PIPE D2241
SYTSTEM
1738
®
(IPEX)
D1784, UL 1738
SCHEDULE
40
FITTINGS D2466
SYTSTEM
1738
®
FITTINGS
D1784, UL 1738
ABS
SCHEDULE 40 PIPE D1527
FITTINGS D2468
CPVC
SCHEDULE 40 PIPE F441
SDR
21
or
26 PIPE F442
FITTINGS F438
POLYPROPYLENE
INNOFLUE
®
(CENTROTHERM)
UL
1738
PRIMER & SOLVENT CEMENT
PVC PRIMER F656
CPVC PRIMER F656
PVC SOLVENT CEMENT D2564
CPVC
SOLVENT
CEMENT
F493
ABS SOLVENT CEMENT D2235
ABS/PVC/CPVC
ALL
PURPOSE CEMENT (FOR PIPE & FITTINGS OF
THE SAME MATERIAL)
D2564, D2235, F493
TRANSITION
CEMENT FOR ABS TO PVC or CPVC D3188
INSTALLATIONS IN CANADA
PVC
&
CPVC
PIPE & FITTINGS
PVC & CPVC SOLVENT CEMENT
TRANSITION CEMENT
INNOFLUE
®
(CENTROTHERM)
POLYPRO
®
(DURAVENT)
SYSTEM 636
®
(IPEX)
VENTING MATERIAL REQUIREMENTS
ULC
S636

12
NO TRANSITION ON
HORIZONTAL PLANE,
THIS CREATES A
WATER TRAP AND
RESTRICTS FLUE
GASES
NOT ACCEPTABLE
Figure 5
Precautions must be taken to prevent condensate from
freezing inside the vent pipe. All vent piping exposed to
freezing temperatures must be insulated with 1/2” thick
closed cell foam. Inspect piping for leaks prior to installing
insulation.
Pipe Sizing
Consult table 4 to determine what diameter piping is
required for your installation. Lengths shown in table
4 apply to single pipe & two pipe installations. In a two
pipe installation do not add intake and vent pipe lengths
together. Both pipes would normally be equal in length, if
dierent, then the longest pipe must be within the limits of
table 4. It is preferable to up-size from 2” to 2.5” or 3” pipe
if the pipe length & elbow count are near maximum. This
will help avoid nuisance pressure switch opening caused
by prevailing winds & sudden changes in atmospheric
pressure.
1 2 3 4 5 6 7 8
2
90 85
80 75
70 65 60 55
3
158 151 144 137 130 123 116 109
2
55
50 45 40 35 30 25 20
3
151 144 137 130 123 116 109 102
2 90
85 80
75 70 65 60 55
3 158 151 144 137 130 123 116 109
2 55
50 45 40 35 30 25 20
3 151 144 137 130 123 116 109 102
1
2 3 4 5 6 7 8
*RVS960603BU 3 100 93
87 81 75 69 63
57
*RVS960805CU 3 80 73
67 61 55 49 43 37
*DVS960603BU 3 100 93 87 81
75 69 63 57
*DVS960805CU 3 80 73 67 61
55 49 43 37
*DVS960603BU
*DVS960805CU
0 - 4,999 FT ALTITUDE
5,000 - 7,500 FT ALTITUDE
MODEL
Pipe Size
(in)
Number of Elbows
*RVS960805CU
MODEL
Pipe Size
(in)
Number of Elbows
*RVS960603BU
Table 4
Vent Pipe Connection
The vent pipe outlet is sized to accept 2” pipe. Secure vent
pipe directly into the furnace tting with the appropriate
glue. Alternately, a small section of 2” pipe may be glued
in the furnace socket and a rubber coupling installed
to allow removal for future service. Piping should be
routed in a manner to avoid contact with refrigerant lines,
metering devices, condensate drain lines, etc. If necessary,
clearances may be increased by creating an oset using
two 45° elbows (Figure 6).
Increased Clearance Configuration
Figure 6
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a
precaution when removing plugs.
Combustion Air Pipe Connection
If the furnace is being installed without a combustion air
pipe, a 90° elbow should be used on the combustion air
intake to guard against blockage.
On up ow / horizontal models, secure the combustion
air intake pipe to the air intake coupling using a rubber
coupling supplied with the furnace. The rubber coupling
may be omitted by inverting the intake coupling and gluing
pipe directly to it. Piping may also be glued to the intake
coupling in its original position by using a plastic coupling.
VENT-DRAIN
Figure 7

13
Figure 8
Figure 9
Vent & Intake Options for Condensate Management
The RF000142 coupling (Figure 7) can be secured directly
to the furnace intake and/or vent piping if condensation
is a concern. If the RF000142 is used on the combustion
air inlet, it must be installed with the arrow pointing
up. It should be noted, the combustion air will actually
be moving in a direction opposite of the arrow on the
RF000142 coupling. It must have a eld supplied, trapped
drain tube free-draining to proper condensate disposal
location. A loop in the drain tube can serve as a trap. The
unused RF000142 drain tting should be capped. A eld
supplied tee installed in the vent and/or intake pipe is also
an acceptable method of capturing condensation. For
vertical vent piping, a PVC wye can be used for capturing
condensation (see gure 9). Any of these options must
have a eld supplied, trapped drain tube or pipe, free-
draining to proper condensate disposal location. A loop in
the drain tube can serve as a trap.
Alternate Vent & Intake Pipe Connections
(Upflow/Horizontal Models Only)
When installing a furnace horizontally with the left side
down, alternate ue and combustion air pipe connections
may be used. This method allows the ue and combustion
air piping to be run vertically through the side of the furnace
(facing up in horizontal left). The alternate vent location
is the 3” hole directly in line with the induced draft blower
outlet.
When using the horizontal alternate vent conguration, you
must use the RF000142 vent drain kit. See Figures 9 & 10
& follow steps below.
NOTE: In the horizontal left installation
position, a means of condensate collection must
be provided to keep vent pipe condensate from
entering the draft inducer housing. If the vent
drain elbow is eliminated from the installation,
the RF000142 kit must be used.
Insert flange. Cut 2 ½” long.RF000142
2 ½”
Figure 10

14
Vent/Flue Pipe Cuts
Figure 11
WARNING
The rubber elbow is not designed to support a load. When
the rubber elbow is mounted externally to the furnace
cabinet, extreme care must be taken to adequately support
field-supplied vent/flue piping, as damage can result in leaks
causing bodily injury or death due to exposure to flue gas-
es, including carbon monoxide.
CAUTION
Be sure not to damage internal wiring or other components
when reinstalling coupling and screws.
1. Remove the four screws from the vent pipe ange on
top the furnace.
2. Remove the internal elbow, vent pipe and gasket.
3. Cut the internal vent pipe 2 1/2” from the ange.
Discard the un-anged section.
4. Remove the 3” plastic plug (in line with the inducer
outlet) and insert it in the space vacated by removal of
the internal vent pipe.
5. Install the RF000142 drain coupling with arrow facing
up, on the draft inducer outlet.
6. Insert the 2 1/2” anged section of pipe with gasket
through the 3” hole and connect to RF000142 drain
coupling. Secure it with gear clamp provided.
7. Use the four self-tapping screws removed in step 1 to
secure ange to cabinet.
8. Connect drain hose to the uncapped port on the
RF000142 coupling, refer to page 19, Section
entitled “Horizontal Installation with Left Side Down -
Alternate” for drain connection details.
When using the alternate venting location, either in a
horizontal left side down installation or a vertical installation
using down – venting, the alternate combustion air opening
can be used. A locating dimple is located on the right
side of the furnace cabinet. The locating dimple is 1-7/8”
measured from the front edge of the cabinet in line with the
knock out. To use the alternate combustion air location:
1. Remove screws and combustion air ange and gasket
from cabinet.
2. Insert the 3” cabinet plug from the drain bag assembly
in the unused combustion air hole.
3. Drill a pilot hole at the cabinet dimple (size dictated by
knockout tool used).
4. Use a knockout tool to create a 3” diameter hole.
5. Secure the combustion air ange and gasket to
the furnace cabinet using the self-tapping screws
removed in step 1.
Pipe Termination
Products of combustion must always be vented outside. A
vent pipe must never terminate in an attic, crawl space, or
any other part of a dwelling. Follow the vent pipe & intake
pipe termination requirements listed below as well as all
applicable local, State and National codes.
All terminations (vent and/or intake) must be located at
least 12” above ground level or the anticipated snow level.
All vent terminations (non-direct and direct vent) must
terminate at least 3 feet above any forced air inlet located
within 10 feet.
The vent termination of a non-direct vent application must
terminate at least 4 feet below, 4 feet horizontally from, or
1 foot above any door, window, or gravity air inlet into any
building.
The vent termination of a direct vent application must
terminate at least 12” from any opening through which ue
gases may enter a building (door, window, or gravity air
inlet).
The vent termination of vent pipe run vertically through a
roof must terminate at least 12” above the roof line (or the
anticipated snow level) and be at least 12” from any vertical
wall (including any anticipated snow build up).
A vent termination shall not terminate over public walkways
or over an area where condensate or vapor could create a
nuisance or hazard or could be detrimental to the operation
of regulators, relief valves, or other equipment.
The combustion air intake termination of a direct vent
application should not terminate in an area which is
frequently dusty or dirty.
Vent & combustion air pipes may terminate vertically
through a roof, or horizontally through an outside wall. The
combustion air intake and vent pipe can be terminated in
two dierent pressure zones. The intake vent can terminate
on one side of the building, while the ue vent can be
terminated on another side of the building or through
the roof. In addition, the combustion air intake can be
terminated in a suciently ventilated attic. Vertical vent
pipe terminations should be as shown in Figure 12. The
penetration of pipes through the roof must be sealed water
tight with proper ashing such as is used with a plastic
plumbing vent.

15
Figure 12
Horizontal vent pipe terminations should be as shown in
the following gures. To secure the pipe passing through
the wall and prohibit damage to piping connections, a
coupling should be installed on either side of the wall and
solvent cemented to a length of pipe connecting the two
couplings. The length of pipe should be the wall thickness
plus the depth of the socket ttings to be installed on the
inside and outside of the wall. The wall penetration should
be sealed with silicone caulking material.
12"
Non-Direct Vent
Vent/Flue Termination
No Terminations
Above Walkway
12"
min.
4'
min.
Non-Direct Vent
Vent/Flue Termination
Direct Vent
Vent/Flue Termination
<10'
Forced Air
Inlet
Non-Direct Vent
&
Direct Vent
Vent/Flue Terminations
Grade or Highest
Anticipated
Snow Level
3' min.
12" min.
4' min.
12" min.
Vent Termination Clearances
Figure 13
COMBUSTION AIR INTAKE
(OPTIONAL)
*Not required for
single pipe installation
TEE (OPTIONAL)
9
6
”
M
A
X
.
-
3
”
M
I
N
.
R
O
O
F
L
I
N
E
12” MIN
HEIGHT
DIFFERENCE
12” MIN TO ROOF OR
HIGHEST ANTICIPATED
SNOW LEVEL
Vertical Termination
Figure 14
STRAIGHT
ELBOWS
Figure 15

16
VENT/FLUE TEE (
or
45° ELBOW
TURNED DOWN or
90° ELBOW TURNED
DOWN
OPTIONAL)
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
12" MIN.
Horizontal Termination (Single Pipe)
Above Highest Anticipated Snow Level
Figure 16
12" MIN. TO GRADE OR
HIGHEST ANTICIPATED
SNOW LEVEL
6” MAX
10”- 24”
4” MIN
Standard Horizontal Terminations (Dual Pipe)
Figure 17
90°
ELBOWS
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
3” - 24”
Alternate Horizontal Vent Termination (Dual Pipe)
Figure 18
90°
ELBOWS
Combustion Air Intake may also be snorkeled
to obtain 12” min ground clearance.
Alternate Vent Termination Above Anticipated Snow Level
(Dual Pipe)
Figure 19
3” MIN
12” MIN TO GRADE OR HIGHEST
ANTICIPATED SNOW LEVEL
3”MIN
24”MAX
12” MIN SEPA RATION
Termination of Multiple Direct Vent Furnaces
Figure 20
Vent/Intake Terminations For Installation of
Multiple Direct Vent Furnaces
If more than one direct vent furnace is to be installed
vertically through a common roof top, maintain the same
minimum clearances between the exhaust vent and air
intake terminations of adjacent units as with the exhaust
vent and air intake terminations of a single unit.
If more than one direct vent furnace is to be installed
horizontally through a common side wall, maintain the
clearances as in the following gure. Always terminate all
exhaust vent outlets at the same elevation and always
terminate all air intakes at the same elevation.

