Daikin RXM18WVJU9 Atmosphera 18K BTU 1.5 Ton Ductless Mini Split Heat Pump Condenser, R-32

Product's Documents

Below are documents related to this product, you can read online or download:
User Manual Installation Instruction
RXM18WVJU9 photo

User Manual

This is the main product document for model RXM18WVJU9. Additionally, the document applies to other Daikin models: RXM18WVJU9, 12K, 24K

The file format is pdf, 182 pages, you can download this manual here .

background
[Applied Models]
Inverter Pair : Heat Pump
Inverter Pair
Wall Mounted Type FTXM-W/V Series
Service
Manual
SiUS042113EA
background
SiUS042113EA
i Table of Contents
Introduction ....................................................................................... 1
1. Safety Cautions...........................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers................................. 2
1.2 Warnings and Cautions Regarding Safety of Users..................................... 8
2. Icons Used ................................................................................................11
3. Revision History ........................................................................................12
Part 1 General Information ............................................................. 13
1. Applicable Models .....................................................................................14
2. Functions...................................................................................................15
Part 2 Specifications....................................................................... 16
1. Specifications ............................................................................................17
1.1 FTXM-W Series.......................................................................................... 17
1.2 FTXM-V Series........................................................................................... 19
Part 3 Printed Circuit Board Connector Wiring Diagram................ 21
1. Indoor Unit.................................................................................................22
2. Outdoor Unit..............................................................................................26
2.1 09/12 class ................................................................................................. 26
2.2 18/24 class ................................................................................................. 28
Part 4 Functions and Control .......................................................... 30
1. Main Functions..........................................................................................31
1.1 Temperature Control .................................................................................. 31
1.2 Frequency Principle.................................................................................... 31
1.3 Airflow Direction Control............................................................................. 33
1.4 COMFORT AIRFLOW Operation ............................................................... 34
1.5 Fan Speed Control for Indoor Unit ............................................................. 36
1.6 Hybrid Cooling............................................................................................ 37
1.7 Automatic Cooling/Heating Changeover .................................................... 40
1.8 Thermostat Control..................................................................................... 41
1.9 NIGHT SET Mode ...................................................................................... 42
1.10 ECONO Operation .................................................................................... 42
1.11 2-Area INTELLIGENT EYE Operation ....................................................... 43
1.12 INTELLIGENT EYE Operation ................................................................... 47
1.13 POWERFUL Operation .............................................................................. 49
1.14 Clock Setting .............................................................................................. 50
1.15 WEEKLY TIMER Operation ....................................................................... 51
1.16 Brightness Setting of Indoor Unit Display................................................... 57
1.17 CLEAN Operation....................................................................................... 58
1.18 Wireless LAN Connection .......................................................................... 60
1.19 Other Functions.......................................................................................... 65
background
SiUS042113EA
Table of Contents ii
2. Thermistor Functions ................................................................................66
3. Control Specification .................................................................................68
3.1 Mode Hierarchy .......................................................................................... 68
3.2 Frequency Control...................................................................................... 68
3.3 Standby Electricity Saving (Suspend Function) ......................................... 70
3.4 Controls at Mode Changing/Start-up.......................................................... 71
3.5 Discharge Pipe Temperature Control......................................................... 73
3.6 Input Current Control.................................................................................. 74
3.7 Freeze-up Protection Control ..................................................................... 75
3.8 Heating Peak-cut Control ........................................................................... 75
3.9 High Pressure Protection Control............................................................... 76
3.10 Outdoor Fan Control................................................................................... 77
3.11 Liquid Compression Protection Function.................................................... 77
3.12 Defrost Control ........................................................................................... 78
3.13 Electronic Expansion Valve Control ........................................................... 79
3.14 Malfunctions ............................................................................................... 82
Part 5 Remote Controller ................................................................ 83
1. Applicable Remote Controller ...................................................................84
2. ARC466A70 ..............................................................................................85
3. ARC466A71 ..............................................................................................87
Part 6 Service Diagnosis ................................................................. 89
1. General Problem Symptoms and Check Items .........................................91
2. Troubleshooting with LED .........................................................................92
2.1 Indoor Unit.................................................................................................. 92
2.2 Outdoor Unit ............................................................................................... 92
3. Service Diagnosis .....................................................................................93
3.1 Method 1 .................................................................................................... 93
3.2 Method 2 .................................................................................................... 94
4. Troubleshooting ........................................................................................96
4.1 Error Codes and Description ...................................................................... 96
4.2 Indoor Unit PCB Abnormality ..................................................................... 97
4.3 Freeze-up Protection Control/Heating Peak-cut Control ............................ 98
4.4 Indoor Fan Motor (DC Motor) or Related Abnormality ............................. 100
4.5 Indoor Heat Exchanger Thermistor or Related Abnormality..................... 102
4.6 Room Temperature Sensor Abnormality/Humidity Sensor
Abnormality .............................................................................................. 103
4.7 Refrigerant Shortage ................................................................................ 104
4.8 Low-voltage Detection or Over-voltage Detection.................................... 106
4.9 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)........ 108
4.10 Unspecified Voltage (Between Indoor Unit and Outdoor Unit) ................. 110
4.11 Outdoor Unit PCB Abnormality................................................................. 111
4.12 Actuation of High Pressure Switch ........................................................... 112
4.13 OL Activation (Compressor Overload) ..................................................... 113
4.14 Compressor Lock ..................................................................................... 116
4.15 DC Fan Lock ............................................................................................ 117
background
SiUS042113EA
iii Table of Contents
4.16 Input Overcurrent Detection ..................................................................... 118
4.17 Four Way Valve Abnormality.................................................................... 120
4.18 Discharge Pipe Temperature Control....................................................... 122
4.19 High Pressure Control in Cooling ............................................................. 124
4.20 System Shutdown due to Temperature Abnormality in
the Compressor........................................................................................ 126
4.21 Compressor System Sensor Abnormality ................................................ 127
4.22 Position Sensor Abnormality .................................................................... 128
4.23 DC Voltage/Current Sensor Abnormality.................................................. 131
4.24 Thermistor or Related Abnormality (Outdoor Unit)................................... 133
4.25 Electrical Box Temperature Rise.............................................................. 135
4.26 Radiation Fin Temperature Rise .............................................................. 136
4.27 Output Overcurrent Detection .................................................................. 138
5. Check ......................................................................................................141
5.1 Thermistor Resistance Check .................................................................. 141
5.2 Indoor Fan Motor Connector Check ......................................................... 142
5.3 Power Supply Waveform Check............................................................... 142
5.4 Electronic Expansion Valve Check........................................................... 143
5.5 Four Way Valve Performance Check ....................................................... 144
5.6 Inverter Unit Refrigerant System Check................................................... 145
5.7 Inverter Analyzer Check ........................................................................... 145
5.8 Outdoor Fan Motor Check........................................................................ 147
5.9 Installation Condition Check..................................................................... 148
5.10 Discharge Pressure Check....................................................................... 149
5.11 Outdoor Fan System Check ..................................................................... 149
5.12 Main Circuit Short Check.......................................................................... 149
5.13 Capacitor Voltage Check.......................................................................... 151
5.14 Power Module Check ............................................................................... 152
Part 7 Trial Operation and Field Settings ..................................... 154
1. Pump Down Operation............................................................................155
2. Forced Cooling Operation .......................................................................156
3. Trial Operation ........................................................................................157
4. Field Settings ..........................................................................................159
4.1 Temperature Display Switch .................................................................... 159
4.2 When 2 Units are Installed in 1 Room...................................................... 159
4.3 Facility Setting (cooling at low outdoor temperature) ............................... 160
4.4 Warmer Airflow Setting............................................................................. 161
4.5 Drain Pan Heater...................................................................................... 163
4.6 Service Mode of Wireless Remote Controller .......................................... 164
5. Silicone Grease on Power Transistor/Diode Bridge................................167
Part 8 Appendix ............................................................................. 168
1. Piping Diagrams......................................................................................169
1.1 Indoor Unit................................................................................................ 169
1.2 Outdoor Unit ............................................................................................. 170
background
SiUS042113EA
Table of Contents iv
2. Wiring Diagrams......................................................................................172
2.1 Indoor Unit................................................................................................ 172
2.2 Outdoor Unit ............................................................................................. 174
3. Operation Limit........................................................................................176
background
SiUS042113EA
1 Introduction
1. Safety Cautions...........................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers................................. 2
1.2 Warnings and Cautions Regarding Safety of Users..................................... 8
2. Icons Used ................................................................................................11
3. Revision History ........................................................................................12
Introduction
background
SiUS042113EA Safety Cautions
Introduction 2
1. Safety Cautions
Be sure to read the following safety cautions before conducting repair work.
After the repair work is complete, be sure to conduct a test operation to ensure that the equipment
operates normally, and explain the cautions for operating the product to the customer.
Caution Items The caution items are classified into Warning and Caution. The Warning items are
especially important since death or serious injury can result if they are not followed closely. The
Caution items can also lead to serious accidents under some conditions if they are not
followed. Therefore, be sure to observe all the safety caution items described below.
Pictograms This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown in the illustration or near the symbol.
1.1 Warnings and Cautions Regarding Safety of Workers
Servicing shall be performed only as recommended by the manufacturer and licensed or certified in
their jurisdiction.
This manual is for the
person in charge of
maintenance and
inspection.
This appliance is
filled with R-32.
Warning
Do not store equipment in a room with fire sources (e.g., naked
flames, gas appliances, electric heaters).
Be sure to disconnect the power cable from the socket before
disassembling equipment for repair.
Working on equipment that is connected to the power supply may cause
an electrical shock.
If it is necessary to supply power to the equipment to conduct the repair or
inspect the circuits, do not touch any electrically charged sections of the
equipment.
If refrigerant gas is discharged during repair work, do not touch the
discharged refrigerant gas.
Refrigerant gas may cause frostbite.
When disconnecting the suction or discharge pipe of the
compressor at the welded section, evacuate the refrigerant gas
completely at a well-ventilated place first.
If there is gas remaining inside the compressor, the refrigerant gas or
refrigerating machine oil discharges when the pipe is disconnected, and it
may cause injury.
If refrigerant gas leaks during repair work, ventilate the area.
Refrigerant gas may generate toxic gases when it contacts flames.
background
Safety Cautions SiUS042113EA
3 Introduction
Be sure to discharge the capacitor completely before conducting
repair work.
The step-up capacitor supplies high-voltage electricity to the electrical
components of the outdoor unit.
A charged capacitor may cause an electrical shock.
Do not turn the air conditioner on or off by plugging in or
unplugging the power cable.
Plugging in or unplugging the power cable to operate the equipment may
cause an electrical shock or fire.
Be sure to wear a safety helmet, gloves, and a safety belt when
working in a high place (more than 2 m (6.5 ft)).
Insufficient safety measures may cause a fall.
In case of R-32 / R-410A refrigerant models, be sure to use pipes,
flare nuts and tools intended for the exclusive use with the R-32 /
R-410A refrigerant.
The use of materials for R-22 refrigerant models may cause a serious
accident, such as a damage of refrigerant cycle or equipment failure.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-410A / R- 22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
Caution
Do not repair electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Do not clean the air conditioner with water.
Washing the unit with water may cause an electrical shock.
Be sure to provide an earth / grounding when repairing the
equipment in a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable
when cleaning the equipment.
The internal fan rotates at a high speed, and may cause injury.
Be sure to conduct repair work with appropriate tools.
The use of inappropriate tools may cause injury.
Warning
background
SiUS042113EA Safety Cautions
Introduction 4
Checking the area
Before beginning work, conduct safety checks to minimize the risk of ignition. When repairing the
refrigerating system, take the following precautions before work.
Work procedure
Work shall be conducted under a controlled procedure so as to minimize the risk of working in the
presence of R-32 or vapor.
General working area
All maintenance staff and others working in the local area shall be instructed on the nature of work
being carried out.
Work in confined spaces shall be avoided.
The area around the workspace shall be sectioned off. Ensure that the conditions within the area
have been made safe by control of flammable materials.
Checking for presence of refrigerant
The working area shall be checked with an appropriate refrigerant detector before and during work,
to ensure the technician is aware of potentially flammable atmospheres.
Ensure that the leak detection equipment being used is suitable for use with R-32, i.e.
non-sparking, adequately sealed or intrinsically safe.
Fire extinguishing equipment
If any hot work is to be conducted on the refrigeration equipment or any associated parts,
appropriate fire extinguishing equipment shall be made available at hand. Prepare a dry powder or
CO
2
fire extinguisher adjacent to the working area.
No ignition sources
During work on a refrigeration system which involves exposing any piping work that contains or has
contained R-32, any sources of ignition shall not be used in a manner that may lead to the risk of
fire or explosion. All possible ignition sources, including cigarette smoking, should be kept at a safe
distance from the site of installation, repairing, or removing space. Before starting work, the area
around the equipment shall be examined to make sure that there are no flammable hazard or
ignition risks. No Smoking signs shall be displayed.
Ventilated area
Ensure that the working area is open or that it is adequately ventilated before work. Adequate
ventilation shall be maintained during the entire period of work. The ventilation should disperse any
released refrigerant and preferably discharge it into the external atmosphere.
Checking the refrigeration equipment
Where electrical components are to be changed, the new components shall be fit for the purpose
and have the correct specifications.
Be sure to check that the refrigerating cycle section has cooled
down enough before conducting repair work.
Working on the unit when the refrigerating cycle section is hot may cause
burns.
Conduct welding work in a well-ventilated place.
Using a welder in an enclosed room may cause oxygen deficiency.
Caution
background
Safety Cautions SiUS042113EA
5 Introduction
The manufacturer's maintenance and service guidelines shall be followed at all times.
If there are any unclear points, consult the manufacturer's technical department for assistance.
The following checks shall be applied to any installation work involving R-32:
The amount of charge is in accordance with the size of the room where the refrigerant
containing parts are installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the
presence of refrigerant;
Marking on the equipment is visible and legible. Markings and signs that are illegible shall be
corrected;
Refrigeration pipes or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, or the
refrigerant containing components are constructed of materials which are inherently
resistant to corrosion or are suitably protected against corrosion.
Checking electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component
inspection procedures. In case there is any fault that could endanger safety, no electrical supply
shall be connected to the circuit until the fault is satisfactorily dealt with. Initial safety checks shall
include:
that capacitors are discharged: this shall be done in a safe manner to avoid possibility of
sparking;
that no live electrical components and wiring are exposed while charging, recovering or
purging the system;
that the equipment is grounded at all times.
Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from the
equipment being worked upon before the removal of any sealed covers, etc. If it is absolutely
necessary to have power supplied to equipment during servicing, continuously operating leak
detection shall be installed at the most dangerous point of the system in order to warn of a
potentially hazardous situation.
Particular attention shall be paid to the following: ensure that working on electrical components
does not alter the casing in such a way that affects the level of protection including damage to
cables, excessive number of connections, terminals different from the original specification,
damage to seals, incorrect fitting of glands, etc.
Ensure that the equipment is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the
purpose of preventing the ingression of flammable atmospheres. Replacement parts shall be in
accordance with the manufacturer's specifications.
The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment.
Intrinsically safe components do not have to be isolated before working on them.
Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance load to the circuit without ensuring that this
will not exceed the permissible voltage and current for the equipment in use.
Only intrinsically safe components can be worked on in the presence of a flammable atmosphere.
The test apparatus shall be of correct rating.
Replace components only with parts specified by the manufacturer. Using other parts may result in
ignition of the refrigerant leaked into the atmosphere.
Wiring
Check that wiring is not subject to wear, corrosion, excessive pressure, vibration, sharp edges or
any other adverse environmental effects. The check shall also take into account the effects of
ageing or continuous vibration from sources such as compressors or fans.
background
SiUS042113EA Safety Cautions
Introduction 6
Detecting of R-32
Under no circumstances shall potential sources of ignition be used in the search for or detection of
refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
Leak detection methods
The following leak detection methods can be applied for systems containing R-32.
Electronic leak detectors shall be used to detect R-32, but the sensitivity may not be adequate or
may need re-calibration (detection equipment shall be calibrated in a refrigerant-free area).
Ensure that the detector is not a potential source of ignition and that it is suitable for the refrigerant
used. Leak detection equipment shall be set to the percentage of the lower flammability limit (LFL)
of the refrigerant and calibrated to fit the refrigerant employed. The appropriate percentage of gas
(maximum 25%) shall be confirmed.
Leak detection fluids (bubble method or fluorescent method agents and such) are also suitable for
use with most refrigerants but the use of detergents containing chlorine shall be avoided as the
chlorine may react with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed or extinguished.
If a refrigerant leakage which requires brazing is found, all of the refrigerant shall be recovered from
the system, or isolated (by means of shut off valves) in a part of the system remote from the point of
the leakage. Removal of refrigerant shall be according to the following section (Removal and
evacuation).
Removal and evacuation
When breaking the refrigerant circuit to make repairs or any other purpose, conventional
procedures may be used. However, flammability must be taken into consideration. The following
procedure shall be adhered to:
Remove refrigerant;
Purge the circuit with inert gas;
Evacuate the inert gas;
Purge again with inert gas;
Carry out cutting or brazing of the circuit.
The refrigerant shall be recovered into the correct recovery cylinders. The system shall be cleaned
with OFN to render the unit safe. (= Flushing) This process may need to be repeated several times.
Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved through breaking the vacuum by filling the system with OFN until the
working pressure is achieved, then venting the OFN into the atmosphere, and finally pulling the
system down to vacuum again. This process shall be repeated until no refrigerant remains within
the system. After the last OFN charge is finished, the system shall be vented down to atmospheric
pressure to enable work. This operation is especially important if brazing operations on the piping
work are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and that there is
ventilation available.
Charging procedures
In addition to conventional charging procedures, the following requirements shall be met.
Ensure that the charging equipment to be used is not contaminated by different refrigerants.
Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in
them.
Cylinders shall be kept in an appropriate position according to the manufacturer’s
instructions.
Ensure that the refrigeration system is grounded before charging the system with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system.
background
Safety Cautions SiUS042113EA
7 Introduction
Before recharging, the system shall be tested for leakage with OFN. On completion of charging, the
system shall be tested before commissioning. Follow up leakage test shall be carried out before
leaving the site.
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the
equipment and all its details. It is recommended to train technicians so that the entire refrigerant is
recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in
case analysis is required prior to re-use of recovered refrigerant.
Comprehend the equipment and its operation.
Isolate the system electrically.
Before starting work, ensure that:
mechanical handling equipment is available if required, for handling refrigerant cylinders;
protective equipment can be used in compliance with specifications;
the recovery process is supervised by a competent person at all times;
recovery equipment and cylinders conform to the appropriate standards.
Pump down the refrigerant system, if possible.
If vacuum cannot be ensured, apply a manifold so that refrigerant can be removed from
various parts of the system.
Make sure that the cylinder is situated on the scale before recovery takes place.
Start the refrigerant recovery device and operate it in accordance with the manufacturer's
instructions.
Do not overfill cylinders. (Do not exceed 80% liquid charge volume).
Do not exceed the maximum working pressure of the cylinder, even temporarily.
When the cylinders have been filled correctly and the process is completed, make sure that
the cylinders and the equipment are removed from site promptly and all valves on the
equipment are closed.
Recovered refrigerant shall not be charged into another refrigeration system before it has
been cleaned and checked.
Labelling
Equipment shall be labelled stating that it has been decommissioned and emptied of refrigerant.
The label shall be dated and signed. Ensure that there are labels on the equipment stating the
equipment contains R-32.
Refrigerant recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended to conduct training so that all refrigerants can be removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are used.
Ensure that the correct number of cylinders for holding the total system charge are available. All
cylinders to be used must be designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be equipped with a
pressure relief valve and associated shut-off valves in good working order. If possible, empty
recovery cylinders shall be cooled in a separate place before recovery is conducted.
The recovery equipment shall be in good working order with instructions concerning the equipment
at hand, and shall be suitable for the recovery of R-32. In addition, a set of calibrated weighing
scales shall be available and in good working order. Hoses shall be equipped with leak-free
disconnect couplings and in good condition. Before using the recovery device, check that it has
undergone proper maintenance, that it is in satisfactory working order
, and that any
associated
electrical components are sealed to prevent ignition in the event of a refrigerant leakage. Consult
manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
cylinder, with the relevant Waste Transfer Note attached. Do not mix refrigerants in recovery units
and especially not in cylinders.
background
SiUS042113EA Safety Cautions
Introduction 8
If compressors or compressor oil are to be removed, ensure that the refrigerant melted into the oil
has been evacuated to an acceptable level to make certain that R-32 does not remain within the oil.
The evacuation process shall be carried out before returning the compressor to the supplier. Only
electric heating to the compressor body shall be employed to accelerate this process. Oil drained
from the system shall be treated safely.
1.2 Warnings and Cautions Regarding Safety of Users
Warning
Do not store the equipment in a room with fire sources (e.g., naked
flames, gas appliances, electric heaters).
Be sure to use parts listed in the service parts list of the applicable
model and appropriate tools to conduct repair work. Never attempt
to modify the equipment.
The use of inappropriate parts or tools may cause an electrical shock,
excessive heat generation or fire.
If the power cable and lead wires are scratched or have deteriorated,
be sure to replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the
same power outlet with other electrical appliances, since it may
cause an electrical shock, excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and
follow the local technical standards related to the electrical
equipment, the internal wiring regulations, and the instruction
manual for installation when conducting electrical work.
Insufficient power circuit capacity and improper electrical work may cause
an electrical shock or fire.
Be sure to use the specified cable for wiring between the indoor and
outdoor units.
Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that
the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may
cause an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cables may cause an electrical shock or fire.
Placing heavy items on the power cable, or heating or pulling the power
cable may damage it.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-410A / R- 22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
background
Safety Cautions SiUS042113EA
9 Introduction
If the refrigerant gas leaks, be sure to locate the leaking point and
repair it before charging the refrigerant. After charging the
refrigerant, make sure that there is no leak.
If the leaking point cannot be located and the repair work must be
stopped, be sure to pump-down, and close the service valve, to prevent
refrigerant gas from leaking into the room. Refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such
as those from fan type and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation
site has sufficient strength to withstand the weight of the
equipment.
If the installation site does not have sufficient strength or the installation
work is not conducted securely, the equipment may fall and cause injury.
Check to make sure that the power cable plug is not dirty or loose,
then insert the plug into a power outlet securely.
If the plug is dusty or has a loose connection, it may cause an electrical
shock or fire.
When replacing the coin battery in the remote controller, be sure to
dispose of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases
depending on the conditions of the installation site, to prevent
electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If combustible gas leaks and remains around the unit, it may cause a fire.
Check to see if parts and wires are mounted and connected
properly, and if connections at the soldered or crimped terminals
are secure.
Improper installation and connections may cause excessive heat
generation, fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
A corroded installation platform or frame may cause the unit to fall,
resulting in injury.
Check the earth / grounding, and repair it if the equipment is not
properly earthed / grounded.
Improper earth / grounding may cause an electrical shock.
Be sure to measure insulation resistance after the repair, and make
sure that the resistance is 1 M or higher.
Faulty insulation may cause an electrical shock.
Warning
background
SiUS042113EA Safety Cautions
Introduction 10
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause water to enter the room and wet the furniture
and floor.
Do not tilt the unit when removing it.
The water inside the unit may spill and wet the furniture and floor.
Caution
background
Icons Used SiUS042113EA
11 Introduction
2. Icons Used
The following icons are used to attract the attention of the reader to specific information.
Icon Type of
Information
Description
Warning
Warning Warning is used when there is danger of personal injury.
Caution
Caution Caution is used when there is danger that the reader,
through incorrect manipulation, may damage equipment,
lose data, get an unexpected result or have to restart (part
of) a procedure.
Note
Note Note provides information that is not indispensable, but
may nevertheless be valuable to the reader, such as tips
and tricks.
Reference
Reference Reference guides the reader to other places in this binder
or in this manual, where he/she will find additional
information on a specific topic.
background
SiUS042113EA Revision History
Introduction 12
3. Revision History
Month/Year Version Revised contents
04 / 2021 SiUS042113E First edition
09 / 2022 SiUS042113EA
Model addition:
FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9
RXM09WVJU9, RXM12WVJU9, RXM18WVJU9, RXM24WVJU9
01 / 2023 SiUS042113EA Specification update and correction of error
background
SiUS042113EA
13 Part 1 General Information
1. Applicable Models .....................................................................................14
2. Functions...................................................................................................15
Part 1
General Information
background
SiUS042113EA Applicable Models
Part 1 General Information 14
1. Applicable Models
Indoor Unit Outdoor Unit
FTXM09WVJU9
FTXM12WVJU9
FTXM18WVJU9
FTXM24WVJU9
FTXM09VVJU
FTXM12VVJU
FTXM18VVJU
FTXM24VVJU
RXM09WVJU9
RXM12WVJU9
RXM18WVJU9
RXM24WVJU9
RXM09VVJU
RXM12VVJU
RXM18VVJU
RXM24VVJU
background
Functions SiUS042113EA
15 Part 1 General Information
2. Functions
Category Functions
FTXM Series
09/12 class 18/24 class
Basic Functions Inverter (with inverter power control) 
Operation limit Refer to page 176
Standby electricity saving 
Compressor Swing compressor 
Reluctance DC motor 
Comfortable
Airflow
Power-airflow dual flaps 
Wide-angle louvers 
Auto-swing (up and down) 
Auto-swing (right and left) 
3-D airflow 
COMFORT AIRFLOW operation (COANDA flap) 
Draftless airflow in heating 
Comfort Control Auto fan speed 
Switchable fan speed 
Indoor unit quiet operation 
QUIET OUTDOOR UNIT operation (manual) 
INTELLIGENT EYE operation (auto energy saving) 
2-area INTELLIGENT EYE operation (focus and comfort) —
Quick warming function (preheating operation) —
Hot-start function 
Automatic defrosting 
Fan stop when thermo-off in cooling 
Automatic operation (cooling and heating) 
Program dry function — —
Hybrid cooling (dehumidifying function) 
Fan operation 
Lifestyle
Convenience
Inverter powerful operation 
ECONO operation 
Indoor unit ON/OFF button 
Signal reception indicator 
Health and
Cleanliness
Titanium apatite deodorizing filter 
Mold proof air filter 
Wipe-clean flat panel 
CLEAN (mold proof) operation 1 1
Removable drain pan 
Remote Control
and Timer
WEEKLY TIMER operation 
Count up-down ON/OFF timer 
24-hour ON/OFF TIMER 
NIGHT SET mode 
R/C with back light 
°F/°C changeover R/C temperature display (factory setting: °F) 
Wireless LAN adaptor (built in) 
DIII-NET compatible (adaptor) option option
Worry Free
(Reliability &
Durability)
Au
to
-restart (after power failure) 
Self-diagnosis with R/C 
Anti-corrosion treatment of outdoor heat exchanger 
Flexibility Multi-split/split type compatible indoor unit — —
Chargeless 49.2 ft (15 m) 49.2 ft (15 m)
Either side drain (right or left) 
Year-round cooling applicable (–20°C(4°F)) 2 
Remote Control Wireless 
Wired option option
—
1
2
: Available
: Not available
: Factory setting Off
: This operation limit is allowed by installing the air direction adjustment grille (option).
background
SiUS042113EA
Part 2 Specifications 16
1. Specifications ............................................................................................17
1.1 FTXM-W Series.......................................................................................... 17
1.2 FTXM-V Series........................................................................................... 19
Part 2
Specifications
background
Specifications SiUS042113EA
17 Part 2 Specifications
1. Specifications
1.1 FTXM-W Series
Model
Indoor Unit FTXM09WVJU9 FTXM12WVJU9
Outdoor Unit
RXM09WVJU9 RXM12WVJU9
Cooling Heating Cooling Heating
3RZHU6XSSO\
3KDVH
1 I 1 I
+]9 +]9 +]9
&DSDFLW\5DWHG0LQ0D[ %WXK a a a a
3RZHU&RQVXPSWLRQ5DWHG W 552 - 552 701 - 701 909 - 909 906 - 906
3RZHU)DFWRU5DWHG % 92.8 - 92.5 94.7 - 94.6 96.3 - 96.2 96.8 - 96.8
6((5+63) 27.40 11.20 25.20 10.70
((55DWHG %WXKā: 16.30 — 13.20 —
&235DWHG W/W — 4.60 — 4.40
Piping Connection Liquid
LQPP
I I
*DV
LQPP
I I
'UDLQ
LQPP
I I
0D[,QWHUXQLW3LSLQJ/HQJWK IWP  
0D[,QWHUXQLW+HLJKW'LႇHUHQFH IWP  
&KDUJHOHVV IWP  
$PRXQWRI$GGLWLRQDO&KDUJHRI
5HIULJHUDQW
R]IWJP  
Indoor Unit FTXM09WVJU9 FTXM12WVJU9
)URQW3DQHO&RORU :KLWH1 :KLWH1
$LUÀRZ5DWHV H
FIP
(m
3
PLQ
   
