Installation Instructions for
*R9S96/*D9S96 & *R9S92
Single-Stage Gas Furnace
(Type FSP CATEGORY IV Direct or Non Direct Vent Air Furnace)
(Type FSP CATÉGORIE IV Direct ou four á air soufflé non direct)
Installer:
Affix all manuals
adjacent to the unit.
As a professional installer you have an obligation to know
the product better than the customer. This includes all
safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself
with this Instruction Manual. Pay special attention to all
safety warnings. Often during installation or repair it is
possible to place yourself in a position which is more
hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product
safely and to know it well enough to be able to instruct a
customer in its safe use.
Safety is a matter of common sense...a matter of thinking
before acting. Most dealers have a list of specic good
safety practices...follow them.
The precautions listed in this Installation Manual are
intended as supplemental to existing practices. However,
if there is a direct conict between existing practices and
the content of this manual, the precautions listed here take
precedence.
IOG-2037A
09/2023
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
*NOTE: Please contact your distributor or our
website for the applicable Specification Sheet
referred to in this manual.
90% HEX
DO NOT LIFT
PRODUCT USING
HEAT EXCHANGER
These furnaces comply with requirements embodied
in the American National Standard / National Standard
of Canada ANSI Z21.47·CSA-2.3 Gas Fired Central
Furnaces.
Do not bypass safety devices.
WARNING
19001 Kermier Rd. Waller, TX 77484
www.goodmanmfg.com • www.amana-hac.com
© 2023 Daikin Comfort Technologies Manufacturing, L.P.
is a registered trademark of Maytag Corporation or its related companies and is used under license.
All rights reserved.
Only personnel that have been trained to install, adjust,
service, maintenance or repair (hereinafter, “service”)
the equipment specified in this manual should service the
equipment.
This equipment is not intended for use by persons
(including children) with reduced physical, sensory or
mental capacities, or lack of experience and knowledge,
unless they have been given supervision or instruction
concerning use of the appliance by a person responsible
for their safety.
Children should be supervised to ensure that they do not
play with the equipment.
The manufacturer will not be responsible for any injury
or property damage arising from improper supervision,
service or service procedures. If you service this unit, you
assume responsibility for any injury or property damage
which may result. In addition, in jurisdictions that require
one or more licenses to service the equipment specified in
this manual, only licensed personnel should service the
equipment. Improper supervision, installation, adjustment,
servicing, maintenance or repair of the equipment specified
in this manual, or attempting to install, adjust, service
or repair the equipment specified in this manual without
proper supervision or training may result in product
damage, property damage, personal injury or death.
WARNING
WARNING
This furnace may be paired with a cooling unit that uses R-32
refrigerant. If the cooling unit paired with this furnace does
not use R-32, the R-32 function in the furnace control board
needs to be turned off. please see the electrical and the R-32
sections for more details.
Refrigerant systems other than 410A or R32 may require
an additional mitigation control board. Refer to the
installation manual of the indoor evaporator coil to
determine installation requirements for that supplier’s
refrigerant detection system.

2
TABLE OF CONTENTS
Safety Considerations .................................................2
Electrostatic Discharge (ESD) Precautions ............3
To the Installer ..............................................................4
Product Application ......................................................4
Location Requirements & Considerations ................6
Clearances and Accessibility .....................................7
Combustion & Ventilation Requirements ...................8
Installation Positions ...................................................8
Horizontal Applications & Considerations .............10
Materials - Installations in the U.S.A. .....................11
Materials - Installations in Canada ......................... 11
Pip Installation ............................................................. 11
Combustion Air Pipe Connection ..............................13
Vent/Intake Terminations for Installation of
multiple direct vent furnaces ..................................17
Condensate Drain Lines & Drain Trap .....................17
Electrical Connections ..............................................22
R-32 Information ...........................................................26
Gas Supply and Piping ..................................................26
High Altitude Installation ..........................................27
Circulating air & filters .............................................30
Startup Procedure & Adjustment .............................33
Gas Supply Pressure Measurement .........................35
Operational Checks .....................................................37
Safety Circuit Description ........................................37
Maintenance ..................................................................38
Filters .............................................................................38
Before Leaving an Installation .................................39
Repair and Replacement Parts ..................................39
Status codes ..................................................................40
Troubleshooting .........................................................41
Airflow Tables - *D9S96 ..............................................44
Airflow Tables - *R9S92 ..............................................46
Airflow Tables - *R9S96 ..............................................48
Wiring Diagram .............................................................50
Special Instructions for Products Installed
in the State of Massachusetts ..................................51
Start-Up Checklist .......................................................52
SAFETY CONSIDERATIONS
Adhere to the following warnings and cautions when
installing, adjusting, altering, servicing, or operating the
furnace. To ensure proper installation and operation,
thoroughly read this manual for specics pertaining to the
installation and application of this product.
This furnace is manufactured for use with natural gas. It
may be eld converted to operate on L.P. gas by using the
appropriate L.P. conversion kit listed in the PROPANE
GAS/HIGH ALTITUDE INSTALLATIONS section of this
manual
Install this furnace only in a location and position
as specied in LOCATION REQUIREMENTS &
CONSIDERATIONS section and INSTALLATION
POSITIONS section of this manual.
Provide adequate combustion and ventilation air to the
furnace as specied in COMBUSTION & VENTILATION
AIR REQUIREMENTS section of this manual.
Combustion products must be discharged to the outdoors.
Connect this furnace to an approved vent system only, as
specied in VENT/FLUE PIPE & COMBUSTION AIR PIPE
section of this manual.
Never test for gas leaks with an open ame. Use a
commercially available soap solution made specically for
the detection of leaks to check all connections, as specied
in GAS SUPPLY AND PIPING section of this manual.
Always install a furnace to operate within the furnace’s
intended temperature-rise range with a duct system which
has external static pressure within the allowable range, as
specied on the furnace rating plate and OPERATIONAL
CHECKS section of these instructions.
When a furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace.
A gas-red furnace for installation in a residential
garage must be installed as specied in the LOCATION
REQUIREMENTS AND CONSIDERATIONS section of
this manual.
This furnace may be used as a construction site heater
only if certain conditions are met. These conditions are
listed in the PRODUCT APPLICATION section of this
manual.
CAUTION
FROZEN AND BURST WATER PIPE HAZARD
Failure to protect against the risk of freezing may result
in property damage. Special precautions MUST be made if
installing furnace in an area which may drop below freezing.
This can cause improper operation or damage to equipment.
If the furnace environment has the potential of freezing,
the drain trap and drain line must be protected. The use of
accessory drain trap heaters, electric heat tape and/or RV
antifreeze is recommended for these installations.
WARNING
To prevent personal injury or death due to improper
installation, adjustment, alteration, service, or maintenance,
refer to this manual. For additional assistance or
information, consult a qualified installer, servicer agency
or the gas supplier.

3
Failure to follow the safety warnings exactly could
result in serious injury, death or property damage.
Never test for gas leaks with an open flame.
Use a commercially available soap solution made
specifically for the detection of leaks to check all
connections. A fire or explosion may result causing
property damage, personal injury or loss of life.
WARNING
FIRE OR EXPLOSION HAZARD
AVERTISSEMENT
RISQUE D’INCENDIE OU D’EXPLOSION
Si les consignes de sécurité ne sont pas suivies à la lettre,
cela peut entraîner la mort, de graves blessures ou des
dommages matériels.
Ne jamais vérifier la présence de fuites de gaz au moyen
d’une flamme nue. Vérifier tous les raccords en utilisant
une solution savonneuse commerciale conçue spécialement
pour la détection de fuites. Un incendie ou une explosion
risque de se produire, ce qui peut entraîner la mort, des
blessures ou des dommages matériels.
Shipping Inspection
All units are securely packed in shipping containers
tested according to International Safe Transit Association
specications. The carton must be checked upon arrival
for external damage. If damage is found, a request for
inspection by carrier’s agent must be made in writing
immediately.
The furnace must be carefully inspected on arrival for
damage and bolts or screws which may have come loose
in transit. In the event of damage the consignee should:
1. Make a notation on delivery receipt of any visible
damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. With concealed damage, carrier must be notied as
soon as possible - preferably within ve days.
4. File the claim with the following support documents
within a nine month statute of limitations.
• Original or certied copy of the Bill of Lading, or
indemnity bond.
• Original paid freight bill or indemnity in lieu
thereof.
• Original or certied copy of the invoice, showing
trade and other discounts or reductions.
• Copy of the inspection report issued by carrier’s
representative at the time damage is reported to
carrier.
The carrier is responsible for making prompt inspection of
damage and for a thorough investigation of each claim.
The distributor or manufacturer will not accept claims from
dealers for transportation damage.
WARNING
Heating unit should not be utilized without reasonable
routine, inspection, maintenance and supervision. If the
building in which any such device is routinely inspected,
maintained and monitored. In the event that the building may
be exposed to freezing temperatures and will be vacant,
all water-bearing pipes should be drained. The building
should be properly winterized and the water source closed.
In the event that the building may be exposed to freezing
temperatures and will be vacant, any hydronic coil units
should be drained as well and, in such case, alternative heat
sources should be utilized.
WARNING
If the information in these instructions is not followed
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
– Do not store or use gasoline or other flammable vapors
and liquid in the vicinity of this or any other appliance.
– What to do if you smell gas:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions. If you can
not reach your gas supplier, call the fire department.
– Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING
To prevent possible property damage, personal injury or
death due to electrical shock, the furnace must be located
to protect the electrical components from water.
Drain trap must be primed at time of installation. Trap is
internally partitioned; add water to both inlet ports until
water appears at both sides of the outlet opening. Failure
to prime trap at time of installation may have a negative
eect on combustion quality and pressure switch action.

4
NOTE: This unit should be installed in a
manner so that it is not accessible to the
public.
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS
WARNING
Should overheating occur or the gas supply fail to shut
off, turn off the manual gas shutoff valve external to the
furnace before turning off the electrical supply.
WARNING
Possible property damage, personal injury or death due to
fire, explosion, smoke, soot, condensation, electrical shock,
or carbon monoxide may result from improper installation,
repair operation, or maintenance of this product.
NOTE: Discharge your body’s static electricity
before touching unit. An electrostatic discharge
can adversely affect electrical components.
Use the following precautions during furnace installation
and servicing to protect the integrated control module
from damage. By putting the furnace, the control, and the
person at the same electrostatic potential, these steps
will help avoid exposing the integrated control module to
electrostatic discharge. This procedure is applicable to both
installed and non-installed (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch
the integrated control module or any wire connected
to the control prior to discharging your body’s
electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of
the furnaces near the control. Any tools held in a
person’s hand during grounding will be discharged.
3. Service integrated control module or connecting
wiring following the discharge process in step 2.
Use caution not to recharge your body with static
electricity; (i.e., do not move or shue your feet, do
not touch ungrounded objects, etc.). If you come in
contact with an ungrounded object, repeat step 2
before touching control or wires.
4. Discharge your body to ground before removing a
new control from its container. Follow steps 1 through
3 if installing the control on a furnace. Return any old
or new controls to their containers before touching
any ungrounded object.
Advertencia especial para la instalación de calentadores ó
manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
El monóxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
Las emisiones de monóxido de carbono pueden circular a través
del aparato cuando se opera en cualquier modo.
RISQUE D'EMPOISONNEMENT AU MONOXYDE DE CARBONE
Le monoxyde de
des
carbone peut causer des maladies graves telles que
dommages permanents au cerveau et meme la mort.
Cette ventilation est nécessaire pour éviter le danger d'intoxication
au CO pouvant survenir si un appareil produisant du monoxyde
de carbone continue de fonctionner au sein de la zone confinée.
CO can cause serious illness including permanent brain
damage or death.