17
3” MIN
12” MIN TO GRADE OR HIGHEST
ANTICIPATED SNOW LEVEL
10”MIN
24”MAX
12” MIN SEPA RATION
Termination of Multiple Direct Vent Furnaces
Figure 21
Concentric Vent Termination
Refer to the directions provided with the Concentric Vent
Kit or IO-619 for installation specications.
Vertical Installation
Horizontal Installation
Allowable Installation Orentation
Side Wall Vent Kit
Figure 22
Side Wall Vent Kit
This kit is to be used with 2” or 3” direct vent systems. The
vent kit must terminate outside the structure and may be
installed with the intake and exhaust pipes located side-
by-side or with one pipe above the other. These kits are
NOT intended for use with single pipe (non-direct vent)
installations.
NOTE: Refer to the directions furnished with
the Side Wall Vent Kit (p/n 0170K00000S or
0170K00001S) for installation specifications.
CONDENSATE DRAIN LINES & DRAIN
TRAP
A condensing gas furnace achieves its high level
of eciency by extracting heat from the products of
combustion to the point where condensation takes place.
The condensate must be collected in the furnace drain trap
and routed to an appropriate drain location in compliance
with local and national codes.
Follow the bullets listed below when installing the drain
system. Refer to the following sections for specic details
concerning furnace drain trap installation and drain hose
hook ups.
• The drain trap supplied with the furnace must be
used.
• The drain trap must be primed at time of installation.
• The drain line between furnace and drain location
must meet local and nation codes.
• The drain line between furnace and drain location
must maintain a 1/4” per foot downward slope toward
the drain.
• Do not trap the drain line in any other location than at
the drain trap supplied with the furnace.
• If the drain line is routed through an area which may
see temperatures near or below freezing, precautions
must be taken to prevent condensate from freezing
within the drain line.
• If an air conditioning coil is installed with the furnace,
a common drain may be used. An open tee must be
installed in the drain line, near the cooling coil, to
relieve positive air pressure from the coil’s plenum.
This is necessary to prohibit any interference with the
function of the furnace’s drain trap.
NOTE: In vertical installations, air conditioning
coil condensate may drain into the furnace trap
as long as there is a trap between the coil and the
furnace trap and the drain pipe is not terminating
below the water level of the furnace trap.
#
3
#1
#2
#4
#5
#
6
#7
#8
#9
#10
#11
100 Degree
Elbow
Coupling
Figure 23
NOTE: Drain components shown for information
purposes only. For horizontal installations, a
Horizontal Drain Kit may be needed. Refer to the
Specifications Sheet for kit part number.

18
General Drain Information
All furnace models come with a factory installed drain trap.
For vertical installations, the trap will remain in the factory
position. All furnace models installed horizontally require
the trap to be relocated. Many drain hoses have a built-in
grommet which will provide a cabinet seal when installed.
See instructions below for your model and installation
position.
NOTE: Both sides of the drain trap must be primed
prior to initial furnace start up.
Acceptable
area for
drain hole
Right side of UPFLOW model shown.
Left side acceptable also.
Figure 24
Field Supplied Drain
Drain the furnace and air conditioning coil if applicable,
in compliance with code requirements. In horizontal
installations, a eld installed rubber coupling will allow
the drain trap to be removed for cleaning. The drain trap
must be primed before initial furnace start up. When
an air conditioning coil drain is connected to the eld
supplied furnace drain, it must be vented. An open tee
must be installed at a height no higher than the bottom
of the furnace collector box to prevent air conditioning
condensate from backing up into the furnace, if the
common drain was blocked.
Upflow Models
Upflow Model Installed Vertically
The trap and factory installed hoses remain as shipped.
The furnace drain may exit either the right or left side of the
furnace cabinet. Both sides of the cabinet have two .875”
diameter holes which can be used interchangeably for
drain and low voltage wiring purposes. If a higher drain exit
is needed, a .875” diameter hole may be added in the area
shown in Figure 24. Any unused cabinet opening must be
sealed. Do not allow drain hose to sag or trap water.
Hose #1
Hose #2
45
º
barb-pipe
adapter
45
barb-pipe
adapter
º
Installer selects right or left side drain
and installs this hose accordingly
Figure 25
Drain Exiting Right Side
1. Locate and Install the 45º pipe/hose drain coupling
from the outside of the cabinet (barbed end goes
in the cabinet) through hole in the right side of the
cabinet and secure with two eld supplied #8 self-
tapping screws (See Figure 24).
2. Locate the long drain hose #3 and cut at line “A”.
3. Install large end of hose #3 to trap outlet and secure
with 1.25” clamp.
4. Install smaller end of hose #3 on 45º elbow and
secure with 1” clamp.
5. Refer to Field Supplied Drain section for instructions
on eld supplied/installed drain on outlet of furnace
trap.
Drain Exiting Left Side
1. Install the 45º pipe/hose drain coupling from the
outside of the cabinet (barbed end goes in the
cabinet) through the hole in the left side of the cabinet
and secure with two eld supplied #8 self-tapping
screws (see Figure 24).
2. Locate the long drain hose #3 and cut at “B” line for a
17.5” cabinet; cut at line “C” for a 21” cabinet; do not
cut for a “D” width cabinet.
3. Install large end of hose #3 to trap outlet and secure
with 1.25” clamp.
4. Install smaller end of hose #3 on 45º elbow and
secure with 1” clamp.
5. Refer to Field Supplied Drain section for instructions
on eld supplied/installed drain on outlet of furnace
trap.

19
Hose #11
Hose #2
Figure 26
NOTE: Horizontal Drain Kit 0270F05404 needed for
horizontal installations.
Horizontal Installation with Right Side Down
Minimum 5 ½” clearance is required for the drain trap
beneath the furnace.
1. Remove the clamps from both ends of the drain
hoses.
2. Remove the two screws holding the drain trap to the
blower deck.
3. Remove the trap and two hoses from the blower deck
4. Remove the two plugs from the right side of the
cabinet and install them in the blower deck.
5. Draining the Vent Elbow: Locate hose #2 (factory
installed) and cut 1” away from the 45º bend, discard
the 45º section. Insert hose #2 from outside the
cabinet through the cabinet drain hole nearest the top,
secure it to the barbed tting in the elbow with a red
clamp.
6. Draining the Collector Box: Install the non-grommet
end of hose #11 from outside the cabinet in the
bottom drain hole. Install on collector box and secure
with a silver clamp.
7. Use two silver clamps and secure the hoses to drain
trap. The trap outlet faces the front of the furnace.
Secure the trap to the cabinet using two screws
removed in step 2 by inserting the two screws through
the large set of holes in the top mounting tabs of the
trap into the two predrilled holes in the side of the
cabinet.
8. Refer to Field Supplied Drain section for instructions
on eld supplied/installed drain on outlet of furnace
trap.
Hose #6
Hose #5
Hose #11
Front Cover
Pressure Switch
Tube Location
Figure 27
Horizontal Installation with Left Side Down
Minimum 5 ½” clearance is required for the drain trap
beneath the furnace.
*See Front Cover Pressure Switch Tube Location on Figure
26.
1. Remove the clamps from the two drain tubes on the
trap.
2. Remove the two screws holding the drain trap to the
blower deck.
3. Remove the trap and hoses from the blower deck.
4. Remove the two plugs from the left side of the cabinet
and install them in the blower deck.
5. Draining the Vent Elbow: Locate hose #6. Measuring
from the non-grommet end; cut o and discard 1 ½”
for a “D” width cabinet, 5” for a “C” width cabinet, 8 ½”
for a “B” width cabinet.
6. Remove the rubber plug from vent – drain elbow side
port. Place hose #6 on the vent – drain elbow side
port and secure with a silver clamp.
7. Unused vent-drain elbow drip leg port must be sealed
to prevent ue gases from escaping. Insert the rubber
plug removed in step 6 into the unused elbow drain
port. Inserting a blunt tool such as a 3/16’’ Allen
wrench into the center of the rubber plug will stretch
the plug and allow complete insertion.
8. Locate hose #5 and cut 3” from the non-grommet end.
Discard the section without the grommet.
9. Insert the cut end of tube #5 through the lower cabinet
drain hole.
10. Connect hose #6 & hose #5 using 100º elbow and
secure with two red clamps
11. Draining the Collector Box: Remove cap from left
side collector box drain port (bottom in horizontal left
position) and install it on right side (top) collector box
drain port.
12. Install the non-grommet end of hose #11 from outside
the cabinet in the upper drain hole. Install on collector
box and secure with a silver clamp.

20
13. Use two silver clamps and secure the hoses to drain
trap. The trap outlet faces the front of the furnace.
Secure the trap to the cabinet using two screws
removed in step 2 by inserting the two screws through
the large set of holes in the top mounting tabs of the
trap into the two pre-drilled holes in the side of the
cabinet.
14. Refer to Field Supplied Drain section for instructions
on eld supplied/installed drain on outlet of furnace
trap.
Insert flange. Cut 2 ½” long.RF000142
2 ½”
Figure 28
Horizontal Installation with Left Side Down -
Alternate
*See Front Cover Pressure Switch Tube Location on Figure
26.
1. Draining the RF000142 Coupling: Locate hose #2
(factory installed). Cut o and discard the 45° radius
end.
2. Install 90°radius end of hose #2 on RF000142 drain
outlet and secure with a red clamp.
3. Insert coupling in hose #2 and secure with a red
clamp.
4. Locate hose #5 and cut 3” from the non-grommet end.
Discard the section without the grommet.
5. Insert the cut end of tube #5 through the lower cabinet
drain hole.
6. Insert 100° elbow in the cut end of hose #5.
7. Locate hose #6. Using red clamps, connect between
the coupling and 100° elbow, cutting o excess
tubing.
8. Draining the Collector Box: Remove cap from left
side collector box drain port (bottom in horizontal left
position) and install it on right side (top) collector box
drain port and secure with a red clamp.
9. Install the non-grommet end of hose #11 from outside
the cabinet in the upper drain hole. Install on collector
box and secure with a silver clamp.
10. Use two silver clamps and secure the hoses to drain
trap. The trap outlet faces the front of the furnace.
Secure the trap to the cabinet using two screws
removed in step 2 by inserting the two screws through
the large set of holes in the top mounting tabs of the
trap.
Downflow Models
Downflow Model Installed Vertically
The furnace drain may exit the right or left side of the
furnace cabinet (left side preferred) Trap and factory
installed hoses remain as shipped if the drain will exit the
left side of the cabinet. Draining from the right side requires
relocation of the trap to outside the cabinet.
Drain Exiting Left Side (See Figure 29)
1. Install a eld supplied rubber coupling secured with
a 1 1/4” clamp to enable removing the trap for future
cleaning. Alternately, a PVC tting may be glued on
the trap outlet.
2. Install drain per local and National codes.
Hose #4 x 3
Hose #5
Non-ULN furnace shown (ULN similar)
Figure 29
Drain Exiting Right Side (See Figure 30)
1. Removing the gas manifold assembly will provide
better access when re-locating the trap. To remove
the gas manifold, remove the four screws that fasten
the gas manifold assembly to the bracket.
2. Remove hose clamps and hoses from trap.
3. Remove trap.
4. (Draining the Vent Elbow) Insert the non-grommet
end hose #10 into the cabinet back drain hole. Insert
a coupling into the drip leg of the vent-drain elbow
and secure with a silver clamp. Secure hose #10 on
vent - drain elbow barb tting with a silver clamp.
5. (Draining the Collector Box) Insert non-grommet

21
end of hose #9 into the cabinet front drain hole and
secure on collector box drain port with a silver clamp.
6. Mate the drain trap inlets to the hoses and secure
with silver clamps.
7. Line up the trap mounting holes with the pre-drilled
holes in the furnace and secure with 2 screws
removed in step 2.
8. Refer to Field Supplied Drain section for instructions
on eld supplied / installed drain on outlet of furnace
trap.
Non-ULN furnace shown (ULN similar)
Figure 30
Downflow Model Installed Horizontally with Right
Side Down (See Figure 31)
Minimum 5 1/2” clearance is required for the drain trap
beneath the furnace.
NOTE: For horizontal installations, some of the
required hoses are found in the factory-installed hose
assemblies. Remove the hose clamps to obtain the
respective hoses needed for installation, and install
per the following directions.
1. Remove the drain trap and factory installed drain
tube assemblies.
2. Remove two 1’’ plugs from right side of cabinet.
3. (Draining the Collector Box) From outside the
cabinet, insert the non-grommet end hose #7 into the
back drain hole and secure to collector box drain port
using a silver clamp.
4. (Draining the Vent Elbow) Insert the straight barbed
coupling into the vent - drain elbow drip leg and
secure with a red clamp.
Non-ULN furnace shown (ULN similar)
Figure 31
5. From outside the cabinet, insert the non-grommet
end of hose #8 into the front cabinet drain hole and
secure on the vent - drain elbow barb tting using a
red clamp.
6. Place the drain hoses on the trap inlets and secure
with silver clamps. The outlet of the trap must face
the original bottom of furnace.
7. Using the two sheet metal screws provided in the
cabinet, secure the trap to the furnace.
8. Refer to Field Supplied Drain section for instructions
on eld supplied/installed drain on outlet of furnace
trap.
Downflow Model Installed Horizontally with Left
Side Down (See Figure 32)
Minimum 5 1/2” clearance is required for the drain trap
beneath the furnace.
*Also see Front Cover Pressure Switch Tube Location on
page 9.
1. Remove the factory installed drain trap and hose
assemblies. Leave the 100° elbow inserted and
clamped in the vent-drain elbow.
2. Remove two 1”plugs from left side of cabinet
3. (Draining the Collector Box) Remove the cap from
the left side of the collector box drain port (bottom
in horizontal left position) and install it on right side
drain port.
4. Place radius end of hose #4 (factory installed) on
the collector box drain port and secure with a silver
clamp.
5. Insert hose #2 from outside the cabinet in the front
drain hole.
6. Connect hose #4 & hose #2 together using a straight
barbed coupling and two gold clamps (factory
installed).
7. (Draining the Vent Elbow) Remove rubber plug from
vent – drain elbow side port.
8. The unused vent-drain elbow drip leg port must
be plugged to prevent ue gases from escaping.
Insert rubber plug removed in step 7 into the 100°
elbow. (Inserting a blunt tool such as a 3/16’’ Allen
wrench into the center of the rubber plug will stretch
the plug and allow complete insertion)