M    
L    
SL    
)DQ Type &URVV)ORZ)DQ &URVV)ORZ)DQ
Speed Steps 6WHSV4XLHW$XWR 6WHSV4XLHW$XWR
+HDW([FKDQJHU Type
0XOWL6OLW)LQI+L;%WXEH 0XOWL6OLW)LQI+L;%WXEH
5RZVî6WDJHV/HQJWKPP
/ FPI
î
î
î
î
î
î
'LPHQVLRQV+î:î' LQPP îîîî îîîî
3DFNDJHG'LPHQVLRQV+î:î' LQPP îîîî îîîî
:HLJKW0DVV OEVNJ  
*URVV:HLJKW*URVV0DVV OEVNJ  
6RXQG3UHVVXUH/HYHO+0/6/ G%$ 43 / 33 / 25 / 22 43 / 35 / 30 / 25 45 / 37 / 29 / 23 45 / 39 / 32 / 26
Outdoor Unit RXM09WVJU9 RXM12WVJU9
&DVLQJ&RORU ,YRU\:KLWH ,YRU\:KLWH
Compressor Type +HUPHWLFDOO\6HDOHG6ZLQJ7\SH +HUPHWLFDOO\6HDOHG6ZLQJ7\SH
Model <%.&;$ <%.&;$
5HIULJHUDQW2LO Type FW50DA FW50DA
&KDUJH R]/  
5HIULJHUDQW Type 5 5
&KDUJH OEVNJ  
$LUÀRZ5DWHV H / SL FIP
(m
3
PLQ








)DQ Type Propeller Propeller
+HDW([FKDQJHU Type
:DႉH)LQI+L;6/WXEH :DႉH)LQI+L;6/WXEH
5RZVî6WDJHV/HQJWKPP
/ FPI
î î
'LPHQVLRQV+î:î' LQPP îîîî îîîî
3DFNDJHG'LPHQVLRQV+î:î' LQPP îîîî îîîî
:HLJKW0DVV OEVNJ  
*URVV:HLJKW*URVV0DVV OEVNJ  
6RXQG3UHVVXUH/HYHO+6/ G%$ 47 / — 49 / — 49 / — 52 / —
&RQGLWLRQV%DVHGRQ ,QGRRU)'%&'%
):%&:%
2XWGRRU)'%&'%
):%&:%
3LSLQJ/HQJWKIWP
,QGRRU)'%&'%
):%&:%
2XWGRRU)'%&'%
):%&:%
3LSLQJ/HQJWKIWP
,QGRRU)'%&'%
):%&:%
2XWGRRU)'%&'%
):%&:%
3LSLQJ/HQJWKIWP
,QGRRU)'%&'%
):%&:%
2XWGRRU)'%&'%
):%&:%
3LSLQJ/HQJWKIWP
'UDZLQJ1R 3D142773A 3D142773A
1RWHV 6/7KHTXLHWIDQOHYHORIWKHDLUÀRZUDWHVHWWLQJ 6/7KHTXLHWIDQOHYHORIWKHDLUÀRZUDWHVHWWLQJ
&RQYHUVLRQ)RUPXODH
NFDOK N:î
%WXK N:î
FIP P
3
PLQî
background
SiUS042113EA Specifications
Part 2 Specifications 18
Model
Indoor Unit FTXM18WVJU9 FTXM24WVJU9
Outdoor Unit
RXM18WVJU9 RXM24WVJU9
Cooling Heating Cooling Heating
3RZHU6XSSO\
3KDVH
1 I 1 I
+]9 +]9 +]9
&DSDFLW\5DWHG0LQ0D[ %WXK a a a a
3RZHU&RQVXPSWLRQ5DWHG W    
3RZHU)DFWRU5DWHG % 95.5 - 95.4 97.6 - 97.6 97.3 - 97.3 99.0 - 99.0
6((5+63) 22.70 10.00 22.00 10.00
((55DWHG %WXKā: 12.50 — 12.00 —
&235DWHG W/W — 3.60 — 3.54
Piping Connection Liquid
LQPP
I I
*DV
LQPP
I I
'UDLQ
LQPP
I I
0D[,QWHUXQLW3LSLQJ/HQJWK IWP  
0D[,QWHUXQLW+HLJKW'LႇHUHQFH IWP  
&KDUJHOHVV IWP  
$PRXQWRI$GGLWLRQDO&KDUJHRI
5HIULJHUDQW
R]IWJP  
Indoor Unit FTXM18WVJU9 FTXM24WVJU9
)URQW3DQHO&RORU :KLWH1 :KLWH1
$LUÀRZ5DWHV H
FIP
(m
3
PLQ
   
M    
L    
SL    
)DQ Type &URVV)ORZ)DQ &URVV)ORZ)DQ
Speed Steps 6WHSV4XLHW$XWR 6WHSV4XLHW$XWR
+HDW([FKDQJHU Type
0XOWL6OLW)LQI+L;%WXEH 0XOWL6OLW)LQI+L;%WXEH
5RZVî6WDJHV/HQJWKPP
/ FPI
î
î
î
î
î
î
'LPHQVLRQV+î:î' LQPP îîîî îîîî
3DFNDJHG'LPHQVLRQV+î:î' LQPP îîîî îîîî
:HLJKW0DVV OEVNJ  
*URVV:HLJKW*URVV0DVV OEVNJ  
6RXQG3UHVVXUH/HYHO+0/6/ G%$ 49 / 41 / 36 / 33 49 / 40 / 35 / 32 51 / 44 / 37 / 34 51 / 42 / 37 / 34
Outdoor Unit RXM18WVJU9 RXM24WVJU9
&DVLQJ&RORU ,YRU\:KLWH ,YRU\:KLWH
Compressor Type +HUPHWLFDOO\6HDOHG6ZLQJ7\SH +HUPHWLFDOO\6HDOHG6ZLQJ7\SH
Model <%3%;$ <%3%;$
5HIULJHUDQW2LO Type FW68DA FW68DA
&KDUJH R]/  
5HIULJHUDQW Type 5 5
&KDUJH OEVNJ  
$LUÀRZ5DWHV H / SL FIP
(m
3
PLQ