5
TO THE INSTALLER
Before installing this unit, please read this manual
thoroughly to familiarize yourself with specic items which
must be adhered to, including but not limited to: unit
maximum external static pressure, gas pressures, BTU
input rating, proper electrical connections, circulating air
temperature rise, minimum or maximum CFM, and motor
speed connections.
PRODUCT APPLICATION
This furnace is primarily designed for residential home-
heating applications. It is not designed or certied for use in
mobile homes, trailers or recreational vehicles. Neither is it
designed or certied for outdoor applications. The furnace
must be installed indoors (i.e., attic space, crawl space, or
garage area provided the garage area is enclosed with an
operating door).
This furnace can be used in the following non-industrial
commercial applications:
Schools, Oce buildings, Churches, Retail stores,
Nursing homes, Hotels/motels, Common or oce areas
In such applications, the furnace must be installed with the
following stipulations:
• It must be installed per the installation instructions
provided and per local and national codes.
• It must be installed indoors in a building constructed
on site.
• It must be part of a ducted system and not used in a
free air delivery application.
• It must not be used as a “make-up” air unit.
• It must be installed as a two-pipe system for
combustion air.
• All other warranty exclusions and restrictions apply
This furnace is an ETL dual-certied appliance and
is appropriate for use with natural or propane gas
(NOTE: If using propane, a propane conversion kit is
required).
Dual certication means that the combustion air inlet pipe
is optional and the furnace can be vented as a:
Non-direct vent (single pipe) central forced air furnace in
which combustion air is taken from the installation area or
from air ducted from the outside or,
Direct vent (dual pipe) central forced air furnace in which
all combustion air supplied directly to the furnace burners
through a special air intake system outlined in these
instructions.
WARNING
To prevent property damage, personal injury, or death due to
fire, do not install this furnace in a mobile home, trailer, or
recreational vehicle.
This furnace may be used as a construction site heater
ONLY if all of the following conditions are met:
• The vent system is permanently installed per these
installation instructions.
• A room thermostat is used to control the furnace.
Fixed jumpers that provide continuous heating
CANNOT be used and can cause long term
equipment damage. Bimetal thermostats, or any
thermostat aected by vibration, must not be used
during construction.
• Return air ducts are provided and sealed to the
furnace.
• A return air temperature range between 60ºF (16ºC)
and 80ºF (27ºC) is maintained.
• MERV 11 air lter(s) are installed in the system
and inspected daily and replaced as needed during
construction and upon completion of construction.
• The input rate and temperature rise are set per the
furnace rating plate.
• The furnace must be installed as a two-pipe system,
using 100% outside air for combustion during
construction.
• The furnace heat exchanger, components, duct
system, air lters and evaporator coils are thoroughly
cleaned following nal construction clean up by a
qualied person.
• All furnace operating conditions (including ignition,
input rate, temperature rise and venting) are veried
according to these installation instructions.
• Furnace doors must be in place on the furnace while
the furnace is operating in any mode.
• Damage or repairs due to failure to comply with
these requirements are not covered under the
warranty.
NOTE: The Commonwealth of Massachusetts
requires that the following additional
requirements must also be met:
• Gas furnaces must be installed by a licensed
plumber or gas tter.
• A T-handle gas cock must be used.
• If the unit is to be installed in an attic, the
passageway to and the service area around the unit
must have ooring.
To ensure proper furnace operation, install, operate and
maintain the furnace in accordance with these installation
and operation instructions, all local building codes and
ordinances. In their absence, follow the latest edition of the
National Fuel Gas Code (NFPA 54/ANSI Z223.1), and/or
CAN/CSA B149.1-15 Installation Codes, local plumbing or
wastewater codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1) can be obtained from any of the following:
American National Standards Institute
23 West 43rd Street, 4th Floor
New York, NY 10036

6
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley
Independence, OH 441311
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE Guide” or “Manual
J-Load Calculations” published by the Air Conditioning
Contractors of America.
A copy of the CAN/CSA B149.1-15 Installation Codes can
also be obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W 1R3
LOCATION REQUIREMENTS &
CONSIDERATIONS
Follow the instructions listed below and the guidelines
provided in the Combustion and Ventilation Air
Requirements section when selecting a furnace location.
WARNING
To prevent possible equipment damage, property damage,
personal injury, or death, the following bullet points must
be observed when installing this unit.
WARNING
Possible property damage, personal injury or death due to
fire, explosion, smoke, soot, condensation, electrical shock,
or carbon monoxide may result from improper installation,
repair operation, or maintenance of this product.
• Centrally locate the furnace with respect to the
proposed or existing air distribution system.
• Ensure the temperature of the return air entering the
furnace is between 55°F and 100°F when the furnace
is heating.
• Provide provisions for venting combustion products
outdoors through a proper venting system. Special
consideration should be given to vent/ue pipe
routing and combustion air intake pipe when
applicable. Refer to Vent/Flue Pipe and Combustion
Air Pipe -Termination Locations for appropriate
termination locations and to determine if the
piping system from furnace to termination can be
accomplished within the guidelines given. NOTE:
The length of ue and/or combustion air piping can
be a limiting factor in the location of the furnace.
• Locate the furnace so condensate ows downwards
to the drain. Do not locate the furnace or its
condensate drainage system in any area subject to
below freezing temperatures without proper freeze
protection.
• Ensure adequate combustion air is available for
the furnace. Improper or insucient combustion air
can expose building occupants to gas combustion
products that could include carbon monoxide. Refer
to Combustion and Ventilation Air Requirements.
• Set the furnace on a level oor to enable proper
condensate drainage. If the oor becomes wet or
damp at times, place the furnace above the oor
on a concrete base sized approximately 1-1/2” larger
than the base of the furnace. Refer to the Horizontal
Applications and Considerations for leveling of
horizontal furnaces.
• Ensure upow or horizontal furnaces are not installed
directly on carpeting, or any other combustible
material. The only combustible material allowed is
wood.
• A special accessory sub-base must be used for
upright counterow unit installations over any
combustible material (including wood). Refer to sub-
base instructions for installation details. (NOTE: A
sub-base will not be required if an air conditioning
coil is located beneath the furnace between the
supply air opening and the combustible oor.
• Exposure to contaminated combustion air will result
in safety and performance-related problems. Do
not install the furnace where the combustion air is
exposed to the following substances:
permanent wave solutions
chlorinated waxes or cleaners
chlorine-based
carbon tetrachloride
water softening chemicals
swimming pool chemicals
deicing salts or chemicals
halogen type refrigerants
printing inks
cleaning solutions (such as perchloroethylene)
paint removers
varnishes
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
masonry acid washing materials
• Enclose a non-direct vent furnace if it is installed
near an area frequently contaminated by any of
the above substances. This protects the non-direct
vent furnace from airborne contaminants. To ensure
that the enclosed non-direct vent furnace has an
adequate supply of combustion air, provide air from
a nearby uncontaminated room or from outdoors.
Refer to the Combustion and Ventilation Air
Requirements for details.

7
• If the furnace is used in connection with a cooling
coil unit, install the furnace upstream or in parallel
with the cooling coil unit. Premature heat exchanger
failure will result if the cooling unit is placed ahead of
the furnace.
• For vertical (upow or downow) applications, the
minimum cooling coil width shall not be less than
furnace width minus 1”. Additionally, a coil installed
above an upow furnace or under a counterow
furnace may be the same width as the furnace or
may be one size larger than the furnace. Example:
a “C” width coil may be installed with a “B” width
furnace.
• For upow applications, the front of the coil and
furnace must face the same direction.
• If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition
source are located not less than 18 inches (457 mm)
above the oor. Protect the furnace from physical
damage by vehicles.
• If the furnace is installed horizontally, ensure the
access doors are not on the “up/top” or “down/
bottom” side of the furnace.
• Do not connect this furnace to a chimney ue that
serves a separate appliance designed to burn solid
fuel.
• On Counterow Installations, the air conditioning coil
must be downstream on the supply (positive) side of
the furnace heat exchanger.
• Counterow Installation over a noncombustible oor.
Before setting the furnace over the plenum opening,
ensure the surface around the opening is smooth
and level. A tight seal should be made between the
furnace base and oor by using a silicone rubber
caulking compound or cement grout.
• Counterow Installation over a combustible oor.
If installation over a combustible oor becomes
necessary, use an accessory sub-base (see
Specication Sheet applicable for your model for
details.) A special accessory sub-base must be used
for upright counterow unit installations over any
combustible material including wood. Refer to sub-
base instructions for installation details. Follow the
instructions with the sub-base for proper installation.
Do not install the furnace directly on carpeting, tile, or
other combustible material other than wood ooring.
(NOTE: The sub-base will not be required if an air
conditioning coil is installed between the supply air
opening on the furnace and the oor.)
POSITION*
SIDES REAR FRONT
BOTTOM
FLUE TOP
Upflow 0" 0" 3" C 0" 1"
Horizontal 6" 0" 3" C 0" 6"
*R9S96 & *R9S92 MINIMUM CLEARANCES TO
COMBUSTIBLE MATERIALS (INCHES)
C= If placed on combustible oor, oor MUST be wood only.
POSITION*
SIDES REAR FRONT
BOTTOM
FLUE TOP
Upflow 0" 0" 3" NC 0" 1"
Horizontal 6" 0" 3" C 0" 6"
*D9S96 MINIMUM CLEARANCES TO COMBUSTIBLE
MATERIALS (INCHES)
C= If placed on combustible oor, oor MUST be wood only.
NC= For installation on non-combustible oor only. A combustible subbase
must be used for installations on combustible ooring.
TOP
BOTTOM
SIDE SIDE SIDE
TOP
BOTTOM
Upflow Counterflow Horizontal
Figure 1
CLEARANCES AND ACCESSIBILITY
NOTES:
• For servicing or cleaning, a 24” front clearance is
required.
• Unit connections (electrical, ue and drain) may
necessitate greater clearances than the minimum
clearances listed above.
• Clearance in accordance with local installation
codes, the requirements of the gas supplier and the
manufacturer’s installation instructions.
• Dégaugement conforme aux codes d’installation
locaux, aux exigences du fournisseur de gaz et aux
instructions d’installation du fabricant.
• In all cases, accessibility clearance must take
precedence over clearances from the enclosure
where accessibility clearances are greater.
Installations must adhere to the clearances to combustible
materials to which this furnace has been design certied.
The minimum clearance information for this furnace is
provided on the unit’s clearance label. These clearances
must be permanently maintained. Clearances must also
accommodate an installation’s gas, electrical, and drain
trap and drain line connections. If the alternate combustion
air intake or vent/ue connections are used additional
clearance must be provided to accommodate these
connections. Refer to Vent/Flue Pipe and Combustion Air
Pipe for details.
NOTE: In addition to the required clearances to
combustible materials, a minimum of 24 inches
service clearance must be available in front of
the unit.