22
Hose #4
Hose #5
Hose #4
Hose #2
Non-ULN furnace shown (ULN similar)
Figure 32
9. Place radius end of hose #4 on the side port of vent
– drain elbow and secure with a gold clamp.
10. Insert a ½” diameter PVC pipe (factory installed) into
hose #4 and secure with a gold clamp.
11. Insert the non-grommet end of hose #5 (factory
installed) from outside the cabinet in the back drain
hole.
12. Insert 100º elbow in hose #5 and secure with a red
clamp.
13. Locate hose #4 and cut a cut o a 4” straight section
and discard the radius end.
14. Connect the 4” straight section of hose #4 to the
100º elbow and the PVC pipe and secure with red
clamps.
15. Connect the hoses to the trap inlets and secure
with silver clamps, drain trap outlet must point to the
original bottom of the furnace.
16. Using the two sheet metal screws provided in the
cabinet, secure the trap to the furnace.
17. Refer to Field Supplied Drain section for instructions
on eld supplied / installed drain on outlet of furnace
trap.
ELECTRICAL CONNECTIONS
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a
precaution when removing hole plugs.
Wiring Harness
The wiring harness is an integral part of this furnace.
Wires are color coded for identication purposes. Refer to
the wiring diagram for wire routings. If any of the original
wire as supplied with the furnace must be replaced, it must
be replaced with wiring material having a temperature
rating of at least 105°C. Any replacement wiring must be a
copper conductor.
115 Volt Line Connections
Before proceeding with electrical connections, ensure
that the supply voltage, frequency, and phase correspond
to that specied on the unit rating plate. Power supply to
the furnace must be NEC Class 1, and must comply with
all applicable codes. The furnace must be electrically
grounded in accordance with local codes or, in their
absence, with the latest edition of The National Electric
Code, ANSI NFPA 70.
Use a separate fused branch electrical circuit containing
properly sized wire, and fuse or circuit breaker. The fuse
or circuit breaker must be sized in accordance with the
maximum overcurrent protection specied on the unit
rating plate. An electrical disconnect must be provided at
the furnace location.
Connect hot, neutral, and ground wires as shown in the
wiring diagram located on the unit’s blower door. Metal
conduit is not considered a substitute for an actual ground
wire to the unit. For direct vent applications, the cabinet
opening to the junction box must be sealed air tight using
either an UL approved bushing such as Heyco Liquid
Tight or by applying non-reactive UL approved sealant to
bushing.
Line polarity must be observed when making eld
connections. Line voltage connections can be made
through either the right or left side panel. The furnace is
shipped congured for a left side electrical connection with
the junction box located inside the burner compartment. To
make electrical connections through the opposite side of
the furnace, the junction box must be relocated to the other
side of the burner compartment prior to making electrical
connections. To relocate the junction box, follow the steps
shown in the Junction Box Relocation section.
WARNING
High Voltage!
To avoid personal injury or death due to electrical
shock, disconnect electrical power before servic-
ing or changing any electrical wiring.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
WARNING
High Voltage!
To avoid the risk of injury, electrical shock or
death, the furnace must be electrically ground-
ed in accordance with local codes or in their
absence, with the latest edition of the National
Electric Code.

23
Junction Box Relocation
Line voltage connections can be made through either the
right or left side panel. The furnace is shipped congured
for a left side electrical connection. To make electrical
connections through the opposite side of the furnace,
the junction box must be relocated to the left side prior to
making electrical connections. To relocate the junction box,
perform the following steps.
1. Remove the burner compartment door.
2. Remove and save the two screws securing the
junction box to the side panel.
3. Relocate junction box and associated plugs and
grommets to opposite side panel. Secure with screws
removed in step 2.
IMPORTANT NOTE: Wire routing must not interfere
with circulator blower operation, filter removal
or routine maintenance.
To ensure proper unit grounding, the ground wire should
run from the furnace ground screw located inside the
furnace junction box all the way back to the electrical
panel. NOTE: Do not use gas piping as an electrical
ground. To conrm proper unit grounding, turn o the
electrical power and perform the following check.
1. Measure resistance between the neutral (white)
connection and any unpainted surface.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock
switch which interrupts unit voltage when the blower door
is opened for servicing. Do not defeat this switch.
CoolCloud™ HVAC Phone Application
Actual screens may dier, based on the mobile device.
Figure 33
Figure 34
Figure 35
This furnace is Bluetooth ready and functions with the
CoolCloud HVAC phone application designed to improve
the contractor’s setup / diagnostic experience. Users can
see specic model information, review active diagnostic
error codes, observe system status during operation,
make system menu adjustments, add site visit notes and
run system testing of all operational modes (heat / cool /
fan) directly from the phone. The phone application is also
capable of instantly updating the furnace software anytime
updates are available. The CoolCloud web application will
automatically notify the user if updates are available only
while connected on local Bluetooth network.
NOTE: The software update may take up to 20
minutes to complete.
Quick Start Guide For Communicating
Outdoor Units
EXTREMELY IMPORTANT: For all cooling calls, the
system only requires a single Y input from the thermostat.
For all heating calls (including dual fuel applications), the
system only requires a single W input from the thermostat.
Internal algorithms will control all available cooling and
heating stages, including dual fuel operation based on
these inputs. Any single-stage 24VAC thermostat is
applicable. For proper operation, set up the thermostat to

24
control a single-stage AC outdoor unit and a single-stage
gas furnace. The control board does not accommodate an
O wire thermostat input (reversing valve signal). If using a
heat pump, set up the thermostat, as stated above. Setting
the thermostat for the heat pump control or multi-stage
control may result in incorrect performance.
1. Connect all necessary thermostat wires to the
thermostat connector on the furnace control, as
instructed by the applicable wiring diagrams shown in
this section.
2. Connect the 1 & 2 wires between the indoor and
outdoor unit for communicating operation.
NOTE: Verify two-stage outdoor units include a
24 VAC transformer (for outdoor control board
power). Two-stage outdoor units may not behave
appropriately without this 24 VAC transformer.
R
C
G
Y
Optional
Optional
Optional if
feature
supported by
thermostat
INDOOR
BOARD TERMINAL
CONNECTIONS
OUTDOOR
BOARD TERMINAL
CONNECTIONS
OUTDOOR
TRANSFORMER
1
2
C
R
C
G
Y
1
2
C
Communicating Two-Stage Air Conditioner or Heat Pump
Figure 36
1
2
C
R
C
G
Y
Optional
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
OUTDOOR
BOARD TERMINAL
CONNECTIONS
1
2
C
R
C
G
Y
24 VAC
Thermostat
Communicating Inverter Air Conditioner or Heat Pump
Figure 37
3. Download the CoolCloud HVAC phone application for
charging and to congure/test system operations.
NOTE: When new versions of Bluetooth
Communication Software and Furnace Control
Software are available, the phone application
notifies the user. Software updates are classified
as either optional or mandatory and installed by
using the phone application. Ensure installation
of all mandatory software updates. Review notes
for optional software updates and install if
necessary.
NOTE: If an E11 code exists for the inverter system
immediately after line voltage is applied (code
shown in the CoolCloud HVAC phone application
or displayed on the inverter control), the System
Verification Test needs to be completed before
any other operation. See the following procedure.
1. Allow the system to remain Idle for 5 minutes.
2. Turn the system verication test on either by using the
CoolCloud phone application, or by entering the SUt
menu through the furnace pushbuttons.
3. Wait for the test to complete.
Charging
1. Inverter units using the CoolCloud HVAC phone
application or control board push button:
a. Charge the inverter units by setting the CR9 menu
(Charge Mode) to ON through the furnace control
board pushbuttons or the CoolCloud HVAC phone
application.
b. The System will remain in charge mode (high
speed) for 60 minutes before timing out.
c. The installer must manually shut o charge mode
once complete.
2. Two-stage outdoor units using the CoolCloud HVAC
application:
a. Charge the outdoor unit as required using the
charging information provided with the outdoor
equipment.
Gas Furnace Testing
1. Two-stage Operation using the CoolCloud HVAC
application:
a. Select the gas heat icon after entering the furnace
menus.
b. Select any value less than 50% for low stage
operation and any value greater than 50% for high
stage operation.
2. Conrm thermostat heating and cooling calls function
properly with equipment.
Quick Start Guide For Non-Communicating
Outdoor Units
When setting up a ComfortBridge™ furnace for use
with a non-communicating outdoor unit, the installing
contractor must set airow in the “ton” menu on the
PCB or in the CoolCloud HVAC APP. Failure to do so
will result in the furnace PCB displaying “IdL” and
the blower not operating with a call for cooling. This
condition indicates that the installer MUST set up the
airow, and is not an indication that the control board

25
needs replacement.
EXTREMELY IMPORTANT: For two-stage gas
heating, the system only needs a single W input.
Internal algorithms will control the staging of
the gas furnace automatically based on the single
W input. For non-communicating outdoor unit
wiring, see instructions below.
1. Use the wiring diagrams below to connect low voltage
thermostat wires.
NOTE: When installing the furnace with a non-
communicating heat pump wire directly from the
“O” terminal on the thermostat to the reversing
valve “O” terminal on the non-communicating heat
pump.
R
C
G
Y
Optional
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
1
2
C
R
C
G
Y
C
Y
Remote
Condensing Unit
(Single-Stage Cooling)
24 VAC
Thermostat
Non-Communicating Single-Stage A/C
Figure 38
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
1
2
C
R
C
G
Y
C
Y
Remote
Condensing Unit
(Two-Stage Cooling)
24 VAC
Thermostat
Y2
Non-Communicating Two-Stage A/C
Figure 39
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
Y
24 VAC
Thermostat
1
2
C
Heat Pump
Optional
R
C
Y
Non-Communicating Single-Stage Heat Pump
Figure 40
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
Y
24 VAC
Thermostat
1
2
C
Two Stage
Heat Pump
R
C
Y
Y2
Y2
Non-Communicating Two-Stage Heat Pump
Figure 41
2. Download the CoolCloud HVAC phone application.
NOTE: When new versions of Bluetooth
Communication Software and Furnace Control
Software are available, the phone application
notifies the user. Software updates are classified
as either optional or mandatory and installed by
using the phone application. Install all mandatory
software updates. Review notes for optional
software updates and install if necessary.
3. Select the Non-Comm Outdoor Setting menu (Od5)
using the onboard pushbuttons or the CoolCloud
HVAC phone application. Select 1 AC for single stage
Air Conditioners, 1HP for single stage heat pumps, 2
AC for two-stage air conditioners, and 2 HP for
two-stage Heat Pumps.
4. Go to the tonnage units menu (ton) and select the
tonnage value that corresponds to the desired airow
for the outdoor unit. See the following table.

26
NOTE: For two-stage non-communicating outdoor
units, the system will stage airflow automatically
for low stage operation.
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
1 400
2.3 920 3.6 1440 4.9 1960
1.1 440 2.4 960 3.7 1480
5
2000
1.2 480 2.5 1000 3.8 1520 5.1 2040
1.3 520 2.6 1040 3.9 1560 5.2 2080
1.4 560 2.7 1080 4 1600 5.3 2120
1.5 600 2.8 1120 4.1 1640 5.4 2160
1.6 640 2.9 1160 4.2 1680 5.5 2200
1.7 680
3 1200 4.3 1720 5.6 2240
1.8 720 3.1 1240 4.4 1760 5.7 2280
1.9 760 3.2 1280 4.5 1800 5.8 2320
2 800 3.3 1320 4.6 1840 5.9 2360
2.1 840 3.4 1360 4.7 1880 6 2400
2.2 880 3.5 1400 4.8 1920
Table 5
NOTE: The system will not provide airflows above
the Max Airflow Value.
3 Ton Models = 1,400 CFM
5 Ton Models = 2,200 CFM
5. Use the CoolCloud HVAC phone application to
congure and test furnace operations.
NOTE: The phone application cannot test a
non-communicating outdoor unit. Utilize the
thermostat for outdoor unit testing.
Gas Furnace Testing
a. Two-stage operation using the CoolCloud HVAC
application:
a. Select the gas heat icon after entering the
furnace menus.
b. Select any value less than 50% for low stage
operation and any value greater than 50% for
high stage operation.
6. Conrm thermostat heating and cooling calls
function properly with equipment.
Quick Start Guide for Gas Heat Only Setup
(No Outdoor Unit)
EXTREMELY IMPORTANT: The furnace only requires
a single W input for 2 stage gas heat control.
Internal algorithms will control staging of the
gas furnace automatically.
1. Connect all necessary thermostat wires to the
thermostat connector on the furnace control, as
shown in the following diagram.
R
W
DH/Y2
24 VAC
Thermostat
Indoor
Board Terminal
Connections
C
G
Optional
Optional
Dehum
R
W
C
G
Gas Heat Only
Figure 42
2. Download the CoolCloud HVAC phone application
and use it to congure and test furnace operations.
NOTE: When new versions of Bluetooth
Communication Software and Furnace Control
Software are available, the phone application
notifies the user. Software updates are classified
as either optional or mandatory and installed by
using the phone application. Install all mandatory
software updates. Review notes for optional
software updates and install if necessary.
Gas Furnace Testing
a. Two-stage operation using the CoolCloud HVAC
application:
a. Select the gas heat icon after entering the
furnace menus.
b. Select any value less than 50% for low stage
operation and any value greater than 50% for
high stage operation.
3. Conrm thermostat heating call functions correctly
with equipment.
Dehumidification
Control logic allows the furnace’s circulating blower to
operate at a reduced speed during a combined thermostat
call for cooling, and a dehumidication demand. This
lower blower speed increases moisture removal as
it passes through the indoor coil. The control board
includes a 24-volt dehumidication input (DH) on the
low-voltage wiring connector. The terminal features
dual conguration functionality and can accommodate
enabling dehumidication when the input is energized
or de-energized. When using an external dehumidistat,
connect between the R and DH terminals. If the humidistat
closes on humidity rise or the thermostat energizes this