)DQ Type Propeller Propeller
+HDW([FKDQJHU Type
:DႉH)LQI+L;6/WXEH :DႉH)LQI+L;6/WXEH
5RZVî6WDJHV/HQJWKPP
/ FPI
î î
'LPHQVLRQV+î:î' LQPP îîîî îîîî
3DFNDJHG'LPHQVLRQV+î:î' LQPP îîîî îîîî
:HLJKW0DVV OEVNJ  
*URVV:HLJKW*URVV0DVV OEVNJ  
6RXQG3UHVVXUH/HYHO+6/ G%$ 54 / — 55 / — 55 / — 56 / —
&RQGLWLRQV%DVHGRQ ,QGRRU)'%&'%
):%&:%
2XWGRRU)'%&'%
):%&:%
3LSLQJ/HQJWKIWP
,QGRRU)'%&'%
):%&:%
2XWGRRU)'%&'%
):%&:%
3LSLQJ/HQJWKIWP
,QGRRU)'%&'%
):%&:%
2XWGRRU)'%&'%
):%&:%
3LSLQJ/HQJWKIWP
,QGRRU)'%&'%
):%&:%
2XWGRRU)'%&'%
):%&:%
3LSLQJ/HQJWKIWP
'UDZLQJ1R 3D142774A 3D142774A
1RWHV 6/7KHTXLHWIDQOHYHORIWKHDLUÀRZUDWHVHWWLQJ 6/7KHTXLHWIDQOHYHORIWKHDLUÀRZUDWHVHWWLQJ
&RQYHUVLRQ)RUPXODH
NFDOK N:î
%WXK N:î
FIP P
3
PLQî
background
Specifications SiUS042113EA
19 Part 2 Specifications
1.2 FTXM-V Series
Model Indoor Unit FTXM09VVJU FTXM12VVJU
Outdoor Unit RXM09VVJU RXM12VVJU
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
Capacity Rated (Min. - Max.) Btu/h 9,000 (4,400 ~ 12,500) 11,000 (4,400 ~ 19,500) 12,000 (4,800 ~ 16,000) 13,600 (4,800 ~ 22,600)
Power Consumption (Rated) W 552 701 909 906
Power Factor (Rated) % 92.5 94.6 96.2 96.8
SEER / HSPF 27.40 13.80 25.20 13.00
EER (Rated) Btu/Wh 16.30 — 13.20 —
COP (Rated) W/W — 4.60 — 4.40
Piping
Connection
Liquid in. (mm) 1/4 (6.4) 1/4 (6.4)
Gas in. (mm) 3/8 (9.5) 3/8 (9.5)
Drain in. (mm) 5/8 (16) 5/8 (16)
Max. Interunit Piping Length ft (m) 82-1/64 (25) 82-1/64 (25)
Max. Interunit Height Difference ft (m) 65-5/8 (20) 65-5/8 (20)
Chargeless ft (m) 49.2 (15) 49.2 (15)
Amount of Additional Charge of
Refrigerant
oz/ft
(g/m)
0.22 (20) 0.22 (20)
Indoor Unit FTXM09VVJU FTXM12VVJU
Front Panel Color (Munsell No.) White (N-9.5) White (N-9.5)
Airflow Rates H
cfm
(m³/min)
515 (14.6) 515 (14.6) 557 (15.8) 557 (15.8)
M 340 (9.6) 370 (10.5) 394 (11.2) 412 (11.7)
L 249 (7.1) 304 (8.6) 292 (8.3) 340 (9.6)
SL 219 (6.2) 249 (7.1) 225 (6.4) 255 (7.2)
Fan Type Cross Flow Fan Cross Flow Fan
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Heat Exchanger Type Multi Slit Fin Multi Slit Fin
Rows × Stages, Fin Pitch
(mm)
2 × 18, 1.4
1 × 8, 1.4
1 × 4, 1.4
2 × 18, 1.4
1 × 8, 1.4
1 × 4, 1.4
Dimensions (H × W × D) in. (mm) 11-3/4 × 36-1/4 × 10-13/16 (299 × 920 × 275) 11-3/4 × 36-1/4 × 10-13/16 (299 × 920 × 275)
Packaged Dimensions (H × W × D) in. (mm) 14-15/16 × 39-3/4 × 15-3/8 (380 × 1,010 × 391) 14-15/16 × 39-3/4 × 15-3/8 (380 × 1,010 × 391)
Weight (Mass) lbs (kg) 29 (13) 29 (13)
Gross Weight (Gross Mass) lbs (kg) 38 (17) 38 (17)
Sound Pressure Level (H / M / L / SL) dB(A) 43 / 33 / 25 / 22 43 / 35 / 30 / 25 45 / 37 / 29 / 23 45 / 39 / 32 / 26
Outdoor Unit RXM09VVJU RXM12VVJU
Casing Color Ivory White Ivory White
Compressor Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2Y147BKCX1A 2Y147BKCX1A
Refrigerant Oil Type FW50DA FW50DA
Charge oz (L) 15.17 (0.430) 15.17 (0.430)
Refrigerant Type R-32 R-32
Charge lbs (kg) 2.16 (0.98) 2.16 (0.98)
Airflow Rates H / SL cfm
(m³/min)
1,317 / 1,183
(37.3 / 33.5)
1,296 / 922
(36.7 / 26.1)
1,487 / 1,317
(42.1 / 37.3)
1,487 / 922
(42.1 / 26.1)
Fan Type Propeller Propeller
Heat Exchanger Type Waffle Fin Waffle Fin
Rows × Stages, Fin Pitch
(mm)
2 × 26, 1.4 2 × 26, 1.4
Dimensions (H × W × D) in. (mm) 23-7/16 × 33-1/4 × 11-13/16 (595 × 845 × 300) 23-7/16 × 33-1/4 × 11-13/16 (595 × 845 × 300)
Packaged Dimensions (H × W × D) in. (mm) 26 × 39-5/8 × 16-15/16 (660 × 1,007 × 430) 26 × 39-5/8 × 16-15/16 (660 × 1,007 × 430)
Weight (Mass) lbs (kg) 96 (44) 96 (44)
Gross Weight (Gross Mass) lbs (kg) 103 (47) 103 (47)
Sound Pressure Level (H / SL) dB(A) 47 / — 49 / — 49 / — 52 / —
Conditions Based on Indoor ; 80°FDB (26.7°CDB) /
67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB) /
75°FWB (24°CWB)
Piping Length: 25 ft (7.5 m)
Indoor ; 70°FDB (21.1°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6.1°CWB)
Piping Length: 25 ft (7.5 m)
Indoor ; 80°FDB (26.7°CDB) /
67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB) /
75°FWB (24°CWB)
Piping Length: 25 ft (7.5 m)
Indoor ; 70°FDB (21.1°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6.1°CWB)
Piping Length: 25 ft (7.5 m)
Drawing No. 3D133578A 3D133578A
Note(s) SL: The quiet fan level of the airflow rate setting. SL: The quiet fan level of the airflow rate setting.
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm =
m³/min ×
35.3
background
SiUS042113EA Specifications
Part 2 Specifications 20
Model Indoor Unit FTXM18VVJU FTXM24VVJU
Outdoor Unit RXM18VVJU RXM24VVJU
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
Capacity Rated (Min. - Max.) Btu/h 18,000 (9,000 ~ 22,000) 21,600 (9,000 ~ 30,200) 21,600 (9,000 ~ 26,000) 24,000 (9,000 ~ 32,200)
Power Consumption (Rated) W 1,440 1,665 1,728 1,986
Power Factor (Rated) % 95.4 97.6 97.3 99
SEER / HSPF 22.70 12.50 22.00 12.50
EER (Rated) Btu/Wh 12.50 — 12.50 —
COP (Rated) W/W — 3.80 — 3.54
Piping
Connection
Liquid in. (mm) 1/4 (6.4) 1/4 (6.4)
Gas in. (mm) 1/2 (12.7) 5/8 (15.9)
Drain in. (mm) 5/8 (16) 5/8 (16)
Max. Interunit Piping Length ft (m) 98-1/2 (30) 98-1/2 (30)
Max. Interunit Height Difference ft (m) 82-1/64 (25) 82-1/64 (25)
Chargeless ft (m) 49.2 (15) 49.2 (15)
Amount of Additional Charge of
Refrigerant
oz/ft
(g/m)
0.22 (20) 0.22 (20)
Indoor Unit FTXM18VVJU FTXM24VVJU
Front Panel Color (Munsell No.) White (N-9.5) White (N-9.5)
Airflow Rates H
cfm
(m³/min)
776 (22.0) 776 (22.0) 845 (23.9) 845 (23.9)
M 583 (16.5) 559 (15.8) 652 (18.5) 606 (17.2)
L 482 (13.7) 467 (13.2) 498 (14.1) 498 (14.1)
SL 428 (12.1) 413 (11.7) 451 (12.8) 451 (12.8)
Fan Type Cross Flow Fan Cross Flow Fan
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Heat Exchanger Type Multi Slit Fin Multi Slit Fin
Rows × Stages, Fin Pitch
(mm)
2 × 18, 1.4
1 × 8, 1.4
1 × 4, 1.4
2 × 18, 1.4
1 × 8, 1.4
1 × 4, 1.4
Dimensions (H × W × D) in. (mm) 11-3/4 × 43-5/16 × 10-13/16 (299 × 1,100 × 275) 11-3/4 × 43-5/16 × 10-13/16 (299 × 1,100 × 275)
Packaged Dimensions (H × W × D) in. (mm) 15-13/16 × 47-11/16 × 15-1/2 (401 × 1,212 × 393) 15-13/16 × 47-11/16 × 15-1/2 (401 × 1,212 × 393)
Weight (Mass) lbs (kg) 33 (15) 33 (15)
Gross Weight (Gross Mass) lbs (kg) 46 (21) 46 (21)
Sound Pressure Level (H / M / L / SL) dB(A) 49 / 41 / 36 / 33 49 / 40 / 35 / 32 51 / 44 / 37 / 34 51 / 42 / 37 / 34
Outdoor Unit RXM18VVJU RXM24VVJU
Casing Color Ivory White Ivory White
Compressor Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2Y260BPBX1A 2Y260BPBX1A
Refrigerant Oil Type FW68DA FW68DA
Charge oz (L) 31.75 (0.900) 31.75 (0.900)
Refrigerant Type R-32 R-32
Charge lbs (kg) 2.98 (1.35) 2.98 (1.35)
Airflow Rates H / SL cfm
(m³/min)
2,119 / 1,833
(60.0 / 51.9)
2,062 / 1,773
(58.4 / 50.2)
2,179 / 1,833
(61.7 / 51.9)
2,119 / 1,833
(60.0 / 51.9)
Fan Type Propeller Propeller
Heat Exchanger Type Waffle Fin Waffle Fin
Rows × Stages, Fin Pitch
(mm)
2 × 32, 1.4 2 × 32, 1.4
Dimensions (H × W × D) in. (mm) 28-15/16 × 34-1/4 × 12-5/8 (735 × 870 × 320) 28-15/16 × 34-1/4 × 12-5/8 (735 × 870 × 320)
Packaged Dimensions (H × W × D) in. (mm) 31-7/8 × 41-1/2 × 18-1/4 (810 × 1,056 × 464) 31-7/8 × 41-1/2 × 18-1/4 (810 × 1,056 × 464)
Weight (Mass) lbs (kg) 132 (60) 132 (60)
Gross Weight (Gross Mass) lbs (kg) 143 (65) 143 (65)
Sound Pressure Level (H / SL) dB(A) 54 / — 55 / — 55 / — 56 / —
Conditions Based on Indoor ; 80°FDB (26.7°CDB) /
67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB) /
75°FWB (24°CWB)
Piping Length: 25 ft (7.5 m)
Indoor ; 70°FDB (21.1°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6.1°CWB)
Piping Length: 25 ft (7.5 m)
Indoor ; 80°FDB (26.7°CDB) /
67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB) /
75°FWB (24°CWB)
Piping Length: 25 ft (7.5 m)
Indoor ; 70°FDB (21.1°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6.1°CWB)
Piping Length: 25 ft (7.5 m)
Drawing No. 3D133579 3D133579
Note(s) SL: The quiet fan level of the airflow rate setting. SL: The quiet fan level of the airflow rate
setting.
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
background
SiUS042113EA
21 Part 3 Printed Circuit Board Connector Wiring Diagram
1. Indoor Unit.................................................................................................22
2. Outdoor Unit..............................................................................................26
2.1 09/12 class ................................................................................................. 26
2.2 18/24 class ................................................................................................. 28
Part 3
Printed Circuit Board
Connector Wiring Diagram
background
SiUS042113EA Indoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram 22
1. Indoor Unit
Control PCB
(A1P)
1) S16 Connector for optional adaptor
2) S21 Connector for optional adaptor
3) S200 Connector for DC fan motor
4) S300A, S301B Connector for power supply PCB (A2P)
5) S400 Connector for swing motors
6) S501 Connector for indoor heat exchanger thermistor (R1T)
7) S600 Connector for humidity sensor PCB (A4P)
8) S602 Connector for INTELLIGENT EYE sensor PCB (A5P)
9) S800 Connector for display/signal receiver PCB (A3P)
10) S801 Connector for wireless LAN connection PCB (A6P)
S501
S300A
S301B
S400
S200
S21
S16
S600
S800
S801
S602
2P578254-10
2P578254-11
background
Indoor Unit SiUS042113EA
23 Part 3 Printed Circuit Board Connector Wiring Diagram
Power Supply
PCB (A2P)
FTXM-W Series
FTXM-V Series
1) S101 Connector for terminal strip (indoor-outdoor transmission)
2) S102, S103 Connector for control PCB (A1P)
3) FG Connector for terminal strip (frame ground)
4) F1U Fuse (3.15 A, 250 V)
5) R1V Varistor
S102 S103
FG F1U S101R1V
2P659905-7
S102 S103
FG F1U S101R1V
2P578255-7
background
SiUS042113EA Indoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram 24
Display/Signal
Receiver PCB
(A3P)
Humidity Sensor
PCB (A4P)
INTELLIGENT
EYE Sensor PCB
(A5P)
1) S920 Connector for control PCB (A1P)
2) BS1 Indoor unit ON/OFF switch
(Forced cooling operation ON/OFF switch)
Refer to page 156 for details of forced cooling operation.
3) H1P LED for operation (green)
4) H2P LED for timer (yellow)
5) H3P LED for CLEAN operation (green)
6) H4P LED for INTELLIGENT EYE (green)
7) H5P LED for wireless LAN connection (yellow)
3P579849-1
H3P
H4P
H5P
H2P
BS1
H1P
S920
1) Connector Connector for control PCB (A1P)
3E860023-1
Connector
1) Connector Connector for control PCB (A1P)
09/12 class 18/24 class
3EB86013-1
Connector
Connector
3P629375-1
background
Indoor Unit SiUS042113EA
25 Part 3 Printed Circuit Board Connector Wiring Diagram
Wireless LAN
connection PCB
(A6P)
1) Connector Connector for control PCB (A1P)
Connector
2P571193-4
background
SiUS042113EA Outdoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram 26
2. Outdoor Unit
2.1 09/12 class
Main PCB (A1P)
1) S20 Connector for electronic expansion valve coil
2) S40 Connector for overload protector and high pressure switch
3) S70 Connector for DC fan motor
4) S80 Connector for four way valve
5) S90 Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge
pipe temperature)
6) S97 Connector for liquid pipe thermistor
7) HL1, HN1, S Wire harness for terminal strip
8) E1, E2 Wire harness for earth/ground wire
9) U, V, W Wire harness for compressor
10) FU1, FU2 Fuse (3.15 A, 250 V)
11) FU3 Fuse (30 A, 250 V)
12) LEDA LED for service monitor (green)
13) V1, V2, V3 Varistor
14) J4 Jumper for facility setting
Refer to page 160 for details.
15 J5 Jumper for warmer airflow setting
Refer to page 161 for details.
16) J9 Jumper for drain pan heater
Refer to page 163 for details.
background
Outdoor Unit SiUS042113EA
27 Part 3 Printed Circuit Board Connector Wiring Diagram
Caution
Replace the PCB if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
2P628602-1
2P628602-2
LEDA
FU1
FU3
FU2
S90
S40
S20
S70
V2
V3
V1
S80
S97
E2
E1
HN1
S
HL1
W V U
J9 J4
J5
background
SiUS042113EA Outdoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram 28
2.2 18/24 class
Main PCB (A1P)
1) S Connector for terminal block (indoor - outdoor transmission)
2) S20 Connector for electronic expansion valve coil (White)
3) S40 Connector for overload protector and high pressure switch
4) S70 Connector for DC fan motor
5) S80 Connector for four way valve coil
6) S90 Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe,
liquid pipe)
7) S201, S202 Wire harness for service monitor PCB (A2P)
8) CK1 Wire harness for voltage endurance test
9) HL1, HN1 Wire harness for terminal block (power supply)
10) E1, E2 Wire harness for earth/ground wire
11) U, V, W Wire harness for compressor
12) FU1, FU2 Fuse (3.15 A, 250 V)
13) FU3 Fuse (30 A, 250 V)
14) V2, V3, V401 Varistor
V401
E1, E2
FU1 V3
V2
FU3
HN1
HL1
CK1
S20
S90
S201
S
S70
S202
U, V, W
FU2S80
S40
2P455785-15
2P455785-22
background
Outdoor Unit SiUS042113EA
29 Part 3 Printed Circuit Board Connector Wiring Diagram
Service Monitor
PCB (A2P)
SW1 ~ SW4 and LED1 ~ LED5 do not work.
1) S501, S502 Connector for main PCB (A1P)
2) LEDA LED for service monitor (green)
3) SW5-2 Switch for warmer airflow setting
Refer to page 161 for details.
4) SW5-3 Switch for facility setting
Refer to page 160 for details.
5) SW6-1 Switch for drain pan heater
Refer to page 163 for details.
background
SiUS042113EA
Part 4 Functions and Control 30
1. Main Functions..........................................................................................31
1.1 Temperature Control .................................................................................. 31
1.2 Frequency Principle.................................................................................... 31
1.3 Airflow Direction Control............................................................................. 33
1.4 COMFORT AIRFLOW Operation ............................................................... 34
1.5 Fan Speed Control for Indoor Unit ............................................................. 36
1.6 Hybrid Cooling............................................................................................ 37
1.7 Automatic Cooling/Heating Changeover .................................................... 40
1.8 Thermostat Control..................................................................................... 41
1.9 NIGHT SET Mode ...................................................................................... 42
1.10 ECONO Operation .................................................................................... 42
1.11 2-Area INTELLIGENT EYE Operation ....................................................... 43
1.12 INTELLIGENT EYE Operation ................................................................... 47
1.13 POWERFUL Operation .............................................................................. 49
1.14 Clock Setting .............................................................................................. 50
1.15 WEEKLY TIMER Operation ....................................................................... 51
1.16 Brightness Setting of Indoor Unit Display................................................... 57
1.17 CLEAN Operation....................................................................................... 58
1.18 Wireless LAN Connection .......................................................................... 60
1.19 Other Functions.......................................................................................... 65
2. Thermistor Functions ................................................................................66
3. Control Specification .................................................................................68
3.1 Mode Hierarchy .......................................................................................... 68
3.2 Frequency Control...................................................................................... 68
3.3 Standby Electricity Saving (Suspend Function) ......................................... 70
3.4 Controls at Mode Changing/Start-up.......................................................... 71
3.5 Discharge Pipe Temperature Control......................................................... 73
3.6 Input Current Control.................................................................................. 74
3.7 Freeze-up Protection Control ..................................................................... 75
3.8 Heating Peak-cut Control ........................................................................... 75
3.9 High Pressure Protection Control............................................................... 76
3.10 Outdoor Fan Control................................................................................... 77
3.11 Liquid Compression Protection Function.................................................... 77
3.12 Defrost Control ........................................................................................... 78
3.13 Electronic Expansion Valve Control ........................................................... 79
3.14 Malfunctions ............................................................................................... 82
Part 4
Functions and Control
background
Main Functions SiUS042113EA
31 Part 4 Functions and Control
1. Main Functions
1.1 Temperature Control
Definitions of
Temperatures
The definitions of temperatures are classified as following.
Room temperature: temperature of lower part of the room
Set temperature: temperature set by remote controller
Room thermistor temperature: temperature detected by room temperature thermistor
Target temperature: temperature determined by microcomputer
Temperature
Control
The temperature of the room is detected by the room temperature thermistor. However, there is a
difference between the temperature detected by room temperature thermistor and the temperature
of lower part of the room, depending on the type of the indoor unit or installation condition. In
practice, the temperature control is done by the target temperature appropriately adjusted for the
indoor unit and the temperature detected by room temperature thermistor.
1.2 Frequency Principle
Control
Parameters
The frequency of the compressor is controlled by the following 2 parameters:
The load condition of the operating indoor unit
The difference between the room thermistor temperature and the target temperature
The target frequency is adapted by additional parameters in the following cases:
Frequency restrictions
Initial settings
Forced cooling operation
Inverter Principle To regulate the capacity, a frequency control is needed. The inverter makes it possible to control
the rotation speed of the compressor. The followings explain the inverter principle:
Phase 1
The supplied AC power source is converted into the DC power source for the present.
Phase 2
The DC power source is reconverted into the three phase AC power source with variable
frequency.
When the frequency increases, the rotation speed of the compressor increases resulting in an
increase of refrigerant circulation. This leads to a larger amount of heat exchange per unit.
Target temperature
Set temperature
Room temperature
Room thermistor temperature
(R12321)
background
SiUS042113EA Main Functions
Part 4 Functions and Control 32
When the frequency decreases, the rotation speed of the compressor decreases resulting in a
decrease of refrigerant circulation. This leads to a smaller amount of heat exchange per unit.
The following drawing shows a schematic view of the inverter principle:
Inverter Features The inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor temperature
and cooling/heating load.
Quick heating and quick cooling
The rotation speed of the compressor is increased when starting the heating (cooling).
This enables to reach the set temperature quickly.
Even during extreme cold weather, high capacity is achieved. It is maintained even when the
outdoor temperature is 2C (35.6°F).
Comfortable air conditioning
A fine adjustment is integrated to keep the room temperature constant.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the room
temperature at low power.
Frequency Limits The following functions regulate maximum frequency:
Low frequency
Four way valve operation compensation. Refer to page 71.
High frequency
Compressor protection function. Refer to page 72.
Discharge pipe temperature control. Refer to page 73.
Input current control. Refer to page 74.
Freeze-up protection control. Refer to page 75.
Heating peak-cut control. Refer to page 75.
Defrost control. Refer to page 78.
Forced Cooling
Operation
Refer to page 156 for details.
Refrigerant circulation rate (high)
high f
low f
freq=variable
Refrigerant circulation rate (low)
high speed
low speed
(R2812)
Amount of heat
exchanged air (large)
freq=
constant
50 Hz
50 Hz
60 Hz
60 Hz
capacity=
variable
Amount of heat
exchanged air (small)
AC
power
DC
power
Amount of heat exchanged air
(large)
Amount of heat exchanged air
(small)
background
Main Functions SiUS042113EA
33 Part 4 Functions and Control
1.3 Airflow Direction Control
Power-Airflow
Dual Flaps
The large flap sends a large volume of air downward to the floor and provides an optimum control in
cooling, dry and heating operation.
Cooling/Dry
During cooling or dry operation, the flap retracts into the indoor unit. Then, cool air can be blown far
and distributed all over the room.
Heating
During heating operation, the large flap directs airflow downward to spread the warm air to the
entire room.
Wide-Angle
Louvers
The louvers, made of elastic synthetic resin, provide a wide range of airflow that guarantees
comfortable air distribution.
Auto-Swing The following tables explain the auto-swing process for cooling, dry, heating and fan:
3-D Airflow Alternative repetition of vertical and horizontal swing motions enables uniform air-conditioning of
the entire room.
When the horizontal swing and vertical swing are both set to automatic operation, the airflow
becomes 3-D airflow. The horizontal and vertical swing motions are alternated and the airflow
direction changes in the order shown in the following diagram.
(1) The vertical blades (louvers) move from the right to the left.
(2) The horizontal blades (flaps) move downward.
(3) The vertical blades (louvers) move from the left to the right.
(4) The horizontal blades (flaps) move upward.
Flap (up and down)
Louver
(right and left)
Cooling/Dry Heating Fan
R4003783 R4003784 R4003785
R4003764
(R19554)
(2)
(4)
(3)
(1)
background
SiUS042113EA Main Functions
Part 4 Functions and Control 34
1.4 COMFORT AIRFLOW Operation
Outline New flap structure is developed with technology Coanda. In cooling operation, ceiling airflow
provides cool air upward along the ceiling as far as entire the room. In heating operation, draftless
airflow directs warm air straight downward to your feet.
Apply new airflow system, providing a comfortable cooling and heating space without draft
feeling and spreading comfort airflow with large air volume in low velocity with double airflow
technology to disseminate a wide of airflow in low velocity even with the large air volume.
Wind reaches far
Reaching distance 16.4 ft (5 m) (for 09/12 class), 32.8 ft (10 m) (for 18/24 class)
The comfort mode is set during cooling. Measure the distance that can secure a wind speed of
0.4 m/s or more at a position of 1.18 inch (30 mm) from the ceiling.
R4003805
Reaching distance 9.84 ft (3 m) (for all class)
The comfort mode is set during heating. Measure the distance that can secure a wind speed of
0.3 m/s or less at a position of 3.28 ft (1 m) from the floor.
R4003809
Ceiling airflow (Cooling)
16.4 ft (5 m) (for 09/12 class)
32.8 ft (10 m) (for 18/24 class)
1.18 inch (30 mm)
Wind speed 0.4 m/s or more
Draftless airflow (Heating)
Wind speed 0.3 m/s or less
3.28 ft (1 m)
*Floor temperature sensor is not mounted on.
30°
9.84 ft (3 m)
background
Main Functions SiUS042113EA
35 Part 4 Functions and Control
Note(s)
Operation
To start the operation:
Press Comfort button.
The icon appears on the display.
To stop the operation:
Press Comfort button again.
The icon disappears from the display. The flaps will return to the memory position from before
COMFORT AIRFLOW operation
POWERFUL operation and COMFORT AIRFLOW operation cannot be used at the same time.
The airflow rate will be set to AUTO.
If the upward and downward airflow direction is selected, the COMFORT AIRFLOW function will
be canceled. Priority is given to the function of whichever button is pressed last.
If there is an obstruction under the air conditioner when using heating, the airflow may not reach
the center of the room and the room may be difficult to warm up.
COOL / DRY operation HEAT operation FAN operation
Flaps direction Goes up Goes down
Not available
Airflow rate AUTO
Comfort button
background
SiUS042113EA Main Functions
Part 4 Functions and Control 36
Note(s)
1.5 Fan Speed Control for Indoor Unit
Outline Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room
thermistor temperature and the target temperature.
Automatic Fan
Speed Control
In automatic fan speed operation, the step SL is not available.
R4003512
= The airflow rate is automatically controlled within this range when FAN setting button is set
to automatic
.
Cooling
The following drawing explains the principle of fan speed control for cooling.
The upper limit is at M tap in 30 minutes from the operation start.
Heating
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
The fan stops during defrost operation.
HeatingCoolingStep
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
(R21654)
+2.5°C (+4.5°F)
+1.5°C (+2.7°F)
+0.5°C (+0.9°F)
MH*
M
ML
L
+3°C (+5.4°F)
+2°C (+3.6°F)
+1°C (+1.8°F)
Fan speed
Room thermistor temperature – target temperature
background
Main Functions SiUS042113EA
37 Part 4 Functions and Control
1.6 Hybrid Cooling
Operation Hybrid cooling becomes effective when COOL or DRY is selected from MODE button of the remote
controller. In cooling operation, hybrid cooling is automatically activated when the room
temperature approaches to the target temperature set from the remote controller. When more
cooling capacity is required, the operation automatically returns to the normal cooling operation.
During dry operation, in addition to the above, the indoor unit fan is automatically controlled to help
dehumidification.
R4003786
Outline In hybrid cooling, only a part of the heat exchanger is cooled. The cool, dehumidified air is mixed
with the room air, and then blown out at around the same temperature with the room air. This is to
keep dehumidification effect after the target temperature is reached. The area of the heat
exchanger to be cooled is determined automatically based on the amount of humidity to remove.
Particularly, when the amount of humidity is large, the area of the heat exchanger to be cooled also
becomes large. When the amount of humidity is small, the area of heat exchanger becomes small,
too.
MODE selector button
• Selects the operation mode.
AUTO DRY COOL HEAT FAN
(R25241)
Temperature is controlled by
mixing the room air
Normal cooling Hybrid cooling:
After the target temperature
is reached
Dehumidification effect
continues by partially cooling
the heat exchanger
background
SiUS042113EA Main Functions
Part 4 Functions and Control 38
Details Humidity to be removed
The amount of air to be dehumidified changes depending on the amount of humidity to be removed.
To remove the larger amount of humidity, the amount of air passing through the heat exchanger
becomes larger while the absolute humidity difference unchanged.
(1) Suction air
(2) Dehumidified suction air (air passed through the cooled part of the heat exchanger)
(3) Dehumidified air mixed with room air
Room temperature control in dry operation
Room temperature zones in dry operation are described as below.
(2)
(3)
(1)
Dehumidifying
amount
Absolute humidity x (kg/kg)
Dry-bulb temperature t (°C)
(R25238)
(R25242)
J
3
2.5
1.5
0.5
0
−0.5
(c)
(d)
Thermostat ON (a)
When room temperature decreases When room temperature increases
Thermostat OFF (b)
1
2
I
H
G
F
E
D
C
B
A
Room temperature
− target temperature
background
Main Functions SiUS042113EA
39 Part 4 Functions and Control
Refer to the table below for (a) Thermostat ON and (b) Thermostat OFF values in various room
temperatures when dry operation is started.
* Refer to Thermostat Control on P. 41 for details.
Indoor unit fan control in dry operation
During dry operation, fan rotation speed is automatically controlled according to the room
temperature zones shown above and airflow rate cannot be set manually. In addition, fan rotation
speed is also adjusted with the room humidity.
* In all steps from H to L, the fan rotation speed is specific to dry operation and different from that in
cooling operation.
Liquid pipe temperature control using electronic expansion valve
Evaporation temperature in indoor unit is controlled to make the temperature indicated by the liquid
pipe thermistor, near the outlet side of the electronic expansion valve, reach the target temperature.
R4003500
Temperature when dry operation is
started
(a)
Thermostat
ON
(b)
Thermostat
OFF
(c) (d)
26°C (78.8°F) ≤ Room temperature –2.5°C
(–4.5°F)
–3°C
(–5.4°F)
–1.5°C
(–2.7°F)
–2°C
(–3.6°F)
23°C (73.4°F) ≤ Room temperature <
26°C (78.8°F)
–2.5°C
(–4.5°F)
–3°C
(–5.4°F)
–1.5°C
(–2.7°F)
–2°C
(–3.6°F)
Room temperature < 23°C (73.4°F) –2°C
(–3.6°F)
–2.5°C
(–4.5°F)
–1°C
(–1.8°F)
–1.5°C
(–2.7°F)
Room temperature
zone
Fan tap
J
H
I
H
MHG
F
E
M
D
CML
B
L
A
Compressor
Expansion valve
Outdoor
unit
Liquid pipe thermistor
Indoor
unit
background
SiUS042113EA Main Functions
Part 4 Functions and Control 40
1.7 Automatic Cooling/Heating Changeover
Outline When the automatic operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Details Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
1. The set temperature (Ts) determines the target temperature (Tt).
(Ts = 18 ~ 30°C (64.4 ~ 86°F))
2. The target temperature (Tt) is calculated as;
Tt = Ts + C
where C is the correction value.
C = 0°C (0°F)
3. Thermostat ON/OFF point and operation mode switching point are as follows.
(1) Heating Cooling switching point:
Tr Tt + 3.0°C (+ 5.4°F)
(2) Cooling Heating switching point:
Tr < Tt – 2.5°C (– 4.5°F)
(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating operation.
4. During initial operation
Tr Ts : Cooling operation
Tr < Ts : Heating operation
R4003810
Ex: When the target temperature is 25°C (77°F)
Cooling → 23°C (73.4°F): Thermostat OFF → 22.5°C (72.5°F): Switch to heating
Heating → 27°C (80.6°F): Thermostat OFF → 28°C (82.4°F): Switch to cooling
Target temperature + 3.0°C (+5.4°F)
Heating Operation
Target temperature – 2.5°C (–4.5°F)
Cooling Operation
Target temperature – 2.0°C (–3.6°F)
= Thermostat OFF
Target temperature + 2.0°C (+3.6°F)
= Thermostat OFF
background
Main Functions SiUS042113EA
41 Part 4 Functions and Control
Reference
1.8 Thermostat Control
Outline Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Details Thermostat OFF Conditions
The temperature difference is in the zone A.
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling: 10 minutes, Heating: 10 seconds)
Cooling
Heating
Refer to Temperature Control on page 31 for details.
Zone BZone B
Zone AZone A
OFFOFF
ONON
Zone CZone C
Room thermistor temperature – target temperature
–1.0°C (–1.8°F)
–2.0°C (–3.6°F)
(R24031)
–0.5°C (–0.9°F)
–1.5°C (–2.7°F)
Zone BZone B
Zone AZone A
OFFOFF
ONON
Zone CZone C
2.0°C (3.6°F)
1.0°C (1.8°F)
0.5°C (0.9°F)
1.5°C (2.7°F)
2.0°C (3.6°F)
Room ther
mistor temper
ature – target temperature
(R24033)
background
SiUS042113EA Main Functions
Part 4 Functions and Control 42
1.9 NIGHT SET Mode
Outline When the OFF TIMER is set, NIGHT SET mode is automatically activated. NIGHT SET mode
keeps the airflow rate setting.
Details NIGHT SET mode continues operation at the target temperature for the first one hour, then
automatically raises the target temperature slightly in the case of cooling, or lowers the target
temperature slightly in the case of heating. This prevents excessive cooling in summer and
excessive heating in winter to ensure comfortable sleeping conditions, and also conserves
electricity.
Cooling
Heating
1.10 ECONO Operation
Outline ECONO operation reduces the maximum operating current and the power consumption.
This operation is particularly convenient for energy-saving. It is also a major bonus when breaker
capacity does not allow the use of multiple electrical devices and air conditioners.
It can be easily activated by pressing Econo/Quiet button on the wireless remote controller.
Details When this function is activated, the maximum capacity also decreases.
The remote controller can send the ECONO command when the unit is in cooling, heating, dry,
or automatic operation. This function can only be set when the unit is running. To cancel the
ECONO operation, press Econo/Quiet button several times until the ECONO symbol
disappears.
This function and POWERFUL operation cannot be used at the same time. The latest command
has the priority.
(R23917)
Target temperature
+0.5°C (+0.9°F)
temperature shift
Operation stops
at the set hour
0.5°C (0.9°F)
1 hour
TIMER operation
NIGHT SET Mode ON
Target temperature
–2°C (–3.6°F)
temperature shift
1 hour
2°C (3.6°F)
(R23918)
TIMER operation
NIGHT SET Mode ON
ECONO operation
(R22012)
Normal operation
Maximum during normal operation
Maximum during ECONO operation
Time
Power
consumption
and current
background
Main Functions SiUS042113EA
43 Part 4 Functions and Control
Note(s)
To start operation
Press the Econo/Quiet button and select the desired mode.
Each time the Econo/Quiet button is pressed, a different setting option is displayed on the
LCD.
To cancel operation
Press the Econo/Quiet button until no icon is displayed.
This operation is performed with lower power and therefore may not provide a sufficient cooling
(heating) effect.
Pressing the ON/OFF button causes the settings to be canceled, and the ECONO icon
disappears from the LCD.
If the power consumption level is already low, switching to ECONO operation will not reduce the
power consumption.
1.11 2-Area INTELLIGENT EYE Operation
Applicable
Models
FTXM09/12WVJU9, FTXM09/12VVJU
Outline The following functions can be performed by the microcomputer and a motion sensor.
1. Reduction of the capacity when there is nobody in the room in order to save electricity (energy
saving operation)
2. Dividing the room into plural areas and detecting presence of humans in each area. Moving the
airflow direction to the area with no human automatically to avoid direct airflow on humans.
Details 1. INTELLIGENT EYE detection method
R4003811
The motion sensor detects human motion by receiving infrared rays and sends the pulse wave
output.
The microcomputer in the indoor unit carries out a sampling every 20 msec. If the motion sensor
detects 10 times or more of the wave output in one second in total, and the High signal
continues for 2 sec., the microcomputer judges humans are in the room as the human detection
signal is ON.
2-area INTELLIGENT EYE motion sensor divides the area into 2 and detects presence of
humans in each area.
ECONO QUIET OUTDOOR
UNIT
blank
No Setting
Combination
1 sec.
Sampling (20 msec.)
High
Low
ON
OFF
High
Low
(Condition of 10 times or more output)
Human motion
2 sec.
If the detection signal (High) continues for 2 sec. or more,
the microcomputer judges humans are in the room.
Detection signal
from the motion
sensor
Human detection
signal
Motion sensor
output
If the motion sensor detects the outputs
10 times/sec. or more, the microcomputer
judges the detection signal from the
motion sensor is High.
background
SiUS042113EA Main Functions
Part 4 Functions and Control 44
Image of 2-area INTELLIGENT EYE
R4003428
2. Motions (in cooling)
R4003436
In FAN operation, the fan speed is reduced by 60 rpm when no one is in the area.
When there is no signal from the motion sensor in 20 minutes, the microcomputer judges that
nobody is in the room and operates the unit at a temperature shifted from the target
temperature. (Cooling/Dry: 1 ~ 2°C (1.8 ~ 3.6°F) higher, Heating: 2°C (3.6°F) lower, Auto:
according to the operation mode at that time)
Top view
Indoor unit
Wall
Area AArea B
A microcomputer judges someone by
the detection signal from each area A and B.
ON
OFF
Reset Reset Reset
20 min.
1 ~ 2°C (1.8 ~ 3.6 °F)
ON
OFF
ON
OFF
Operation
OFF
Fan speed (#)
Set speed Set speed
Target temperature
Remote controller
Sensor button
Detection signal

60 rpm
within
20 min.
within
20 min.
within
20 min.
background
Main Functions SiUS042113EA
45 Part 4 Functions and Control
Note(s)
Note(s)
3. Airflow direction in 2-area INTELLIGENT EYE operation
Detection method: The opposite area of detected area is set as the target direction.
1. Human detection signal ON in both areas A and B: Shift the airflow direction to area B (left side)
2. Human detection signal ON in area A: Shift the airflow direction to area B (left side)
3. Human detection signal ON in area B: Shift the airflow direction to area A (right side)
4. Human detection signal OFF in both areas A and B: No change
When the human detection signal is OFF for 20 minutes in both areas A and B, the unit starts
energy saving operation.
For dry operation, the temperature cannot be set with a remote controller, but the target
temperature is shifted internally.
Comfort/Focus
Airflow
Depending on the settings, you can select the airflow control whether blowing directly toward
(Focus) or away from (Comfort) the people.
R4003787
Notes on energy saving operation
If no presence detected in the room for 20 minutes, the energy saving operation will start, and
the INTELLIGENT EYE lamp goes off.
If human movement is detected again, the INTELLIGENT EYE lamp lights up and energy
saving operation terminates.
This operation changes the temperature by –3.6°F (–2.0°C) in HEAT / +3.6°F (+2.0°C) in COOL
/ +3.6°F (+2.0°C) in DRY operation from the set temperature.
When the room temperature exceeds 86°F (30.0°C), the operation changes the temperature by
+1.8°F (+1.0°C) in COOL / +1.8°F (+1.0°C) in DRY operation from the set temperature.
This operation decreases the airflow rate slightly in FAN operation only.
Top view
Wall
Indoor unit
Area A
Area B
Left
Right
Human
(R3853)
[Example]
A person is detected in
area 1.
A person is detected in
area 2.
People are detected in
both areas.
No people are detected in
the areas.
Area 1 Area 2 Area 1 Area 2 Area 1 Area 2
When INTELLIGENT EYE
operation is used, the unit will
not blow air directly at people
(only in their general direction).
The air conditioner will switch
to energy-saving mode after
20 minutes.
Area 1 Area 2
Area 1 Area 2
background
SiUS042113EA Main Functions
Part 4 Functions and Control 46
Notes on INTELLIGENT EYE operation
Application range is as follows.
If the air conditioner is in INTELLIGENT EYE operation and the mode “Do not blow directly on
people” is selected, the louvers adjust the airflow direction if there are people in the sensing
areas of the INTELLIGENT EYE so that the leftward or rightward airflow will not be directed to
the people. If no people are detected in either area 1 or 2 for 20 minutes, the air conditioner
switches to the energy-saving mode with the set temperature shifted by 3.6°F (2.0°C). The air
conditioner may switch to the energy-saving operation even if there are people in the areas.
This may occur depending on the clothes the people are wearing, if there is no movement of the
people in the areas.
The airflow direction from the louvers will be leftward if there are people in both areas 1 and 2.
The air will also flow left if there is a person right in front of the sensor as the sensor judges that
there are people in both areas.
Due to the position of the sensor, people might be exposed to the airflow of the indoor unit if
they are close to the front side of the indoor unit. If there are people close to the front side of the
indoor unit or in both areas, it is recommended to use the COMFORT AIRFLOW and
INTELLIGENT EYE operations simultaneously. Using both modes together, the air conditioner
will not direct the airflow towards the people.
The sensor could also mistakenly detect pets, sunlight, fluttering curtains and light reflected off
of mirrors as passers-by.
The sensor may not detect moving objects further than 23ft (7m) away. (Please see the
application range)
Sensor detection sensitivity changes according to the indoor unit location, the speed of
passers-by, temperature range, etc.
NIGHT SET mode will not switch on during use of INTELLIGENT EYE operation.
90°
55°
23ft (7m)
55°
Vertical angle 90°
(Side view)
Horizontal
angle 110°
(Top view)
23ft (7m)
background
Main Functions SiUS042113EA
47 Part 4 Functions and Control
1.12 INTELLIGENT EYE Operation
Applicable
Models
FTXM18/24WVJU9, FTXM18/24VVJU
Outline This function detects the presence of humans in the room with a motion sensor and reduces the
capacity when there is nobody in the room in order to save electricity.
Details 1. INTELLIGENT EYE detection method
R4003811
The motion sensor detects human motion by receiving infrared rays and sends the pulse wave
output.
The microcomputer in the indoor unit carries out a sampling every 20 msec. If the motion sensor
detects 10 times or more of the wave output in one second in total, and the High signal
continues for 2 sec., the microcomputer judges humans are in the room as the human detection
signal is ON.
2. Motions (in cooling)
R4003436
In FAN operation, the fan speed is reduced by 60 rpm when no one is in the area.
When there is no signal from the motion sensor in 20 minutes, the microcomputer judges that
nobody is in the room and operates the unit at a temperature shifted from the target
temperature. (Cooling/Dry: 1 ~ 2°C (1.8 ~ 3.6°F) higher, Heating: 2°C (3.6°F) lower, Auto:
according to the operation mode at that time)
1 sec.
Sampling (20 msec.)
High
Low
ON
OFF
High
Low
(Condition of 10 times or more output)
Human motion
2 sec.
If the detection signal (High) continues for 2 sec. or more,
the microcomputer judges humans are in the room.
Detection signal
from the motion
sensor
Human detection
signal
Motion sensor
output
If the motion sensor detects the outputs
10 times/sec. or more, the microcomputer
judges the detection signal from the
motion sensor is High.
ON
OFF
Reset Reset Reset
20 min.
1 ~ 2°C (1.8 ~ 3.6 °F)
ON
OFF
ON
OFF
Operation
OFF
Fan speed (#)
Set speed Set speed
Target temperature
Remote controller
Sensor button
Detection signal