8
A furnace installed in a conned space (i.e., a closet or
utility room) must have two ventilation openings with a
total minimum free area of 0.25 square inches per 1,000
BTU/hr of furnace input rating. Refer to Specication
Sheet applicable to your model for minimum clearances to
combustible surfaces. One of the ventilation openings must
be within 12 inches of the top; the other opening must be
within 12 inches of the bottom of the conned space. In a
typical construction, the clearance between the door and
door frame is usually adequate to satisfy this ventilation
requirement.
Existing Furnace Removal
NOTE: When an existing furnace is removed from
a venting system serving other appliances, the
venting system may be too large to properly vent
the remaining attached appliances.
The following vent testing procedure is repro duced from the
American National Standard/National Standard of Canada
for Gas-Fired Central Furnaces ANSI Z21.47, CSA-2.3
latest edition Section 1.23.1.
Thermostat Location
WARNING
To avoid property damage, personal injury or death,
sufficient fresh air for proper combustion and ventilation
of flue gas must be supplied. Most homes require outside air
be supplied into the furnace area.
The thermostat should be placed approximately ve feet
from the oor on a vibration-free, inside wall in an area
having good air circulation. Do not install the thermostat
where it may be inuenced by any of the following:
• Drafts, or dead spots behind doors, in corners, or
under cabinets.
• Hot or cold air from registers.
• Radiant heat from the sun.
• Light xtures or other appliances.
• Radiant heat from a replace.
• Concealed hot or cold water pipes, or chimneys.
• Unconditioned areas behind the thermostat, such as
an outside wall. Consult the instructions packaged
with the thermostat for mounting instructions and
further precautions.
COMBUSTION & VENTILATION
REQUIREMENTS
Improved construction and additional insulation in buildings
have reduced heat loss by reducing air inltration and
escape around doors and windows. These changes have
helped in reducing heating/cooling costs but have created
a problem supplying combustion and ventilation air for
gas red and other fuel burning appliances. Appliances
that pull air out of the house (clothes dryers, exhaust
fans, replaces, etc.) increase the problem by starving
appliances for air.
House depressurization can cause back drafting or
improper combustion of gas-red appliances, thereby
exposing building occupants to gas combustion products
that could include carbon monoxide.
If this furnace is to be installed in the same space with
other gas appliances, such as a water heater, ensure there
is an adequate supply of combustion and ventilation air
for the other appliances. Refer to the latest edition of the
National Fuel Gas Code NFPA 54/ANSI Z223.1 or CAN/
CSA B1491-15 Installation Codes or applicable provisions
of the local building codes for determining the combustion
air requirements for the appliances.
Most homes will require outside air be supplied to the
furnace area by means of ventilation grilles or ducts
connecting directly to the outdoors or spaces open to the
outdoors such as attics or crawl spaces.
INSTALLATION POSITIONS
This furnace may be installed in an upright position or
horizontal on either the left or right side panel. Do not
install this furnace on its back. For upright upow furnaces,
return air ductwork may be attached to the side panel(s)
and/or base pan. For upright counterow furnaces, return
air ductwork must be attached to the top end of the blower
compartment. For any horizontally installed furnaces, return
ductwork must be attached to the blower compartment end
of the furnace. NOTE: Ductwork must never be attached
to the back of the furnace. Contact your distributor for
proper airow requirements and number of required
ductwork connections. Refer to “Recommended Installation
Positions” gure for appropriate installation positions,
ductwork connections, and resulting airow arrangements.
Figure 2A
Figure 2B

9
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning
or death.
The following steps shall be followed with each appliance
connected to the venting system placed in operation, while
any other appliances connected to the venting system are
not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required by the National Fuel
Gas Code, ANSI Z223.1 or the Natural Gas and
Propane Installation Code, CSA B149.1-15 and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they shall operate at maximum speed.
Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously.
7. Test for spillage from draft hood appliances at the
draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the
above tests, the venting system must be corrected
in accordance with the National Fuel Gas Code ANSI
Z223.1/NFPA 54 and/or National Gas and Propane
Installation Code CSA B149.1-15.
9. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas
burning appliance to their previous conditions of use.
AVERTISSEMENT
RISQUE D’INTOXICATION AU MONOXYDE DE CARBONE
Si les étapes décrites ci-dessous ne sont pas suivies pour
chacun des appareils raccordés au système de ventilation
au moment de sa mise en marche, cela peut entraîner une
intoxication au monoxyde de carbone ou la mort.
Les étapes suivantes doivent être suivies pour chacun des
appareils raccordés au système de ventilation au moment
de sa mise en marche, alors que tous les autres appareils
raccordés au système de ventilation ne sont pas en marche:
1. Sceller toutes les ouvertures inutilisées du système
de ventilation.
2. Inspecter le système de ventilation afin de vérifier si
la taille et l’inclinaison par rapport à l’horizontale
sont conformes aux exigences du National Fuel Gas
Code, ANSI Z223.1/NFPA 54 ou du Code d’installation
du gaz naturel et du propane, CSA B149.1 et à ces
instructions. Vérifier qu’il n’y a pas d’obstruction
ou de restriction, de fuite, de corrosion et d’autres
problèmes qui pourraient entraîner une situation
dangereuse.
3. Si possible, fermer toutes les portes et fenêtres du
bâtiment ainsi que toutes les portes séparant l’endroit
où se trouvent les appareils raccordés au système de
ventilation et les autres zones du bâtiment.
4. Fermer le registre des foyers.
5. Mettre les sécheuses en marche ainsi que tous les
autres appareils qui ne sont pas raccordés au système
de ventilation. Mettre en marche tous les ventilateurs
de tirage, comme celui des hottes de cuisine et des
salles de bains, et les régler à la puissance maximale.
Ne pas mettre en marche les ventilateurs d’été.
6. Suivre les instructions d’allumage. Mettre en marche
l’appareil soumis à l’inspection. Régler le thermostat
de manière à ce que l’appareil fonctionne en continu.
7. Vérifier la présence de fuite au niveau de l’ouverture
du coupe-tirage des appareils qui en sont dotés après
5 minutes de fonctionnement du brûleur principal.
Utiliser la flamme d’une allumette ou d’une bougie.
8. Si un problème de ventilation est observé pendant l’un
des essais décrits ci-dessus, des correctifs doivent
être apportés au système de ventilation conformément
au National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou)
au Code d’installation du gaz naturel et du propane,
CSA B149.1.
9. Une fois qu’il a été déterminé que chaque appareil
raccordé au système de ventilation fonctionne
correctement au moyen des essais décrits ci-dessus,
les portes, les fenêtres, les ventilateurs, les
registres de foyer et tous les autres appareils de
combustion alimentés au gaz doivent être remis dans
leur état initial.

10
Figure 2C
Figure 2D
HORIZONTAL APPLICATIONS &
CONSIDERATIONS
2" 2" 3/8"
ANGLE
IRON
(3
PLACES
)
X X
Figure 3
When installing a furnace horizontally, additional
consideration must be given to the following:
Furnace Suspension
If suspending the furnace from rafters or joists, use 3/8”
threaded rod and 2”x2”x1/8” angle iron as shown in the
following diagram. The length of rod will depend on the
application and the clearances necessary.
If the furnace is installed in a crawl space it must be
suspended from the oor joist or supported by a concrete
pad. Never install the furnace on the ground or allow it to
be exposed to water.
Front Cover Pressure Switch Tube Location
When a furnace is installed horizontally with left side down,
the front cover pressure switch tube must be re-located to
the lower port of the collector box cover.
1. Remove tube from front cover pressure switch and
collector box cover.
2. Remove rubber plug from bottom collector box port
and install on top collector box port.
3. Locate 24” x 1/4” tube in bag assembly.
4. Install one end on front cover pressure switch.
5. Route tube to lower port on collector box cover and
cut o excess tubing.
Drain Trap and Lines
In horizontal applications the condensate drain trap is
secured to the furnace side panel, suspending it below the
furnace. A minimum clearance of 5.5” below the furnace
must be provided for the drain trap. Additionally, the
appropriate downward piping slope must be maintained
from the drain trap to the drain location. Refer to
Condensate Drain Trap and Lines for further details. If the
drain trap and drain line will be exposed to temperatures
near or below freezing, adequate measures must be taken
to prevent condensate from freezing.
Leveling
Leveling ensures proper condensate drainage from
the heat exchanger. For proper ue pipe drainage, the
furnace must be level lengthwise from end to end. The
furnace should have a slight tilt from back to front with the
access doors downhill from the back panel approximately
1/2 to 3/4 inches. The slight tilt allows the heat exchanger
condensate, generated in the recuperator coil, to ow
forward to the recuperator coil front cover.
Alternate Electrical and Gas Line Connections
This furnace has provisions allowing for electrical and gas
line connections through either side panel. In horizontal
applications the connections can be made either through
the “top” or “bottom” of the furnace.
Drain Pan
A drain pan must be provided if the furnace is installed
above a conditioned area. The drain pan must cover the
entire area under the furnace (and air conditioning coil if
applicable).
Freeze Protection
If the drain line is routed through an area which may see
temperatures near or below freezing, precautions must be
taken to prevent condensate from freezing within the drain
line.
VENT PIPE & COMBUSTION AIR PIPE

11
WARNING
Upon completion of the furnace installation, carefully
inspect the entire flue system both inside and outside of the
furnace to assure it is properly sealed. Leaks in the flue
system can result in serious personal injury or death due to
exposure to flue products, including carbon monoxide.
WARNING
Failure to follow these instructions can result in bodily
injury or death. Carefully read and follow all instructions
given in this section.
This manual will refer to the pipe that discharges products
of combustion to the outdoors as the “vent” pipe or
“ue” pipe. The pipe that supplies air for combustion
to the furnace will be referred to as the “intake” pipe or
“combustion air” pipe.
This furnace is dual certied and may be installed as a non-
direct vent (single pipe) or direct vent (dual pipe) appliance.
MATERIALS – INSTALLATIONS IN THE
U.S.A.
PVC, CPVC, or ABS pipe & ttings are typically used as
venting and intake pipe materials. All 90° elbows must
be medium or long radius types. A medium radius elbow
should measure ~3-1/16” minimum from the plane of
one opening to the center line of the other opening for 2”
diameter pipe, and ~4-9/16” minimum for 3” pipe.
In addition to these materials, Innoue® by Centrotherm
Eco Systems is also an approved vent and combustion
air materials for installations in the U.S.A. Manufacturers
Installation instructions for these products must be
followed. These products have specic instructions for
installing, joining and terminating. Do not mix materials
or components of one manufacturer with materials or
components of another manufacturer. Refer to the following
chart for plastic pipe & ttings specications.
MATERIALS – INSTALLATIONS IN CANADA
All installations in Canada must conform to the
requirements of CAN/CSA B149.1-15 code. All vent
components, including primer and cement, must be listed
to ULC S636. The certied pipe and ttings should be
clearly marked with the ULC standard “S636”. The primer
and cement used must be of the same manufacturer as
the vent system. For Royal Pipe System 636; use GVS-
65 Primer (Purple) and GVS-65 PVC Solvent Cement.
For IPEX System 636, use PVC/CPVC Primer, Purple
or clear. Use PVC Solvent cement (Gray). For Canadian
installations, ABS may be used as a combustion air pipe
only. ABS is not an approved vent material in Canada.
If ABS is used as a combustion air pipe, it must be CSA
certied. Always follow the manufacturer’s instructions
in the use of primer and cement. Do not use primer and
cement around potential sources of ignition. Do not use
primer or cement beyond its expiration date.
PVC
ASTM
STANDARD
SCHEDULE 40 PIPE D1785
SDR 21 or 26 PIPE D2241
SYTSTEM
1738
®
(IPEX)
D1784, UL 1738
SCHEDULE
40 FITTINGS
D2466
SYTSTEM
1738
®
FITTINGS
D1784, UL 1738
ABS
SCHEDULE 40 PIPE D1527
FITTINGS D2468
CPVC
SCHEDULE 40 PIPE F441
SDR
21
or
26 PIPE F442
FITTINGS F438
POLYPROPYLENE
INNOFLUE
®
(CENTROTHERM)
UL
1738
PRIMER & SOLVENT CEMENT
PVC
PRIMER F656
CPVC PRIMER F656
PVC SOLVENT CEMENT
D2564
CPVC
SOLVENT
CEMENT
F493
ABS SOLVENT CEMENT D2235
ABS/PVC/CPVC
ALL
PURPOSE CEMENT (FOR PIPE & FITTINGS OF
THE SAME MATERIAL)
D2564, D2235, F493
TRANSITION CEMENT
FOR ABS TO PVC or CPVC D3188
INSTALLATIONS IN CANADA
PVC
&
CPVC
PIPE & FITTINGS
PVC & CPVC SOLVENT CEMENT
TRANSITION CEMENT
INNOFLUE
®
(CENTROTHERM)
POLYPRO
®
(DURAVENT)
SYSTEM 636
®
(IPEX)
VENTING
MATERIAL
REQUIREMENTS
ULC
S636
PIPE INSTALLATION
This furnace is manufactured with 2” CPVC vent & intake
couplings. Use transition cement to connect PVC or ABS
pipe to these ttings. For furnaces requiring installation of
3” pipe, the transition from 2” to 3” should be done as close
to the furnace as possible, and only when the piping is
sloped enough to prevent condensation from collecting.
This furnace must not be connected to Type B, BW, or
L vent or vent connector, and must not be vented into
masonry chimney. A masonry chimney may be used as
a chase or passageway for approved venting materials
providing the masonry chimney is not also being used to
vent products of combustion. Never common vent this
appliance with another appliance. Never use a vent which