27
terminal when dehumidication is required, set the control
board “dHL” (Dehum Logic) menu setting to “HI” using the
pushbuttons or CoolCloud HVAC phone application. If the
humidistat opens on humidity rise or the thermostat de-
energizes this terminal when dehumidication is required,
set the “dHL” (Dehum Logic) menu to “Lo” using the
pushbuttons or CoolCloud HVAC phone application.
Auxiliary Alarm Switch
The control is equipped with a 24VAC Aux Alarm,
accommodating condensate switch installations. The
connection is designated as CONDENSATE IN/OUT on
the control board. By default, the connected AUX switch
is normally closed and opens when the water level in the
evaporator coil base pan reaches an unacceptable level.
The control responds by displaying an EEf error code and
turning o the outdoor condensing unit. If the AUX switch
is detected to be in the closed position for 30 seconds,
regular operation resumes and the error message is no
longer displayed.
Pushbutton Menu
LEFT CENTER
RIGHT
Figure 43
The furnace includes three on-board pushbuttons allowing
users to navigate indoor and outdoor system menus.
The “RIGHT” and “LEFT” buttons enable the user to
scroll through the main menus and to then scroll through
available options within specic menus. The “CENTER”
button enters the main menu and then permanently selects
options within those menus.
NOTE: After scrolling to the desired option
within a menu, that option may be flashing on the
7-segment displays. This condition indicates no
selection is selected. Pressing the Center button
twice chooses the option. The first press stops
the flashing, and the second makes the selection
official and returns to the main menu.
Accessories
When installing an external humidier, dehumidier, or
ventilator, it may require airow setting modication at the
HVAC system to function accordingly.
1. Make sure the installed 24VAC thermostat is capable
of controlling the accessory or accessories.
2. Connect the appropriate accessory control wires
to the accessory devices from the thermostat
(see thermostat manual for connection and setup
instructions).
3. If the thermostat is capable of providing a continuous
fan call (G signal) during accessory operation:
Make sure to connect the thermostat G terminal to the
G terminal on the indoor unit. Set up the thermostat,
ensuring the G signal energizes during accessory
operation.
4. Select the appropriate fan only airow for the
accessory using the indoor unit pushbutton menus or
the CoolCloud HVAC phone application.
5. Using the thermostat, independently test each
accessory in parallel with the continuous fan mode for
proper airow.
115 VAC
HUM
115 VAC EAC
115 VAC Accessories - Accessories Wiring
Figure 44
Low Voltage Ventilation
The Ventilation connections provide dry contact for eld
ventilator wiring connections. These connections are
normally open and energize during the R-32 fault/alarm
condition. A VT IN and a VT OUT connectors are provided
and are shown in the image below.
Low Voltage A2L Alarm
The A2L alarm connection provides 24VAC for eld alarm
wiring connections. These connections are normally open
and energize during the R-32 fault/alarm condition. An A2L
Alarm connector is provided and is shown in the image
below.

28
R-32 Sensor
24 Volt A2L
Alarm
(Optional)
24 Volt
Ventilation
(Optional)
24 VAC Accessories - Accessories Wiring
Figure 45
Ramping Profiles
The variable-speed circulator oers four dierent
ramping proles. Use these proles to enhance cooling
performance and increase comfort level. Select ramping
proles on the user menu.
• Prole A (1) provides only an OFF delay of one (1)
minute at 100% of the cooling demand airow.
OFF
100% CFM 100% CFM
1 min
OFF
Figure 46
• Prole B (2) ramps up to full cooling demand airow
by rst stepping up to 50% of the total demand for
30 seconds. The motor then ramps to 100% of the
required airow. The motor provides a one-minute,
post-cycle OFF delay at 100% airow.
50% CFM
1/2 min
100% CFM
100% CFM
1 min
OFF
OFF
Figure 47
• Prole C (3) ramps up to 85% of the full cooling
demand airow and operates for approximately 7
1/2 minutes. The motor then steps up to the 100%
demand airow. The motor provides a one-minute,
post-cycle OFF delay at 100% airow.
100% CFM
OFF
OFF
Figure 48
• Prole D (4) ramps up to 50% demand for 1/2 minute,
then ramps to 85% of the full cooling demand for 7
1/2 minutes. Once elapsed, the motor runs at 100%
capacity for the remainder of the cycle, and provides a
post-cycle OFF delay at 50% airow.
OFF
OFF
Figure 49
115 Volt Line Connection or Electronic Air
Cleaner
WARNING
HIGH VOLTAGE
To avoid personal injury or death due to
electrical shock, disconnect electrical power
before servicing or changing any electrical
wiring.
The accessory load specications are as follows:
EAC 1.0 AMP maximum at 120 VAC
Table 6
The furnace integrated control module is equipped with
a line voltage accessory terminal for controlling power to
an optional, eld-supplied electronic air cleaner or any
device required to operate in parallel with a circulating fan
demand.
To connect an electronic air cleaner using the line voltage
EAC terminal:
• Turn OFF power to the furnace before installing any
accessories.
• Follow the air cleaner manufacturers’ instructions
for locating, mounting, grounding, and controlling
accessories. Utilize 1/4” quick connect terminals to
make accessory wiring connections to the furnace
integrated control module.
• Connect the hot terminal utilized for accessory
operation to the EAC terminal and the neutral side
of power to NEUTRAL bus on the integrated furnace
control or the neutral connection in the furnace
junction box.
• All eld wiring must conform to applicable codes.
• If necessary for the installer to supply additional line
voltage wiring to the inside of the furnace, wiring
must conform to all local codes and have a minimum
temperature rating of 105°C.
• All line voltage wire splices must be inside the furnace

29
cabinet.
R-32 FEATURES
R-32 Function
This furnace is equipped with a control board that is
capable of shutting o the gas heat and turning on the
blower fan in case of an R-32 refrigerant leak in the indoor
cooling unit. If the cooling unit that is paired with this
furnace does not utilize R-32 as the refrigerant, the R-32
functionalities in the furnace control board will need to be
turned o for the furnace to run properly.
R-32 function on the control board is ON by default. The
R-32 function can be disabled through the furnace control
by entering the A2L Function Enabled menu and selecting
“no”. If A2L function is disabled, the furnace control will
ignore all A2L functions. If A2L function is enabled, the
control will monitor the R-32 sensor information.
R-32 Sensor Wire Routing
Important Note: Wiring routing must not interfere
with circulator blower operation, lter removal or
routine maintenance. Wire should not be routed near
hot surfaces and should be protected from sharp
edges.
The R-32 Sensor wire coming from the indoor refrigeration
unit will need to be routed into the furnace and connected
to the connection point on the furnace control board. This
wire should be routed alongside the thermostat wires
through the low voltage openings in the left or right side of
the furnace blower compartment. Please see the electrical
section for the location of the R-32 Sensor connection on
the control board.
Furnace Startup
During furnace start up, the furnace control will identify the
connected R-32 sensor and will start monitoring the sensor
communication. A green LED located next to the sensor con-
nection will indicate if there is communication between the fur-
nace control and the R-32 sensor. The LED will be ON during
the duration of the startup and then will either start blinking
or turn OFF. The blinking LED signies that communication
with the R-32 sensor is present. The LED OFF signies that
there is no signal with the sensor.
If there are no alarms or faults, the furnace will go into regular
run mode after a warm up period. The furnace control monitors
the R-32 sensor once per second.
R-32 Refrigerant Leak
If the R-32 sensor on the indoor cooling unit detects a spec-
ied concentration of R-32 refrigerant, the furnace will enter
Mitigation Mode to dilute the refrigerant concentrations in case
of a leak. In Mitigation Mode, the furnace will do the following:
1. Display the A2L Refrigerant Leakage error code (EAL).
2. Shut down the gas operation.
3. Energize the optional ventilation and alarm outputs.
4. Run the fan at max CFM airow.
Once the R-32 sensor stops detecting a leak, the fan will
continue to run for 5 minutes. After the 5 minutes, if there
are no other alarms or faults, the control will de-energize the
optional ventilation and alarm outputs and then go back to
the original operating mode per the thermostat.
A2L Verification
The A2L Function Verication menu allows the installer to
verify if the R-32 function operates properly. This menu
simulates the refrigerant leak process and is only able to be
used when there are no active alarms or faults. To verify the
R-32 functions, enter the A2L Function Verication menu
and select “YES”. Once “YES” is selected, the furnace will
do the following:
1. Display the A2L Refrigerant Leakage code (EAL).
2. Shut down the gas operation.
3. Energize the optional ventilation and alarm outputs.
4. Run the fan at max CFM airow.
The control will exit the verication function if:
1. The 5 minute timeout expires or
2. An alarm or fault is detected or
3. The user turns OFF the A2L Function Verication.
STARTUP PROCEDURE & ADJUSTMENT
NOTE: This furnace is equipped with a control board
that is capable of monitoring for R-32 refrigerant leaks
in the indoor refrigeration unit. Please verify that the
R-32 sensor wire is plugged in to the furnace control
board before startup, if applicable. If furnace is not
paired with an R-32 Rergeration system, the default
settings in the furnace control board will need to be
changed. Please see the R-32 section for additional
information.
Furnace must have a 115 VAC power supply properly
connected and grounded. Correct operation is dependent
on proper wiring polarity. In addition to the following start-
up and adjustment items, refer to further information in
Operational Checks section.
Furnace Cabinet
Check that all furnace cabinet sealing components are in
place (plugs, grommets, gaskets). NOTE: Seal all bottom
panel return duct connections and perforations with duct
sealant compound or other suitable method to prevent
air leakage. For optimal performance, verify that all door
gaskets are correctly in place and replace as needed to
avoid air leakage.
Drain Trap Priming
Prime the drain trap before furnace startup. To prime, ll
both sides of the drain trap with water. This step ensures
proper furnace drainage upon startup and prohibits the
possibility of ue gases escaping through the drain system.
Furnace Operation
Purge gas lines of air prior to startup. Be sure not purge
lines into an enclosed burner compartment. Follow NFPA

30
54, National Fuel Gas Code for proper purging methods.
In Canada, follow approved purging methods in CAN/CSA
B149.1-15.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector,
or other approved method. Verify proper operation of all
required kits (high altitude, ect.).
Furnace Startup
1. Close the manual gas shuto valve external to the
furnace.
2. Turn o the electrical power to the furnace.
3. Set the room thermostat to the lowest possible
setting.
4. Remove the burner compartment door.
NOTE: The ignition device in this furnace lights
automatically. Do not try to light the burner by
hand.
5. Move the furnace gas valve manual control to the
OFF position.
6. Wait ve minutes, then smell for gas. Be sure to check
near the oor as some types of gas are heavier than
air.
7. If you smell gas after ve minutes, immediately follow
the safety instructions in the Safety Considerations
on page 3 of this manual. If you do not smell gas after
ve minutes, move the furnace gas valve manual
control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shuto valve external to the
furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room
temperature.
12. After the burners light, set the thermostat to the
desired temperature.
Furnace Shutdown
1. Set the thermostat to the lowest setting.
The integrated control will close the gas valve and
extinguish ame. Following a 15 second delay, the
induced draft blower will be de-energized. After the
fan OFF delay time expires, the blower de-energizes.
2. Remove the burner compartment door and move the
furnace gas valve manual control to the OFF position.
3. Close the manual gas shuto valve external to the
furnace.
4. Replace the burner compartment door.
GAS SUPPLY AND PIPING
CAUTION
To prevent unreliable operation or equipment damage,
the gas manifold pressure must be as specified on the unit
rating plate. Only minor adjustments should be made by
adjusting the gas valve pressure regulator.
WARNING
Possible property damage, personal injury, or death may
occur if the correct conversion kits are not installed. The
appropriate kits must be applied to ensure safe and proper
furnace operation. All conversions must be preformed by a
qualified installer or service agency.
Natural Gas
Minimum: 4.5" W.C.
Maximum: 10.0" W.C.
INLET GAS SUPPLY PRESSURE
Table 7
Inlet gas supply pressures must be maintained within the
ranges specied in the table 7. The supply pressure must
be constant and available with all other household gas red
appliances operating. The minimum gas supply pressure
must be maintained to prevent unreliable ignition. The
maximum must not be exceeded to prevent unit overring.
WARNING
To avoid possible unsatisfactory operation or equipment dam-
age due to underfiring of equipment, use the proper size of
natural gas piping needed when running pipe from the meter/
tank to the furnace.
Gas Valve
This unit is equipped with a 24 volt gas valve controlled
during furnace operation by the integrated control module.
Taps for measuring the gas supply pressure and manifold
pressure are provided on the valve.
The gas valve has a manual ON/OFF control located on
the valve itself. This control may be set only to the “ON”
or “OFF” position. Refer to the lighting instructions label
or Startup Procedure & Adjustment for use of this control
during start up and shut down periods.
Gas Piping Connections
WARNING
To avoid possible unsatisfactory operation or equipment dam-
age due to underfiring of equipment, use the proper size of
natural gas piping needed when running pipe from the meter/
tank to the furnace.
When sizing gas lines, be sure to include all appliances
which will operate simultaneously. The gas piping supplying
the furnace must be properly sized based on the gas ow