60 rpm
within
20 min.
within
20 min.
within
20 min.
background
SiUS042113EA Main Functions
Part 4 Functions and Control 48
Note(s)
For dry operation, the temperature cannot be set with a remote controller, but the target
temperature is shifted internally.
Notes on Energy saving operation
If no presence detected in the room for 20 minutes, the energy saving operation will start, and
the INTELLIGENT EYE lamp goes off.
If human movement is detected again, the INTELLIGENT EYE lamp lights up and energy
saving operation terminates.
This operation changes the temperature by –3.6°F (–2.0°C) in HEAT / +3.6°F (+2.0°C) in COOL
/ +3.6°F (+2.0°C) in DRY operation from the set temperature.
When the room temperature exceeds 86°F (30.0°C), the operation changes the temperature by
+1.8°F (+1.0°C) in COOL / +1.8°F (+1.0°C) in DRY operation from the set temperature.
This operation decreases the airflow rate slightly in FAN operation only.
Notes on INTELLIGENT EYE operation
Application range is as follows.
The air conditioner may switch to the energy-saving operation even if there are people in the
areas.
This may occur depending on the clothes the people are wearing, if there is no movement of the
people in the areas.
The sensor could also mistakenly detect pets, sunlight, fluttering curtains and light reflected off
of mirrors as passers-by.
The sensor may not detect moving objects further than 23ft (7m) away. (Please see the
application range)
Sensor detection sensitivity changes according to the indoor unit location, the speed of
passers-by, temperature range, etc.
NIGHT SET mode will not switch on during use of INTELLIGENT EYE operation.
90°
55°
23ft (7m)
55°
Vertical angle 90°
(Side view)
Horizontal
angle 110°
(Top view)
23ft (7m)
background
Main Functions SiUS042113EA
49 Part 4 Functions and Control
Notes
1.13 POWERFUL Operation
Outline In order to exploit the cooling and heating capacity to full extent, the air conditioner can be operated
by increasing the indoor fan rotating speed and the compressor frequency.
Details When POWERFUL button is pressed, the fan speed and target temperature are converted to the
following states for 20 minutes.
A = 70 ~ 80 rpm
Ex: POWERFUL operation in cooling
POWERFUL operation cannot be used together with ECONO, COMFORT AIRFLOW or QUIET
OUTDOOR UNIT operation.
Operation mode Fan speed Target temperature
COOL H tap + A rpm 18°C (64.4°F)
DRY Dry rotating speed + A rpm Lowered by 2.5°C (4.5°F)
HEAT H tap + A rpm 31°C (87.8°F)
FAN H tap + A rpm —
AUTO Same as cooling/heating in
POWERFUL operation
The target temperature is kept
unchanged.
(R24589)
Target temp.
Fan
A rpm
H tap
Set tap
20 minutes
Lower limit of cooling
temperature
Remote controller registers
20 minutes independently.
POWERFUL
ON
POWERFUL
OFF
Ending conditions:
1. Lapse of 20 minutes
2. System operation OFF
3. POWERFUL operation OFF
18°C (64.4°F)
background
SiUS042113EA Main Functions
Part 4 Functions and Control 50
1.14 Clock Setting
ARC466 Series The clock can be set by taking the following steps:
1. Press Clock button.
 is displayed, then MON and blink.
2. Press Select or Select button to set the clock to the current day of the week.
3. Press Clock button.
 blinks.
4. Press Select or Select button to set the clock to the present time.
Holding down Select or Select button rapidly increases or decreases the time display.
5. Press Clock button to set the clock. Point the remote controller at the indoor unit when pressing
the button.
 blinks and clock setting is completed.
0:00
Select
button
Clock
button
(R19926)
background
Main Functions SiUS042113EA
51 Part 4 Functions and Control
1.15 WEEKLY TIMER Operation
Outline Up to 4 timer settings can be saved for each day of the week (up to 28 settings in total).
The 3 items: ON/OFF, temperature, and time can be set.
Details
Setting example of the WEEKLY TIMER
The same timer settings are used from Monday through Friday, while different timer settings are used for the weekend.
[Monday]
Make timer settings for programs 1-4.
6:00 8:30 17:30 22:00
77°F (25.0°C) 81°F (27.0°C)
program 1 program 2 program 3 program 4
ON OFF ON OFF
ON ON OFFOFF
[Tuesday]
to
[Friday]
Use the copy mode to make settings for Tuesday to Friday, because these settings are the same as
those for Monday.
6:00 8:30 17:30 22:00
77°F (25.0°C) 81°F (27.0°C)
program 1 program 2 program 3 program 4
ON OFF ON OFF
[Saturday] No timer settings
[Sunday]
Make timer settings for programs 1-4.
8:00 10:00 19:00 21:00
81°F (27.0°C)
81°F (27.0°C)
77°F (25.0°C)
ON OFF OFF ON
program 1 program 2 program 3 program 4
ON
ON
OFF
OFF
• Up to 4 reservations per day and 28 reservations per week can be set using the WEEKLY TIMER. The effective use of the
• The use of ON-ON-ON-ON settings, for example, makes it possible to schedule operating mode and set temperature
changes. Furthermore, by using OFF-OFF-OFF-OFF settings, only the turn off time of each day can be set. This will turn off
the air conditioner automatically if you forget to turn it off.
background
SiUS042113EA Main Functions
Part 4 Functions and Control 52
To use WEEKLY TIMER operation
Setting mode
• Make sure the day of the week and time are set.
If not, set the day of the week and time.
6:00 8:30 17:30 22:00
77°F (25.0°C)
81°F (27.0°C)
program 1 program 2 program 3 program 4
ON OFF ON OFF
[Monday]
Setting Displays
Day and number ON/OFF Time Temperature
1. Press .
• The day of the week and the reservation number of the current day will be displayed.
• 1 to 4 settings can be made per day.
2. Press to select the desired day of the week
and reservation number.
• Pressing changes the reservation number and the day of the week.
3. Press .
• The day of the week and reservation number will be set.
• “
” and “ ” blink.
4. Press to select the desired mode.
• Pressing changes the “ ” or “ ” setting in sequence.
ON TIMER OFF TIMER
blank
No Setting
Pressing puts the sequence in reverse.
• In case the reservation has already been set, selecting “ blank ” deletes the reservation.
• Proceed to STEP
9 if “ blank ” is selected.
• To return to the day of the week and reservation number setting, press
.
5. Press .
• The ON/OFF TIMER mode will be set.
• “
” and the time blink.
background
Main Functions SiUS042113EA
53 Part 4 Functions and Control
6.
Press to select the desired time.
• The time can be set between 0:00 and 23:50 in 10-minute intervals.
• To return to the ON/OFF TIMER mode setting, press
.
• Proceed to STEP
9 when setting the OFF TIMER.
7.
Press .
• The time will be set.
• “
” and the temperature blink.
8.
Press to select the desired temperature.
• The temperature can be set between 50°F (10.0°C) and 90°F (32.0°C).
COOL or AUTO: The unit operates at 64°F (18.0°C) even if it is set at 50°F (10.0°C) to
63°F (17.0°C).
HEAT or AUTO : The unit operates at 86°F (30.0°C) even if it is set at 87°F (31.0°C) to
90°F (32.0°C).
• To return to the time setting, press
.
• The set temperature is only displayed when the mode setting is on.
9.
Press .
• Check for a receiving tone and that the OPERATION lamp blinks twice.
• The TIMER lamp lights orange.
• Temperature and time are set in the case of ON TIMER operation, and the time is set in
the case of OFF TIMER operation.
• The next reservation screen will appear.
• To continue further settings, repeat the procedure from STEP
4.
Display
10.
Press to complete the setting.
• “ ” is displayed on the LCD and WEEKLY TIMER operation is activated.
• A reservation made once can be easily copied and the same settings used for another
day of the week. Refer to
Copy mode
.
NOTE
Notes on WEEKLY TIMER operation
•
• The day of the week, ON/OFF TIMER mode, time and set temperature (only for ON TIMER mode) can be set with the WEEKLY TIMER.
• WEEKLY TIMER and ON/OFF TIMER operation cannot be used at the same time. The ON/OFF TIMER operation has priority if it is set while
WEEKLY TIMER is still active. The WEEKLY TIMER will enter the standby state, and “
” will disappear from the LCD. When the ON/
OFF TIMER is up, the WEEKLY TIMER will automatically become active.
•
Turning off the circuit breaker, power failure, and other similar events will render operation of the indoor unit’s internal clock inaccurate. Reset the clock.
• can be used only for the time and temperature settings. It cannot be used to go back to the reservation number.
background
SiUS042113EA Main Functions
Part 4 Functions and Control 54
Copy mode
• A reservation made once can be copied to another day of the week. The whole reservation of
the selected day of the week will be copied.
6:00 8:30 17:30 22:00
77°F (25.0°C)
81°F (27.0°C)
6:00 8:30 17:30 22:00
77°F (25.0°C)
81°F (27.0°C)
COPY
program 1 program 2 program 3 program 4
ON OFF ON OFF
[Monday]
program 1 program 2 program 3 program 4
ON OFF ON OFF
[Tuesday]
to
[Friday]
Setting Displays
Copy Paste Normal
1.
Press .
2.
Press
3.
Press .
• The whole reservation of the selected day of the week will be copied.
4.
Press to select the destination day of the week.
5.
Press .
• Check for a receiving tone and that the OPERATION lamp blinks twice.
• The reservation will be copied to the selected day of the week. The whole reservation of
the selected day of the week will be copied.
• To continue copying the settings to other days of the week, repeat STEP
4 and STEP 5.
6.
Press to complete the setting.
• “ ” is displayed on the LCD and WEEKLY TIMER operation is activated.
NOTE
Note on COPY MODE
• The entire reservation of the source day of the week is copied in the copy mode.
In the case of making a reservation change for any day of the week individually after copying the content of weekly reservations, press
and
change the settings in the steps of
Setting mode
.
background
Main Functions SiUS042113EA
55 Part 4 Functions and Control
•
Setting Displays
Normal
1. Press .
• The day of the week and the reservation number of the current day will be displayed.
2. Press to select the day of the week and the
• Pressing displays the reservation details.
•
.
The mode is switched to setting mode. Proceed to
Setting mode
STEP 4.
3. Press
• “ ” is displayed on the LCD and WEEKLY TIMER operation is activated.
To deactivate WEEKLY TIMER operation
Press while “ ” is displayed on the
LCD.
• “ ” disappears from the LCD.
• The TIMER lamp goes off.
• To reactivate the WEEKLY TIMER operation, press
again.
• If a reservation deactivated with
is activated once again, the last reservation mode
will be used.
NOTE
• again to reactivate the
WEEKLY TIMER operation.
background
SiUS042113EA Main Functions
Part 4 Functions and Control 56
To delete reservations
An individual reservation
1. Press .
• The day of the week and the reservation number will be displayed.
2. Press to select the day of the week and the
reservation number to be deleted.
3. Press .
• “ ” and “ ” or “ ” blink.
4. Press until no icon is displayed.
• Pressing changes the ON/OFF TIMER mode in sequence.
• Selecting “blank” will cancel any reservation you may have.
ON TIMER OFF TIMER
blank
No Setting
Pressing puts the sequence in reverse.
5. Press .
• Check for a receiving tone and that the OPERATION lamp blinks twice.
• The selected reservation will be deleted.
6. Press .
• If there are still other reservations, WEEKLY TIMER operation will be activated.
Reservations for each day of the week
• This function can be used for deleting reservations for each day of the week.
•
1. Press .
• The day of the week and the reservation number will be displayed.
2.
Press to select the day of the week to be deleted.
3. Hold for about 5 seconds.
• Check for a receiving tone and that the OPERATION lamp blinks twice.
• The reservation of the selected day of the week will be deleted.
4. Press .
• If there are still other reservations, WEEKLY TIMER operation will be activated.
All reservations
Hold for about 5 seconds with the normal display.
•
Check for a receiving tone and that the OPERATION lamp blinks twice.
• “ ” disappears from the LCD.
• The TIMER lamp goes off.
• All reservations will be deleted.
• This operation is not functional while the WEEKLY TIMER setting screen is displayed.
background
Main Functions SiUS042113EA
57 Part 4 Functions and Control
Note(s)
1.16 Brightness Setting of Indoor Unit Display
Outline The brightness of the indoor unit display can be adjusted as desired. Also, the display can be
turned OFF.
Details 1. Press and hold Menu button for 2 seconds.
2. Press Select ▲ or Select ▼ button to select menu number 1.
LED appears and 1 blinks.
R4003795
3. Press Menu (push 2sec) button to confirm the select setting.
4. Press Select ▲ or Select ▼ button to change the setting as follows:
R4003796
5. Press Menu (push 2sec) button again. Brightness will be set to the chosen value.
6. Press Cancel to return to the default screen.
The display automatically returns to the default screen after 60 seconds. To return to the default
screen sooner, press Cancel button twice.
BRIGHTNESS High
(default)
BRIGHTNESS Low BRIGHTNESS Off
background
SiUS042113EA Main Functions
Part 4 Functions and Control 58
Note(s)
1.17 CLEAN Operation
Outline The CLEAN function dries the interior of the indoor unit to reduce the amount of condensation
present. When COOL or DRY operation is performed, condensation may occur inside the air
conditioner. It is recommended to dry the inside of the air conditioner using CLEAN operation.
Details To operate automatically
1. Press and hold Menu (push 2sec) button for 2 seconds.
2. Press Select ▲ or Select ▼ button to select menu number 2.
Mold proof icon appears and 2 blinks.
3. Press Menu (push 2sec) button to confirm the select setting.
4. Press Select ▲ or Select ▼ button to change the setting as follows:
R4003797
5. Press Menu (push 2sec) button again.
Automatic CLEAN operation will be enabled or disabled according to the chosen setting.
If automatic CLEAN operation is enabled, CLEAN icon appears on the LCD and the CLEAN
PROOF lamp lights green when CLEAN operation is in progress.
R4003798
6. Press Cancel to return to the default screen.
Note on CLEAN setting
The display automatically returns to the default screen after 60 seconds. To return to the default
screen sooner, press Cancel button twice.
Notes on CLEAN operation
When you want to stop CLEAN operation midway, press ON/OFF button twice.
After DRY or COOL operation stops, the air conditioner starts CLEAN operation automatically,
and then stops automatically 140 minutes later.
This operation dries the inside of the air conditioner using FAN operation and HEAT operation.
The indoor temperature and humidity may not suit your preferences.
The CLEAN function dries the interior of the indoor unit to reduce the amount of condensation
present.
CLEAN operation is not available when the unit is turned off using the OFF TIMER or turned off
using a smartphone.
The flaps may sometimes close to increase the drying effect inside the air conditioner.
CLEAN operation automatically dries the inside of the air conditioner each time after COOL and
DRY operation is stopped.
CLEAN operation may not be performed if the COOL or DRY operation time is short.
If CLEAN operation does not suit your preference, set operation to “OFF”.
Automatic operation is disabled
(default)
Automatic operation is enabled
Display
background
Main Functions SiUS042113EA
59 Part 4 Functions and Control
Relation between CLEAN operation and indoor unit lamps
Air conditioner LCD CLEAN lamp
Operating
(OPERATION lamp lights up)
CLEAN is “ON” Lights up
CLEAN is “OFF” Goes off
Not operating
(OPERATION lamp goes off)
CLEAN is “ON” Goes off
Lights up
(CLEAN is “Operating”)
CLEAN is “OFF” Goes off
background
SiUS042113EA Main Functions
Part 4 Functions and Control 60
1.18 Wireless LAN Connection
Operation
Wireless LAN connection adapter
The Wireless LAN connection adapter function requires the Daikin Comfort Control App for connecting to the air conditioner and
controlling it via your smartphone or tablet over your network.
Attention
•
Wireless LAN sends and receives data using radio waves so there is a risk of transmitted data being subject to eavesdropping and illegal access.
When using wireless LAN, manage the SSID/KEY of the wireless LAN connection adapter, the SSID/KEY of the wireless router, and the app login
information so that they will not be known to others, and ensure that you have an adequate understanding of the risks involved.
In the case that the product is accessed and operated illegally, turn off the wireless LAN connection adapter function.
• Do not use this product near a microwave oven. (This can affect wireless LAN communications.)
• This product cannot be directly connected to the communication line of a telecommunications carrier (internet service provider,
etc.). When connecting to the internet, be sure to connect via a device such as a router.
When the wireless LAN connection adapter function is turned on, the right side of the air conditioner may become slightly warm, but this is not
an abnormality.
[About the SSID and KEY]
• The [SSID] and [KEY] shown on the serial number sticker are necessary when connecting the air conditioner to a smartphone via wireless LAN.
WARNING
•
This product may cause electromagnetic interference.
•
This product may cause faulty behavior of the equipment.
• The user is responsible for providing the following items before using this product:
Smartphone or tablet PC
Internet line and communicating device (Modem/router or similar device)
Wireless LAN access point
Application name: [Daikin Comfort Control App] (free)
For details on the installation method for the Daikin Comfort Control App.
Wireless LAN connection adapter lamp (Orange)
• The Wireless LAN connection adapter lamp lights when connecting to a router (Wireless LAN
access point).
• For Wireless LAN connection adapter operation.
Display
WARNING
When operating an air conditioner from outside the home, it is not possible to check the air conditioner or the surroundings of the air
conditioner, or the state of the people in the room. Therefore, make sure to adequately check for safety before use.
In some cases, there is a risk of death, severe injury, or property damage.
Check the following in advance (while at home)
• Timer settings or reservations that other users may have made. (There is a risk of causing harm to the health of people, animals, or plants in
the home if operation starts and stops unexpectedly)
•
staining of household items)
Check the following before/while operating a unit from outside the home
• If you know that there is someone at home, inform the person when turning the air conditioner on or off from outside the home. (If someone at
home is standing on something such as a stool, the air conditioner turning on or off unexpectedly could surprise them and cause them to fall or
topple over. Additionally, a sudden change in the indoor/outdoor temperature could harm the health of people at home)
· The air conditioner can be turned off and temperature adjustment can be made using a remote controller in the home.
· Do not use the function if the only people at home are persons who are unable to make adjustments to temperature or other settings
themselves, such as young children, disabled persons, or elderly persons.
• Regularly check the settings and operating status of the air conditioner. (Sudden changes in indoor/outdoor temperature pose a health hazard.
There is a risk of harm to animals and plants)
If an error occurs during operation, immediately turn off the air conditioner and contact your dealer.
background
Main Functions SiUS042113EA
61 Part 4 Functions and Control
Wireless LAN connection
Web site:
https://daikincomfort.com/products/thermostats-controls/daikin-comfort-control-app
For inf
ormation on the latest version of Wireless LAN control, please see the web site above.
For instruction about how to operate the Daikin Comfort Control App application, please refer to the operation manual at the web site.
Contains FCC ID: VPYLB1YA
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation.
FCC CAUTION
This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.
Contains IC: 772C-LB1YA
This device complies with Industry Canada’s applicable licence-exempt RSSs.
Operation is subject to the following two conditions:
(1) This device may not cause interference; and
(2) This device must accept any interference, including interference that may cause undesired operation of the device.
This equipment complies with IC radiation exposure limits set forth for an uncontrolled environment and meets RSS-102 of the IC radio frequency (RF)
Exposure rules. This equipment should be installed and operated keeping the radiator at least 7-7/8 inches (20cm) or more away from person’s body.
The FCC responsible party is Goodman Manufacturing Company, L.P., and may be contacted by calling (713)-861-2500, or at 19001 Kermier Rd.,
Waller, TX 77484.
(www.GoodmanMFG.com)
And this intentional radiator has an industry Canada ID: IC 772C-LB1YA.
The manufacturer of the intentional radiator (model no. Type1YA) is Murata Manufacturing co., Ltd (www.murata.com).
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment and meets the FCC radio frequency (RF) Exposure
Guidelines. This equipment should be installed and operated keeping the radiator at least 7-7/8 inches (20cm) or more away from person’s body.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Application software installation
• Before downloading the application software for installing, please read ‘‘ ”
.
For Android Phones
1) Open [Google Play].
2) Search using the application name:
[Daikin Comfort Control App].
3) Follow the directions on the screen to install.
For iOS Phones
1) Open the [App Store].
2) Search using the application name:
[Daikin Comfort Control App].
3) Follow the directions on the screen to install.
Attention
• Stop the operation before setting the wireless connection.
To set
There are 2 options to connect the wireless LAN connection adapter with your smart device.
Connect the wireless LAN connection adapter to your home network.
The wireless LAN connection adapter will communicate with your smart device in your home network using a modem, router
or a similar device.
Connect the wireless LAN connection adapter to your smart device directly.
background
SiUS042113EA Main Functions
Part 4 Functions and Control 62
1.
While operation is stopped, press and hold
the button for 5 seconds.
2.
Press
•“ ” appears on the LCD.
•“
” blinks.
Check the indoor unit LED.
Wireless LAN connection adapter lamp Status
Blinking for 1 second Communication is OK
Blinking for 3 seconds
Please initialize the wireless LAN
connection adapter
Does not blink or light
Communication is abnormal
There is a possibility of equipment failure
Please request repair
3.
Press to return to the default screen.
To connect the wireless LAN connection adapter to your home network
The wireless LAN connection adapter can be connected to your home network using:
• the WPS button on the router (if present)
• the SSID and KEY number on the unit.
To connect using the WPS button
1.
While operation is stopped, press and hold
the button for 5 seconds.
2.
Press or and select menu number .
•“ ” appears on the LCD.
•“
” blinks.
3.
Press
• The wireless LAN connection adapter lamp blinks more quickly.
4.
Press the WPS button on your communication device
(router, for example) within approximately 1 minute.
Refer to the manual of your communication device.
• The wireless LAN connection adapter lamp lights.
5.
Press to return to the default screen.
background
Main Functions SiUS042113EA
63 Part 4 Functions and Control
NOTE
Notes on wireless LAN operation
• If the wireless LAN connection adapter lamp lights, repeat steps 1 through 5.
If connection is still impossible, use the procedures in “
To reset the connection setting to the factory default
” to perform setting.
• If the LED displa
y is distracting, change the brightness setting.
To connect the wireless LAN connection adapter to your
smart device directly
To connect without using the WPS function
1. While operation is stopped, press and hold
the button for 5 seconds.
2. Press or and select menu number .
•“ ” appears on the LCD.
•“
” blinks.
3. Press to connect to the access point.
• The wireless LAN connection adapter lamp blinks for 1 second.
4. Connect with your smart device to the access
point in the same way as to a standard wireless
network.
• Select the SSID (DaikinAP*****) printed on the unit or in the accessory set, and enter the
password.
• The wireless LAN connection adapter lamp lights.
5. Press to return to the default screen.
6. Open the Daikin Comfort Control App and tap
connect to the home network following the
instructions on the screen.
7. Connect your smartphone to the home network.
background
SiUS042113EA Main Functions
Part 4 Functions and Control 64
To turn off the wireless connection
To use the remote controller
1.
While operation is stopped, press and hold
the button for 5 seconds.
2.
Press or and select menu .
•“ ” appears on the LCD.
•“
” blinks, and communication is OFF.
3.
Press and hold the button for 2 seconds
• The wireless LAN connection adapter lamp turn off.
4.
Press to return to the default screen.
To reset the connection setting to the factory default
• If you want to reset the connection settings, it is possible to initialize the wireless LAN connection
adapter to its factory default state. If initialized, data including the network settings and power
consumption history will be erased.
• When discarding or transferring to another user, initialize the connection adapter to erase the
internal data.
To reset
1.
While operation is stopped, press and hold
the button for 5 seconds.
2.
Press or and select menu .
•“ ” appears on the LCD.
•“
” blinks.
3.
Press and hold the button for 2 seconds
• The wireless LAN connection adapter lamp blinks for 1 second.
4.
Press to return to the default screen.
background
Main Functions SiUS042113EA
65 Part 4 Functions and Control
Note(s)
Note(s)
Note
1.19 Other Functions
1.19.1 Hot-Start Function
In order to prevent the cold air blast that normally occurs when heating operation is started, the
temperature of the indoor heat exchanger is detected, and the airflow is either stopped or
significantly weakened resulting in comfortable heating.
The cold air blast is prevented using similar control when defrost control starts or when the
thermostat is turned ON.
1.19.2 Signal Receiving Sign
When the indoor unit receives a signal from the remote controller, the unit emits a signal receiving
sound.
1.19.3 Indoor Unit ON/OFF Switch
ON/OFF switch is provided on the display of the unit.
Press ON/OFF switch once to start operation. Press once again to stop it.
ON/OFF switch is useful when the remote controller is missing or the battery has run out.
The operation mode refers to the following table.
Forced cooling operation
Forced cooling operation can be started by pressing ON/OFF switch for 5 ~ 9 seconds while the
unit is not operating.
Refer to page 156 for details.
Forced cooling operation is not started if ON/OFF switch is pressed for 10 seconds or more.
1.19.4 Auto-restart Function
If a power failure (even a momentary one) occurs during the operation, the system restarts
automatically in the same conditions as before when the power supply is restored to the conditions
prior to the power failure.
It takes 3 minutes to restart the operation because 3-minute standby function is activated.
Operation mode Temperature setting Airflow rate
AUTO 25°C (77°F) Automatic
R4003799
ON/OFF switch
background
SiUS042113EA Thermistor Functions
Part 4 Functions and Control 66
2. Thermistor Functions
(1) Discharge
Pipe Thermistor
The discharge pipe thermistor is used for controlling discharge pipe temperature. If the
discharge pipe temperature (used in place of the inner temperature of the compressor) rises
abnormally, the operating frequency becomes lower or the operation halts.