12
is used by a solid fuel appliance.
Piping may run vertically or horizontally and must be
adequately supported to prevent strain on joints, sagging,
separation, and detachment from the furnace. Horizontal
runs of piping must be supported every three to ve feet.
Condensation within the furnace secondary heat exchanger
and in the vent pipe is a normal occurrence. Vent pipe
must be installed to maintain a minimum 1/4 inch per foot
downward slope toward the furnace to return condensate to
the furnace’s drain system. Condensation may also occur
in the intake pipe. This commonly takes place during the
summer months when humid air enters an intake pipe that
runs through a cool basement or other conditioned space.
Precautions should be taken to prevent condensate from
freezing inside the ue/vent pipe, combustion air intake
pipe and/or at the pipe terminations. All ue/vent and/
or combustion air piping exposed to temperatures below
35°F for extended periods of time should be insulated with
1/2” thick closed cell foam. All vent/ue piping exposed
to outdoors in excess of the terminations permitted as
described in the provided installation manual should be
insulated with 1/2” thick closed cell foam. Inspect piping
for leaks prior to installing insulation. If the combustion air
intake or ue vent pipe is to be installed above a nished
ceiling or other area where dripping of condensate will
be objectionable, insulating the combustion air pipe may
be necessary. Use 1/2” thick closed cell foam insulation
where required. Refer to vent & intake options for using the
RF000142 kit and managing condensation.
PREFERRED
Figure 4
TRANSITION NO LESS
THAN 45 DEGREES TO
HORIZONTAL PLANE TO
AVOID CREATING A WATER
TRAP IN VENT PIPING.
ACCEPTABLE
Figure 5
NO TRANSITION ON
HORIZONTAL PLANE,
THIS CREATES A
WATER TRAP AND
RESTRICTS FLUE
GASES
Figure 6
WARNING
To avoid bodily injury, fire or explosion, solvent cements
must be kept away from all ignition sources (i.e., sparks, open
flames, and excessive heat) as they are combustible liquids.
Avoid breathing cement vapors or contact with skin and/or
eyes.
Pipe Sizing
Consult tables 4 & 5 to determine what diameter piping is
required for your installation. Lengths shown in the chart
apply to single pipe & two pipe installations. In a two pipe
installation the length shown refers to only one pipe, vent
or intake. Both pipes would normally be equal in length, if
dierent, then the longest pipe must be within the limits of
table 4. It is preferable to up-size from 2” to 2.5” or 3” pipe
if the pipe length & elbow count are near maximum. This
will help avoid nuisance pressure switch opening caused
by prevailing winds & sudden changes in atmospheric
pressure.
MODEL
PIPE
SIZE
1 2 3 4 5 6 7 8
2 75 70 65 60 55 50 45 40
3 114 107 100 93 86 79 72 65
2 45 40 35 30 25 20 15 10
3 168 161 154 147 140 133 126 119
2 35 30 25 20 15 10 5 N/A
3 168 161 154 147 140 133 126 119
2 60 55 50 45 40 35 30 25
3 113 106 99 92 85 78 71 64
2 45 40 35 30 25 20 15 10
3 120 113 106 99 92 85 78 71
2 40 35 30 25 20 15 10 5
3 151 144 137 130 123 116 109 102
2 N/A N/A N/A N/A N/A N/A N/A N/A
3 158 151 144 137 130 123 116 109
2 100 95 90 85 80 75 70 65
3 137 130 123 116 109 102 95 88
2 45 40 35 30 25 20 15 10
3 168 161 154 147 140 133 126 119
2 40 35 30 25 20 15 10 5
3 120 113 106 99 92 85 78 71
2 N/A N/A N/A N/A N/A N/A N/A N/A
3 113 106 99 92 85 78 71 64
2 N/A
N/A N/A N/A N/A N/A N/A N/A
3 110 103 96 89 82 75 68 61
NOTE: FOR INSTALLATIONS AT OR ABOVE 5,000 FEET ALTITUDE, USE 3” PIPE.
R9S960803BN - add 20’ of 2” pipe for upflow position
1) Maximum allowable limits listed on individual lengths for inlet and flue and NOT a
combination
2) Minimum requirement for each vent pipe is five (5) feet in length and one elbow/tee
3) Tee used in the vent/flue termination must be included when determining the number
of elbows in the piping system.
4) 2 1/2" or 3" diameter pipe can be used in place of 2" diameter pipe
Number of Elbows
*R9S960403AN
*R9S961005CN
*R9S961205DN
*R9S960603BN
*R9S960803BN
*R9S960804CN
*R9S960805CN
*D9S960403BN
*D9S960603BN
*D9S960804CN
*D9S961005CN
*D9S961205DN
Table 4

13
MODEL
PIPE
SIZE
1 2 3 4 5 6 7 8
2 75 70 65 60 55 50 45 40
3 114 107 100 93 86 79 72 65
2 55 50 45 40 35 30 25 20
3 127 120 113 106 99 92 85 78
2 30 25 20 15 10 5 N/A N/A
3 72 65 58 51 44 37 30 23
2 30 25 20 15 10 5 N/A N/A
3 72 65 58 51 44 37 30 23
2 40 35 30 25 20 15 10 5
3 72 65 58 51 44 37 30 23
2 60 55 50 45 40 35 30 25
3 168 161 154 147 140 133 126 119
2 30 25 20 15 10 5 N/A N/A
3 113 106 99 92 85 78 71 64
2 N/A N/A N/A N/A N/A N/A N/A N/A
3 65 58 51 44 37 30 23 16
NOTE: FOR INSTALLATION AT OR ABOVE 5,000 FEET ALTITUDE, USE 3” PIPE.
*R9S920803BN - add 10' of 2" pipe for up flow position, add 66' of 3" pipe for up flow
position
*R9S920804CN - add 25' of 2" pipe for up flow position, add 58' of 3" pipe for up flow
position
*R9S920805CN - add 15' of 2" pipe for upflow position, add 58' of 3" pipe for upflow
position
1) Maxim um allowable limits listed on individual lengths for inlet and flue and NOT a
com bination
2) Minim um requirement for each vent pipe is five (5) feet in length and one elbow/tee
3)
Tee used in the vent/flue termination must be included when determining the num ber
of elbows in the piping system.
Number of Elbows
*R9S920403AN
*R9S920603BN
*R9S920803BN
*R9S920804CN
*R9S920805CN
*R9S921004CN
*R9S921005CN
*R9S921205DN
Table 5
1. Maximum allowable limits listed on individual lengths
for inlet and ue and NOT a combination.
2. Minimum requirement for each vent pipe ve (5) feet
in length and one elbow/tee.
3. Tee used in the vent/ue termination must be
included when determining the number of elbows in
the piping system.
4. 2 ½” or 3” diameter pipe can be used in place of 2”
diameter pipe.
5. Increased Clearance Conguration using (2) 45 deg.
Long Sweep elbows should be considered equivalent
to one 90 deg. elbow.
6. One 90° elbow should be secured to the combustion
air intake connection.
Vent Pipe Connection
The vent pipe outlet is sized to accept 2” pipe. Secure vent
pipe directly into the furnace tting with the appropriate
glue. Alternately, a small section of 2” pipe may be glued
in the furnace socket and a rubber coupling installed
to allow removal for future service. Piping should be
routed in a manner to avoid contact with refrigerant lines,
metering devices, condensate drain lines, etc. If necessary,
clearances may be increased by creating an oset using
two 45° elbows (Figure 7).
45 DEGREE
ELBOWS
Increased Clearance Configuration
Figure 7
COMBUSTION AIR PIPE CONNECTION
If the furnace is being installed without a combustion air
pipe, a 90° elbow should be used on the combustion air
intake to guard against blockage.
On up ow / horizontal models, secure the combustion
air intake pipe to the air intake coupling using a rubber
coupling supplied with the furnace. The rubber coupling
may be omitted by inverting the intake coupling and gluing
pipe directly to it. Piping may also be glued to the intake
coupling in its original position by using a plastic coupling.
On counterow units secure the combustion air intake
pipe to the air intake coupling using the rubber coupling
and worm gear hose clamps provided with the unit. The
counterow rubber coupling allows service removal of air
intake piping internal to the furnace blower compartment.
The combustion air intake pipe can also be secured directly
to the counterow unit air intake pipe coupling.
Vent & Intake Pipe Options for Condensate
Management
The RF000142 coupling (Figure 9) can be secured directly
to the furnace intake and/or vent if condensation/rain water
is a concern. If the RF000142 is used on the combustion
air inlet, it must be installed with the arrow pointing up. It
should be noted, the combustion air will actually be moving
in a direction opposite of the arrow on the RF000142
coupling. It must have a eld supplied, trapped drain tube
free-draining to a proper condensate disposal location.
A loop in the drain tube can serve as a trap. The unused
RF000142 drain tting must be capped. A eld supplied
tee installed in the and/or vent pipe is also an acceptable
method of catching condensation. For vertical vent piping,
a PVC wye can be used for catching condensation (see
Figure 8B). Any of these options must have a eld supplied,
trapped drain tube or pipe, free-draining to a proper
condensate disposal location. A loop in the drain tube can
serve as a trap.

14
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a
precaution when removing hole plugs.
Alternate Vent & Intake Pipe Connections
(Upflow/Horizontal models only)
When installing a furnace horizontally with the left side
down, alternate ue and combustion air pipe connections
may be used. This method allows the ue and combustion
air piping to be run vertically through the side of the furnace
(facing up in horizontal left). The alternate vent location
is the 3” hole directly in line with the induced draft blower
outlet.
When using the horizontal alternate vent conguration, you
must use the RF000142 vent drain kit. See Figures 8-11 &
follow steps below.
NOTE: In the horizontal left installation
position, a means of condensate collection must
be provided to keep vent pipe condensate from
entering the draft inducer housing. If the vent
drain elbow is eliminated from the installation,
the RF000142 kit must be used.
Tee Installation in Intake Pipe
Figure 8A
Vent Piping with PVC WYE
Figure 8B
VENT-DRAIN
Figure 9
Insert flange. Cut 2 ½” long.
R 000142
F
Figure 10