31
required, specic gravity of the gas, and length of the run.
The gas line installation must comply with local codes, or
in their absence, with the latest edition of the National Fuel
Gas Code, NFPA 54/ANSI Z223.1
To connect the furnace to the building’s gas piping, the
installer must supply a ground joint union, drip leg, manual
shuto valve, and line and ttings to connect to gas valve.
In some cases, the installer may also need to supply a
transition piece from 1/2” pipe to a larger pipe size.
The following stipulations apply when connecting gas
piping. Refer to Gas Piping Connections Figures 50, 51
and 52 for typical gas line connections to the furnace.
• Gas piping must be supported external to the furnace
cabinet so that the weight of the gas line does not
distort the burner rack, manifold or gas valve.
• Use black iron or steel pipe and ttings for building
piping. Where possible, use new pipe that is properly
chamfered, reamed, and free of burrs and chips. If old
pipe is used, be sure it is clean and free of rust, scale,
burrs, chips, and old pipe joint compound.
• Use pipe joint compound on male threads ONLY.
Always use pipe joint compound (pipe dope) that
is APPROVED FOR ALL GASES. DO NOT apply
compound to the rst two threads.
• Use ground joint unions.
• Install a drip leg to trap dirt and moisture before it can
enter the gas valve. The drip leg must be a minimum
of 3” long.
• Install a 1/8” NPT pipe plug tting, accessible for test
gauge connection, immediately upstream of the gas
supply connection to the furnace.
• Always use a back-up wrench when making the
connection to the gas valve to keep it from turning.
The orientation of the gas valve on the manifold must
be maintained as shipped from the factory. Maximum
torque for the gas valve connection is 375 in-lbs;
excessive over-tightening may damage the gas valve.
• Install a manual shuto valve between the gas
meter and unit within six feet of the unit. If a union
is installed, the union must be downstream of the
manual shuto valve, between the shuto valve and
the furnace.
• Tighten all joints securely.
1/2" 3/4" 1" 1 1/4" 1 1/2"
10 132 278 520 1050 1600
20 92 190 350 730 1100
30 73 152 285 590 980
40 63 130 245 500 760
50 56 115 215
440 670
60 50 105 195 400 610
70 46 96 180 370 560
80 43 90 170 350 530
90 40 84 160 320 490
100 38 79 150 305 460
Nominal Black Pipe Size
Length of
Pipe in Feet
Natural Gas Capacity of Pipe
In Cubic Feet of Gas Per Hour (CFH)
(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based
on 0.60 Specific Gravity Gas)
CFH =
BTUH Furnace Input
Heating Value of Gas (BTU/Cubic Foot)
Table 8
• Connection method must be in compliance with all
local and national codes. US: National Fuel Gas
Code (NFGC) NFPA 54-2012/ANSI Z223.1-2012 and
the Installation Standards, Warm Air Heating and Air
Conditioning Systems ANSI/NFPA 90B.
Connect the furnace to the building piping by one of
the following methods:
– Rigid metallic pipe and ttings.
– Semi-rigid metallic tubing and metallic ttings.
Aluminum alloy tubing must not be used in exterior
locations. In order to seal the grommet cabinet
penetration, rigid pipe must be used to reach the
outside of the cabinet. A semi-rigid connector to the
gas piping may be used from there.
• Use listed gas appliance connectors in accordance
with their instructions. Connectors must be fully in the
same room as the furnace.
• Protect connectors and semirigid tubing against
physical and thermal damage when installed. Ensure
aluminum-alloy tubing and connectors are coated to
protect against external corrosion when in contact
with masonry, plaster, or insulation, or subjected to
repeated wetting by liquids such as water (except rain
water), detergents, or sewage.
The gas piping may enter the left or right side of the
furnace cabinet. The installer must supply following ttings
starting from the gas valve.
• 1/2” dia x 2” long nipple
• 90 degree elbow
• Additional length of rigid piping enough to reach the
outside of the cabinet
• Grounded joint union
• Drip leg
• Manual gas shut o valve

32
A semi-rigid connector to the gas piping can be used
outside the cabinet per local codes. ½” NPT pipe and
ttings are required. Model requires one 90 degree elbow,
one 2” nipple and additional nipple to reach outside the
cabinet.
A semi-rigid connector to the gas piping can be used
outside the cabinet per local codes. From the elbow, the
length of pipe and the ttings required will vary by the side
chosen, location of union and cabinet width. The union may
be placed inside or outside of the cabinet.
Alternate
Gas Line
Location
Plug in
Alternate
Gas Line
Hole
* Ground
Joint
Pipe
Union
Gas Valve
*Ground
Joint
Pipe
Union
Manual Shut Off Valve
(upstream from
ground joint
pipe union)
Grommet
in Standard
Gas Line
Hole
Drip Leg
Burner
Manifold
* NOTE: Union may be inside furnace cabinet where allowed by local codes.
Upflow
Figure 50
Alternate
Gas Line
Location
Plug in
Alternate
Gas Line
Hole
Gas Valve
Burners
Manual Shut Off Valve
(upstream from ground joint pipe union)
Drip Leg
Grommet
in Standard
Gas Line
Hole
*Ground
Joint
Pipe Union
*Ground
Joint
Pipe Union
*NOTE: Union may be inside furnace cabinet where allowed by local codes.
Downflow
Non-ULN furnace shown (ULN similar)
Figure 51
Manual Shut Off Valve
(upstream from
ground joint pipe union)
Drip Leg
Plug in Alternate Gas Line Hole
Grommet in
Standard Gas Line Hole
Alternate
Union
Location
Burner
Drain Trap
Gas Valve
Plug in Main Gas Line Hole
Manifold
Upflow - Horizontal Left
Downflow - Horizontal Left Similar (not shown)
Figure 52
Gas Piping Checks
WARNING
To avoid the possibility of explosion or fire, never use a
match or open flame to test for leaks.
Before placing unit in operation, leak test the unit and gas
connections.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector, or
other approved testing methods.
CAUTION
To prevent possible property damage or personal injury
due to fire, the following instructions must be performed
regarding gas connections, pressure testing, location of
shutoff valve and installation of gas piping.
NOTE: Never exceed specified pressures for
testing. Higher pressure may damage the gas valve
and cause subsequent overfiring, resulting in heat
exchanger failure.
Disconnect this unit and shuto valve from the gas supply
piping system before pressure testing the supply piping
system with pressures in excess of ½ psig (3.48 kPa).
Isolate this unit from the gas supply piping system by
closing its external manual gas shuto valve before
pressure testing supply piping system with test pressures
equal to or less than ½ psig (3.48 kPA).

33
WARNING
If the gas furnace is installed in a basement, an excavat-
ed area or confined space, it is strongly recommended to
contact a certified contractor to install a gas detecting
warning device in case of a gas leak.
CIRCULATING AIR & FILTERS
Duct Work - Air Flow
WARNING
Never allow the products of combustion, including carbon
monoxide, to enter the return duct work or circulation air
supply.
Duct systems and register sizes must be properly designed
for the CFM and external static pressure rating of the
furnace. Ductwork should be designed in accordance
with the recommended methods of “Air Conditioning
Contractors of America” Manual D.
Install the duct system in accordance with Standards of
the National Board of Fire Underwriters for the Installation
of Air Conditioning, Warm Air Heating and Ventilating
Systems. Pamphlets No. 90A and 90B.
A closed return duct system must be used, with the
return duct connected to the furnace. NOTE: Ductwork
must never be attached to the back of the furnace. For
installations requiring 1800 CFM or more, use a bottom
return or two-sided return. Flexible joints may be used
for supply and return connections to reduce noise
transmission. To prevent the blower from interfering with
combustion air or draft when a central return is used, a
connecting duct must be installed between the unit and the
utility room wall. Never use a room, closet, or alcove as a
return air chamber.
Checking Duct Static
Refer to your furnace rating plate for the maximum ESP
(external duct static) rating.
Total external static refers to everything external to the
furnace cabinet. Cooling coils, lters, ducts, grilles,
registers must all be considered when reading your total
external static pressure. The supply duct pressure must be
read between the furnace and the cooling coil. This reading
is usually taken by removing the “A” shaped block o
plate from the end on the coil; drilling a test hole in it and
reinstalling the block o plate. Take a duct static reading
at the test hole. Tape up the test hole after your test is
complete. The negative pressure must be read between
the lter and the furnace blower.
Too much external static pressure will result in insucient
air that can cause excessive temperature rise. This can
cause limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed as
follows:
1. With clean lters in the furnace, use a manometer to
measure the static pressure of the return duct at the
inlet of the furnace (Negative Pressure).
2. Measure the static pressure of the supply duct
(Positive Pressure).
3. The dierence between the two numbers is .4” w.c.
Example:
static reading from return duct = -.1” w.c.
static reading from supply duct = .3” w.c.
total external static pressure on this system = .4” w.c.
NOTE: Both readings may be taken simultaneously
and read directly on the manometer if so
desired. If an air conditioner coil or Electronic
Air Cleaner is used in conjunction with the
furnace, the readings must also include theses
components, as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum
listed on the furnace rating plate, check for closed
dampers, registers, undersized and/or oversized poorly laid
out duct work.
The temperature rise of the furnace must be within the
temperature rise range listed on the furnace rating plate.
CUTAWAY OF DUCTWORK
TO EXPOSE COIL
DIGITAL
MANOMETER
RETURN
AIR
Mode
.
SUPPLY
AIR
Checking Static Pressure
(80% Furnace Shown, 90% Similar)
Figure 53
WARNING
Edges of sheet metal holes may be sharp. Use gloves as
a precaution when removing sheet metal from return air
openings.

34
Bottom Return Air Opening [Upflow Models]
The bottom return air opening on upow models utilizes
a “lance and cut” method to remove sheet metal from the
duct opening in the base pan. To remove, simply press
out the lanced sections by hand to expose the metal strips
retaining the sheet metal over the duct opening. Using
tin snips, cut the metal strips and remove the sheet metal
covering the duct opening. In the corners of the opening,
cut the sheet metal along the scribe lines to free the duct
anges. Using the scribe line along the duct ange as a
guide, unfold the duct anges around the perimeter of the
opening using a pair of seamer pliers or seamer tongs.
NOTE: Airflow area will be reduced by
approximately 18% if duct flanges are not
unfolded. This could cause performance issues
and noise issues.
CUT FOUR CORNERS
AFTER REMOVING SHEET
METAL
CUT USING TIN SNIPS
PRESS OUT BY HAND
SCRIBE LINES OUTLINING
DUCT FLANGES
Duct Flange Cut Outs
Figure 54
When the furnace is used in connection with a cooling unit,
the furnace should be installed in parallel with or on the
upstream side of the cooling unit to avoid condensation
in the heating element. With a parallel ow arrangement,
the dampers or other means used to control the ow of
air must be adequate to prevent chilled air from entering
the furnace and, if manually operated, must be equipped
with means to prevent operation of either unit unless the
damper is in the full heat or cool position.
When the furnace is installed without a cooling coil, it is
recommended that a removable access panel be provided
in the outlet air duct. This opening shall be accessible
when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for visual light
inspection or such that a sampling probe can be inserted
into the airstream. The access panel must be made to
prevent air leaks when the furnace is in operation.
NOTE: In a horizontal installation the air
conditioning coil must be adequately supported
by proper brackets and supports. Inadequate coil
support can result in furnace cabinet distortion
and air leakage.
When the furnace is heating, the temperature of the return
air entering the furnace must be between 55°F and 100°F.
Filters - Read This Section Before Installing The
Return Air Duct work
Filters must be used with this furnace. Discuss lter
maintenance with the building owner. Filters do not ship
with this furnace, but must be provided, sized and installed
externally by the installer. Filters must comply with UL900
or CAN/ULCS111 standards. Damage or repairs due to
the installation of the furnace without lters is not covered
under the warranty.
On upow units, guide dimples locate the side return cutout
locations. Use a straight edge to scribe lines connecting
the dimples. Cut out the opening on these lines. NOTE: An
undersized opening will cause reduced airow.
Refer to the Filter Sizing Chart to determine lter area
requirements.
Model Minimum Recommended Filter Size^
*RVS960603BU 1 - 16 X 25 Side or Bottom
*RVS960805CU 1 - 20 X 25 Bottom/2 - 16 X 25 Side Return
*DVS960603BU 2 - 10 X 20 or 1 - 14 X 25 Top Return
*DVS960805CU 2 - 14 X 20 or 1 - 20 X 25 Top Return
Filter Sizing Chart
^ Larger filters may be used, filters may also be centrally located.
Table 9
Change filters before occupants take ownership of a new home!
One of the most common causes of a problem in a forced
air heating system is a blocked or dirty lter. Circulating
air lters must be inspected monthly for dirt accumulation
and replaced if necessary. Failure to maintain clean
lters can cause premature heat exchanger failure. A
new home may require more frequent replacement until
all construction dust and dirt is removed. Circulating air
lters are to be installed in the return air duct external to
the furnace cabinet. Consider installing an air cleaner with
deep-pleated media lter at the time of furnace installation.
A deep-pleated lter with a MERV rating of 8 (minimum)
will often provide better ltration to protect equipment and
the air distribution system than a standard 1” lter and
often has lower static pressure loss than a 1” lter. Also
a deep-pleated lter will typically require less frequent
replacement intervals. Avoid using highly restrictive 1”
lters which produce static pressure loss greater than .25”
W.C. In some installations the minimum lter size required
(consult lter sizing chart above) will not lend itself to a lter
installation on the side of the furnace. The installation of a
centrally installed air cleaner cabinet or a return duct lter
installation may oer more practicality.