The discharge pipe thermistor is used for detecting disconnection of the discharge pipe
thermistor.
(2) Outdoor Heat
Exchanger
Thermistor
The outdoor heat exchanger thermistor is used for controlling the target discharge pipe
temperature. The system sets the target discharge pipe temperature according to the outdoor
and indoor heat exchanger temperature, and controls the electronic expansion valve opening so
that the target discharge pipe temperature can be obtained.
In cooling operation, the outdoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature drops
below the outdoor heat exchanger temperature by more than a certain value, the discharge pipe
thermistor is judged as disconnected.
In cooling operation, the outdoor heat exchanger thermistor is used for high pressure protection.
(3) Outdoor
Temperature
Thermistor
The outdoor temperature thermistor detects the outdoor air temperature and is used for
refrigerant shortage detection, input current control, outdoor fan control, liquid compression
protection function, and so on.
(4) Indoor Heat
Exchanger
Thermistor
The indoor heat exchanger thermistor is used for controlling the target discharge pipe
temperature. The system sets the target discharge pipe temperature according to the outdoor
and indoor heat exchanger temperature, and controls the electronic expansion valve opening so
that the target discharge pipe temperature can be obtained.
In cooling operation, the indoor heat exchanger thermistor is used for freeze-up protection
control. If the indoor heat exchanger temperature drops abnormally, the operating frequency
becomes lower or the operation halts.
In heating operation, the indoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature drops
below the indoor heat exchanger temperature by more than a certain value, the discharge pipe
thermistor is judged as disconnected.
Four way valve
Compressor
(R25225)
Expansion valve
(2) Outdoor Heat
Exchanger
Thermistor
(3) Outdoor
Temperature
Thermistor
(5) Room
Temperature
Thermistor
(6) Liquid Pipe
Thermistor
(1) Discharge Pipe
Thermistor
(4) Indoor Heat
Exchanger
Thermistor
background
Thermistor Functions SiUS042113EA
67 Part 4 Functions and Control
(5) Room
Temperature
Thermistor
The room temperature thermistor detects the room air temperature and is used for controlling
the room air temperature.
(6) Liquid Pipe
Thermistor
The liquid pipe thermistor is used for control in hybrid cooling. The microcomputer sets the
target liquid pipe temperature and controls the electronic expansion valve opening so that the
temperature from the liquid pipe thermistor becomes the target temperature.
background
SiUS042113EA Control Specification
Part 4 Functions and Control 68
Note(s)
3. Control Specification
3.1 Mode Hierarchy
Outline The air conditioner control has normal operation mode, forced operation mode, and power
transistor test mode for installation and servicing.
Details
Unless specified otherwise, dry operation command is regarded as cooling operation.
3.2 Frequency Control
Outline The compressor frequency is determined according to the difference between the room thermistor
temperature and the target temperature.
Air conditioner control mode
Forced operation mode
Forced cooling operation (for pump down operation)
Power transistor test mode
Normal operation mode
Fan
Cooling (includes drying)
Heating
Heating
Defrosting
Stop (indoor unit: OFF)
Preheating control
Discharging from capacitor
Stop
(R22375)
Command frequency
Limit frequency
Skip control
Upper limit function
Compressor protection function
Lower limit function
Four way valve operation compensation, etc.
Target frequency
(R18023)
When the shift of the frequency is less than zero (ΔF<0) by PI control,
the target frequency is used as the command frequency.
Dropping function
Input current control, etc.
Upper limit frequency
FMAX
Lower limit frequency
FMIN
Initial frequency
PI control
Defrost control
background
Control Specification SiUS042113EA
69 Part 4 Functions and Control
Details 1. Determine command frequency
Command frequency is determined in the following order of priority.
(1) Limiting defrost control time
(2) Forced cooling
(3) Indoor frequency command
2. Determine upper limit frequency
The minimum value is set as an upper limit frequency among the frequency upper limits of the
following functions:
Compressor protection, input current, discharge pipe temperature, heating peak-cut, freeze-up
protection, defrost control.
3. Determine lower limit frequency
The maximum value is set as an lower limit frequency among the frequency lower limits of the
following functions:
Four way valve operation compensation, draft prevention, pressure difference upkeep.
4. Determine prohibited frequency
There is a certain prohibited frequency such as a power supply frequency.
Initial Frequency When starting the compressor, the frequency is initialized according to the D value of the indoor
unit.
D signal: Indoor frequency command
The difference between the room thermistor temperature and the target temperature is taken as the
D value and is used for D signal of frequency command.
D signal for cooling
OFF = Thermostat OFF
D signal for heating
OFF = Thermostat OFF
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
–2.0°C (–3.6°F) OFF 0°C (0°F) 4 2.0°C (3.6°F) 8
–1.5°C (–2.7°F) 1 0.5°C (0.9°F) 5 2.5°C (4.5°F) 9
–1.0°C (–1.8°F) 2 1.0°C (1.8°F) 6 — —
–0.5°C (–0.9°F) 3 1.5°C (2.7°F) 7 — —
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
–2.0°C (–3.6°F) OFF 0°C (0°F) 4 2.0°C (3.6°F) 8
–1.5°C (–2.7°F) 1 0.5°C (0.9°F) 5 2.5°C (4.5°F) 9
–1.0°C (–1.8°F) 2 1.0°C (1.8°F) 6 3.0°C (5.4°F) 10
–0.5°C (–0.9°F) 3 1.5°C (2.7°F) 7 3.5°C (6.3°F) 11
background
SiUS042113EA Control Specification
Part 4 Functions and Control 70
PI Control 1. P control
The D value is calculated in each sampling time (20 seconds), and the frequency is adjusted
according to its difference from the frequency previously calculated.
2. I control
If the operating frequency does not change for more than a certain fixed time, the frequency is
adjusted according to the D value.
When D value is low, the frequency is lowered.
When D value is high, the frequency is increased.
3. Frequency control when other controls are functioning
When frequency is dropping:
Frequency control is carried out only when the frequency drops.
For limiting lower limit:
Frequency control is carried out only when the frequency rises.
4. Upper and lower limit of frequency by PI control
The frequency upper and lower limits are set according to the command of the indoor unit.
When the indoor or quiet outdoor unit operation command comes from the indoor unit, the upper
limit frequency is lower than the usual setting.
3.3 Standby Electricity Saving (Suspend Function)
Outline This function is to save standby electricity consumption while the air conditioner is not in operation
by partially separating the electrical circuit of indoor and outdoor units from the power source.
Details Standby electricity saving function can be activated/deactivated from the service mode of the
remote controller. Refer to page 164 for details.
When standby electricity saving is ON, the system enters suspend state if both indoor and
outdoor units are not in operation.
The system will not go into suspend state when some voltage is applied to the outdoor unit for
protection purpose even if the indoor unit is not in operation.
In suspend state, power supply to the outdoor unit is halted and there is no communication
between the indoor unit and the outdoor unit.
Also the service monitor LED (LED A) lights off.
To return from the suspend state, start fan or other operation to turn on the indoor unit.
background
Control Specification SiUS042113EA
71 Part 4 Functions and Control
3.4 Controls at Mode Changing/Start-up
3.4.1 Preheating Control
Applicable
Models
RXM18/24WVJU9, RXM18/24VVJU
Outline The inverter operation in open phase starts with the conditions of the preheating command from the
indoor unit, the outdoor temperature, the discharge pipe temperature, and the radiation fin
temperature.
Details ON Condition
Outdoor temperature < A°C
Discharge pipe temperature < (outdoor temperature + B)°C
OFF condition
Outdoor temperature > C°C
Discharge pipe temperature > (outdoor temperature + D)°C
3.4.2 Four Way Valve Switching
Outline The four way valve coil is energized/not energized depending on the operation mode.
(Heating: ON, Cooling/Dry/Defrost: OFF)
In order to eliminate the switching sound as the four way valve coil switches from ON to OFF when
the heating is stopped, the OFF delay switch of the four way valve is carried out.
Details OFF delay switch of four way valve
The four way valve coil is energized for 160* seconds after the operation is stopped.
*10 seconds in heating operation when the outdoor temperature is lower than -9 °C (15.8°F)
3.4.3 Four Way Valve Operation Compensation
Outline At the beginning of operation as the four way valve is switched, the pressure difference to activate
the four way valve is acquired when the output frequency is higher than a certain fixed frequency,
for a certain fixed time.
Details Starting Conditions
When the compressor starts and the four way valve switches from OFF to ON
When the four way valve switches from ON to OFF during operation
When the compressor starts after resetting
When the compressor starts after the fault of four way valve switching
The lower limit of frequency keeps A Hz for B seconds for any of the conditions above.
ABCD
(°C) (°F) (°C) (°F) (°C) (°F) (°C) (°F)
18 64 10 ~ 18 50 ~ 64 22 72 12 ~ 20 54 ~ 68
09/12 class 18/24 class
Cooling Heating Cooling Heating
A (Hz) 46 36 28 30
B (seconds) 60 60 70 70
background
SiUS042113EA Control Specification
Part 4 Functions and Control 72
3.4.4 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning off.
The function is not used when defrosting.
3.4.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows. (The
function is not used when defrosting.)
09/12 class 18/24 class
Cooling Heating Cooling Heating
A (Hz)36364848
B (Hz)52524848
C (Hz)68686262
D (Hz) 80 80 80 80
E (Hz) 110 110 — —
F (sec) 120 120 100 100
G (sec) 120 120 800 800
H (sec) 480 480 300 300
J (sec) 180 180 470 470
K (sec) 600 600 — —
(sec.)
Time
(R23251)
(Hz)
Frequency
C
D
E
B
FGHJK
A
background
Control Specification SiUS042113EA
73 Part 4 Functions and Control
3.5 Discharge Pipe Temperature Control
Outline The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep
the discharge pipe temperature from rising further.
Details
Zone Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Up zone The upper limit of frequency increases.
Reset zone The upper limit of frequency is canceled.
(°C) (°F)
A 118 244
B 108 226
C 103 217
D 97 207
E 85 185
(R25005)
Discharge pipe
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
E
A
B
C
D
background
SiUS042113EA Control Specification
Part 4 Functions and Control 74
3.6 Input Current Control
Outline The microcomputer calculates the input current while the compressor is running, and sets the
frequency upper limit based on the input current.
In case of heat pump models, this control is the upper limit control of the frequency and takes
priority over the lower limit control of four way valve operation compensation.
Details
Frequency control in each zone
Stop zone
After the input current remains in the stop zone for 2.5 seconds, the compressor is stopped.
Dropping zone
The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is lowered by 2 Hz every second until it reaches the keep zone.
Keep zone
The present maximum frequency goes on.
Reset zone
Limit of the frequency is canceled.
Limitation of current dropping and stop value according to the outdoor temperature
The current drops when outdoor temperature becomes higher than a certain level (depending on
the model).
09/12 class 18 class 24 class
Cooling Heating Cooling Heating Cooling Heating
A (A) 13.0 13.0 20.0 20.0 20.0 20.0
B (A) 11.5 12.0 16.25 18.25 18.0 19.25
C (A) 10.5 11.0 15.25 17.25 17.0 18.25
Compressor Stop
Input current
Dropping zone
Stop zone
Keep zone
Reset zone
(R23249)
A
(A)
B
C
background
Control Specification SiUS042113EA
75 Part 4 Functions and Control
3.7 Freeze-up Protection Control
Outline During cooling operation, the signal sent from the indoor unit determines the frequency upper limit
and prevents freezing of the indoor heat exchanger. The signals from the indoor unit are divided
into zones.
Details The operating frequency limitation is judged with the indoor heat exchanger temperature.
R4003644
3.8 Heating Peak-cut Control
During heating operation, the indoor heat exchanger temperature determines the frequency upper
limit to prevent abnormal high pressure.
The operating frequency limitation is judged with the indoor heat exchanger temperature.
Reset zone
Up zone
Keep zone
Dropping zone
Stop zone
13°C (55.4°F)
7°C (44.6°F)
3°C (37.4°F)
0°C (32.0°F)
5°C (41.0°F)
(Reference)
Indoor heat exchanger
temperature (R2T)
Zone
Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Up zone The upper limit of frequency increases.
Reset zone The upper limit of frequency is canceled.
09/12 class 18/24 class
(°C) (°F) (°C) (°F)
A 62 144 60 140
B 54 129 54 129
C 50 122 51 124
D 48 118 49 120
E 44 111 44 111
Indoor heat exchanger
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
(R23928)
D
C
B
A
E
background
SiUS042113EA Control Specification
Part 4 Functions and Control 76
3.9 High Pressure Protection Control
Outline In order to prevent abnormal high pressures in the system and hence avoiding activation of the high
pressure safety device the below control function will be activated.
Details
Indoor heat exchanger
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
Pressure
4.15 MPa
High Pressure
Protection
Control
Heating
Peak- cut
control
Condensing
temperature
HPS ≥ 4.15 MPa
Compressor on
Compressor stop ( E3 indication)
Stopped 4 times
in 60 seconds
Abnormal stop ( E3 indication)
Normal operation
background
Control Specification SiUS042113EA
77 Part 4 Functions and Control
3.10 Outdoor Fan Control
1. Fan ON control to cool down the electrical box
The outdoor fan is turned ON when the electrical box temperature is high while the compressor
is OFF.
2. Fan OFF control during defrosting
The outdoor fan is turned OFF while defrosting.
3. Fan OFF delay when stopped
The outdoor fan is turned OFF 60 ~ 70 seconds after the compressor stops.
4. Fan speed control for pressure difference upkeep
The rotation speed of the outdoor fan is controlled for keeping the pressure difference during
cooling operation with low outdoor temperature.
When the pressure difference is low, the rotation speed of the outdoor fan is reduced.
When the pressure difference is high, the rotation speed of the outdoor fan is controlled as
well as normal operation.
5. Fan speed control during forced operation
The outdoor fan is controlled as well as normal operation during forced operation.
6. Fan speed control during POWERFUL operation
The rotation speed of the outdoor fan is increased during POWERFUL operation.
7. Fan speed control during indoor/quiet outdoor unit operation
The rotation speed of the outdoor fan is reduced by the command of the indoor/quiet outdoor
unit operation.
8. Fan ON/OFF control when operation (cooling, heating, dry) starts/stops
The outdoor fan is turned ON when the operation starts. The outdoor fan is turned OFF when
the operation stops.
3.11 Liquid Compression Protection Function
Outline The compressor stops according to the outdoor temperature for protection.
Details Operation stops depending on the outdoor temperature.
The compressor turns off under the conditions that the system is in cooling operation and the
outdoor temperature is below 0°C (32°F).
background
SiUS042113EA Control Specification
Part 4 Functions and Control 78
3.12 Defrost Control
Outline Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat
exchanger temperature must be more than a certain value to finish defrosting.
Details Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than A minutes (depending on the duration of the previous defrost control) of accumulated
time have passed after the start of the operation, or ending the previous defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature. (B°C)
09/12 class 18/24 class
A (minutes) 15 ~ 25 48
B (°C) 6 ~ 11.5 4 ~ 12
(°F) 43 ~ 53 39 ~ 54
C (Hz) 48 48
D (Hz) 80 62
E (seconds) 35 60
F (seconds) 60 60
G (seconds) 120 ~ 570 120 ~ 460
H (seconds) 75 60
J (pulse) 470 450
K (pulse) 400 ~ 444 490
L (pulse) 402 400
Frequency
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 Hz 0 Hz
C Hz
D Hz
5 ~ 8 sec.
PI control
5 ~ 8 sec.
H sec.
(R21278)
E sec.
F sec.
G sec.
K pulse zone
Electronic
expansion valve
opening
Normal
control
J pulse
zone
L pulse
zone
Starting
control
background
Control Specification SiUS042113EA
79 Part 4 Functions and Control
3.13 Electronic Expansion Valve Control
Outline The following items are included in the electronic expansion valve control.
Electronic expansion valve is fully closed
1. Electronic expansion valve is fully closed when turning on the power.
2. Pressure equalizing control
Open Control
1. Electronic expansion valve control when starting operation
2. Electronic expansion valve control when the frequency changes
3. Electronic expansion valve control for defrosting
4. Electronic expansion valve control when the discharge pipe temperature is abnormally high
5. Electronic expansion valve control when the discharge pipe thermistor is disconnected
Feedback Control
Target discharge pipe temperature control
Details The followings are the examples of electronic expansion valve control for each operation mode.
R4003560
: Available
: Not available
Control
Status
Starting operation control
Control when the frequency changes
Target discharge pipe temperature control
Discharge pipe thermistor disconnection control
High discharge pipe temperature control
Defrost control (heating only)
Pressure equalizing control
Opening limit control
Power on ; Compressor stop
Operation start
Frequency change under starting control
During target discharge pipe temperature control
Frequency change under target discharge pipe
temperature control
Discharge pipe thermistor disconnection
Frequency change under discharge pipe thermistor
disconnection control
During defrost control
background
SiUS042113EA Control Specification
Part 4 Functions and Control 80
3.13.1 Initialization as Power Supply On
The electronic expansion valve is initialized (fully closed) when the power is turned on. Then, the
valve opening position is set and the pressure is equalized.
3.13.2 Pressure Equalizing Control
When the compressor is stopped, the pressure equalizing control is activated. The electronic
expansion valve opens, and develops the pressure equalization.
3.13.3 Opening Limit Control
The maximum and minimum opening of the electronic expansion valve are limited.
The electronic expansion valve is fully closed when cooling operation stops, and is controlled at a
fixed opening during defrosting.
3.13.4 Starting Operation Control
The electronic expansion valve opening is controlled when the operation starts, thus preventing
superheating or liquid compression.
3.13.5 Control when the Frequency Changes
When the target discharge pipe temperature control is active, if the target frequency changes to a
specified value in a certain time period, the target discharge pipe temperature control is canceled
and the target opening of the electronic expansion valve is changed according to the frequency
shift.
3.13.6 High Discharge Pipe Temperature Control
When the compressor is operating, if the discharge pipe temperature exceeds a certain value, the
electronic expansion valve opens and the refrigerant runs to the low pressure side.
This procedure lowers the discharge pipe temperature.
09/12 class 18/24 class
Maximum opening (pulse) 470 490
Minimum opening (pulse) 30 40
background
Control Specification SiUS042113EA
81 Part 4 Functions and Control
3.13.7 Discharge Pipe Thermistor Disconnection Control
Outline The disconnection of the discharge pipe thermistor is detected by comparing the discharge pipe
temperature with the condensing temperature. If the discharge pipe thermistor is disconnected, the
electronic expansion valve opens according to the outdoor temperature and the operation
frequency, operates for a specified time, and then stops.
After 3 minutes, the operation restarts and checks if the discharge pipe thermistor is disconnected.
If the discharge pipe thermistor is disconnected, the system stops after operating for a specified
time.
If the disconnection is detected repeatedly, the system is shut down. When the compressor runs for
60 minutes without any error, the error counter is reset.
Details Determining thermistor disconnection
When the starting control (Cooling: A seconds, Heating: B seconds) finishes, the detection timer for
disconnection of the discharge pipe thermistor (C seconds) starts. When the timer is over, the
following adjustments are made.
1. When the operation mode is cooling
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
(Discharge pipe temperature + D) °C < (outdoor heat exchanger temperature)
2. When the operation mode is heating
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
(Discharge pipe temperature + D) °C < (indoor heat exchanger temperature)
When the thermistor is disconnected
When the disconnection is ascertained, the compressor continues operation for 9 minutes and then
stops.
If the compressor stops repeatedly, the system is shut down.
*1 1200 seconds: in heating operation when the outdoor temperature is lower than -10°C (14°F)
*2 1800 seconds: in heating operation when the outdoor temperature is lower than -15°C (5°F)
09/12 class 18/24 class
A (seconds) 1 30
B (seconds) 1 30
C (seconds) 720
*1
1020
*2
D (°C) 6 6
(°F) 42.8 42.8
background
SiUS042113EA Control Specification
Part 4 Functions and Control 82
3.13.8 Target Discharge Pipe Temperature Control
The target discharge pipe temperature is obtained from the indoor and outdoor heat exchanger
temperature, and the electronic expansion valve opening is adjusted so that the actual discharge
pipe temperature becomes close to the target discharge pipe temperature. (Indirect SH
(superheating) control using the discharge pipe temperature)
The electronic expansion valve opening and the target discharge pipe temperature are adjusted
every 20 seconds. The opening degree of the electronic expansion valve is adjusted by the
following.
Target discharge pipe temperature
Actual discharge pipe temperature
Previous discharge pipe temperature
3.14 Malfunctions
3.14.1 Sensor Malfunction Detection
Sensor malfunction can be detected in the following thermistor:
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Outdoor temperature thermistor
3.14.2 Detection of Overcurrent and Overload
Outline In order to protect the inverter, an excessive output current is detected and the OL temperature is
observed to protect the compressor.
Details If the inverter current exceeds A A, the system shuts down the compressor.
If the OL (Compressor head) temperature exceeds B°C (°F), the compressor stops.
SC
(Subcooling)
SH
(Superheating)
The target discharge pipe
temperature is set as to become
the target SH.
The inclination does not change
depending on the operating condition.
(R23014)
09/12 class 18 class 24 class
Cooling Heating Cooling Heating Cooling Heating
A (A) 13.0 13.0 20 20 20 20
B (°C) 125 125 125 125 125 125
(°F) 257 257 257 257 257 257
background
SiUS042113EA
83 Part 5 Remote Controller
1. Applicable Remote Controller ...................................................................84
2. ARC466A70 ..............................................................................................85
3. ARC466A71 ..............................................................................................87
Part 5
Remote Controller
background
SiUS042113EA Applicable Remote Controller
Part 5 Remote Controller 84
Note
1. Applicable Remote Controller
Refer to the operation manual of applicable model for details. You can download operation
manuals from Daikin Business Portal:
Daikin Business Portal Document Search Item Category Installation/Operation Manual
(URL: https://global1d.daikin.com/business_portal/login/
)
Series Model Name Remote Controller Reference Page
FTXM-W
FTXM09WVJU9
ARC466A70 85
FTXM12WVJU9
FTXM18WVJU9
ARC466A71 87
FTXM24WVJU9
FTXM-V
FTXM09VVJU
ARC466A70 85
FTXM12VVJU
FTXM18VVJU
ARC466A71 87
FTXM24VVJU
background
ARC466A70 SiUS042113EA
85 Part 5 Remote Controller
Reference
2. ARC466A70
Refer to the following pages for details.
Signal transmitter
Display (LCD)
• Changes the temperature setting.
Auto Indoor unit quiet Low
Middle low
MiddleMiddle highHigh
ON/OFF button
• Press this button once to start
operation.
Press once again to stop it.
∗ STD : Indoor temperature at the time
when the Dry operation is
started.
TEMPERATURE
adjustment buttons
• Displays the current settings.
(In this illustration, each section is
shown with all its displays on for the
purpose of explanation.)
•
To use the remote controller, aim the
transmitter at the indoor unit. If there is
anything blocking the signals between
the unit and the remote controller,
such as a curtain, the unit may not
operate.
•
The maximum transmission distance
is about 23 ft (7 m).
FAN setting button
• When the airflow is set to “ ” ,
indoor unit quiet operation will
start and the noise from the unit
will become quieter.
• In indoor unit quiet operation,
operation sound becomes weak.
(The airflow rate also decreases.)
• In DRY operation, the airflow rate
setting is not available.
• Selects the airflow rate setting.
Receiver
POWERFUL
1
button and
Wireless LAN
2
button
(push 5 seconds)
• Starts POWERFUL operation.
• Wireless LAN connection.
< ARC466A70 >
: AUTO
: DRY
: COOL
: HEAT
: FAN
Not available
64 ~ 86˚F
(18.0 ~ 30.0˚C)
64 ~ 90˚F
(18.0 ~ 32.0˚C)
STD ~ (STD–5˚F)
(STD~(STD−3.0°C))
50 ~ 86˚F
(10.0 ~ 30.0˚C)
1 POWERFUL Operation P.49
2 Wireless LAN Connection P.60
background
SiUS042113EA ARC466A70
Part 5 Remote Controller 86
Reference
Refer to the following pages for details.
OFF TIMER button
(NIGHT SET mode)
ON TIMER button
CLOCK
8
button
SELECT button
• Press this button and adjust
the day and time with
SELECT button.
Press this button again to
complete TIMER setting.
TIMER CANCEL button
• Cancels the timer setting.
• It cannot be used for
WEEKLY TIMER operation.
• Changes the clock, ON/OFF
TIMER and WEEKLY
TIMER settings.
• Press this button and adjust
the day and time with
SELECT button.
Press this button again to
complete TIMER setting.
SENSOR button
(INTELLIGENT EYE
Operation
3
)
Do not blow
directly on people
• Every time you press Sensor
button, the setting changes in
the following order.
SWING
6
buttons and
MENU button
(push 2 seconds)
• Adjusts the airflow direction.
• When you press SWING
button, the flap moves up and
down, or (and) the louver
moves right and left. The flap
(louver) stops when you press
SWING button again.
• Adjusts the display brightness.
• MOLD PROOF operation.
• Flash streamer air cleaning
operation.
• QUIET OUTDOOR UNIT
operation is not available in
FAN and DRY operation.
• QUIET OUTDOOR UNIT
operation and POWERFUL
operation cannot be used at
the same time. Priority is
given to the function you
pressed last.
ECONO
5
/QUIET button
ECONO
Blank
No setting
Combination
• Every time you press
ECONO/QUIET button, the
setting changes in the
following order.
QUIET OUTDOOR
UNIT
• The INTELLIGENT EYE
lamp lights green.
Blow directly
on people
Blank
No Setting
WEEKLY buttons (WEEKLY
TIMER
7
Operation)
Open the Front Cover
COMFORT
4
button
• Starts COMFORT AIRFLOW
operation.
Mode button
• Selects the operation mode.
AUTO DRY COOL HEAT FAN
: Weekly button
: Program button
: Copy button
: Back button
: Next button