15
Figure 11
1. Remove the four screws from the vent pipe ange on
top of the furnace.
2. Remove the internal elbow, vent pipe & gasket.
3. Cut the internal vent pipe 2 1/2” from the ange.
Discard the un-anged section.
4. Remove the 3” plastic plug (in line with the inducer
outlet) and insert it in the space vacated by removal
of the internal vent pipe.
5. Install the RF000142 drain coupling with arrow facing
up, on the draft inducer outlet.
6. Insert the 2 ½” anged section of pipe with gasket
through the 3” hole and connect to RF000142 drain
coupling. Secure it with gear clamp provided.
7. Use the four self-tapping screws removed in step 1 to
secure ange to cabinet.
8. Connect drain hose to the uncapped port on the
RF000142 coupling, refer to page xx, section
entitled “Horizontal Installation with Left Side Down –
Alternate” for drain connection details
When using the alternate venting location, either in a
horizontal left side down installation or a vertical installation
using down – venting, the alternate combustion air opening
can be used. A locating dimple is located on the right
side of the furnace cabinet. The locating dimple is 1-7/8”
measured from the front edge of the cabinet in line with the
knock out.
To use the alternate combustion air location:
1. Remove screws and combustion air ange and
gasket from cabinet.
2. Insert the 3” cabinet plug from the drain bag
assembly in the unused combustion air hole.
3. Drill a pilot hole at the cabinet dimple (size dictated
by knockout tool used).
4. Use a knockout tool to create a 3” diameter hole.
5. Secure the combustion air ange & gasket to the
furnace cabinet using the self-tapping screws
removed in step 1.
WARNING
The rubber elbow is not designed to support a load. When
the rubber elbow is mounted externally to the furnace
cabinet, extreme care must be taken to adequately support
field-supplied vent/flue piping, as damage can result in leaks
causing bodily injury or death due to exposure to flue gases,
including carbon monoxide.
CAUTION
Be sure not to damage internal wiring or other components
when reinstalling coupling and screws.
Vent Pipe
Use alternate vent
& combination
air locations
Combustion Air Pipe
Field Supplied
Drain Tee on Vent Pipe
Condensate trapped
to prevent flue gas from escaping
and routed to field supplied
condensate disposal
1/4” per foot min.
slope to furnace
6’ Max.
Floor
B
a
s
e
m
e
n
t
/
C
r
a
w
l
s
p
a
c
e
DOWN VENTING UPFLOW MODEL FURNACES ONLY
All piping and fittings must be joined per material manufacturers specifications
to prevent separation and flue gas leaks.
Figure 12
Pipe Termination
Products of combustion must always be vented outside. A
vent pipe must never terminate in an attic, crawl space, or
any other part of a dwelling. Follow the vent pipe & intake
pipe termination requirements listed below as well as all
applicable local, State and National codes.
All terminations (vent and/or intake) must be located at
least 12” above ground level or the anticipated snow level.
All vent terminations (non-direct and direct vent) must
terminate at least 3 feet above any forced air inlet located
within 10 feet.
The vent termination of a non-direct vent application must
terminate at least 4 feet below, 4 feet horizontally from, or
1 foot above any door, window, or gravity air inlet into any
building.
The vent termination of a direct vent application must
terminate at least 12” from any opening through which ue
gases may enter a building (door, window, or gravity air
inlet).
The vent termination of vent pipe run vertically through a
roof must terminate at least 12” above the roof line (or the
anticipated snow level) and be at least 12” from any vertical
wall (including any anticipated snow build up).

16
A vent termination shall not terminate over public walkways
or over an area where condensate or vapor could create a
nuisance or hazard or could be detrimental to the operation
of regulators, relief valves, or other equipment.
The combustion air intake termination of a direct vent
application should not terminate in an area which is
frequently dusty or dirty.
Vent & combustion air pipes may terminate vertically
through a roof, or horizontally through an outside wall. The
combustion air intake and vent pipe terminations must
be in the same atmospheric pressure zone. Vertical vent
pipe terminations should be as shown in gure 14. The
penetration of pipes through the roof must be sealed water
tight with proper ashing such as is used with a plastic
plumbing vent.
Horizontal vent pipe terminations should be as shown in
the following gures. To secure the pipe passing through
the wall and prohibit damage to piping connections, a
coupling should be installed on either side of the wall and
solvent cemented to a length of pipe connecting the two
couplings. The length of pipe should be the wall thickness
plus the depth of the socket ttings to be installed on the
inside and outside of the wall. The wall penetration should
be sealed with silicone caulking material.
12"
Non-Direct Vent
Vent/Flue Termination
No Terminations
Above Walkway
12"
min.
4'
min.
Non-Direct Vent
Vent/Flue Termination
Direct Vent
Vent/Flue Termination
<10'
Forced Air
Inlet
Non-Direct Vent
&
Direct Vent
Vent/Flue Terminations
Grade or Highest
Anticipated
Snow Level
3' min.
12" min.
4' min.
12" min.
Vent Termination Clearances
Figure 13
COMBUSTION AIR INTAKE
(OPTIONAL)
*Not required for
single pipe installation
TEE (OPTIONAL)
9
6
”
M
A
X
.
-
3
”
M
I
N
.
R
O
O
F
L
I
N
E
12” MIN
HEIGHT
DIFFERENCE
12” MIN TO ROOF OR
HIGHEST ANTICIPATED
SNOW LEVEL
Figure 14
STRAIGHT
ELBOWS
Figure 15
Horizontal Termination (Single Pipe) Above Highest Anticipated
Snow Level
Figure 16
90º OR 45°
ELBOW
12" MIN. TO GRADE OR
HIGHEST ANTICIPATED
SNOW LEVEL
6” MAX
10”- 24”
4” MIN
Standard Horizontal Terminations (Dual Pipe)
Figure 17

17
90°
ELBOWS
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
3” - 24”
Alternate Horizontal Vent Termination (Dual Pipe)
Figure 18
90°
ELBOWS
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
3”-24” BETWEEN PIPES
Combustion Air Intake may also be snorkeled
to obtain 12” min ground clearance.
Alternate Vent Termination Above Anticipated Snow Level
(Dual Pipe)
Figure 19
Vent & Combustion Air Intake Measurements for
Standard Horizontal Terminations (Dual Pipe)
Center to center = 10” min / 24” max.
Vertical separation: 0” - 24”
Vent termination from wall = 8” min / 12” max.
Combustion air intake from wall = 6” max.
Vent and intake clearance to ground or anticipated snow
level = 12” min.
3” MIN
12” MIN TO GRADE OR HIGHEST
ANTICIPATED SNOW LEVEL
3”MIN
24”MAX
12” M IN SEPA RATION
Termination of Multiple Direct Vent Furnaces
Figure 20
VENT/INTAKE TERMINATIONS FOR
INSTALLATION OF MULTIPLE DIRECT
VENT FURNACES
If more than one direct vent furnace is to be installed
vertically through a common roof top, maintain the same
minimum clearances between the exhaust vent and air
intake terminations of adjacent units as with the exhaust
vent and air intake terminations of a single unit.
If more than one direct vent furnace is to be installed
horizontally through a common side wall, maintain the
clearances as in the Figure 20. Always terminate all
exhaust vent outlets at the same elevation and always
terminate all air intakes at the same elevation.
Vertical Installation
Horizontal Installation
Side Wall Vent Kit
Figure 21
Concentric Vent Termination
Refer to the directions provided with the Concentric Vent
Kit or IO-619 for installation specications.
Side Wall Vent Kit
This kit is to be used with 2” or 3” direct vent systems. The
vent kit must terminate outside the structure and may be
installed with the intake and exhaust pipes located side-
by-side or with one pipe above the other. These kits are
NOT intended for use with single pipe (non-direct vent)
installations. Refer to the directions furnished with the
Side Wall Vent Kit (p/n 0170K00000S or 0170K00001S)
for installation specications.
CONDENSATE DRAIN LINES &
DRAIN TRAP
A condensing gas furnace achieves its high level
of eciency by extracting heat from the products of
combustion to the point where condensation takes place.
The condensate must be collected in the furnace drain trap
and routed to an appropriate drain location in compliance
with local and national codes.
Follow the bullets listed below when installing the drain
system. Refer to the following sections for specic details
concerning furnace drain trap installation and drain hose
hook ups.
• The drain trap supplied with the furnace must be
used.
• The drain trap must be primed at time of installation.

18
the drain to exit the right side. All furnace models installed
horizontally require the trap to be relocated. Many drain
hoses have a built–in grommet which will provide a cabinet
seal when installed. See instructions below for your model
and installation position.
NOTE: Both sides of the drain trap must be primed
prior to initial furnace start up.
Side Cut-Out
12”
3”
Right side shown.
Acceptable
area for
drain hole.
Figure 23
Field Supplied Drain
Drain the furnace and air conditioning coil if applicable,
in compliance with code requirements. In horizontal or
counterow installations, a eld installed rubber coupling
will allow the drain trap to be removed for cleaning. The
drain trap must be primed before initial furnace start up.
When an air conditioning coil drain is connected to the
eld supplied furnace drain, it must be vented. An open
tee must be installed at a height no higher than the bottom
of the furnace collector box to prevent air conditioning
condensate from backing up into the furnace, if the
common drain was blocked.
Upflow Model Installed Vertically
The trap and factory installed hoses remain as shipped.
The furnace drain may exit either the right or left side of the
furnace cabinet. Both sides of the cabinet have two .875”
diameter holes which can be used interchangeably for
drain and low voltage wiring purposes. If a higher drain exit
is needed, a .875” diameter hole may be added in the area
shown in Figure 24. Any unused cabinet opening must be
sealed. Do not allow drain hose to sag or trap water.
Drain Exiting Right Side
1. Locate and Install the 45º pipe / hose drain coupling
from the outside of the cabinet (barbed end goes
in the cabinet) through hole in the right side of the
cabinet and secure with two eld supplied #8 self-
tapping screws (see Figure 24).
2. Locate the long drain hose #3 and cut at line “A” .
3. Install large end of hose #3 to trap outlet and secure
with 1.25” clamp.
• The drain line between furnace and drain location
must meet local and nation codes.
• The drain line between furnace and drain location
must maintain a 1/4 inch per foot downward slope
toward the drain.
• Do not trap the drain line in any other location than at
the drain trap supplied with the furnace.
• If the drain line is routed through an area which
may see temperatures near or below freezing,
precautions must be taken to prevent condensate
from freezing within the drain line.
• If an air conditioning coil is installed with the furnace,
a common drain may be used. An open tee must
be installed in the drain line, near the cooling coil, to
relieve positive air pressure from the coil’s plenum.
This is necessary to prohibit any interference with the
function of the furnace’s drain trap.
NOTE: In vertical installations, air conditioning
coil condensate may drain into the furnace trap
as long as there is a trap between the coil and the
furnace trap and the drain pipe is not terminating
below the water level of the furnace trap.
#
3
#1
#2
#4
#5
#
6
#7
#8
#9
#10
#11
100 Degree
Elbow
Coupling
Figure 22
NOTE: Drain components shown for information purposes only.
For horizontal installation, a Horizontal Drain Kit may be
needed. Refer to the specifications sheet for kit part number.
General Drain Information
All furnace models come with a factory installed drain trap.
For vertical installations, the trap will remain in the factory
position except for a counterow when the installer desires

19
Installer selects right or left side drain
and installs this hose accordingly.
Hose #1
Hose #2
45 degree
barb-pipe
adapter
45 degree
barb-pipe
adapter
Figure 24
4. Install smaller end of hose #3 on 45º elbow and
secure with 1” clamp.
5. Refer to Field Supplied Drain section for instructions
on eld supplied / installed drain on outlet of furnace
trap.
Drain Exiting Left Side
1. Install the 45 degree pipe / hose drain coupling
from the outside of the cabinet (barbed end goes in
the cabinet) through the hole in the left side of the
cabinet and secure with two eld supplied #8 self-
tapping screws (see Figure 24).
2. Locate the long drain hose #3 and cut at “B” line for a
17.5” cabinet; cut at line “C” for a 21” cabinet; do not
cut for a “D” width cabinet.
3. Install large end of hose #3 to trap outlet and secure
with 1.25” clamp.
4. Install smaller end of hose #3 on 45º elbow and
secure with 1” clamp.
5. Refer to Field Supplied Drain section for instructions
on eld supplied / installed drain on outlet of furnace
trap.
Hose #11
Hose #2
Figure 25
Upflow Model Installed Horizontally
with Right Side Down
Minimum 5 1/2” clearance is required for the drain trap
beneath the furnace.
1. Remove the clamps from both ends of the drain
hoses.
2. Remove the two screws holding the drain trap to the
blower deck.
3. Remove the trap and two hoses from the blower
deck
4. Remove the two plugs from the right side of the
cabinet and install them in the blower deck.
5. (Draining the Vent Elbow ) Locate hose #2 (factory
installed) and cut 1” away from the 45 degree bend,
discard the 45 degree section. Insert hose #2 from
outside the cabinet through the cabinet drain hole
nearest the top, secure it to the barbed tting in the
elbow with a red clamp.
6. (Draining the Collector Box) Install the non-grommet
end of hose #11 from outside the cabinet in the
bottom drain hole. Install on collector box and secure
with a silver clamp.
7. Use two silver clamps and secure the hoses to drain
trap. The trap outlet faces the front of the furnace.
Secure the trap to the cabinet using two screws
removed in step 2 by inserting the two screws
through the large set of holes in the top mounting
tabs of the trap into the two pre-drilled holes in the
side of the cabinet.
8. Refer to Field Supplied Drain section for instructions
on eld supplied / installed drain on outlet of furnace
trap.
Upflow Model Installed Horizontally with Left
Side Down
Minimum 5 1/2” clearance is required for the drain trap
beneath the furnace.
*Also see Front Cover Pressure Switch Tube Location on
page 10.
1. Remove the clamps from the two drain tubes on the
trap.
2. Remove the two screws holding the drain trap to the
blower deck.
3. Remove the trap and hoses from the blower deck.