35
AIR FLOW
SIDE RETURN
EXTERNAL FILTER
RACK KIT
(EITHER SIDE)
Possible Upright Upflow
Figure 55
Horizontal Installations
Filters must be installed in either the central return register
or in the return air duct work.
Gas Supply Pressure Measurement
Gas Pressure Test
CAUTION
To prevent unreliable operation or equipment damage, the
inlet gas supply pressure must be as specified on the unit
rating plate with all other household gas fired appliances
operating.
The line pressure supplied to the gas valve must be within
the range specied on Table 7 (page 30). The supply
pressure can be measured at the gas valve inlet pressure
tap or at a hose tting installed in the gas piping drip leg.
The supply pressure must be measured with the burners
operating. To measure the gas supply pressure, use the
following procedure.
1. Turn OFF gas to furnace at the manual gas shuto
valve external to the furnace. Back inlet pressure test
port screw turn counter clockwise, not more than one
turn.
2. Connect a calibrated manometer (or appropriate gas
pressure gauge) at either the gas valve inlet pressure
tap or the gas piping drip leg. See White-Rodgers
36J22Y-204 gas valve gure below for location of inlet
pressure tap.
Regulator Cover
Screw
Mode
10.0
White-Rodgers Model 36J22Y-204 Connected to Manometer
Figure 56
NOTE: If measuring gas pressure at the drip leg, a
field-supplied hose barb fitting must be installed
prior to making the hose connection. If using the
inlet pressure tap on the White-Rodgers 36J22 gas
valve, then use the 36G/J Valve Pressure Check Kit,
Part No. 0151K00000S.
3. Turn ON the gas supply and operate the furnace and
all other gas consuming appliances on the same gas
supply line.
4. Measure furnace gas supply pressure with burners
ring. Supply pressure must be within the range
specied in the Inlet Gas Supply Pressure table 7
(page 30).
If supply pressure diers from table, make the
necessary adjustments to pressure regulator, gas
piping size, etc., and/or consult with local gas utility.
5. Turn OFF gas to furnace at the manual shuto valve
and disconnect manometer. Reinstall plug and tighten
as needed before turning on gas to furnace.
6. Turn OFF any unnecessary gas appliances stated in
step 3.

36
Mode
10.0
Measuring Inlet Gas Pressure (Alt. Method)
Figure 57
Gas Manifold Pressure Measurement and
Adjustment
Only small variations in gas pressure should be made by
adjusting the gas valve pressure regulator. The manifold
pressure must be measured with the burners operating.
To measure and adjust the manifold pressure, use the
following procedure.
1. Turn OFF gas to furnace at the manual gas shuto
valve external to the furnace.
2. Turn o all electrical power to the system.
3. Outlet pressure tap connections: White-Rodgers
36J22 valve: Back outlet pressure test screw (outlet
pressure tap) out one turn (counterclockwise, not
more than one turn).
4. Connect calibrated manometer (or appropriate
pressure gauge) at the gas valve outlet pressure tap.
See White-Rodgers 36J22Y-204 gas valve Figure 56
for location of outlet pressure tap.
5. Turn ON the gas supply.
6. Turn on power and close thermostat “R” and “W”
contacts to provide a call for heat.
7. Measure the gas manifold pressure with burners
ring. Adjust manifold pressure using the Manifold
Gas Pressure table 10 shown below.
Gas Range Nominal
Natural 2.8 - 3.2" w.c. 3.0" w.c.
Manifold Gas Pressure
Table 10
8. Remove regulator cover screw from the outlet
pressure regulator adjust tower and turn screw
clockwise to increase pressure or counterclockwise to
decrease pressure. Replace regulator cover screw.
9. Turn o all electrical power and gas supply to the
system.
10. Remove the manometer hose from the hose barb
tting or outlet pressure tap.
11. Replace outlet pressure tap: White-Rodgers 36J22
valve: Turn outlet pressure test screw in to seal
pressure port (clockwise, 7 in-lb minimum).
12. Turn on electrical power and gas supply to the
system.
13. Close thermostat contacts “R” and “W” to energize the
valve.
Using a leak detection solution or soap suds, check for
leaks at outlet or screw (White-Rodgers valve). Bubbles
forming indicate a leak. SHUT OFF GAS AND REPAIR ALL
LEAKS IMMEDIATELY!
CAUTION
To prevent unreliable operation or equipment damage, the
inlet gas supply pressure must be as specified on the unit
rating plate with all other household gas fired appliances
operating.
Gas Input Rate Measurement (Natural Gas Only)
The actual gas input rate to the furnace must never be
greater than that specied on the unit rating plate. To
measure natural gas input using the gas meter, use the
following procedure.
1. Turn OFF the gas supply to all other gas-burning
appliances except the furnace.
2. While the furnace is operating at high re rate, time
and record one complete revolution of the gas meter
dial, measuring the smallest quantity, usually the dial
that indicates 1/2 cu. ft. per revolution. You will use this
number to calculate the quantity of gas in cubic ft. if
the furnace would consume if it ran steadily for one
hour (3600 seconds).
3. If the 1/2 cu. ft. dial was used, multiply your number x
2.
EXAMPLE: If it took 23 seconds to complete one
revolution of the 1/2 ft. dial (23 x 2 = 46).
This tells us that at this rate, it would take 46 seconds to
consume one cu. ft. of gas.
This tells us that in one hour, the furnace would consume
78 cu. ft. of gas (3600 / 46 = 78).
The typical value range for 1 cu. ft. of natural gas is around
1025 BTU. Check with your gas utility, if possible. In this
example, the furnace is consuming 80,000 BTUH.
NOTE: The final manifold pressure cannot vary
by more than ± 0.2” w.c. for Natural gas from the
specified setting. Consult your local gas supplier
if additional input rate adjustment is required.

37
4. Turn ON gas to and relight all other appliances
turned o in step 1. Be certain that all appliances
are functioning properly and that all pilot burners (if
applicable) are operating.
Temperature Rise
Air temperature rise is the temperature dierench between
supply and return air. The proper amount of temperature
rise is usually obtained when the unit is operated at the
rated input with the “as shipped” blower speed. If the
correct amount of temperature rise is not obtained, it may
be necessary to change the blower speed.
Temperature rise must be within the range specied on the
unit rating plate. An incorrect temperature rise may result
in condensing in or overheating of the heat exchanger.
The temperature rise of the furnace must be within the
temperature rise range listed on the furnace rating plate.
Determine and adjust temperature rise as follows:
1. Operate furnace with burners ring for approximately
ten minutes. Ensure all registers are open and all
duct dampers are in their nal (fully or partially open)
position.
2. Place thermometers in the return and supply ducts as
close to the furnace as possible. Thermometers must
not be inuenced by radiant heat by being able to
“see” the heat exchanger.
3. Subtract the return air temperature from the supply
air temperature to determine the air temperature rise.
Allow adequate time for thermometer readings to
stabilize.
4. Adjust temperature rise by adjusting the circulator
blower speed. Increase blower speed to reduce
temperature rise. Decrease blower speed to increase
temperature rise. Refer to Startup Procedure and
Adjustment - Circulator Blower Speeds for speed
changing details.
SUPPLY
AIR
RETURN
AIR
Temperature Rise Measurement
Figure 58
OPERATIONAL CHECKS
SAFETY CIRCUIT DESCRIPTION
CAUTION
To avoid personal injury or death, do not remove internal
compartment covers or attempt any adjustment. Electrical
components are contained in both compartments. Contact
a qualified service agent at once if an abnormal operation
should develop.
Do not bypass safety devices.
WARNING
A number of safety circuits are employed to ensure safe
and proper furnace operation. These circuits serve to
control any potential safety hazards and serve as inputs
in the monitoring and diagnosis of abnormal function.
These circuits are continuously monitored during furnace
operation by the integrated control module.
Integrated Control Module
The integrated control module is an electronic device
which, if a potential safety concern is detected, will take the
necessary precautions and provide diagnostic information
through an LED.
Primary Limit
The primary limit control is located on the partition panel
and monitors heat exchanger compartment temperatures.
It is a normally closed (electrically), automatic reset,
temperature activated sensor. The limit guards against
overheating as a result of insucient conditioned air
passing over the heat exchanger.
Auxiliary Limit
The auxiliary limit controls are located on or near the
circulator blower and monitors blower compartment
temperatures. They are a normally closed (electrically),
manual-reset sensors. These limits guard against
overheating as a result of insucient conditioned air
passing over the heat exchanger.
Burner Temperature Switch
The burner temperature switch is mounted on the burner
assembly to monitor the burner box temperature. It is
normally closed (electrically), auto-reset sensor. This
switch guards against the burner ames not being properly
drawn into the heat exchanger.
Pressure Sensor
Pressure sensor is mounted on the induced draft blower.
Its function is to regulate the induced draft blower’s speed
in order to maintain proper air-fuel ratio for clean and
reliable combustion.

38
Pressure Switches
The pressure switches are normally open (closed during
operation) negative air pressure activated switches. They
monitor the airow (combustion air and ue products)
through the heat exchanger via pressure taps located on
the induced draft blower and the coil front cover. These
switches guard against insucient airow (combustion
air and ue products) through the heat exchanger and/or
blocked condensate drain conditions.
Flame Sensor
The ame sensor is a probe mounted to the burner
assembly which uses the principle of ame rectication to
determine the presence or absence of ame.
TROUBLESHOOTING
Troubleshooting Chart
Refer to the Troubleshooting Codes chart for assistance in
determining the source of unit operational problems.
MAINTENANCE
WARNING
High Voltage!
To avoid personal injury or death due to electri-
cal shock, disconnect electrical power BEFORE
performing any service or maintenance.
Annual Inspection
The furnace should be inspected by a qualied installer, or
service agency at least once per year. This check should
be performed at the beginning of the heating season.
This will ensure that all furnace components are in proper
working order and that the heating system functions
appropriately. Pay particular attention to the following
items. Repair or service as necessary.
• Flue pipe system. Check for blockage and/or leakage.
Check the outside termination and the connections at
and internal to the furnace.
• Heat exchanger. Check for corrosion and/or buildup
within the heat exchanger passageways.
• Burners. Check for proper ignition,and ame sense.
• Drainage system. Check for blockage and/or leakage.
Check hose connections at and internal to furnace.
• Wiring. Check electrical connections for tightness and/
or corrosion. Check wires for damage.
• Filters. Check for Blockage
• R-32 Sensor Wire. Check R-32 sensor wire
connection for tightness and check wire for damage.
FILTERS
Filter Maintenance
A return air lter is not supplied with this furnace; however,
there must be a means of ltering all of the return air. The
installer will supply lter(s) at the time of installation.
Improper lter maintenance is the most common cause of
inadequate heating or cooling performance. Filters should
be cleaned (permanent) or replaced (disposable) every two
months or as required.
Burner
WARNING
To prevent personal injury or death, do not remove any in-
ternal compartment covers or attempt any adjustment. Elec-
trical components are not contained in both compartments.
Contact a qualified service agent at once if an abnormal
flame appearance should develop.
The Ultra Low NOx furnace uses a premix burner. The
burner box is sealed to achieve safe and reliable operation.
SCREW
SENSOR
GASKET
IGNITOR
GASKET
LIMIT
GASKET
BURNER BOX
Burner Box
Figure 59
NOTE: Location of flame sensor, igniter and
burner limit switch may vary depending on the
model.
Induced Draft and Circulator Blowers
The bearings in the induced draft blower and circulator
blower motors are permanently lubricated by the
manufacturer. No further lubrication is required. Check
motor windings for accumulation of dust which may cause
overheating. Clean as necessary.

39
Condensate Trap and Drain System
(Qualified Servicer Only)
Annually inspect the drain tubes, drain trap, and eld-
supplied drain line for proper condensate drainage. Check
drain system for hose connection tightness, blockage, and
leaks. Clean or repair as necessary.
Flame Sensor (Qualified Servicer Only)
Under some conditions, the fuel or air supply can create a
nearly invisible coating on the ame sensor. This coating
acts as an insulator causing a drop in the ame sense
signal. If the ame sense signal drops too low the furnace
will not sense ame and will lock out. The ame sensor
should be carefully cleaned by a qualied servicer using
emery cloth or steel wool. Following cleaning, the ame
sense signal should be above 3 micro amps.
Flue Passages (Qualified Servicer Only)
The heat exchanger ue passageways should be inspected
at the beginning of each heating season.
BEFORE LEAVING AN INSTALLATION
• Cycle the furnace with the thermostat at least three
times. Verify cooling and fan only operation.
• Review the Owner’s Manual with the homeowner and
discuss proper furnace operation and maintenance.
• Leave literature packet near furnace.
REPAIR AND REPLACEMENT PARTS
• When ordering any of the listed functional parts, be
sure to provide the furnace model, manufacturing, and
serial numbers with the order.
• Although only functional parts are shown in the parts
list, all sheet metal parts, doors, etc. may be ordered
by description.
• Parts are available from your distributor.
Functional Parts List-
Gas Valve Blower Motor
Gas Manifold Blower Wheel
Natural Gas Orice Blower Mounting Bracket
Igniter Blower Cuto
Flame Sensor Blower Housing
Burner Temperature Switch Pressure Switches
Primary Limit Switch Burner Assembly
Coil Front Cover Drain Trap
Auxiliary Limit Switch Burner Box Gasket
Transformer Integrated Control Module
Door Switch Pressure Sensor
Induced Draft Blower
Heat Exchanger with Recuperator Coil