3 2-area INTELLIGENT EYE operation P.43 6 Auto-swing P.33
4 COMFORT AIRFLOW operation P.34 7 WEEKLY TIMER operation P.51
5 ECONO operation P.42 8 Clock setting P.50
background
ARC466A71 SiUS042113EA
87 Part 5 Remote Controller
Reference
3. ARC466A71
Refer to the following pages for details.
Signal transmitter
Display (LCD)
• Changes the temperature setting.
Auto Indoor unit quiet Low
Middle low
MiddleMiddle highHigh
ON/OFF button
• Press this button once to start
operation.
Press once again to stop it.
∗ STD : Indoor temperature at the time
when the Dry operation is
started.
TEMPERATURE
adjustment buttons
• Displays the current settings.
(In this illustration, each section is
shown with all its displays on for the
purpose of explanation.)
•
To use the remote controller, aim the
transmitter at the indoor unit. If there is
anything blocking the signals between
the unit and the remote controller,
such as a curtain, the unit may not
operate.
•
The maximum transmission distance
is about 23 ft (7 m).
FAN setting button
• When the airflow is set to “ ” ,
indoor unit quiet operation will
start and the noise from the unit
will become quieter.
• In indoor unit quiet operation,
operation sound becomes weak.
(The airflow rate also decreases.)
• In DRY operation, the airflow rate
setting is not available.
• Selects the airflow rate setting.
Receiver
POWERFUL
1
button and
Wireless LAN
2
button
(push 5 seconds)
• Starts POWERFUL operation.
• Wireless LAN connection.
< ARC466A71 >
: AUTO
: DRY
: COOL
: HEAT
: FAN
Not available
64 ~ 86˚F
(18.0 ~ 30.0˚C)
64 ~ 90˚F
(18.0 ~ 32.0˚C)
STD ~ (STD–5˚F)
(STD~(STD−3.0°C))
50 ~ 86˚F
(10.0 ~ 30.0˚C)
1 POWERFUL operation P.49
2 Wireless LAN connection P.60
background
SiUS042113EA ARC466A71
Part 5 Remote Controller 88
Reference
Refer to the following pages for details.
ON TIMER button
CLOCK
8
button
SELECT button
• Changes the clock, ON/OFF
TIMER and WEEKLY
TIMER settings.
• Press this button and adjust
the day and time with
SELECT button.
Press this button again to
complete TIMER setting.
SWING
6
buttons and
MENU button
(push 2 seconds)
• Adjusts the airflow direction.
• When you press SWING
button, the flap moves up and
down, or (and) the louver
moves right and left. The flap
(louver) stops when you press
SWING button again.
• Adjusts the display brightness.
• MOLD PROOF operation.
• Flash streamer air cleaning
operation.
• QUIET OUTDOOR UNIT
operation is not available in
FAN and DRY operation.
• QUIET OUTDOOR UNIT
operation and POWERFUL
operation cannot be used at
the same time. Priority is
given to the function you
pressed last.
ECONO
5
/QUIET button
ECONO
Blank
No setting
Combination
• Every time you press
ECONO/QUIET button, the
setting changes in the
following order.
QUIET OUTDOOR
UNIT
WEEKLY buttons (WEEKLY
TIMER
7
Operation)
Open the Front Cover
Mode button
• Selects the operation mode.
AUTO DRY COOL HEAT FAN
: Weekly button
: Program button
: Copy button
: Back button
: Next button
SENSOR button
(INTELLIGENT EYE
Operation
3
)
blank
Intelligent eye No Setting
SELECT button
• Changes the clock, ON/OFF
TIMER and WEEKLY
TIMER settings.
TIMER CANCEL button
• Cancels the timer setting.
• It cannot be used for
WEEKLY TIMER operation.
OFF TIMER button
(NIGHT SET mode)
• Press this button and adjust
the day and time with
SELECT button.
Press this button again to
complete TIMER setting.
COMFORT
4
button
• Starts COMFORT AIRFLOW
operation.
3 INTELLIGENT EYE operation P.47 6 Auto-swing P.33
4 COMFORT AIRFLOW operation P.34 7 WEEKLY TIMER operation P.51
5 ECONO operation P.42 8 Clock setting P.50
background
SiUS042113EA
89 Part 6 Service Diagnosis
1. General Problem Symptoms and Check Items .........................................91
2. Troubleshooting with LED .........................................................................92
2.1 Indoor Unit.................................................................................................. 92
2.2 Outdoor Unit ............................................................................................... 92
3. Service Diagnosis .....................................................................................93
3.1 Method 1 .................................................................................................... 93
3.2 Method 2 .................................................................................................... 94
4. Troubleshooting ........................................................................................96
4.1 Error Codes and Description ...................................................................... 96
4.2 Indoor Unit PCB Abnormality ..................................................................... 97
4.3 Freeze-up Protection Control/Heating Peak-cut Control ............................ 98
4.4 Indoor Fan Motor (DC Motor) or Related Abnormality ............................. 100
4.5 Indoor Heat Exchanger Thermistor or Related Abnormality..................... 102
4.6 Room Temperature Sensor Abnormality/Humidity Sensor
Abnormality .............................................................................................. 103
4.7 Refrigerant Shortage ................................................................................ 104
4.8 Low-voltage Detection or Over-voltage Detection.................................... 106
4.9 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)........ 108
4.10 Unspecified Voltage (Between Indoor Unit and Outdoor Unit) ................. 110
4.11 Outdoor Unit PCB Abnormality................................................................. 111
4.12 Actuation of High Pressure Switch ........................................................... 112
4.13 OL Activation (Compressor Overload) ..................................................... 113
4.14 Compressor Lock ..................................................................................... 116
4.15 DC Fan Lock ............................................................................................ 117
4.16 Input Overcurrent Detection ..................................................................... 118
4.17 Four Way Valve Abnormality.................................................................... 120
4.18 Discharge Pipe Temperature Control....................................................... 122
4.19 High Pressure Control in Cooling ............................................................. 124
4.20 System Shutdown due to Temperature Abnormality in
the Compressor........................................................................................ 126
4.21 Compressor System Sensor Abnormality ................................................ 127
4.22 Position Sensor Abnormality .................................................................... 128
4.23 DC Voltage/Current Sensor Abnormality.................................................. 131
4.24 Thermistor or Related Abnormality (Outdoor Unit)................................... 133
4.25 Electrical Box Temperature Rise.............................................................. 135
4.26 Radiation Fin Temperature Rise .............................................................. 136
4.27 Output Overcurrent Detection .................................................................. 138
5. Check ......................................................................................................141
5.1 Thermistor Resistance Check .................................................................. 141
Part 6
Service Diagnosis
background
SiUS042113EA
Part 6 Service Diagnosis 90
5.2 Indoor Fan Motor Connector Check ......................................................... 142
5.3 Power Supply Waveform Check............................................................... 142
5.4 Electronic Expansion Valve Check........................................................... 143
5.5 Four Way Valve Performance Check ....................................................... 144
5.6 Inverter Unit Refrigerant System Check................................................... 145
5.7 Inverter Analyzer Check ........................................................................... 145
5.8 Outdoor Fan Motor Check........................................................................ 147
5.9 Installation Condition Check..................................................................... 148
5.10 Discharge Pressure Check....................................................................... 149
5.11 Outdoor Fan System Check ..................................................................... 149
5.12 Main Circuit Short Check.......................................................................... 149
5.13 Capacitor Voltage Check.......................................................................... 151
5.14 Power Module Check ............................................................................... 152
background
General Problem Symptoms and Check Items SiUS042113EA
91 Part 6 Service Diagnosis
1. General Problem Symptoms and Check Items
Symptom Check Item Measures
Reference
Page
The unit does not
operate.
Check the power supply. Check if the rated voltage is supplied. —
Check the type of the indoor unit. Check if the indoor unit type is compatible with the
outdoor unit.
—
Check the outdoor temperature. Heating/cooling operations are not available when
the outdoor temperature is out of the operation
limit. Check the reference page for the operation
limit.
176
Diagnose with remote controller
indication.
—96
Check the remote controller
addresses.
Check if address settings for the remote controller
and indoor unit are correct.
159
Operation sometimes
stops.
Check the power supply. A power failure of 2 to 10 cycles stops air
conditioner operation. (Operation lamp OFF)
—
Check the outdoor temperature. Heating/cooling operations are not available when
the outdoor temperature is out of the operation
limit. Check the reference page for the operation
limit.
176
Diagnose with remote controller
indication.
—96
The unit operates but
does not cool, or does
not heat.
Check for wiring and piping errors in
the connection between the indoor
unit and outdoor unit.
——
Check for thermistor detection errors. Check if the thermistor is mounted securely. —
Check for faulty operation of the
electronic expansion valve.
Set the unit to cooling operation, and check the
temperature of the liquid pipe to see if the
electronic expansion valve works.
—
Diagnose with remote controller
indication.
—96
Diagnose by service port pressure
and operating current.
Check for refrigerant shortage.
—
Large operating noise
and vibrations
Check the resistance between the
terminals of the power module.
—152
Check the power module. — —
Check the installation condition. Check if the required spaces for installation
(specified in the installation manual) are provided.
—
background
SiUS042113EA Troubleshooting with LED
Part 6 Service Diagnosis 92
2. Troubleshooting with LED
2.1 Indoor Unit
Operation Lamp The operation lamp blinks when any of the following errors is detected.
1. A protection device of the indoor or outdoor unit is activated, or when the thermistor
malfunctions.
2. A signal transmission error occurs between the indoor and outdoor units.
In either case, conduct the diagnostic procedure described in the following pages.
R4003807
2.2 Outdoor Unit
The outdoor unit has one green LED (LED A) on the PCB. When the microcomputer works in order,
the LED A blinks.
Refer to pages 26, 28 for the location of LED.
Operation
lamp
(green)
background
Service Diagnosis SiUS042113EA
93 Part 6 Service Diagnosis
Notes
3. Service Diagnosis
3.1 Method 1
1. When Timer Cancel button is held down for 5 seconds, 00 is displayed on the temperature
display screen.
2. Press Timer Cancel button repeatedly until a long beep sounds.
1. A short beep or two consecutive beeps indicate non-corresponding codes.
2. To return to the normal mode, hold Timer Cancel button down for 5 seconds. When the remote
controller is left untouched for 60 seconds, it also returns to the normal mode.
3. Not all the error codes are displayed. When you cannot find the error code, try method 2.
Refer to page 94.
The code indication changes in the sequence shown below.
ARC466A70, A71
(R24045)
< ARC466 Series >
Timer Cancel button
No. Code No. Code No. Code No. Code No. Code
1 00 10 E6 19 C9 28 A1 37 EA
2 A5 11 H6 20 CC 29 E1 38 AH
3 E7 12 H0 21 C4 30 UA 39 FA
4 F3 13 A6 22 C5 31 U3 40 E8
5 F6 14 U0 23 CH 32 UF 41 E3
6 L3 15 C7 24 J3 33 UH 42 H3
7 L4 16 A3 25 J6 34 P4 43 F8
8 L5 17 H8 26 J8 35 H7 44 A0
9 U4 18 H9 27 E5 36 U2 ——
background
SiUS042113EA Service Diagnosis
Part 6 Service Diagnosis 94
3.2 Method 2
1. Press the center of Temp button and Mode button at the same time.
5C is displayed on the LCD.
R6000375
2. Select 5C (service check) with Temp or Temp button.
3. Press Mode button to enter the service check mode.
The left-side number blinks.
R6000373
4. Press Temp or Temp button and change the number until you hear the two consecutive
beeps or the long beep.
5. Diagnose by the sound.
Beep: The left-side number does not correspond with the error code.
Two consecutive beeps: The left-side number corresponds with the error code but the
right-side number does not.
(R24046)
(R24047)
(R24048)
background
Service Diagnosis SiUS042113EA
95 Part 6 Service Diagnosis
Long beep: Both the left-side and right-side numbers correspond with the error code.
The numbers indicated when you hear the long beep are the error code.
Refer to page 96.
6. Press Mode button.
The right-side number blinks.
7. Press Temp or Temp button and change the number until you hear the long beep.
8. Diagnose by the sound.
Beep: The left-side number does not correspond with the error code.
Two consecutive beeps: The left-side number corresponds with the error code but the
right-side number does not.
Long beep: Both the left-side and right-side numbers correspond with the error code.
9. Determine the error code.
The numbers indicated when you hear the long beep are the error code.
Refer to page 96.
10.Press Mode button for 5 seconds to exit from the service check mode.
When the remote controller is left untouched for 60 seconds, it returns to the normal mode also.
(R24047)
(R11673)
(R24048)
(R24047)
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 96
4. Troubleshooting
4.1 Error Codes and Description
: Displayed only when system-down occurs.
Error
Codes
Description
Reference
Page
System 00 Normal —
U0 Refrigerant shortage 104
U2 Low-voltage detection or over-voltage detection 106
U4 Signal transmission error (between indoor unit and outdoor
unit)
108
UA Unspecified voltage (between indoor unit and outdoor unit) 110
Indoor
Unit
A1 Indoor unit PCB abnormality 97
A5 Freeze-up protection control/heating peak-cut control 98
A6 Fan motor (DC motor) or related abnormality 100
C4 Indoor heat exchanger thermistor or related abnormality 102
C9 Room temperature thermistor or related abnormality 103
CC Humidity sensor abnormality 103
Outdoor
Unit
E1 Outdoor unit PCB abnormality 111
E3 Actuation of high pressure switch 112
E5 OL activation (compressor overload) 113
E6 Compressor lock 116
E7 DC fan lock 117
E8 Input overcurrent detection 118
EA Four way valve abnormality 120
F3 Discharge pipe temperature control 122
F6 High pressure control in cooling 124
F8 System shutdown due to compressor internal temperature
abnormality
126
H0 Compressor system sensor abnormality 127
H6 Position sensor abnormality 128
H8 DC voltage/current sensor abnormality 131
H9 Outdoor temperature thermistor or related abnormality 133
J3 Discharge pipe thermistor or related abnormality 133
J6 Outdoor heat exchanger thermistor or related abnormality 133
J8 Liquid pipe thermistor or related abnormality 133
L3 Electrical box temperature rise 135
L4 Radiation fin temperature rise 136
L5 Output overcurrent detection 138
P4 Radiation fin thermistor or related abnormality 133
background
Troubleshooting SiUS042113EA
97 Part 6 Service Diagnosis
Note
4.2 Indoor Unit PCB Abnormality
Error Code A1
Method of Error
Detection
The system checks if the circuit works properly within the microcomputer of the indoor unit.
Error Decision
Conditions
The system cannot set the internal settings.
Supposed
Causes
Defective indoor unit PCB
Disconnection of connector
Troubleshooting
R6000804
Check the connection of
connectors/wire harness. ★
Correct the connection.
OK?
Start operation.
Error repeats?
Start operation.
Error repeats?
Error repeats?
Combination of
the indoor and outdoor
unit matched?
YES
NO
NO
YES
NO
NO
YES
Caution
To secure the connection,
disconnect the connectors once
and then reconnect.
YES
NO
YES
Match the compatible
models.
Replace the indoor unit
PCB (control PCB).
Completed.
Completed.
Replace the indoor unit
PCB (control PCB).
Completed.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Wire Harness (Connector)
Terminal strip ~ Power supply PCB (S101)
Power supply PCB (S102, S103) ~ Control PCB (S300A, S301B)
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 98
4.3 Freeze-up Protection Control/Heating Peak-cut Control
Error Code A5
Method of Error
Detection
Freeze-up protection control
During cooling operation, the freeze-up protection control (operation halt) is activated according
to the temperature detected by the indoor heat exchanger thermistor.
Heating peak-cut control
During heating operation, the temperature detected by the indoor heat exchanger thermistor is
used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
Error Decision
Conditions
Freeze-up protection control
During cooling operation, the indoor heat exchanger temperature is below 0°C (32°F).
Heating peak-cut control
During heating operation, the indoor heat exchanger temperature is above 60 ~ 62°C (140 ~
144°F).
Supposed
Causes
Short-circuited air
Clogged air filter of the indoor unit
Dust accumulation on the indoor heat exchanger
Defective indoor heat exchanger thermistor
Defective indoor unit PCB
Troubleshooting
NO
NO
NO
Check No. 01
Check the indoor heat exchanger
thermistor.
YES
YES
(R21064)
YES
YES
NO
Caution
Provide sufficient air passage.
Clean the air filter.
Clean the indoor heat
exchanger.
Replace the indoor unit PCB
(control PCB).
Replace the indoor heat
exchanger thermistor.
As
described in the
thermistor characteristic
chart?
Check the air filter.
Check the dust accumulation on
the indoor heat exchanger.
Is there any short circuit?
Dirty?
Dirty?
Check the air passage.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting SiUS042113EA
99 Part 6 Service Diagnosis
Reference
Check No.01 Refer to P.141
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 100
4.4 Indoor Fan Motor (DC Motor) or Related Abnormality
Error Code A6
Method of Error
Detection
The rotation speed detected by the microcomputer software during indoor fan motor operation
determines abnormal fan motor operation.
Error Decision
Conditions
The detected rotation speed does not reach the demanded rotation speed of the target tap, and
is less than 50% of the maximum fan motor rotation speed.
The fan motor does not rotate for continuously more than 5 seconds after it starts.
Supposed
Causes
Remarkable decrease in power supply voltage
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB
background
Troubleshooting SiUS042113EA
101 Part 6 Service Diagnosis
Reference
Troubleshooting
R6000805
Rubber cushion
Check No.03 Refer to P.142
R6000768
Caution
OK?
NO
YES
YES
NO
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the connector for
connection.
Foreign matters in or
around the fan?
Rotate the fan by hand.
Correct the connection.
Remove the foreign matters.
Turn off the power supply.
(Unplug the power cable or turn
the breaker off.)
Check No. 03
NO
YES
YES
NO
Check the fan motor for
breakdown or short circuit.
Fan rotates smoothly?
Resistance OK?
Replace the indoor fan motor.
Replace the indoor unit PCB
(control PCB).
YES
NO
NO
Abnormal
sound occurs?
Is the rubber cushion
properly fitted?
YES
Correct the position of
rubber cushion or replace
the rubber cushion.
Replace the bearing rubber
cushion.
Note: The motor may break when the
motor connector is disconnected
with the power supply on.
(Turn off the power supply before
connecting the connector also.)
To secure the connection,
once disconnect the connector
and then reconnect it.
Rubber
cushion
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 102
Reference
4.5 Indoor Heat Exchanger Thermistor or Related Abnormality
Error Code C4
Method of Error
Detection
The temperatures detected by the thermistors determine thermistor errors.
Error Decision
Conditions
The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or less with
the power on.
Supposed
Causes
Disconnection of connector
Defective thermistor(s)
Defective indoor unit PCB
Troubleshooting
C4 : Indoor heat exchanger thermistor
Check No.01 Refer to P.141
YES
(R21870)
NO
Check No. 01
Check the thermistor resistance
value.
YES
NO
Caution
Correct the connection.
Replace the defective
thermistor(s).
Replace the indoor unit PCB
(control PCB).
Normal?
Normal?
Check the connection of
connectors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting SiUS042113EA
103 Part 6 Service Diagnosis
4.6 Room Temperature Sensor Abnormality/Humidity Sensor
Abnormality
Error Code C9, CC
Method of Error
Detection
Sensor abnormality is detected by input value.
Error Decision
Conditions
The communication error of humidity sensor or malfunction of humidity sensor.
Supposed
Causes
Disconnection of connector
Defective humidity sensor
Defective indoor unit PCB
Troubleshooting
R6000515
Correct the connection.
Replace the control PCB.
Completed.
Normal?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the connection of
connectors.
NO
YES
* Connect the connector again for
ensuring the connection.
Replace the humidity sensor
PCB.
Error code displayed?
YES
NO
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 104
4.7 Refrigerant Shortage
Error Code U0
Method of Error
Detection
Refrigerant shortage detection I:
Refrigerant shortage is detected by checking the input current value and the compressor running
frequency. If there is insufficient refrigerant, the input current tends to be lower than the normal
value.
Refrigerant shortage detection II:
Refrigerant shortage is detected by checking the discharge pipe temperature and the opening of
the electronic expansion valve. If there is insufficient refrigerant, the discharge pipe temperature
tends to rise.
Refrigerant shortage detection III:
Refrigerant shortage is detected by checking the difference between suction and discharge
temperature.
Error Decision
Conditions
Refrigerant shortage detection I:
The following conditions continue for 7 minutes.
Input current × input voltage A × output frequency + B
Output frequency > C
Refrigerant shortage detection II:
The following conditions continue for 80 seconds.
Opening of the electronic expansion valve D
Discharge pipe temperature > E × target discharge pipe temperature + F(°C)
(Discharge pipe temperature > E × target discharge pipe temperature + G(°F))
Refrigerant shortage detection III:
Refrigerant shortage is detected when the difference of the temperature is smaller than H(°C (°F))
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
A (–) B (W) C (Hz)
09/12 class 2800/256 –350 55
18/24 class 4000/256 –200 38
D (pulse) E (–) F (°C) G (°F)
09/12 class 470 128/128 cooling: 20, heating: 20 cooling: 68, heating: 68
18/24 class 490 128/128 cooling: 30, heating: 50 cooling: 86, heating: 122
H
09/12 class 18/24 class
Cooling Room thermistor temperature -
indoor heat exchanger thermistor
(°C) 4.0 3.5
(°F) 7 6
Outdoor heat exchanger
temperature - outdoor temperature
(°C) 4.0 3.5
(°F) 7 6
Heating Indoor heat exchanger temperature
– room thermistor temperature
(°C) 4.0 3.5
(°F) 7 6
Outdoor temperature – outdoor
heat exchanger temperature
(°C) 4.0 3.5
(°F) 7 6
background
Troubleshooting SiUS042113EA
105 Part 6 Service Diagnosis
Reference
Troubleshooting
Check No.01 Refer to P.141
(R24716)
Caution
YES
NG
NO
NO
YES
YES
YES
NO
YES
NO
NO
YES
NO
∗ Discharge pipe thermistor
∗ Indoor or outdoor heat exchanger thermistor
∗ Room temperature thermistor
∗ Outdoor temperature thermistor
Check for refrigerant shortage.
Change for a specified amount of
fresh refrigerant.
Reconnect the thermistor(s).
Open the stop valve.
Repair the pipe flare or
replace the union.
Check if any harnesses are
in contact with the piping
and correct as required.
Also, replace any cracked
pipes.
Check the connection of the
power transistor harness.
Also, replace any cracked
pipes.
Replace the defective
thermistor(s).
Completed.
Refrigerant shortage error
again?
Oil leak at internal
piping?
Stop valve closed?
Compressor vibrating
too much?
Oil leak at relay pipe
connections?
Any thermistor
disconnected?
Check No. 01
Check the thermistors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
OK
NO
YES
Replace the outdoor unit PCB
(main PCB).
Replace the compressor.
Completed.
Error again?
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 106
4.8 Low-voltage Detection or Over-voltage Detection
Error Code U2
Method of Error
Detection
Indoor Unit
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Outdoor Unit
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Error Decision
Conditions
Indoor Unit
The voltage detected by the DC voltage detection circuit is below 140 V.
Outdoor Unit
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 162 V (09/12 class), 160 V
(18/24 class).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Over-voltage detection:
The voltage detected by the DC voltage detection circuit is below 458 V (depending on the
model).
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Power supply voltage out of specification
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Short circuit inside the fan motor winding
Noise
Momentary drop of voltage
Momentary power failure
Defective outdoor unit PCB
Defective indoor unit PCB
background
Troubleshooting SiUS042113EA
107 Part 6 Service Diagnosis
Troubleshooting
Correct the power supply.
Replace the outdoor
unit PCB (main PCB).
Check for such factors for a
long term.
(R22370)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NO
YES
YES
NO
YES
YES
Reconnect the harness.
Check the power supply voltage.
Check the connection of the
compressor harness.
Disturbance factors
Noise
Power supply distortion
(Precaution before turning on the power again)
Make sure the power has been off for at
least 30 seconds.
Replace the indoor
unit PCB (control PCB).
Turn on
the power. System
restarted? (Repeat
a few times.)
Error again
within 3 minutes after
turning on the power?
Loose or
disconnected?
NO
YES
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Does the
outdoor fan rotate smoothly?
Is the
voltage fluctuation
within ±10% from the rated
value?
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 108
4.9 Signal Transmission Error (Between Indoor Unit and
Outdoor Unit)
Error Code U4
Method of Error
Detection
The signal transmission data received from the outdoor unit is checked whether it is normal.
Error Decision
Conditions
The data sent from the outdoor unit cannot be received normally, or the content of the data is
abnormal.
Supposed
Causes
Power supply voltage out of specification
Reduction of power supply voltage
Wiring error
Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
Defective outdoor unit PCB
Short circuit inside the fan motor winding
Defective indoor unit PCB
Disturbed power supply waveform
background
Troubleshooting SiUS042113EA
109 Part 6 Service Diagnosis
Reference
Troubleshooting
Check No.11 Refer to P.142
Check No.11
Check the power supply
waveform.
Check the voltage of the
connection wires on the indoor
terminal board between No. 1
and No. 3, and between No. 2
and No. 3.
YES
Blink
Replace the indoor unit PCB
(control PCB).