20
Hose #6
Hose #5
Hose #11
Figure 26
4. Remove the two plugs from the left side of the
cabinet and install them in the blower deck.
5. (Draining the Vent Elbow) Locate hose #6.
Measuring from the non-grommet end; cut o and
discard 1 ½” for a “D” width cabinet, 5” for a “C” width
cabinet, 8 ½” for a “B” width cabinet.
6. Remove the rubber plug from vent – drain elbow side
port. Place hose #6 on the vent – drain elbow side
port and secure with a silver clamp .
7. Unused vent-drain elbow drip leg port must be
sealed to prevent ue gases from escaping.
Insert the rubber plug removed in step 6 into the
unused elbow drain port. Inserting a blunt tool
such as a 3/16’’ Allen wrench into the center of
the rubber plug will stretch the plug and allow
complete insertion.
8. Locate hose #5 and cut 3” from the non-grommet
end. Discard the section without the grommet.
9. Insert the cut end of tube #5 through the lower
cabinet drain hole.
10. Connect hose #6 & hose #5 using 100º elbow and
secure with two red clamps
11. (Draining the Collector Box) Remove cap from left
side collector box drain port (bottom in horizontal left
position) and install it on right side (top) collector box
drain port.
12. Install the non-grommet end of hose #11 from
outside the cabinet in the upper drain hole. Install on
collector box and secure with a silver clamp.
13. Use two silver clamps and secure the hoses to drain
trap. The trap outlet faces the front of the furnace.
Secure the trap to the cabinet using two screws
removed in step 2 by inserting the two screws
through the large set of holes in the top mounting
tabs of the trap into the two pre-drilled holes in the
side of the cabinet. [Removed: Place cap on vent...]
14. Refer to Field Supplied Drain section for instructions
on eld supplied / installed drain on outlet of furnace
trap.
Upflow Model Installed Horizontally With Left
Side Down - Alternate
*Also see Front Cover Pressure Switch Tube Location on
Page 10.
1. (Draining the RF000142 Coupling) Locate hose #2
(factory installed). Cut o and discard the 45° radius
end.
2. Install 90°radius end of hose #2 on RF000142 drain
outlet and secure with a red clamp.
3. Insert coupling in hose #2 and secure with a red
clamp.
4. Locate hose #5 and cut 3” from the non-grommet
end. Discard the section without the grommet.
5. Insert the cut end of tube #5 through the lower
cabinet drain hole.
6. Insert 100 degree elbow in the cut end of hose #5.
7. Locate hose #6. Using red clamps, connect between
the coupling and 100 degree elbow, cutting o
excess tubing.
8. (Draining the Collector Box) Remove cap from left
side collector box drain port (bottom in horizontal left
position) and install it on right side (top) collector box
drain port and secure with a red clamp.
9. Install the non-grommet end of hose #11 from
outside the cabinet in the upper drain hole. Install on
collector box and secure with a silver clamp.
10. Use two silver clamps and secure the hoses to drain
trap. The trap outlet faces the front of the furnace.
Secure the trap to the cabinet using two screws
removed in step 2 by inserting the two screws
through the large set of holes in the top mounting
tabs of the trap.
Insert flange. Cut 2 ½” long.
R 000142
F
Figure 27
CounterFlow Model Installed Vertically
The furnace drain may exit the right or left side of the
furnace cabinet (left side preferred) Trap and factory
installed hoses remain as shipped if the drain will exit the
left side of the cabinet. Draining from the right side requires
relocation of the trap to outside the cabinet.

21
Drain Exiting Left Side (See Figure 28)
1. Install a eld supplied rubber coupling secured with
a 1 1/4” clamp to enable removing the trap for future
cleaning. Alternately, a PVC tting may be glued on
the trap outlet.
2. Install drain per local and National codes.
Hose #4 x 3
Hose #5
Figure 28
Drain Exiting Right Side (See Figure 29)
1. Removing the gas manifold assembly will provide
better access when re-locating the trap. To remove
the gas manifold, remove the four screws that fasten
the gas manifold assembly to the bracket.
2. Remove hose clamps and hoses from trap.
3. Remove trap.
4. (Draining the Vent Elbow) Insert the non-grommet
end hose #10 into the cabinet back drain hole. Insert
a coupling into the drip leg of the vent-drain elbow
and secure with a silver clamp. Secure hose #10 on
vent - drain elbow barb tting with a silver clamp.
5. (Draining the Collector Box) Insert non-grommet
end of hose #9 into the cabinet front drain hole and
secure on collector box drain port with a silver clamp.
6. Mate the drain trap inlets to the hoses and secure
with silver clamps.
7. Line up the trap mounting holes with the pre-drilled
holes in the furnace and secure with 2 screws
removed in step 2.
8. Refer to Field Supplied Drain section for instructions
on eld supplied / installed drain on outlet of furnace
trap.
Figure 29
WARNING
HIGH VOLTAGE
To avoid personal injury or death due to
electrical shock, disconnect electrical power
before servicing or changing any electrical
wiring.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
Counterflow Model Installed Horizontally with
Right Side Down (See Figure 30)
Minimum 5 1/2” clearance is required for the drain trap
beneath the furnace.
NOTE: For horizontal installations, some of the
required hoses are found in the factory-installed
hose assemblies. Remove the hose clamps to obtain
the respective hoses needed for installation, and
install per the following directions.
1. Remove the drain trap and factory installed drain
tube assemblies.
2. Remove two 1’’ plugs from right side of cabinet.
3. (Draining the Collector Box) From outside the
cabinet, insert the non-grommet end hose #7 into the
back drain hole and secure to collector box drain port
using a silver clamp.
4. (Draining the Vent Elbow) Insert the straight barbed
coupling into the vent - drain elbow drip leg and
secure with a red clamp.

22
Figure 30
5. From outside the cabinet, insert the non-grommet
end of hose #8 into the front cabinet drain hole and
secure on the vent - drain elbow barb tting using a
red clamp.
6. Place the drain hoses on the trap inlets and secure
with silver clamps. The outlet of the trap must face
the original bottom of furnace.
7. Using the two sheet metal screws provided in the
cabinet, secure the trap to the furnace.
8. Refer to Field Supplied Drain section for instructions
on eld supplied/installed drain on outlet of furnace
trap.
Counterflow Model Installed Horizontally with
Left Side Down (See Figure 31)
Minimum 5 1/2” clearance is required for the drain trap
beneath the furnace.
*Also see Front Cover Pressure Switch Tube Location on
page 10.
1. Remove the factory installed drain trap and hose
assemblies. Leave the 100° elbow inserted and
clamped in the vent-drain elbow.
2. Remove two 1”plugs from left side of cabinet.
3. (Draining the Collector Box) Remove the cap from
the left side of the collector box drain port (bottom
in horizontal left position) and install it on right side
drain port.
4. Place radius end of hose #4 (factory installed) on
the collector box drain port and secure with a silver
clamp.
5. Insert hose #2 from outside the cabinet in the front
drain hole.
6. Connect hose #4 & hose #2 together using a straight
barbed coupling and two gold clamps (factory
installed).
7. (Draining the Vent Elbow) Remove rubber plug from
vent – drain elbow side port.
8. The unused vent-drain elbow drip leg port must be
plugged to prevent ue gases from escaping. Insert
rubber plug removed in step 7 into the 100° elbow.
(Inserting a blunt tool such as a 3/16’’ Allen wrench
into the center of the rubber plug will stretch the plug
and allow complete insertion)
Hose #4
Hose #5
Hose #4
Hose #2
Figure 31
9. Place radius end of hose #4 on the side port of vent
– drain elbow and secure with a gold clamp.
10. Insert a ½” diameter PVC pipe (factory installed) into
hose #4 and secure with a gold clamp.
11. Insert the non-grommet end of hose #5 (factory
installed) from outside the cabinet in the back drain
hole.
12. Insert 100º elbow in hose #5 and secure with a red
clamp.
13. Locate hose #4 and cut a cut o a 4” straight section
and discard the radius end.
14. Connect the 4” straight section of hose #4 to the 100º
elbow and the PVC pipe and secure with red clamps.
15. Connect the hoses to the trap inlets and secure
with silver clamps, drain trap outlet must point to the
original bottom of the furnace.
16. Using the two sheet metal screws provided in the
cabinet, secure the trap to the furnace.
17. Refer to Field Supplied Drain section for instructions
on eld supplied / installed drain on outlet of furnace
trap.
ELECTRICAL CONNECTIONS
Wiring Harness
The wiring harness is an integral part of this furnace.
Wires are color coded for identication purposes. Refer to
the wiring diagram for wire routings. If any of the original
wire as supplied with the furnace must be replaced, it must
be replaced with wiring material having a temperature
rating of at least 105° C. Any replacement wiring must be a
copper conductor.
115 Volt Line Connections
Before proceeding with electrical connections, ensure
that the supply voltage, frequency, and phase correspond
to that specied on the unit rating plate. Power supply to
the furnace must be NEC Class 1, and must comply with
all applicable codes. The furnace must be electrically

23
grounded in accordance with local codes or, in their
absence, with the latest edition of The National Electric
Code, ANSI NFPA 70 and/or The Canadian Electric Code
CSA C22.1.
WARNING
HIGH VOLTAGE
To avoid personal injury or death due to
electrical shock, disconnect electrical power
before servicing or changing any electrical
wiring.
Humidifier 1.0 Amp maximum at 120 VAC
Electronic Air Cleaner 1.0 Amp maximum at 120 VAC
Use a separate fused branch electrical circuit containing
properly sized wire, and fuse or circuit breaker. The fuse
or circuit breaker must be sized in accordance with the
maximum overcurrent protection specied on the unit rating
plate. An electrical disconnect must be provided at the
furnace location.
Connect hot, neutral, and ground wires as shown in the
wiring diagram located on the unit’s blower door. Metal
conduit is not considered a substitute for an actual ground
wire to the unit. For direct vent applications, the cabinet
opening to the junction box must be sealed air tight using
either an UL approved bushing such as Heyco Liquid
Tight or by applying non-reactive UL approved sealant to
bushing.
Line polarity must be observed when making eld
connections. Line voltage connections can be made
through either the right or left side panel. The furnace
is shipped congured for a left side (right side for
counterows) electrical connection with the junction box
located inside the burner compartment. To make electrical
connections through the opposite side of the furnace, the
junction box must be relocated to the other side of the
burner compartment prior to making electrical connections.
To relocate the junction box, follow the steps shown in the
Junction Box Relocation section.
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a
precaution when removing hole plugs.
WARNING
To prevent personal injury or death to electrical shock,
disconnect electrical power before installing or servicing
this unit.
WARNING
HIGH VOLTAGE
To avoid the risk of injury, electrical shock
or death, the furnace must be electrically
grounded in accordance with local codes or
in their absence, with the latest edition of the
National Electrical Code.
WARNING
To avoid the risk of injury, electrical shock or death, the
furnace must be electrically grounded in accordance with
local codes or, in their absence, with the latest edition of
the National Electrical Code.
115 Volt Line Voltage Connection of Accessories
(Humidifier and Electronic Air Cleaner)
The furnace integrated control module is equipped with
line voltage accessory terminals for controlling power to
an optional eld-supplied humidier and/or electronic air
cleaner.
Turn OFF power to the furnace before installing any
accessories. Follow the humidier or air cleaner
manufacturers’ instructions for locating, mounting,
grounding, and controlling these accessories. Accessory
wiring connections are to be made through the 1/4” quick
connect terminals provided on the furnace integrated
control module. The humidier hot terminal is identied
as 120V HUM-H, its neutral terminal is identied as 120V
HUM-N. The electronic air cleaner hot terminal is identied
as EAC-H, its neutral terminal is identied as 120V
EAC-N. All eld wiring must conform to applicable codes.
Connections should be made as shown. (See Figure 32)
If it is necessary for the installer to supply additional line
voltage wiring to the inside of the furnace, the wiring
must conform to all local codes, and have a minimum
temperature rating of 105°C. All line voltage wire splices
must be made inside the furnace junction box.
The integrated control module humidier terminal 120V
HUM-H is energized with 115 volts whenever the induced
draft blower is energized. This terminal can also be used
to provide 115 volt power to a humidier transformer. The
remaining primary transformer wire would be connected
to the Line N on the control board. The integrated control
module electronic air cleaner terminals EAC-H is energized
with 115 volts whenever the circulator blower is energized.
NOTE: Wire routing must not to interfere with
circulator blower operation, filter removal, or
routine maintenance.