40
MENU OPTIONS
LED
Display
Menu Description
tF
Gas Heat Airflow Trim (default = 0%)
HdI
M aximum Compresso r Run Time Between Defro st Cycles (default
= 120 minutes)
HFd
Heat Pump Heating Airflow Off Delay Time (default = 60 seconds)
Hnd
Heat Pump Heating Airflow On Delay Time (default = 5 seconds)
HP
Select the range that includes the desired compresso r RPS for inverter heating
operation. See inverter manual fo r menu options
HS
Maximum Compressor RPS for Heating Mode (inverter only)
Ht
Reset all heat pump heating settings to factory default.
HSt
Percentage of high stage heat pump heating airflo w to run during
low stage operation . (default = 70%)
HtF
Heat Pump Indoor Airflow Trim (default = 0%)
HtH
High Heating Airflow Trim for Inverter Units. See inverter manual for menu option s
and defaults
HtI
Intermediate Heating Airflo w Trim for Inverter Units. See inverter manual fo r menu
options and defaults
HtL
Low Heating Airflo w Trim for Inverter Units. See inverter manual for menu option s
and defaults
LF
View 6 mo st recent fault code s and clear all fault code s if desired. (furnace)
Ln
Restart communications between the indoor and outdoor unit.
DS
Select the number of stages fo r the non-co mmunicating outdoor
unit. Default = OFF meaning no outdoo r unit.
PPd
Enable Pump Down Mode
Fd
Resets furnace settings to factory defaults.
SCt
M aximum Current Optio n (system will limit capacity to percentage
of maximum current) (default = 100%)
S
Control Shared Data Revision Number
St
Resets all outdoo r unit settings to facto ry defaults.
St
System Verification Test (inverters only)
tn
Indoo r Airflow fo r non-co mmunicating outdoo r units. (values based
on 400CFM per ton ) (default = 3.0 Ton)
Ut
Select Outdoor Unit Elevation (SL=same level, OL = outdoor lower, IL = indoor lower)
Default = Outdoor Lower
CFS
1 = system will try to satisfy the thermostat quickly. 5 (default) = system will try to
satisfy the thermostat more slowly.
tt
Menu is enabled if the SFC menu is set to 6. Select the target time the system will
attempt to satisfy the thermostat.
SUP
Menu is enabled if the SFC menu is set to 6. Select the percentage past the target
time when the system will transition to gas furnace operation during heat mode.
tt
Menu is enabled if the SFC is set to 6. (the gas furnace will run during the next heat call
if the heat pump fails to satisfy the custom target time for this number of
consecutive cycles) (default = 20 cycles)
Utt
Menu is enabled if the SFC menu is set to 6. (if low stage gas heat is able to
consecutively satisfy the thermostat under the set target time for this number of
cycles, the system will transition to the heat pump for primary heating)
SdP
Menu is enabled if the SFC menu is set to 6. (this percentage will help determine when
switching back to heat pump operation is appropriate. Default = 20%. If target time =
20 minutes, low stage furnace operation must satisfy the thermostat by less than 16
minutes. (target time - 20% default = 16 minutes).
LED
Display
Menu Description
ASE
Aux (condensate switch enabled)
t
Enable or disable inverter boost operation. (Compressor speed may increase when
this feature is on) (inverter only)
tt
B
oo
st
mode will operate above this selected temperature. On =
boo st mod e always on (default = 105°F) (inverter only)
CAP
Cooling Airflow Profile setting (default = profile D shown as 4)
CP
Heat Pump compressor lockout temperature. Furnace will act as primary heat
source below this temperature. (Default = 45° F)
CdL
Co mpr
esso r off delay at the beginning and end of a defro st cycle.
(default = 30 second s)
CFd
Cooling Airflow Off Delay Time. (default = 60 seconds)
CL
Resets all cooling settings to factory default.
Cnd
Coo ling Airflo w On Delay Time (default = 5 second s)
C
Control Firmware Revision Number
Cg
Enable or disable inverter charge mode.
CP
Select the range that includes the desired co mpresso r RP S for inverter coo ling
operation . See inverter manual for menu options
CS
Maximum Compressor RPS for cooling mode. (inverter only)
CSt
Pe
r
c
en
tage of high stage coo ling airflo w to run during low stage
operation . (default = 70%)
CtF
Cooling Airflow Trim (default 0%)
CtH
H
ig
h
Coo ling Airflo w Trim fo r inverter units. See inverter manual for menu options
and defaults
CtI
Intermediate Cooling Airflow Trim for inverter units. See inverter manual for menu
options and defaults
CtL
Low Cooling Airflow Trim for inverter units. See inverter manual for menu options
and defaults
dF
C
om
p
resso r run time between defrost cycles. (default = 30
minutes) (2 stage units)
dHE
Enables or disables dehumidification feature in the outdoor unit. (default = Enabled)
dHL
Select "1" to enable dehumidification when the thermostat DH
terminal is energized. Select "0" to enable dehumidification when the thermostat DH
terminal is de-energized. (default = 1)
FCL
View 6 most recent fault code s and Clear Fault Codes if desired
(outdoo r co mmunicating units)
FdF
Force system into a defrost cycle (inverter units)
FSd
Constant Fan Speed as percent of maximum airflow. (Default = 25%)
Fd
Gas Heat Fan Off Delay (default = 90 seconds)
nd
Gas Heat Fan On Delay (default = 30 seconds)
St
Percentage of high stage gas heating airflow to run during low stage gas heat
operation. (default = 70%)
H
Gas Heat
F1
Last 10 Faults
A2
A2L Function Verification
A2E
A2L Function Enabled

41
STATUS CODES
LED
Display Description of System Status
1AC Compressor Cooling, Low Stage (non-communicating units)
2AC Compressor Cooling, High Stage (non-communicating units)
1AC Compressor Heat, Low Stage (non-communicating units)
2AC Compressor Heat, High Stage (non-communicating units)
AC Compressor Cooling, Single-Stage (single stage non-comm. units)
AC1 Compressor Cooling, Low Stage (communicating units)
AC2 Compressor Cooling, High Stage (communicating units)
dHU Dehumidication
FAn Constant Fan
HP Compressor Heat, Single-Stage (single stage non-comm. units)
HP1 Compressor Heat, Low Stage (Communicating Units)
HP2 Compressor Heat, High Stage (Communicating Units)
IDL Idle
vAC Inverter Cooling
vHP Inverter Heating
dFt Defrost
gH Gas Heat

42
TROUBLESHOOTING CHART
Symptom
LED Status
Fault Description Corrective Actions
Check filters for blockage, clean filters or remove
obstruction
Check ductwork for blockage, remove obstruction
and verify all registers are fully open
Verify ductwork is appropriately sized for system,
resize and/or replace ductwork if necessary
Furnace fails to operate
E1
Analog Pressure Sensor Reference Error.
APS reference is out of the range (5.0+/-
0.2)V for 5 seconds
Verify electrical connections to pressure sensor
Furnace fails to operate
E1
Analog Pressure Sensor Null Error.
Inconsistent Pressure reading with inducer
OFF
Verify electrical connections to pressure sensor
Furnace fails to operate
E1d
Analog Pressure Sensor Span Error.
Inconsistent pressure reading with inducer
ON
Verify electrical connections to pressure sensor
Need to check the APS Sensor or its connection if
this error is occurred. The failure conditions occur as
per the following for 5 seconds:
1. The vent is blocked, and the pressure could not
reach (lower than) the target pressure when inducer
stayed at maximum RPM which stored in Shared Data.
2. The vent is blocked, and the pressure could not
reach (higher than) the target pressure when inducer
stays at the minimum RPM (Pressure Switch Min
Limit).
3. APS fault causes the pressure fixed at a value lower
than the target pressure when inducer stayed at
maximum RPM which stored in Shared Data.
4. APS fault causes the pressure fixed at a value higher
than the target pressure when inducer stayed at
minimum RPM (Pressure Switch Min Limit).
Check the APS Sensor or its connection if this error is
occurred. APS input voltage is out of the below ranges
for 5 seconds.
1. If 2" is selected, the voltage range shall be from (0.25-
0.06)V to (4+0.06)V.
2. If 4" is selected, the voltage range shall be from (0.5-
0.06)V to (4.5+0.06)V.
Grounding fault
Poor neutral connection
Check for correct gas pressure Check for correct
burner alignment
Check for and correct burner restriction
Furnace fails to operate
Ed
Data not yet on network
Populate shared data set using CoolCloud HVAC App
Operation different than
expected or no operation
Ed1
Invalid shared data
Verify shared data set is correct for the specific model,
re-populate data using CoolCloud HVAC App if
required
Furnace operates at reduced
performance or operates on
low stage when high stage is
expected
E
Airflow is lower than demanded
Furnace fails to operate
E1
Analog Pressure Error (Blocked Vent Error)
Furnace fails to operate
E1f
Analog Pressure Sensor, Input Error
Furnace fails to operate
Furnace fails to operate
E1
Verify neutral wire connection to furnace & continuity
to ground source
E11
Open roll out switch

43
TROUBLESHOOTING CHART
Symptom
LED Status
Fault Description Corrective Actions
Locate and correct gas interruption
Check front cover pressure switch operation and
verify proper drainage (hose, wiring, contact
operation), correct if necessary Replace or realign
igniter
Check flame sense signal, sand sensor if coated
and/or oxidized
Check flue piping for blockage, proper length, elbows,
and termination
Verify proper induced draft blower performance
Pressure switch circuit is closed at start of
heating cycle
Pressure switch contacts sticking
Short in pressure switch circuit wiring
Pressure switch circuit is not closed
Inspect pressure switch hose, repair/replace if
necessary
Pressure switch hose blocked pinched, or
connected improperly
Inspect flue and/or inlet air piping for blockage, proper
length, elbows, and termination
Blocked flue and/or inlet air pipe, blocked
drain system or weak induced draft blower
Check drain system, correct as necessary
Incorrect pressure switch set point or
malfunctioning switch contacts
Check induced draft blower performance, correct as
necessary
Loose or improperly connected wiring
Check pressure switch operation, replace as needed
Tighten or correct wiring connection
Primary limit circuit is open
Check filters and ductwork for blockage Clean filters
or remove obstruction
Insufficient conditioned air over the heat
exchanger
Check circulator blower speed and performance
Blocked filters, restrictive ductwork,
improper circulator blower speed, or failed
circulator blower motor
Correct speed or replace blower motor if necessary
Loose or improperly connected wiring in
high limit circuit
Tighten or correct wiring connection
Induced draft blower and
circulator blower runs
Flame sensed with no call for heat
Correct short at flame sensor or in flame sensor wiring
continuously
Short to ground in flame sense circuit
Check for lingering or lazy flame Verify proper
operation of gas valve
No furnace operation
Lingering burner flame Slow closing gas
valve
Open fuse
Replace fuse
Short in low voltage wiring
Locate and correct short in low voltage wiring
Flame sense micro amp signal is low
Clean flame sensor if coated or oxidized Inspect for
proper flame sensor alignment
Flame sensor is coated/oxidized
Check inlet air piping for blockage, proper length,
elbows, and termination
Flame sensor incorrectly positioned in
burner fame
Compare current gas pressure to rating plate and
adjust as needed
Lazy burner flame due to improper gas
pressure or combustion air
Problem with igniter circuit
Check and correct wiring from integrated control
module to igniter
Improperly connected or shorted igniter
Diagnose and replace shorted igniter as needed Verify
and correct unit ground wiring if needed
Poor unit ground Check igniter output from control, replace if necessary
Igniter relay fault on integrated control
module
Replace pressure switch Repair short in wiring
Induced draft blower runs
continuously with no furnace
operation
EE2
Circulator blower runs
continuously No
Furnace operation
EE
Furnace lockout due to an excessive
number of ignition “retries” (3 total)
Failure to establish flame Loss
of flame after establishment
Furnace fails to operate
EE1
Normal furnace operation
EE
Furnace fails to operate
EE
EE
No furnace operation
EE
EE
Furnace fails to operate

44
TROUBLESHOOTING CHART
Fault Code Recall
Accessing the furnace’s diagnostic menu provides access to the last six faults detected by the furnace. Faults are stored
most recent to least recent, Any consecutively repeated fault is stored a maximum of three times. EXAMPLE: A clogged
return air lter causes the furnace limit to trip repeatedly. The control will only store this fault the rst three consecutive
times the fault occurs. NOTE: It is highly recommended that the fault history be cleared when performing
maintenance or servicing the furnace.
Symptom
LED Status
Fault Description Corrective Actions
Polarity of 115 volt AC is reversed Correct polarity, check and correct wiring if necessary
Poor unit ground Verify proper ground, correct if necessary
Gas valve is not energized when it should
be
Check Wiring in gas valve circuit
External Gas Valve Error Replace integrated control board
Gas valve is energized when it should not
be
Check wiring in gas valve circuit
Internal Gas Valve Error Replace integrated control board
Check filters and ductwork for blockage, clean filters
or remove obstruction
Check circulator blower speed and performance,
correct speed or replace blower motor if necessary
Tighten or correct wiring connection
Furnace fails to operate
EEF
Aux switch (condensate switch) open Check evaporator drain pan, trap, piping
Furnace stops heating and
only the fan is operating
EAF
Furnace has lost communication with the
R-32 sensor and the furnace is in
mitigation mode.
Verify wire connection to R-32 sensor is not loose.
Verify that the R-32 sensor wire is not damaged.
Replace R-32 Sensor.
Furnace stops heating and
only the fan is operating
EA
R-32 sensor has detected a refrigerant leak
and furnace is in mitigation mode.
Investigate the indoor coil for a refrigerant leak.
Furnace will resume normal operation once a leak is
not detected and the 5 minute delay period is over.
Furnace stops heating and
only the fan is operating
EA1
R-32 sensor has detected a fault and the
furnace is in mitigation mode.
Investigate the R-32 sensor.
Replace the R-32 sensor.
Furnace stops heating and
only the fan is operating
EA2
A2L relay in the furnace control board has
detected a fault and the furnace is in
mitigation mode.
Investigate A2L relay.
Cycle power on the furnace.
Replace integrated control board.
Furnace fails to operate
EEA
Furnace fails to operate
EE
Furnace fails to operate
EEC
Aux limit switch open (blower
compartment)
EEd
Furnace fails to operate