Locate the cause of the
disturbance of the power
supply waveform, and correct
it.
NO
(R21193)
Continuously ON or OFF
NO
YES
YES
NO
Caution
Correct the indoor unit -
outdoor unit connection wires.
Replace the outdoor unit PCB
(main PCB).
Replace the connection wires
between the indoor unit and
outdoor unit.
Is LED A blinking?
Properly insulated?
Is there any disturbance?
Is there any wiring error?
Check the indoor unit - outdoor
unit connection wires.
Check the LED A on the outdoor
unit PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Check the power supply voltage.
Correct the power supply.
YES
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Rotate the
outdoor fan by hand.
Does the outdoor fan rotate
smoothly?
Is the
voltage fluctuation
within ±10% from the
rated value?
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 110
4.10 Unspecified Voltage (Between Indoor Unit and Outdoor
Unit)
Error Code UA
Method of Error
Detection
The supply power is detected for its requirements (pair type is different from multi type) by the
indoor/outdoor transmission signal.
Error Decision
Conditions
The pair type and multi type are interconnected.
Supposed
Causes
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Troubleshooting
(R20435)
Caution
NO
YES
YES
NO
Match the compatible models.
OK?
Correct the connection.
Check the code numbers
(2P012345, for example) of the
indoor and outdoor unit PCB
with the Parts List.
If not matched, change for the
correct PCB.
Are the
connecting wires connected
properly?
Check the combination of the
indoor and outdoor unit.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting SiUS042113EA
111 Part 6 Service Diagnosis
4.11 Outdoor Unit PCB Abnormality
Error Code E1
Method of Error
Detection
The system checks if the microprocessor is working in order.
The system checks if the zero-cross signal comes in properly.
Error Decision
Conditions
The microprocessor program runs out of control.
The zero-cross signal is not detected.
Supposed
Causes
Defective outdoor unit PCB
Noise
Momentary drop of voltage
Momentary power failure
Troubleshooting
(R21809)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
NO
NO
YES
Replace the outdoor unit PCB
(main PCB).
Ground the system.
The cause can be external
factors other than malfunction.
Investigate the cause of noise.
Turn on the power.
Error again?
Check if the outdoor unit is
grounded.
Grounded?
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 112
4.12 Actuation of High Pressure Switch
Error Code E3
Method of Error
Detection
Abnormality is detected when the contact of the high pressure switch opens.
Error Decision
Conditions
High pressure switch (S1PH) activating pressure: 4.15 MPa
High pressure switch (S1PH) recovery pressure: 3.2 MPa
Supposed
Causes
Actuation of high pressure switch (S1PH)
Closed stop valve
Disconnection of connector S40
Disconnection of 2 terminals of high pressure switch (S1PH)
Defective outdoor unit PCB
Broken S1PH harness
Defective high pressure switch (S1PH)
Troubleshooting
NO
YES
Nearly 0 Ω
Resistance ∞
Check
the resistance
between the pins 1 - 2 on
the connector
S40.
Stop valve open?
Open the stop valve.
Nearly 0 Ω
Resistance ∞
Replace the harness for the high
pressure switch.
Replace the high pressure switch
(S1PH).
Disconnect the connector
S40 from the PCB.
Replace the outdoor unit PCB
(main PCB).
Disconnect the 2 terminals of
the high pressure switch
(S1PH).
NO
YES
High
pressure switch
connector S40 properly
connected?
Reconnect the connector.
Check
the resistance
between the 2
terminals of the high
pressure switch
(S1PH).
(R22435)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting SiUS042113EA
113 Part 6 Service Diagnosis
4.13 OL Activation (Compressor Overload)
Error Code E5
Method of Error
Detection
A compressor overload is detected through compressor OL.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of discharge pipe thermistor
Defective discharge pipe thermistor
Disconnection of connector S40
Disconnection of 2 terminals of OL (Q1M)
Defective OL (Q1M)
Broken OL harness
Defective electronic expansion valve or coil
Defective four way valve or coil
Defective outdoor unit PCB
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 114
Note
Reference
Reference
Troubleshooting
OL (Q1M) activating temperature: 120 ~ 130°C (248 ~ 266°F)
OL (Q1M) recovery temperature: 105°C (221°F)
Check No.01 Refer to P.141
Check No.12 Refer to P.143
(R25224)
Caution
YES
NG
NO
OK
OK
NG
NG
OK
YES
NO
NG
OK
∗ Refrigerant shortage
∗ Water mixed
∗ Stop valve
Disconnect the connector S40
from the PCB.
Disconnect the 2 terminals of
the OL (Q1M).
Resistance
∞
Resistance
∞
Nearly 0 Ω
Nearly 0 Ω
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Replace the four way valve
or the coil.
Replace the outdoor unit
PCB (main PCB).
Discharge
pipe thermistor
disconnected?
Check No. 01
Check the discharge pipe
thermistor.
Check No. 13
Check the four way
valve.
Check No. 14
Check the refrigerant
line.
Check No. 12
Check the electronic
expansion valve.
Replace the OL (Q1M).
Replace the OL harness.
Connect the connector S40
properly.
Is the connector
S40 properly connected?
Check
the resistance
between the 2 terminals on
connector S40.
Check the
resistance between the 2
terminals of the OL
(Q1M).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting SiUS042113EA
115 Part 6 Service Diagnosis
Reference
Reference
Check No.13 Refer to P.144
Check No.14 Refer to P.145
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 116
Reference
Reference
4.14 Compressor Lock
Error Code E6
Method of Error
Detection
A compressor lock is detected by the current waveform generated when applying high-frequency
voltage to the motor.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Closed stop valve
Compressor locked
Disconnection of compressor harness
Troubleshooting
Check No.12 Refer to P.143
Check No.15 Refer to P.145
Turn off the power. Disconnect the
harnesses U, V, and W.
(R21067)
Caution
NO
YES
YES
NO
NO
YES
NO
YES
Check No.15
Check with the inverter analyzer.
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Open the stop valve.
∗ Inverter analyzer:
RSUK0917C
Replace the compressor.
Replace the compressor.
Check the electronic
expansion valve coil.
Go to Check No. 12.
Any LED off?
Stop valve
closed?
Emergency stop
without compressor running?
System shut
down after errors repeated
several times?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting SiUS042113EA
117 Part 6 Service Diagnosis
Reference
4.15 DC Fan Lock
Error Code E7
Method of Error
Detection
An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC.
Error Decision
Conditions
The fan does not start in 15 ~ 30 seconds even when the fan motor is running.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Disconnection of the fan motor
Foreign matter stuck in the fan
Defective fan motor
Defective outdoor unit PCB
Troubleshooting
Check No.16 Refer to P.147
(R20416)
Caution
YES
YES
NO
YES
NO
NO
YES
NO
Turn on the power.
Rotate the fan.
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB (main PCB).
Turn off the power and
reconnect the connector.
Remove the foreign
matters.
Replace the outdoor fan
motor.
Replace the outdoor unit
PCB (main PCB).
Fan motor
connector disconnected?
Foreign matters
in or around the fan?
Replace the outdoor fan
motor.
Fan rotates
smoothly?
Pulse signal
generated?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 118
4.16 Input Overcurrent Detection
Error Code E8
Method of Error
Detection
An input overcurrent is detected by checking the input current value with the compressor running.
Error Decision
Conditions
The current exceeds about 13 ~ 20 A (depending on the model) for 2.5 seconds with the
compressor running.
The upper limit of the current decreases when the outdoor temperature exceeds a certain level.
Supposed
Causes
Outdoor temperature is out of operation range.
Defective compressor
Defective power module
Defective outdoor unit PCB
Short circuit
background
Troubleshooting SiUS042113EA
119 Part 6 Service Diagnosis
Reference
Reference
Reference
Troubleshooting
Check No.15 Refer to P.145
Check No.17 Refer to P.148
Check No.18 Refer to P.149
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
* An input overcurrent may result from wrong internal wiring. If the system is interrupted by an input
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
(R21863)
NO
YES
YES
NO
Start operation and measure the
input current.
Check No. 18
Check the discharge pressure.
Check No. 17
Check the installation condition.
Check No.15
Check with the inverter analyzer.
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Any LED off?
Input current
flowing above its stop level?
* Inverter analyzer:
RSUK0917C
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 120
4.17 Four Way Valve Abnormality
Error Code EA
Method of Error
Detection
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
function within their normal ranges in each operation mode.
Error Decision
Conditions
The following condition continues over 1 ~ 10 minutes (depending on the model) after operating for
5 ~ 10 minutes (depending on the model).
Cooling/Dry
A – B < –5°C (A – B < –9°F)
Heating
B – A < –5°C (B – A < –9°F)
A: Room thermistor temperature
B: Indoor heat exchanger temperature
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
background
Troubleshooting SiUS042113EA
121 Part 6 Service Diagnosis
Reference
Reference
Reference
Troubleshooting
Check No.01 Refer to P.141
Check No.13 Refer to P.144
Check No.14 Refer to P.145
NG
OK
NO
OK
NG
OK
YES
NG
Correct the four way valve
coil.
Reconnect the harness.
YES
YES
YES
NO
NO
Replace the outdoor
unit PCB (main PCB).
Replace the defective
thermistor(s).
Refer to the refrigerant line
check procedure.
Replace the four way valve
(defective or dust-clogged).
Reconnect the
thermistor(s).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(R20405)
∗ Refrigerant shortage
∗ Water mixed
∗ Stop valve
Four way valve
coil disconnected (loose)?
Harness
disconnected?
Any thermistor
disconnected?
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
Check No. 13
Check the four way valve
switching output.
Check the continuity of the four way
valve coil and harness.
Replace the four way
valve coil.
NO
Resistance
between harnesses
about 1000 ~ 2000 Ω?
Disconnect the harness from the
connector.
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 122
4.18 Discharge Pipe Temperature Control
Error Code F3
Method of Error
Detection
An error is determined with the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above A, the compressor
stops.
The error is cleared when the discharge pipe temperature has dropped below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
09/12 class
18/24 class
Supposed
Causes
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Troubleshooting
AB
(°C) (°F) (°C) (°F)
(1) above 50 Hz (rising), above 45 Hz (dropping) 118 244 85 185
(2) 21 ~ 50 Hz (rising), 16 ~ 45 Hz (dropping) 106 223 73 163
(3) below 21 Hz (rising), below 16 Hz (dropping) 98 208 65 149
AB
(°C) (°F) (°C) (°F)
118 244 85 185
(R20417)
Caution
NG
OK
OK
OK
NG
NG
∗ Discharge pipe thermistor
∗ Outdoor heat exchanger thermistor
∗ Outdoor temperature thermistor
∗ Refrigerant shortage
∗ Four way valve
∗ Water mixed
∗ Stop valve
Check No. 12
Check the electronic
expansion valve.
Replace the defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
background
Troubleshooting SiUS042113EA
123 Part 6 Service Diagnosis
Reference
Reference
Reference
Check No.01 Refer to P.141
Check No.12 Refer to P.143
Check No.14 Refer to P.145
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 124
4.19 High Pressure Control in Cooling
Error Code F6
Method of Error
Detection
High-pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if the
temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Error Decision
Conditions
The temperature sensed by the outdoor heat exchanger thermistor rises above A.
The error is cleared when the temperature drops below B.
Supposed
Causes
Installation space not large enough
Dirty outdoor heat exchanger
Defective outdoor fan motor
Defective stop valve
Defective electronic expansion valve or coil
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB
AB
(°C) (°F) (°C) (°F)
09/12 class 62 144 54 129
18/24 class 61 142 52 126
background
Troubleshooting SiUS042113EA
125 Part 6 Service Diagnosis
Reference
Reference
Reference
Reference
Reference
Troubleshooting
Check No.01 Refer to P.141
Check No.12 Refer to P.143
Check No.17 Refer to P.148
Check No.18 Refer to P.149
Check No.19 Refer to P.149
(R20418)
Caution
Replace the outdoor fan
motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB (main PCB).
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the installation space.
NG
OK
OK
NG
NG
OK
OK
OK
NG
NG
Check No. 19
Check the outdoor fan.
Check No. 18
Check the discharge
pressure.
Check No. 12
Check the electronic
expansion valve.
Check No. 01
Check the outdoor heat
exchanger thermistor.
Check No. 17
Check the installation
condition.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 126
Reference
4.20 System Shutdown due to Temperature Abnormality in the
Compressor
Error Code F8
Method of Error
Detection
Operation is halted when the temperature detected by the discharge pipe thermistor exceeds the
determined limit.
Error Decision
Conditions
Temperature exceeds the detection threshold of 127.5°C (261.5°F) during forced cooling operation.
Supposed
Causes
Abnormal operation due to air intrusion
Defective discharge pipe thermistor
Troubleshooting
Check No.01 Refer to P.141
YES
(R23655)
NO
OK
NG
Caution
Replace the outdoor unit. #
Replace both the discharge pipe
thermistor and the outdoor unit
PCB (main PCB).
Replace the outdoor unit.
#
Abnormal
deformation of piping in the
outdoor unit
Check No. 01
Check the discharge pipe
thermistor
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
#
Replace the unit as directed in the installation manual, making sure that air does not intrude
into the refrigerant piping.
background
Troubleshooting SiUS042113EA
127 Part 6 Service Diagnosis
4.21 Compressor System Sensor Abnormality
Error Code H0
Method of Error
Detection
The system checks the DC current before the compressor starts.
Error Decision
Conditions
The voltage converted from the DC current before compressor start-up is out of the range 0.5 ~
4.5 V.
The DC voltage before compressor start-up is below 50 V.
Supposed
Causes
Broken or disconnected harness
Defective outdoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
(R24613)
YES
Turn off the power. Then, turn on
the power to restart the system.
YES
NO
Replace the harness.
Replace the outdoor unit
PCB (main PCB).
Is the harness broken?
Restart
operation and error displayed
again?
Check the (relay) harness for the
compressor.
Not a malfunction.
Keep observing.
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 128
4.22 Position Sensor Abnormality
Error Code H6
Method of Error
Detection
A compressor start-up failure is detected by checking the compressor running condition through the
position detection circuit.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Power supply voltage out of specification
Disconnection of the compressor harness
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage outside the specified range
background
Troubleshooting SiUS042113EA
129 Part 6 Service Diagnosis
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Turn off the power.
Check the connection.
Check the power supply voltage.
Correct the power supply.
(R22764)
NO
NO
NO
NO
YES
YES
YES
YES
Check No. 20
Check the short circuit of the
diode bridge.
Check No.15
Check with the inverter analyzer.
Turn off the power. Disconnect the
harnesses U, V, and W.
Turn on the power. Check the
electrolytic capacitor voltage.
Electrical
components or
compressor harnesses
connected as
specified?
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Replace the compressor.
Reconnect the electrical
components or compressor
harnesses as specified.
Replace the outdoor unit
PCB (main PCB).
Inverter analyzer:
RSUK0917C
Normal?
NO
YES
Check No. 18
Check the discharge pressure.
Replace the stop valve.
OK?
Within 320 VDC?
Any LED off?
+ 100
– 50
Is the
power supply
voltage fluctuation within
±10% from the rated
value?
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 130
Reference
Reference
Reference
Check No.15 Refer to P.145
Check No.18 Refer to P.149
Check No.20 Refer to P.149
background
Troubleshooting SiUS042113EA
131 Part 6 Service Diagnosis
4.23 DC Voltage/Current Sensor Abnormality
Error Code H8
Method of Error
Detection
DC voltage or DC current sensor abnormality is identified based on the compressor running
frequency and the input current.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective outdoor unit PCB
Troubleshooting
Replace the outdoor unit PCB (main PCB).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 132
Reference
Reference
Troubleshooting
Check No.15 Refer to P.145
Check No.21 Refer to P.151
(R23155)
Caution
YES
2 sec
Time
NO
YES
YES
NO
NO
NO
YES
YES
NO
Current
(guideline)
Turn off the power. Then, turn on
the power to restart the system.
Start operation.
Check No. 21
Check the capacitor voltage.
Measure the rectifier input voltage.
Turn off the power. Disconnect the
harnesses U, V, and W.
Turn off the power and reconnect
the harnesses. Then turn on the
power again and restart operation.
Check No.15
Check with the inverter analyzer.
Inverter analyzer:
RSUK0917C
Voltage
within the allowable
range (Power supply
voltage ± 15%)?
Replace the outdoor unit
PCB (main PCB).
Check the power supply
voltage.
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor unit
PCB (main PCB).
Replace the compressor.
Capacitor charged when
the indoor unit or outdoor
unit main relay turns on
Rising with increasing
frequency
Correct the power supply or
replace the outdoor unit PCB
(main PCB).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Running current
as shown at right
with relay cable 1
or 2?
Within 320 VDC?
Any LED off?
Compressor running?
+ 100
- 50
background
Troubleshooting SiUS042113EA
133 Part 6 Service Diagnosis
4.24 Thermistor or Related Abnormality (Outdoor Unit)
Error Code H9, J3, J6, J8, P4
Method of Error
Detection
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision
Conditions
The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or less
with the power on.
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Supposed
Causes
Disconnection of the connector for the thermistor
Defective thermistor(s)
Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger thermistor
in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Troubleshooting In case of P4
Replace the outdoor unit PCB (main PCB).
P4 : Radiation fin thermistor
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 134
Reference
Troubleshooting In case of H9, J3, J6, J8
R6000772
H9 : Outdoor temperature thermistor
J3 : Discharge pipe thermistor
J6 : Outdoor heat exchanger thermistor
J8 : Liquid pipe thermistor
Check No.01 Refer to P.141
Caution
NO
YES
YES
NO
NO
YES
Turn on the power again.
Normal?
Reconnect the connectors
or thermistors.
J3 error: The discharge
pipe temperature is
lower than the heat
exchanger temperature.
Replace the defective
thermistor(s).
Outdoor temperature
thermistor
Discharge pipe thermistor
Outdoor heat exchanger
thermistor
Liquid pipe thermistor
Cooling: Outdoor heat
exchanger
thermistor
Heating: Indoor heat
exchanger
thermistor
Replace the indoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
Indoor heat
exchanger thermistor
functioning?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Error displayed
again on remote
controller?
Check No. 01
Check the thermistor resistance
value.
Check No. 01
Check the indoor heat exchanger
thermistor resistance value in the
heating operation.
background
Troubleshooting SiUS042113EA
135 Part 6 Service Diagnosis
Reference
Reference
4.25 Electrical Box Temperature Rise
Error Code L3
Method of Error
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Error Decision
Conditions
With the compressor off, the radiation fin temperature is above A.
The error is cleared when the radiation fin temperature drops below B.
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
rises above C and stops when the radiation fin temperature drops below B.
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Troubleshooting
Check No.17 Refer to P.148
Check No.19 Refer to P.149
ABC
(°C) (°F) (°C) (°F) (°C) (°F)
09/12 class 122 252 64 147 113 235
18/24 class 92 198 70 158 77 171
Caution
WARNING
To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above C and stops when the radiation
fin temperature drops below B.
(R22998)
YES
NO
YES
NG
NO
OK
NO
YES
Turn off the power. Then, turn on
the power to restart the system.
Check the radiation fin
temperature.
Radiation fin dirty?
Check No. 19
Check the outdoor fan.
Error again or
outdoor fan activated?
Replace the outdoor unit
PCB (main PCB).
Clean up the radiation fin.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor fan
motor.
Correct the connectors
and fan motor lead wire.
Replace the outdoor unit
PCB (main PCB).
Above A?
Check the installation
condition.
Go to Check No. 17.
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 136
4.26 Radiation Fin Temperature Rise
Error Code L4
Method of Error
Detection
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
compressor on.
Error Decision
Conditions
If the radiation fin temperature with the compressor on is above A.
The error is cleared when the radiation fin temperature drops below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicone grease not applied properly on the radiation fin after replacing the outdoor unit PCB
AB
(°C) (°F) (°C) (°F)
09/12 class 77 171 38 100
18/24 class 82 180 77 171
background
Troubleshooting SiUS042113EA
137 Part 6 Service Diagnosis
Reference
Reference
Note
Troubleshooting
Check No.17 Refer to P.148
Check No.19 Refer to P.149
Refer to Silicone Grease on Power Transistor/Diode Bridge on page 167 for details.
Caution
Turn off the power. Then, turn on
the power to restart the system.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(R23953)
NO
NG
OK
NO
YES
Check the radiation fin
temperature.
NO
YES
YES
Above A?
Check No. 19
Check the outdoor fan.
Error displayed
again?
Has the PCB
been replaced?
Check if silicone grease is
applied properly on the
radiation fin. If not, apply
the silicone grease.
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor fan
motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB (main PCB).
YES
NO
Radiation fin
dirty?
Clean up the radiation fin.
Check the installation
condition.
Go to Check No. 17.
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 138
4.27 Output Overcurrent Detection
Error Code L5
Method of Error
Detection
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Error Decision
Conditions
A position signal error occurs while the compressor is running.
A rotation speed error occurs while the compressor is running.
An output overcurrent signal is fed from the output overcurrent detection circuit to the
microcomputer.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Poor installation condition
Closed stop valve
Defective power module
Wrong internal wiring
Abnormal power supply voltage
Defective outdoor unit PCB
Power supply voltage out of specification
Defective compressor
background
Troubleshooting SiUS042113EA
139 Part 6 Service Diagnosis
Troubleshooting
(R21438)
Caution
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
YES
NO
An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
Check No. 22
Check No. 17
Check No.15
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Turn off the power. Then, turn on
the power to restart the system.
See if the same error occurs.
Check the power supply voltage.
Monitor the power supply voltage,
discharge and suction pressures,
and other factors for a long term.
Possible causes
Momentary drop of power supply
voltage
Compressor overload
Short circuit
Check the installation condition.
Check with the inverter analyzer.
Check the power module.
Not a malfunction.
Keep observing.
Check the connectors and
other components.
Fully open the stop valve.
Correct the power supply.
Replace the compressor.
Correct the power supply
or replace the outdoor unit
PCB (main PCB).
Replace the outdoor unit
PCB (main PCB).
Error again?
Stop valve fully open?
Voltage as rated?
Any LED off?
Normal?
Inverter analyzer:
RSUK0917C
Short circuit or
wire breakage between
compressor's coil
phases?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the discharge
pressure.
Go to Check No. 18.
background
SiUS042113EA Troubleshooting
Part 6 Service Diagnosis 140
Reference
Reference
Reference
Reference
Check No.15 Refer to P.145
Check No.17 Refer to P.148
Check No.18 Refer to P.149
Check No.22 Refer to P.152
background
Check SiUS042113EA
141 Part 6 Service Diagnosis
Note
5. Check
5.1 Thermistor Resistance Check
Check No.01 Measure the resistance of each thermistor using multimeter.
The resistance values are defined by below table.
If the measured resistance value does not match the listed value, the thermistor must be replaced.
Disconnect the connector of thermistor ASSY from the PCB to measure the resistance between
the pins using multimeter.
To check the thermistor soldered on a PCB, disconnect the PCB from other PCB/parts, and
measure the resistance between the both ends of soldered thermistor.
R6000517
When replacing the defective thermistor(s), replace the thermistor as ASSY.
Multimeter
Resistance range
Thermistor ASSY Soldered thermistor
Multimeter
Thermistor temperature Resistance (kΩ)
(°C) (°F)
R (25°C (77°F)) = 20 kΩ
B = 3950 K
–20 –4 197.8
–15 5 148.2
–10 14 112.1
–5 23 85.60
0 32 65.93
5 41 51.14
10 50 39.99
15 59 31.52
20 68 25.02
25 77 20.00
30 86 16.10
35 95 13.04
40 104 10.62
45 113 8.707
50 122 7.176
(kΩ)
150
100
50
–15 0 15 30 45
(R14467)
5 32 59 86 113
(°C)
(°F)
background
SiUS042113EA Check
Part 6 Service Diagnosis 142
5.2 Indoor Fan Motor Connector Check
Check No.03 Fan motor wire breakdown/short circuit check
1. Check the connector for connection.
2. Turn the power off.
3. Check if each resistance at the phases U - V and V - W is within specified range in the table
below.
R6000511
5.3 Power Supply Waveform Check
Check No.11 Measure the power supply waveform between No. 1 and No. 2 on the terminal strip, and check the
waveform disturbance.
Check if the power supply waveform is a sine wave (Fig.1).
Check if there is waveform disturbance near the zero-cross (sections circled in Fig.2).
U-V/V-W Resistance
()
09/12 class 41 ~ 57
18/24 class 20 ~ 28
3
2
1
Phase U
Phase V
Phase W
S200
[Fig.1] [Fig.2]
(R1736)
(R1444)
background
Check SiUS042113EA
143 Part 6 Service Diagnosis
5.4 Electronic Expansion Valve Check
Check No.12 Conduct the following to check the electronic expansion valve (EV).
1. Check if the EV connector is correctly connected to the PCB.
2. Turn the power off and on again, and check if the EV generates a latching sound.
3. If the EV does not generate a latching sound in step 2, disconnect the connector and check the
continuity using a multimeter.
4. Check the continuity between the pins 5 - 1, 5 - 2, 5 - 3, 5 - 4 (between the pins 6 - 1, 6 - 2, 6 - 3,
and 6 - 4 for the 6P connector models). If there is no continuity between the pins, the EV coil is
faulty.
5. If the continuity is confirmed in step 3, the outdoor unit PCB (main PCB) is faulty.
Harness 5P
5P Connector
Check
S20
5 - 1
5 - 2
5 - 3
5 - 4
1 2 3 4 5
(R23663)
Harness 5P
6P Connector
(5)
CheckS20
6 - 1
6 - 2
6 - 3
6 - 4
1 2 3 4 5 6
(R23593)
background
SiUS042113EA Check
Part 6 Service Diagnosis 144
5.5 Four Way Valve Performance Check
Check No.13
Start heating operation.
(R25254)
NO
YES
YES
Four way valve
coil resistance at
440 - 750 ?
NO
Turn off the power and turn it on
again.