24
115 VAC HUM
115 VAC EAC
Figure 32
Connection of 24 Volt Humidifier
The integrated control module single humidier terminal “24
V HUM” is energized with 24 volts whenever the induced
draft blower is energized. Connect the common side of
the 24 volt humidier to the “C” terminal of the thermostat
terminal strip on the control board.
Low Voltage Ventilation
The Ventilation connections provide dry contact for eld
ventilator wiring connections. These connections are
normally open and energize during the R-32 fault/alarm
condition. VT IN and VT OUT connectors are provided on
the control board and are shown in the image below.
Low Voltage A2L Alarm
The A2L alarm connection provides 24VAC for eld alarm
wiring connections. These connections are normally open
and energize during the R-32 fault/alarm condition. An A2L
Alarm connection is provided on the control board and is
shown in the image below.
Field Installed Accessories
Additional accessories that do not have dedicated terminals
on the furnace control board may require an additional
daughter board to be installed. Please refer to service
manual on your product for more information.
24 VOLT HUM. &
HUMIDISTAT
24 VOLT VENTILATION
(OPTIONAL)
24 VOLT A2L ALARM
(OPTIONAL))
R-32
SENSOR
Figure 33
Junction Box Relocation
Line voltage connections can be made through either the
right or left side panel. The furnace is shipped congured
for a left side electrical connection. To make electrical
connections through the opposite side of the furnace,
the junction box must be relocated to the left side prior to
making electrical connections. To relocate the junction box,
perform the following steps.
1. Remove the burner compartment door.
2. Remove and save the two screws securing the
junction box to the side panel.
3. Relocate junction box and associated plugs and
grommets to opposite side panel. Secure with screws
removed in step.
IMPORTANT NOTE: Wire routing must not interfere
with circulator blower operation, filter removal
or routine maintenance.
To ensure proper unit grounding, the ground wire should
run from the furnace ground screw located inside the
furnace junction box all the way back to the electrical panel.
NOTE: Do not use gas piping as an electrical
ground. To confirm proper unit grounding,
turn off the electrical power and perform the
following check.
1. Measure resistance between the neutral (white)
connection and one of the burners.
Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock
switch which interrupts unit voltage when the blower door is
opened for servicing. Do not defeat this switch.

25
24 Volt Thermostat Wiring
IMPORTANT NOTE: Wiring routing must not
interfere with circulator blower operation, filter
removal or routine maintenance.
Low voltage connections can be made through either the
right or left side panel. Thermostat wiring entrance holes
are located in the blower compartment. The following gure
shows connections for a “heat/cool system”.
This furnace is equipped with a 40 VA transformer to
facilitate use with most cooling equipment. Consult the
wiring diagram, located on the blower compartment door,
for further details of 115 Volt and 24 Volt wiring.
Thermostat Wiring Diagrams
Y
C
Y
C
G
R
W
Y2
Y/Y1
C
G
R
W
ROOM THERMOSTAT
INTEGRATED FURNACE
CONTROL MODULE
REMOTE COOLING UNIT
(SINGLE STAGE)
Thermostat - Single-Stage Heating with Single-Stage Cooling
Figure 34
Y1
C
Y1C
G
R
W
Y2
Y/Y1
C
G
R
W
ROOM THERMOSTAT
INTEGRATED FURNACE
CONTROL MODULE
REMOTE COOLING UNIT
(TWO STAGE)
Y2
Y2
Thermostat - Single-Stage Heating with Two-Stage Cooling
Figure 35
WARNING
HIGH VOLTAGE
To avoid personal injury or death due to
electrical shock, disconnect electrical power
before servicing or changing any electrical
wiring.
Fossil Fuel Applications
This furnace can be used in conjunction with a heat pump
in a fossil fuel application. A fossil fuel application refers to
a combined gas furnace and heat pump installation which
uses an outdoor temperature sensor to determine the most
cost ecient means of heating (heat pump or gas furnace).
A heat pump thermostat is required to properly use a
single-stage furnace in conjunction with a heat pump. Refer
to the fossil fuel kit installation instructions for additional
thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit
installation instructions. All furnace connections must be
made to the furnace two-stage integrated control module
and the “FURNACE” terminal strip on the fossil fuel control
board.
Twinning
Two furnaces of the same model may be twinned. The
integrated control board has a 3/16” terminal labeled “TWIN”
located beside the low voltage thermostat connection strip.
Twinning allows simultaneous operation of two furnaces
and forces the indoor blower motors of each furnace to
operate synchronously into a common duct system. Using
the twinning function will require only eld installed wiring
with no external kits or parts. The staging and speed tap
options must be set the same on both furnaces.
NOTE: Each furnace must be connected to it’s
own 115 VAC power supply. The L1 connection
to each furnace must be in phase (connected to
circuit breakers on the same 115 VAC service
panel phase leg). To verify that the furnaces are
in phase, check from L1 to L1 on each furnace
with a voltmeter. If the furnaces are in phase, the
voltage between both furnaces will be ZERO.
ROOM THERMOSTAT
Y2
Y/Y1
C
G
R
W
Y2
Y/Y1
C
G
R
W
Y2
Y/Y1
C
G
R
W
TWIN
TWIN
COND UNIT
CONTACTOR
COND UNIT
CONTACTOR
FURNACE 1
FURNACE 2
Figure 36
CAUTION
To prevent unreliable operation or equipment damage, the
gas manifold pressure must be as specified on the unit rating
plate. Only minor adjustments should be made by adjusting
the gas valve pressure regulator.
WARNING
Possible property damage, personal injury or death may
occur if the correct conversion kits are not installed. The
appropriate kits must be applied to ensure safe and proper
furnace operation. All conversions must be performed by a
qualified installer or service agency.

26
R-32 INFORMATION
R-32 Function
This furnace is equipped with a control board that is
capable of shutting o the gas heat and turning on the
blower fan in case of an R-32 refrigerant leak in the indoor
evaporator coil. If the cooling unit that is paired with this
furnace does not utilize R-32 as the refrigerant, the R-32
functionalities in the furnace control board will need to be
turned o for the furnace to run properly.
R-32 function on the control board is ON by default. The
R-32 function can be disabled through the furnace control
by entering the A2L Function Enabled menu and selecting
“no”. If A2L function is disabled, the furnace control will
ignore all A2L functions. If A2L function is enabled, the
control will monitor the R-32 sensor information.
To enter the A2L Function Enabled menu, press the left
or right switch until LED displays “A2E”. Press the center
switch and the LED will display the selected option (yes
or no). Press the left of rightswitch to select one of the two
options and press the middle switch to conrm the option.
R-32 Sensor Wire Routing
IMPORTANT NOTE: Wiring routing must not
interfere with circulator blower operation, filter
removal or routine maintenance. Wire should
not be routed near hot surfaces and should be
protected from sharp edges.
The R-32 Sensor wire coming from the indoor evaporator
coil will need to be routed into the furnace and connected
to the connection point on the furnace control board. This
wire should be routed alongside the thermostat wires
through the low voltage openings in the left or right side of
the furnace blower compartment. Please see the electrical
section for the location of the R-32 Sensor connection on
the control board.
Furnace Start-Up
During furnace start up, the furnace control will identify the
connected R-32 sensor and will start monitoring the sensor
communication. A green LED located next to the sensor
connection will indicate if there is communication between
the furnace control and the R-32 sensor. The LED will be
ON during the duration of the startup and then will either
start blinking or turn OFF. The blinking LED signies that
communication with the R-32 sensor is present. The LED
OFF signies that there is no signal with the sensor.
If there are no alarms or faults, the furnace will go into
regular run mode after a warm up period. The furnace
control monitors the R-32 sensor once per second.
R-32 Refrigerant Leak
If the R-32 sensor on the indoor evaporator coil detects
a specied concentration of R-32 refrigerant, the furnace
will enter Mitigation Mode to dilute the refrigerant
concentrations in case of a leak. In Mitigation Mode, the
furnace will do the following:
1. Display the A2L Refrigerant Leakage error code
(EAL)
2. Shut down the gas operation
3. Energize the optional ventilation and alarm outputs
4. Run the fan at max CFM airow
Once the R-32 sensor stops detecting a leak, the fan will
continue to run for 5 minutes. After the 5 minutes, if there
are no other alarms or faults, the control will de-energize
the optional ventilation and alarm outputs and then go back
to the original operating mode per the thermostat.
A2L Verification
The A2L Function Verication menu allows the installer to
verify if the R-32 function operates properly. This menu
simulates the refrigerant leak process and is only able to
be used when there are no active alarms or faults. To verify
the R-32 functions, enter the A2L Function Verication
menu and select “YES”. To enter the A2L Function
Verication menu, press the left or right switch until LED
displays “A2u”. Press the center switch and the LED will
display the selected option (yes or no). Press the left of
right switch to select one of the two options and press
the middle switch to conrm the option. Once “YES” is
selected, the furnace will do the following:
1. Display the A2L Refrigerant Leakage code (EAL)
2. Shut down the gas operation
3. Energize the optional ventilation and alarm outputs
4. Run the fan at max CFM airow
The control will exit the verication function if:
1. The 5 minute timeout expires or
2. An alarm or fault is detected or
3. The user turns OFF the A2L Function Verication.
GAS SUPPLY AND PIPING
Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c.
Propane Gas Minimum: 11.0" w.c. Maximum: 13.0" w.c.
INLET GAS SUPPLY PRESSURE
The furnace rating plate includes the approved furnace gas
input rating and gas types. The furnace must be equipped
to operate on the type of gas applied. This includes any
conversion kits required for alternate fuels and/or high
altitude.
Inlet gas supply pressures must be maintained within the
ranges specied in the following table. The supply pressure
must be constant and available with all other household
gas red appliances operating. The minimum gas supply
pressure must be maintained to prevent unreliable ignition.
The maximum must not be exceeded to prevent unit
overring.