45
WIRING DIAGRAMS
upflow
*RVS96***
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple
power sources may be present. Failure to do so may cause property
damage, personal injury or death.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
0140F20040-A
EMI LINE
FILTER
RD
YL
WH
PK
BK
BK
BL
YL
PK
RD
RD
RD
9
8
12
1
15
11
14
7
2
5
4
13
3
6
10
MODULE
CONTROL
INTEGRATED
TWO-STAGE
EAC
FS
BK
2
PU
WARNING:DISCONNECT
TRANSFORMER
40 VA
N
NO
3
YL
1
SENSOR
FLAME
GR
C
VAC
TO UNIT MUST BE
1
PU
AND GROUNDED.
1
115
BAFFLE LIMIT
AUTO RESET
WH
AUTO RESET
BURNER BOX LIMIT
WH
L
PK
BK
5
YL
SERVICING. WIRING
(ON SOME MODELS)
PK
PK
2
4
BK
DOOR
OPEN)
(OPEN
WHEN
DOOR
SWITCH
COMPARTMENT
BLOWER
GND
C
BLOWER
CIRCULATOR
Ø /60 HZ
DISCONNECT
GAS
VALVE
NOTES:
1. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.
2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED, IT MUST BE
REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105
° C. USE COPPER
CONDUCTORS ONLY.
3. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C. AND LOCAL CODES.
4. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS SWITCH FOR MORE THAN 2
SECONDS WHILE IN STANDBY (NO THERMOSTAT INPUTS)
5. HUMIDIFIER INSTALLATION OPTIONS: USE HUM TERMINAL TO RUN HUMIDIFIER DURING HEAT CALL
COMMUNICATING OR LEGACY MODES). USE HUM-IN AND HUM-OUT TERMINALS TO RUN HUMIDIFIER DURING
HEAT CALL ( COMMUNICATING MODE OR LEGACY MODE) OR INDEPENDENTLY FROM HEAT CALL
(COMMUNICATING MODE ONLY - SETUP IS DONE WITHIN COMMUNICATING THERMOSTAT).
6. WHEN THIS FURNACE IS PAIRED WITH NON R-32 REFRIGERANT SYSTEMS, DEFAULT SETTINGS WILL NEED
TO BE CHANGED. REFER TO INSTALLATION MANUAL FOR FURTHER INSTRUCTIONS.
OVERCURRENT
GND
VAC
CHASSIS
GROUND
2
3
4
GND
INDUCTOR COIL
M
BK
24
BLOWER COMPARTMENT
115 VAC/ 1
BK
3
HARNESS
ECM MTR
POWER BEFORE
RD
BK
TO
RD
POWER SUPPLY WITH
BURNER COMPARTMENT
PROTECTION DEVICE
PROPERLY POLARIZED
JUNCTION
BOX
IGN
IND
-HI
IND
-LO
IND
-N
IGN
-N
AUX
IN
AUX
OUT
3A
FUSE
1
2
R
C
BIAS
BIAS
BIAS
BIAS
TERM
R
C
G W Y
DH
Y2
SAT
GND
GND
NA
RAT
TERM
CT
BREAK OFF
TABS
DATA AC
BREAK OFF
TABS
LEFT
CENTER
RIGHT
STATUS
CODE
PU
LINE
NEUTRAL
BL
GY
BK
RD
YL
WH
RD
BK
BK
WH
WH
GND
TX
RX
YL
WH
WH
RD
GR
YL
GR
BL
BR
GY
VDD
GY
YL
BR
GR
PK
GY
BR
YL
BR
GY
GND
PRESSURE
TRANSDUCER
BR
GY
NO
C
AUTO RESET
PRIMARY LIMIT
RD
1
CONNECTOR
2 CIRCUIT
IGNITER
SURFACE
HOT
2
PRESSURE SWITCH
ID BLOWER
BLOWER
DRAFT (ID)
INDUCED
LIMIT CONTROL
AUXILIARY
AUTO RESET
RD
WH
U
V
W
WH
BK
GR
WH
RD
BK
GY
BL
RD
BK
GR
PU
WIRE
COLOR:
YL
WH
BL
BK
RD
OR
PK
GY
TN
GR
BR
YELLOW
WHITE
BLUE
BLACK
RED
ORANGE
BROWN
PINK
GRAY
TAN
GREEN
PURPLE
VIOLET
COLOR
DESIGNATION:
PU
VT
SWITCH (PRESSURE)
FIELD SPLICE
FIELD GROUND
EQUIPMENT GROUND
PROTECTION DEVICE
PLUG CONNECTION
SWITCH (TEMPERATURE)
JUNCTION
OVERCURRENT
TERMINAL
IGNITER
HIGH VOLTAGE (115V)
HIGH VOLTAGE FIELD
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
PK
GND
1
2
5V
A2L MODE IS ENABLED BY
DEFAULT
REFER TO INSTALLATION MANUAL
FOR FURTHER INSTRUCTIONS.
A2L SENSOR
CONNECTOR
PK
COLLECTOR BOX
PRESSURE SWITCH
PU
GND
PI
5V
E28
RD
BK
GR
MOB_PE
E34
GND
GROUND WIRE
CONNECTED
TO CONTROL
MOUNTING
PANEL
GR
GR

46
WIRING DIAGRAMS
Downflow
*DVS96***
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple
power sources may be present. Failure to do so may cause property
damage, personal injury or death.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
0140F20041-A
EMI LINE FILTER
RD
YL
WH
PK
BK
BK
BL
YL
PK
RD
RD
RD
9
8
12
1
15
11
14
7
2
5
4
13
3
6
10
MODULE
CONTROL
INTEGRATED
TWO-STAGE
EAC
FS
BK
2
PU
TRANSFORMER
40 VA
N
NO
3
YL
1
SENSOR
FLAME
GR
C
VAC
1
PU
1
115
WH
AUTO RESET
BURNER BOX LIMIT
WH
L
PK
BK
5
(ON SOME MODELS)
PK
RD
2
4
BK
DOOR OPEN)
(OPEN WHEN
DOOR SWITCH
COMPARTMENT
BLOWER
GND
C
BLOWER
CIRCULATOR
DISCONNECT
GAS
VALVE
GND
VAC
CHASSIS
GROUND
2
3
4
GND
INDUCTOR COIL
M
BK
24
BLOWER COMPARTMENT
BK
3
HARNESS
ECM MTR
RD
BK
RD
BURNER COMPARTMENT
JUNCTION BOX
IGN
IND
-HI
IND
-LO
IND
-N
IGN
-N
AUX
IN
AUX
OUT
3A
FUSE
1
2
R
C
BIAS
BIAS
BIAS
BIAS
TERM
R
C
G W Y
DH
Y2
SAT
GND
GND
NA
RAT
TERM
CT
BREAK OFF
TABS
DATA AC
BREAK OFF
TABS
LEFT
CENTER
RIGHT
STATUS
CODE
PU
LINE
NEUTRAL
BL
GY
BK
RD
YL
WH
RD
BK
BK
WH
WH
GND
TX
RX
YL
WH
WH
RD
GR
YL
GR
BL
BR
GY
VDD
GY
YL
BR
GR
PK
GY
BR
YL
BR
GY
GND
PRESSURE
TRANSDUCER
BR
GY
NO
C
AUTO RESET
PRIMARY LIMIT
RD
1
CONNECTOR
2 CIRCUIT
IGNITER
SURFACE
HOT
2
PRESSURE SWITCH
ID BLOWER
BLOWER
DRAFT (ID)
INDUCED
LIMIT CONTROL
AUXILIARY
AUTO RESET
RD
WH
U
V
W
WH
BK
RG
WH
PK
RD
BK
GY
BL
RD
BK
GR
PU
WARNING:DISCONNECT
TO UNIT MUST BE
AND GROUNDED.
SERVICING. WIRING
Ø /60 HZ
OVERCURRENT
115 VAC/ 1
POWER BEFORE
TO
POWER SUPPLY WITH
PROTECTION DEVICE
PROPERLY POLARIZED
PK
GND
1
2
5V
A2L SENSOR
CONNECTOR
A2L MODE IS ENABLED BY
DEFAULT
REFER TO INSTALLATION MANUAL
FOR FURTHER INSTRUCTIONS.
YL
COLLECTOR BOX
PRESSURE SWITCH
NOTES:
1. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.
2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED, IT MUST BE
REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105
° C. USE COPPER
CONDUCTORS ONLY.
3. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C. AND LOCAL CODES.
4. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS SWITCH FOR MORE THAN 2
SECONDS WHILE IN STANDBY (NO THERMOSTAT INPUTS)
5. HUMIDIFIER INSTALLATION OPTIONS: USE HUM TERMINAL TO RUN HUMIDIFIER DURING HEAT CALL
COMMUNICATING OR LEGACY MODES). USE HUM-IN AND HUM-OUT TERMINALS TO RUN HUMIDIFIER DURING
HEAT CALL ( COMMUNICATING MODE OR LEGACY MODE) OR INDEPENDENTLY FROM HEAT CALL
(COMMUNICATING MODE ONLY - SETUP IS DONE WITHIN COMMUNICATING THERMOSTAT).
6. WHEN THIS FURNACE IS PAIRED WITH NON R-32 REFRIGERANT SYSTEMS, DEFAULT SETTINGS WILL NEED
TO BE CHANGED. REFER TO INSTALLATION MANUAL FOR FURTHER INSTRUCTIONS.
WIRE
COLOR:
YL
WH
BL
BK
RD
OR
PK
GY
TN
GR
BR
YELLOW
WHITE
BLUE
BLACK
RED
ORANGE
BROWN
PINK
GRAY
TAN
GREEN
PURPLE
VIOLET
COLOR
DESIGNATION:
PU
VT
SWITCH (PRESSURE)
FIELD SPLICE
FIELD GROUND
EQUIPMENT GROUND
PROTECTION DEVICE
PLUG CONNECTION
SWITCH (TEMPERATURE)
JUNCTION
OVERCURRENT
TERMINAL
IGNITER
HIGH VOLTAGE (115V)
HIGH VOLTAGE FIELD
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
GND
PI
5V
E28
RD
BK
GR
MOB_PE
E34
GND
GROUND WIRE
CONNECTED
TO CONTROL
MOUNTING
PANEL
GR
GR

47
Furnace
ELECTRICAL
Line Voltage (Measure L1 to N and N to Ground Voltage) L - N
N - G
Secondary Voltage (Measure Transformer Output Voltage) R - C
Blower Amps
BLOWER EXTERNAL STATIC PRESSURE
Return Air Sta�c Pressure IN. W.C.
Supply Air Sta�c Pressure IN. W.C.
Total External Sta�c Pressure (Ignoring +/- from the reading above, add total here) IN. W.C.
TEMPERATURES
Return Air Temperature (Dry bulb / Wet bulb) DB °F WB °F
DB °F WB °F
Hea�ng Supply Air Temperature DB °F
Temperature Rise DB °F
Delta T (Differenc
e between Supply and Return Temperatures) DB °F
GAS PRESSURES
Gas Inlet Pressure IN. W.C.
Gas Manifold Pressure (Low Fire) IN. W.C.
Gas Manifold Pressure (High Fire) IN. W.C.
Gas Type (NG) = Natural Gas / (LP) = Liquid Propane
Addi�onal Checks
Check wire rou�ngs for any rubbing
Check for kinked pressure switch tubing
Check flue elbow for alignment and clamp �ghtness
Check screw �ghtness on blower wheel
Check factory wiring and wire conne
c�ons
Check product for proper clearances as noted by installa�on instruc�ons
°F to °C formula: (°F - 32) divided by 1.8 = °C °C to °F formula: (°C mul�plied by 1.8) + 32 = °F
Check R-32 sensor wire is connected properly (if applicable)
Model Number
Serial Number
Cooling Supply Air Temperature (Dry bulb / Wet bulb)
START-UP CHECKLIST

48
19001 Kermier Rd., Waller, TX 77484
www.goodmanmfg.com • www.amana-hac.com
© 2024 Daikin Comfort Technologies Manufacturing, L.P.
is a registered trademark of Maytag Corporation or its related companies and is used under license.
All rights reserved.
CUSTOMER FEEDBACK
We are very interested in all product comments.
Please ll out the feedback form on one of the following links:
Goodman
®
Brand Products: (http://www.goodmanmfg.com/about/contact-us).
Amana
®
Brand Products: (http://www.amana-hac.com/about-us/contact-us).
You can also scan the QR code on the right for the product brand
you purchased to be directed to the feedback page.
GOODMAN
®
BRAND
AMANA
®
BRAND
GOODMAN
®
BRAND
AMANA
®
BRAND
PRODUCT REGISTRATION
Thank you for your recent purchase. Though not required to get the protection of
the standard warranty, registering your product is a relatively short process, and
entitles you to additional warranty protection, except that failure by California and
Quebec residents to register their product does not diminish their warranty rights.
The duration of warranty coverages in Texas and Florida diers in some cases.
For Product Registration, please register as follows:
Goodman
®
Brand products: (https://www.goodmanmfg.com/product-registration).
Amana
®
Brand products: (http://www.amana-hac.com/product-registration).
You can also scan the QR code on the right for the product brand
you purchased to be directed to the Product Registration page.