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Replace the four way valve
coil.
Replace the four way valve.
NO
YES
S80 voltage at
0 VDC with compressor on?
S80
voltage at 120 -
380 VDC for 3 sec. after
compressor starts, and then at
about 10 - 24 VDC?
(Fig. 1)
Disconnect the four way valve coil
from the connector and check the
continuity.
(Fig. 1)
Voltage at S80
120 - 380 VDC
10 - 24 VDC
Time
Compressor
ON
3 sec.
< Caution on resetting the power supply >
Be sure to wait for 30 sec. or more after turning off the power.
Four way valve coil
Cooling / Dry : No continuity
Heating : Continuity
background
Check SiUS042113EA
145 Part 6 Service Diagnosis
5.6 Inverter Unit Refrigerant System Check
Check No.14
5.7 Inverter Analyzer Check
Check No.15 Characteristics
Inverter analyzer: RSUK0917C
If an abnormal stop occurs due to compressor startup failure or overcurrent output when using an
inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or some
other failure (main PCB, power module, etc.). The inverter analyzer makes it possible to judge the
cause of trouble easily and securely. Connect an inverter analyzer as a quasi-compressor instead
of compressor and check the output of the inverter.
Operation Method
Step 1
Be sure to turn the power off.
Step 2
Install an inverter analyzer instead of a compressor.
Note:
Make sure the charged voltage of the built-in smoothing electrolytic capacitor drops to 10 VDC or
below before carrying out the service work.
Refrigerant system check
Check for refrigerant leakage.
See the service diagnosis on
refrigerant shortage (U0).
(R15833)
YES
NO
Reconnect the thermistor.
Replace the refrigerant.
Is the discharge
pipe thermistor
disconnected from the
holder?
background
SiUS042113EA Check
Part 6 Service Diagnosis 146
Caution
Reference:
If the terminals of the compressor are not FASTON terminals (difficult to remove the wire on the
terminals), it is possible to connect wires available on site to the outdoor unit from output side of
PCB. Do not connect them to the compressor at the same time, otherwise it may result in incorrect
detection.
Step 3
Activate power transistor test operation from the indoor unit.
1. Turn the power on.
2. Select FAN operation with Mode button on the remote controller.
3. Press the center of Temp button and Mode button at the same time.
4. Select T with Temp or Temp button.
5. Press Mode button to start the power transistor test operation.
Diagnose method (Diagnose according to 6 LEDs lighting status of the inverter analyzer.)
1. If all the LEDs are lit uniformly, the compressor is defective.
Replace the compressor.
2. If the LEDs are not lit uniformly, check the power module.
Refer to Check No.22.
3. If NG in Check No.22, the power module is defective.
Replace the main PCB. The power module is united with the main PCB.
If OK in Check No.22, check if there is any solder cracking on the PCB.
4. If any solder cracking is found, replace the PCB or repair the soldered section.
If there is no solder cracking, replace the PCB.
1. When the output frequency is low, the LEDs blink slowly. As the output frequency increases, the
LEDs blink quicker. The LEDs look like they are lit.
(
R22731
)
(1) Remove the terminals from
the compressor.
(2) Connect the terminals to the
terminals of the inverter
analyzer.
Compressor
Inverter analyzer
Be careful not to let the terminals (U,V,W)
touch each other. Otherwise, high voltage
is applied.
Compressor
background
Check SiUS042113EA
147 Part 6 Service Diagnosis
2. On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
Otherwise, the terminals may be burned due to loosening.
5.8 Outdoor Fan Motor Check
Check No.16 Outdoor fan motor
09/12 class
Check if the sinusoidal voltage is generated between pins 1 - 3 and 3 - 5 when the fan motor is
manually rotated once.
S6000841
18/24 class
Make sure that the voltage of 320 ± 30 V is applied.
1. Set operation OFF and power OFF. Disconnect the connector S70.
2. Check that the voltage between the pins 4 - 7 is 320 VDC.
3. Check that the control voltage between the pins 3 - 4 is 15 VDC.
4. Check that the rotation command voltage between the pins 2 - 4 is 0 ~ 6.5 VDC.
5. Keep operation OFF and power OFF. Connect the connector S70.
6. Check whether 4 pulses (0 ~ 15 VDC) are output at the pins 1 - 4 when the fan motor is rotated
1 turn by hand.
When the fuse is melted, check the outdoor fan motor for proper function.
If NG in step 2 Defective PCB Replace the outdoor unit PCB (main PCB).
If NG in step 4 Defective Hall IC Replace the outdoor fan motor.
If OK in both steps 2 and 4 Replace the outdoor unit PCB (main PCB).
(R15292)
Direction of crimp
FASTON terminal
This size is shortened
by the crimp.
5
3
1 Phase U
Phase V
Phase W
S70
PCB
background
SiUS042113EA Check
Part 6 Service Diagnosis 148
5.9 Installation Condition Check
Check No.17
1
2
3
4
5
6
7
320 VDC
(R25288)
S70
PCB
Actual rotation pulse input (0 ~ 15 VDC)
Rotation command voltage (0 ~ 6.5 VDC)
Control voltage 15 VDC
Installation condition check
OK
Check the allowable
dimensions of the air
suction and
discharge area.
Is the airflow blocked by
obstacles or winds
blowing in the opposite
direction?
(R19394)
NG
YES
YES
NO
Is the discharged air
short-circuited?
NO
NO
YES
Is the outdoor heat
exchanger very dirty?
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Change the installation
location or direction.
Check the outdoor temperature.
(The outdoor temperature
should be within the operation
range.)
background
Check SiUS042113EA
149 Part 6 Service Diagnosis
5.10 Discharge Pressure Check
Check No.18
5.11 Outdoor Fan System Check
Check No.19 DC motor
5.12 Main Circuit Short Check
Check No.20 Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is about
0 V before checking
Measure the resistance between the pins of the DB1 referring to the table below.
If the resistance is or less than 1 k, short circuit occurs on the main circuit.
(R21121)
YES
YES
YES
NO
NO
NO
NO
YES
Is the air filter or
indoor/outdoor heat
exchanger dirty?
Is the
connection pipe deformed?
Is the stop valve
open?
High?
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean the dirty air filter or
indoor/outdoor heat exchanger.
Replace the compressor.
Discharge pressure check
(R21195)
YES
NO
NO
YES
Outdoor fan system is functioning.
Check the outdoor fan system.
Reconnect the connector.
Is
the outdoor fan
running?
Fan motor lead
wire connector
disconnected?
Go to Check No. 16.
Positive terminal (+) of
digital multimeter
~ (2, 3) + (4) ~ (2, 3) – (1)
Negative terminal (–) of
digital multimeter
+ (4) ~ (2, 3) – (1) ~ (2, 3)
Resistance is OK. several k ~ several M
Resistance is NG. 0 or
background
SiUS042113EA Check
Part 6 Service Diagnosis 150
09/12 class
R6000766
18/24 class
1
2
3
4
Multimeter
~~
–
+
–
+
(R24538)
1
2
3
4
Multimeter
–~~+
–
+
background
Check SiUS042113EA
151 Part 6 Service Diagnosis
5.13 Capacitor Voltage Check
Check No.21 Before this check, turn the circuit breaker off and wait for 10 minutes for prevention of electric
shock.
09/12 class
R6000792
To prevent electrical shock, use a multimeter to check that the voltage between DC_P2 (+)
and DC_N2 (–) is 50 V or less.
18/24 class
R6000790
To prevent an electrical shock, use a multimeter to check that the voltage between FU2 and
DC– is 50 V or less.
The surface of the test points (FU2, DC–) may be covered with the coating. Be sure to make
firm contact between the multimeter probes and the test points.
FU2 DC–
Coating
PCB
Multimeter probe
background
SiUS042113EA Check
Part 6 Service Diagnosis 152
5.14 Power Module Check
Check No.22 Check to make sure that the voltage between (+) and (–) of the power module is about 0 V before
checking.
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Follow the procedure below to measure resistance between the terminals of the power module
and the terminals of the compressor with a multimeter. Evaluate the measurement results
referring to the following table.
09/12 class
Positive terminal (+) of
digital multimeter
Power module
(+)
UVW
Power module
(–)
UVW
Negative terminal (–) of
digital multimeter
UVW
Power module
(+)
UVW
Power module
(–)
Resistance is OK. several k ~ several M
Resistance is NG. 0 or
Pin 24: +
Pin 23: U
Pin 22: V
Pin 21: W
Pin 20: –
(R24993)
background
Check SiUS042113EA
153 Part 6 Service Diagnosis
18/24 class
(R24539)
DC–
DC+
WVU
background
SiUS042113EA
Part 7 Trial Operation and Field Settings 154
1. Pump Down Operation............................................................................155
2. Forced Cooling Operation .......................................................................156
3. Trial Operation ........................................................................................157
4. Field Settings ..........................................................................................159
4.1 Temperature Display Switch .................................................................... 159
4.2 When 2 Units are Installed in 1 Room...................................................... 159
4.3 Facility Setting (cooling at low outdoor temperature) ............................... 160
4.4 Warmer Airflow Setting............................................................................. 161
4.5 Drain Pan Heater...................................................................................... 163
4.6 Service Mode of Wireless Remote Controller .......................................... 164
5. Silicone Grease on Power Transistor/Diode Bridge................................167
Part 7
Trial Operation and
Field Settings
background
Pump Down Operation SiUS042113EA
155 Part 7 Trial Operation and Field Settings
Reference
1. Pump Down Operation
Outline In order to protect the environment, be sure to conduct pump down operation when relocating or
disposing of the unit.
Details 1. Remove the valve caps from the liquid stop valve and the gas stop valve.
2. Carry out forced cooling operation.
3. After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4. After 2 to 3 minutes, close the gas stop valve and stop the forced cooling operation.
Refer to Forced Cooling Operation on page 156 for details.
Gas stop valve
Valve cap
Close
Liquid stop valve
Service port
(R25008)
Hexagonal
wrench
background
SiUS042113EA Forced Cooling Operation
Part 7 Trial Operation and Field Settings 156
2. Forced Cooling Operation
Outline The forced cooling operation is allowed when both the following conditions are met.
1. The outdoor unit is not abnormal and not in the 3-minute standby mode.
2. The outdoor unit is not operating.
Protection functions have priority over all other functions during forced cooling operation.
Details With indoor unit ON/OFF switch
Press indoor unit ON/OFF switch for at least 5 seconds. The operation will start.
Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press indoor unit ON/OFF switch.
R4003799
With the indoor unit's remote controller
1. Press Temp, buttons and Mode button at the same time.
2. Press Temp, buttons, select "T", and press Mode button for confirmation.
Forced cooling operation will stop automatically after about 30 minutes.
To stop the operation, press On/Off button.
3. Press Mode button and select the cooling operation.
4. Press On/Off button to turn on the system.
R7000376
ON/OFF switch
1, 2, 3
4
1, 2
2
background
Trial Operation SiUS042113EA
157 Part 7 Trial Operation and Field Settings
Note(s)
3. Trial Operation
Outline Trial operation should be carried out in either cooling or heating operation.
1. Measure the supply voltage and make sure that it is within the specified range.
2. In cooling operation, select the lowest programmable temperature;
in heating operation, select the highest programmable temperature.
3. Carry out the trial operation following the instructions in the operation manual to ensure that all
functions and parts, such as the movement of the louvers, are working properly.
• To protect the air conditioner, restart operation is disabled for 3 minutes after the system has
been turned off.
4. After trial operation is complete, set the temperature to a normal level (78°F to 82°F (26°C to
28°C) in cooling operation, 68°F to 75°F (20°C to 24°C) in heating operation).
When operating the air conditioner in cooling operation in winter, or heating operation in summer,
set it to the trial operation mode using the following method.
Procedure 1. Press Temp, buttons and Mode button at the same time.
2. Press Temp, buttons, select "T", and press Mode button for confirmation.
3. Press On/Off button to turn on the system.
Trial operation will stop automatically after about 30 minutes
To stop the operation, press On/Off button.
Some of the functions cannot be used in the trial operation mode.
R7000370
The air conditioner draws a small amount of power in its standby mode. If the system is not to
be used for some time after installation, shut off the circuit breaker to eliminate unnecessary
power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the
original operation mode when the circuit breaker is turned on again.
1, 2
3
1, 2
2
background
SiUS042113EA Trial Operation
Part 7 Trial Operation and Field Settings 158
Test Items
Test items Symptom
Indoor and outdoor units are installed securely. Fall, vibration, noise
No refrigerant gas leaks. Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain
hose extension are thermally insulated.
Water leakage
Draining line is properly installed. Water leakage
System is properly grounded. Electrical leakage
Only specified wires are used for all wiring, and all
wires are connected correctly.
No operation or burn damage
Indoor or outdoor unit’s air inlet or air outlet are
unobstructed.
Incomplete cooling/heating function
Stop valves are opened. Incomplete cooling/heating function
Indoor unit properly receives remote controller
commands.
No operation
Attached SSID sticker with release paper (1 pc.) is
given to the user.
Unable to connect to wireless LAN
background
Field Settings SiUS042113EA
159 Part 7 Trial Operation and Field Settings
4. Field Settings
4.1 Temperature Display Switch
Procedure Press the upper side of Temp button and On button at the same time for 5 seconds to change
the unit of temperature display.
4.2 When 2 Units are Installed in 1 Room
Outline When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding wireless
remote controller can be set for different address.
Procedure 1. Remove the battery cover of the remote controller, and cut the address jumper (J4).
2. Press the center of Temp button and Mode button on the remote controller at the same time.
3. Select A (address setting) with Temp or Temp button, and press Mode button to enter the
address setting mode.
Then, the indoor unit operation lamp blinks for 1 minute.
4. Press the indoor unit ON/OFF switch while the operation lamp is blinking.
If setting could not be carried out completely while the operation lamp was blinking, carry out
the setting process once again from the beginning.
After setting, press Mode button on the remote controller for 5 seconds to return to the
normal mode.
(R22009)
background
SiUS042113EA Field Settings
Part 7 Trial Operation and Field Settings 160
Caution
Replace the remote controller if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
4.3 Facility Setting (cooling at low outdoor temperature)
Outline This function is limited only for facilities (the target of air conditioning is equipment such as
computers). Never use it in a residence or office (the space where there is a human).
Details 09/12 class
Cutting jumper 4 (J4) on the circuit board of the outdoor unit will expand the operation range to
14°F (–10°C). Installing an air direction adjustment grille (sold separately) will further extend the
operation range to –4°F (–20°C). In these cases, the unit will stop operating if the outdoor
temperature falls below –4°F (–20°C), restarting once the temperature rises above this level.
1. Remove the top plate of the outdoor unit. (4 screws)
2. Remove the electrical wiring box cover.
3. Cut the jumper (J4) of the PCB inside.
18/24 class
Turning on SW5-3 on the PCB of the outdoor unit will extend the operation range to 14°F (–10°C).
Installing an air direction adjustment grille (sold separately) will further extend the operation range
to –4°F (–20°C). In these cases, the unit will stop operating if the outdoor temperature falls below
–4°F (–20°C), restarting once the temperature rises above this level.
R7000285
R7000202
R7000337
(R22634)
Jumper (J4)
ADDRESS
J4
EXIST
CUT
1
2
Temp button
Mode button
Indoor unit
ON/OFF switch
and operation lamp
PCB
HEAT
COOL
4
3
2
1
6
5
E
D
C
B
A
4
3
ON
OFF
2
1
SW5
Turn on switch 3
Screw
Remove
the switch
cover
background
Field Settings SiUS042113EA
161 Part 7 Trial Operation and Field Settings
Reference
Caution
Caution
For the location of the jumper, refer to page 26.
If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind,
provide a windbreak wall.
Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off
when using facility settings.
Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used. A humidifier might cause dew condensation from the indoor unit outlet
vent.
Cutting jumper 4 (J4)/activating the facility setting sets the indoor fan tap to the highest position.
Notify the user about this.
Replace the PCB if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
4.4 Warmer Airflow Setting
Outline The temperature of discharge airflow in heating operation can be adjusted warmer.
The room temperature will be high when getting close to the set temperature.
The discharge airflow does not become warmer in other than heating operation.
Procedure Warmer airflow can be enabled/disabled from remote controller or outdoor unit.
From remote controller
Refer to page 164 for details of setting procedure.
From outdoor unit (RKM-WVJU9 only)
09/12 Class
1. Remove the top plate of the outdoor unit. (4 screws)
2. Remove the Electric wiring box cover.
3. Cut the jumper (J5) of the PCB inside.
R7000381
Cut the jumper (J5)
Electrical wiring box cover Hook
(3 places)
background
SiUS042113EA Field Settings
Part 7 Trial Operation and Field Settings 162
Note(s)
18/24 Class
1. Turn on SW5-2 on the PCB
R7000380
Warmer airflow can be enabled from either indoor or outdoor unit.
Warmer airflow becomes available when either one of the RC or outdoor unit setting is enabled.
For example, if the outdoor unit has the switch for warmer airflow, it can be set even when it is
disabled on the indoor unit.
Also, for the wireless remote controller with field setting function, warmer airflow is enabled when
set on indoor unit with the remote controller field setting, even when it is disabled on outdoor unit.
PCB
HEAT
COOL
4
3
2
1
6
5
E
D
C
B
A
4
3
ON
OFF
2
1
SW5
Turn on switch 2
Screw
Remove
the switch
cover
background
Field Settings SiUS042113EA
163 Part 7 Trial Operation and Field Settings
Reference
4.5 Drain Pan Heater
In high humidity areas or heavy snow areas, it is recommended to attach a drain pan heater
to prevent ice build-up from the bottom frame.
09/12 class
1. Attach the drain pan heater in accordance with the installation manual included with the drain
pan heater.
2. Remove the top plate of the outdoor unit. (4 screws)
3. Remove the electrical wiring box cover.
4. Cut the jumper (J9) of the PCB inside.
18/24 class
1. Attach the drain pan heater in accordance with the installation manual included with the drain
pan heater.
2. Dismount the service lid by removing the 2 screws.
3. Remove the switch cover (1 screw).
4. Turn on SW6-1 on the PCB.
R7000288
For the location of the jumper, refer to page 26.
PCB
HEAT
COOL
4
3
2
1
E
D
C
B
A
ON
OFF
SW6
12
Turn on switch 1
Screw
Remove
the switch
cover
background
SiUS042113EA Field Settings
Part 7 Trial Operation and Field Settings 164
4.6 Service Mode of Wireless Remote Controller
The remote controller mode is hierarchized by special conditions and operation content. Refer
below for the main hierarchy of the menu.
Normal mode
Service mode
Normal mode is operated by the end user.
Simplified service diagnosis on normal mode
The code indication changes every time the TIMER CANCEL button is
pressed.
Service check mode
In service check mode, the left-side number and the right-side
number can be identified individually.
Address setting mode
This mode sets the address corresponding to the jumper position.
Trial operation mode
Press for
5 seconds
Press for
5 seconds
Press for 5 seconds
+
Pressing the center of the temperature adjustment
button has the same function as pressing both
buttons simultaneously.
+
Proceed to
1
(R24917)
background
Field Settings SiUS042113EA
165 Part 7 Trial Operation and Field Settings
Overview of the Settings
* 09/12 class: N/A
Setting items Setting options
Factory
setting
Contents
1
Brightness 0: OFF
1: Dark
2: Bright
N/A
Brightness of indoor unit LED lamp
2
Filter cleaning setting 0: Short
1: Long
N/A
Determines the duration/time to display Filter cleaning sign.
3
Suspend 0: OFF
1: ON
1
Activation/Deactivation of Standby electricity saving (suspend
function)
0: Power will still be supplied to the outdoor unit PCB after the unit
operation stopped.
1: Three minutes after the unit operation stops, the power supply to
the outdoor unit PCB is shut off.
4
Dry keep 0: OFF
1: ON
0
Stops the airflow of indoor unit when the thermostat is OFF to
prevent increase of room humidity.
0: When thermostat is OFF, the fan rotor will still be OPERATING,
hence there is airflow.
1: When thermostat is OFF, the fan rotor will be STOPPED, hence
there is no airflow.
5
Preheating control 0: OFF
1: ON 0*
Activation/Deactivation of compressor preheating
0: Deactivation of compressor preheating
1: Activation of compressor preheating
6
Room temperature
adjustment (cooling)
0: Low 2 (–2°C)
1: Low 1 (–1°C)
2: Standard (0°C)
3: High 1 (+1°C)
4: High 2 (+2°C)
2
Adjustment of indoor temperature thermistor in cooling operation
Used for adjustment of room temperature control.
7
Room temperature
adjustment (heating)
0: Low 2 (–2°C)
1: Low 1 (–1°C)
2: Standard (0°C)
3: High 1 (+1°C)
4: High 2 (+2°C)
2
Adjustment of indoor temperature thermistor in heating operation.
Used for adjustment of room temperature control.
8
Airflow setting when
thermostat off during
cooling operation
0: Keep
1: Soft breeze N/A
Airflow setting when indoor unit thermostat is off.
0: Same airflow as "thermostat on"
1: Lowered to LL tap
9
Wireless/HA priority setting
during automatic operation
0: Wireless
1: HA N/A
Determination of priority control method when HA system is used.
0: Wireless remote controller can be used.
1: Temperature setting from wireless remote controller is disabled.
10
Auto-restart 0: OFF
1: ON
1
This setting decides the operation of the unit when the power supply
resumed after a power supply shutdown (i.e. power failure).
0: When the power supply resumes, the unit remains in stopped
operation.
1: When the power supply resumes, the unit resumes the operation
before the shutdown of power supply.
12
Warmer airflow setting 0: OFF
1:
ON
0
This setting makes the discharge airflow temperature warmer.
1
Field settings mode
Room temperature adjustment settings may be applied.
When changing the settings, make sure the button was correctly pressed by listening for
the beep sound. (The beep can be heard even if the button is pressed within a setting
which is unavailable. In this case, the setting will be invalid.)
Press the buttons to change the setting items and the setting values.
•
Confirm/Send
Setting items Setting values
(R24995)
background
SiUS042113EA Field Settings
Part 7 Trial Operation and Field Settings 166
Notes
Set value on remote controller display may differ from the set value of indoor unit itself, as remote
controller is not synchronized with indoor unit.
background
Silicone Grease on Power Transistor/Diode Bridge SiUS042113EA
167 Part 7 Trial Operation and Field Settings
5. Silicone Grease on Power Transistor/Diode Bridge
Outline Apply the specified silicone grease to the heat generation part of a power transistor/diode bridge
when you replace an outdoor unit PCB. The silicone grease encourages the heat dissipation of a
power transistor/diode bridge.
Details 1. Wipe off the old silicone grease completely.
2. Apply the silicone grease evenly. See the illustrations below for examples of application.
3. Tighten the screws of the power transistor/diode bridge.
4. Make sure that the heat generation parts are firmly contacted to the radiation fin.
Note: Smoke emission may be caused by bad heat radiation when the silicone grease is not
appropriately applied.
OK: Evenly applied
NG: Not evenly applied
NG: Foreign matter is stuck.
(R22541)
Power transistor
(or diode bridge)
Silicone grease
Radiation
fin
PCB
(R21866)
Foreign matter
(R21867)
background
SiUS042113EA
Part 8 Appendix 168
1. Piping Diagrams......................................................................................169
1.1 Indoor Unit................................................................................................ 169
1.2 Outdoor Unit ............................................................................................. 170
2. Wiring Diagrams......................................................................................172
2.1 Indoor Unit................................................................................................ 172
2.2 Outdoor Unit ............................................................................................. 174
3. Operation Limit........................................................................................176
Part 8
Appendix
background
Piping Diagrams SiUS042113EA
169 Part 8 Appendix
1. Piping Diagrams
1.1 Indoor Unit
FTXM09/12WVJU9, FTXM09/12VVJU FTXM18WVJU9, FTXM18VVJU
FTXM24WVJU9, FTXM24VVJU
4D132956 4D132992
4D132994
background
SiUS042113EA Piping Diagrams
Part 8 Appendix 170
1.2 Outdoor Unit
RXM09/12WVJU9, RXM09/12VVJU
RXM18WVJU9, RXM18VVJU
3D131979
3D132216
background
Piping Diagrams SiUS042113EA
171 Part 8 Appendix
RXM24WVJU9, RXM24VVJU
3D132217
background
SiUS042113EA Wiring Diagrams
Part 8 Appendix 172
Note(s)
2. Wiring Diagrams
2.1 Indoor Unit
FTXM09/12WVJU9, FTXM09/12VVJU
A1P: Control PCB
A2P: Power supply PCB
A3P: Display/signal receiver PCB
A4P: Humidity sensor PCB
A5P: INTELLIGENT EYE sensor PCB
A6P: Wireless LAN connection PCB
Refer to page 22 for Printed Circuit Board Connector Wiring Diagram.
C: 3D129547A
background
Wiring Diagrams SiUS042113EA
173 Part 8 Appendix
Note(s)
FTXM18/24WVJU9, FTXM18/24VVJU
A1P: Control PCB
A2P: Power supply PCB
A3P: Display/signal receiver PCB
A4P: Humidity sensor PCB
A5P: INTELLIGENT EYE sensor PCB
A6P: Wireless LAN connection PCB
Refer to page 22 for Printed Circuit Board Connector Wiring Diagram.
C: 3D129548A
background
SiUS042113EA Wiring Diagrams
Part 8 Appendix 174
Note(s)
2.2 Outdoor Unit
RXM09/12WVJU9, RXM09/12VVJU
A1P: Main PCB
Refer to page 26 for Printed Circuit Board Connector Wiring Diagram.
C: 3D129643B
Note: Standby electricity saving circuit is implemented on board.
background
Wiring Diagrams SiUS042113EA
175 Part 8 Appendix
Note(s)
RXM18/24WVJU9, RXM18/24VVJU
A1P: Main PCB
A2P: Service monitor PCB
Refer to page 28 for Printed Circuit Board Connector Wiring Diagram.
C: 3D129644B
Note: Standby electricity saving circuit is implemented on board.
background
SiUS042113EA Operation Limit
Part 8 Appendix 176
3. Operation Limit
RXM09/12/18/24WVJU9, RXM09/12/18/24VVJU
3D133582A
background
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
©
All rights reserved
Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorized importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
Specifications, designs and other content appearing in this brochure are current as of January 2023 but subject to change without notice.
SiUS042113EA
01/2023 AK.B

Specifications

Daikin RXM18WVJU9 Questions and Answers

Questions and Answers

Related Products