27
WARNING
Possible property damage, personal injury or death mat
occur if the correct conversion kits are not installed. The
appropriate kits must be applied to ensure safe and proper
furnace operation. All conversions must be performed by a
qualified installer or service agency.
Gas Altitude Kit Orifice
Manifold
Pressure
Pressure
Switch
Change
Natural None #45 3.5" w.c. None
Propane
LPM-33
1.25mm 10.0" w.c. None
NOTE: In Canada, gas furnaces are only cer�fied to 4500 feet.
0-7000
Gas Valve
This unit is equipped with a 24 volt gas valve controlled
during furnace operation by the integrated control
module. As shipped, the valve is congured for natural
gas. The valve is eld convertible for use with propane
gas by replacing the regulator spring with a propane gas
spring from an appropriate manufacturer’s propane gas
conversion kit. Taps for measuring the gas supply pressure
and manifold pressure are provided on the valve.
The gas valve has a manual ON/OFF control located on
the valve itself. This control may be set only to the “ON”
or “OFF” position. Refer to the lighting instructions label
or Startup Procedure & Adjustment for use of this control
during start up and shut down periods.
Gas Piping Connections
The gas piping supplying the furnace must be properly
sized based on the gas ow required, specic gravity of the
gas, and length of the run. The gas line installation must
comply with local codes, or in their absence, with the latest
edition of the National Fuel Gas Code, NFPA 54/ANSI
Z223.1 or CAN/CSA B149.1-15 in Canada.
To connect the furnace to the building’s gas piping, the
installer must supply a ground joint union, drip leg, manual
shuto valve, and line and ttings to connect to gas valve.
In some cases, the installer may also need to supply a
transition piece from 1/2” pipe to a larger pipe size.
The following stipulations apply when connecting gas
piping. Refer to Gas Piping Connections gure for typical
gas line connections to the furnace.
• Gas piping must be supported external to the furnace
cabinet so that the weight of the gas line does not
distort the burner rack, manifold or gas valve.
• Use black iron or steel pipe and ttings for building
piping. Where possible, use new pipe that is properly
chamfered, reamed, and free of burrs and chips. If
old pipe is used, be sure it is clean and free of rust,
scale, burrs, chips, and old pipe joint compound.
• Use pipe joint compound on male threads ONLY.
Always use pipe joint compound (pipe dope) that
WARNING
To avoid possible unsatisfactory operation of equipment
damage due to underfiring or equipment, use the proper size
of natural/propane gas piping needed when running pipe from
the meter/tank to the furnace.
HIGH ALTITUDE INSTALLATION
When this furnace is installed at high altitude, the
appropriate High Altitude Kit including orices and a
pressure switch(s) must be installed. These changes are
necessary to compensate for the natural reduction in the
density of both the gas fuel and the combustion air at
higher altitude.
Installation of this furnace at altitudes above 7000 ft (2134
m), shall be made in accordance with the Listed High
Altitude Conversion Kit available with this furnace.
Do not derate the furnace by adjusting the manifold
pressure to a lower pressure than specied on the furnace
rating plate. The combination of the lower air density and
a lower manifold pressure will prohibit the burner orice
from drawing the proper amount of air into the burner. This
may cause incomplete combustion, ashback, and yellow
tipping.
In some areas the gas supplier may articially derate the
gas in an eort to compensate for the eects of altitude.
If the gas is articially derated, the appropriate orice size
must be determined based upon the BTU/ft3 content of
the derated gas and the altitude. Refer to the National
Fuel Gas Code, NFPA 54/ANSI Z223.1, and information
provided by the gas supplier to determine the proper orice
size. A dierent pressure switch may be required at high
altitude regardless of the BTU/ft3 content of the fuel used.
Consult the furnace Specication Sheet. All conversions
must be performed by a qualied installer, or service
agency.
Propane Gas Conversion
This furnace is shipped from the factory congured for
natural gas at standard altitude. To operate this furnace
on L.P. gas, a LPM-33 LP Conversion kit must be used.
Propane gas installations require an orice and spring
change to compensate for the energy content dierence
between natural and propane gas.
If converting to LP gas, a low pressure switch should
be installed per the LP kit. This low pressure switch will
prevent the furnace from ring when the LP gas supply
pressure is too low to support proper combustion.
All conversions must be performed by a qualied installer,
or service agency.

28
is APPROVED FOR ALL GASES. DO NOT apply
compound to the rst two threads.
• Use ground joint unions.
• Install a drip leg to trap dirt and moisture before it can
enter the gas valve. The drip leg must be a minimum
of three inches long.
• Install a 1/8” NPT pipe plug tting, accessible for test
gauge connection, immediately upstream of the gas
supply connection to the furnace.
• Always use a back-up wrench when making the
connection to the gas valve to keep it from turning.
The orientation of the gas valve on the manifold
must be maintained as shipped from the factory.
Maximum torque for the gas valve connection is 375
in-lbs; excessive over-tightening may damage the
gas valve.
• Install a manual shuto valve between the gas
meter and unit within six feet of the unit. If a union
is installed, the union must be downstream of the
manual shuto valve, between the shuto valve and
the furnace.
• Tighten all joints securely.
Natural Gas Capacity of Pipe
In Cubic Feet of Gas Per Hour (CFH)
Length of Nominal Black Pipe Size
Pipe in Feet 1/2" 3/4" 1" 1 1/4" 1 1/2"
10 132 278 520 1050 1600
20 92 190 350 730 1100
30 73 152 285 590 980
40 63 130 245 500 760
50 56 115 215 440 670
60 50 105 195 400 610
70 46 96 180 370 560
80 43 90 170 350 530
90 40 84 160 320 490
100 38 79 150 305 460
(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specific Gravity Gas)
CFH =
BTUH Furnace Input
Heating Value of Gas (BTU/Cubic Foot)
• Connection method must be in compliance with all
local and national codes. US: National Fuel Gas
Code (NFGC) NFPA 54-2012/ANSI Z223.1-2012 and
the Installation Standards, Warm Air Heating and Air
Conditioning Systems ANSI/NFPA 90B.
In Canada, CANADA: National Standard of Canada,
Natural Gas and Propane Installation Code
(NSCNGPIC) CSA B149.1-15.
Connect the furnace to the building piping by one of
the following methods:
– Rigid metallic pipe and ttings.
– Semi-rigid metallic tubing and metallic ttings.
Aluminum alloy tubing must not be used in exterior
locations. In order to seal the grommet cabinet
penetration, rigid pipe must be used to reach the
outside of the cabinet. A semi-rigid connector to the
gas piping may be used from there.
• Use listed gas appliance connectors in accordance
with their instructions. Connectors must be fully in the
same room as the furnace.
• Protect connectors and semi-rigid tubing against
physical and thermal damage when installed.
Ensure aluminum-alloy tubing and connectors are
coated to protect against external corrosion when
in contact with masonry, plaster, or insulation, or
subjected to repeated wetting by liquids such as
water (except rain water), detergents, or sewage.
The gas piping may enter the left or right side of the
furnace cabinet. The installer must supply rigid pipe long
enough to reach the outside of the cabinet to seal the
grommet cabinet penetration. A semi-rigid connector to the
gas piping can be used outside the cabinet per local codes.
1/2” NPT pipe and ttings are required. For models with an
“L” shaped manifold, a 4 1/2” long nipple is required. For
models with a hook shaped manifold, a 2” long nipple is
required.
A semi-rigid connector to the gas piping can be used
outside the cabinet per local codes. From the elbow, the
length of pipe and the ttings required will vary by the side
chosen, location of union and cabinet width. The union may
be placed inside or outside of the cabinet.
Alternate
Gas Line
Location
Gas Valve
Burners
Manual Shut Off Valve
(upstream from
ground joint
pipe union)
Drip Leg
Grommet
in Standard
Gas Line
Hole
*Ground
Joint
Pipe
Union
*Ground
Joint
Pipe
Union
*NOTE: Union may be inside furnace cabinet where allowed by local codes.
Manifold
UPFLOW
Figure 37

29
Alternate
Gas Line
Location
Plug in
Alternate
Gas Line
Hole
Gas Valve
Burners
Manual Shut Off Valve
(upstream from ground joint pipe union)
Drip Leg
Grommet
in Standard
Gas Line
Hole
*Ground
Joint
Pipe Union
*Ground
Joint
Pipe Union
*NOTE: Union may be inside furnace cabinet where allowed by local codes.
COUNTERFLOW
Figure 38
Drip Leg
Plug in Main Gas Line Hole
Alternate
Union
Location
Manual Shut Off Valve
(upstream from
ground joint pipe union)
Gas
Valv e
Burners
Drain Trap
Manifold
Plug in Alternate Gas Line Hole
Grommet in
Standard Gas Line Hole
UPFLOW - HORIZONTAL LEFT
Figure 39
Manual Shut Off Valve
(upstream from
ground joint
pipe union)
COUNTERFLOW - HORIZONTAL RIGHT
Figure 40
Gas Piping Checks
Before placing unit in operation, leak test the unit and gas
connections.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector, or
other approved testing methods.
NOTE: Never exceed specified pressures for
testing. Higher pressure may damage the gas valve
and cause subsequent overfiring, resulting in heat
exchanger failure.
Disconnect this unit and shuto valve from the gas supply
piping system before pressure testing the supply piping
system with pressures in excess of 1/2 psig (3.48 kPa).
Isolate this unit from the gas supply piping system by
closing its external manual gas shuto valve before
pressure testing supply piping system with test pressures
equal to or less than 1/2 psig (3.48 kPA).
WARNING
To avoid the possibility of explosion or fire, never use a
match or open flame to test for leaks.

30
WARNING
If the gas furnace is installed in a basement, an excavated
area or confined space, it is strongly recommended to
contact a propane supplier to install a gas detecting warning
device in case of a gas leak.
• Since propane gas is heavier than air, any leaking gas can
settle in any low areas or confined spaces.
• Propane gas odorant may fade, making the gas undetect-
able except with a warning device.
Propane Gas Tanks and Piping
A gas detecting warning system is the only reliable way to
detect a propane gas leak. Rust can reduce the level of
odorant in propane gas. Do not rely on your sense of smell.
Contact a local propane gas supplier about installing a
gas detecting warning system. If the presence of gas
is suspected, follow the instructions listed in the Safety
Considerations section of this manual.
All propane gas equipment must conform to the safety
standards of the National Board of Fire Underwriters,
NBFU Manual 58.
CANADA: National Standard of Canada, Natural Gas and
Propane Installation Code (NSCNGPIC) CSA B149.1-15.
200 PSIG
Maximum
5 to 15 PSIG
(20 PSIG Max.)
Continuous
11" W.C.
Second Stage
Regulator
First Stage
Regulator
Propane Gas Installation (Typ.)
Figure 41
For satisfactory operation, propane gas pressure must be
10” WC at the furnace manifold with all gas appli ances in
operation. Maintaining proper gas pressure depends on
three main factors:
1. Vaporization rate, depending on temperature of the
liquid, and “wetted surface” area of the con tainer or
containers.
2. Proper pressure regulation (Two-stage regulation is
recommended for both cost and eciency).
3. Pressure drop in lines between regulators, and
between second stage regulator and the appliance.
Pipe size will depend on length of pipe run and total
load of all appliances.
Complete information regarding tank sizing for vaporiza-
tion, recommended regulator settings, and pipe sizing is
available from most regulator manufacturers and propane
gas suppliers.
Since propane gas will quickly dissolve white lead and
most standard com mercial compounds, special pipe dope
must be used. Always use a pipe thread sealant approved
for all gases.
Refer to the illustration for typical propane gas installations
and piping.
WARNING
Never allow the products of combustion, including carbon
monoxide, to enter the return ductwork or circulation air
supply.
CIRCULATING AIR & FILTERS
Duct work - Air Flow
Duct systems and register sizes must be properly designed
for the CFM and external static pressure rat ing of the
furnace. Design the ductwork in accor dance with the
recommended methods of “Air Conditioning Contractors of
America” Manual D.
Install the duct system in accordance with Standards of
the National Board of Fire Underwriters for the Installation
of Air Conditioning, Warm Air Heating and Ventilating
Systems. Pamphlets No. 90A and 90B.
A closed return duct system must be used, with the return
duct connected to the furnace. NOTE: Ductwork must
never be attached to the back of the furnace. For upow
installations requiring 1800 CFM or more, use either two
side returns or bottom return or a combination of side /
bottom. Flexible joints may be used for supply and return
con nections to reduce noise transmission. To prevent the
blower from inter fering with combustion air or draft when a
central return is used, a connecting duct must be installed
between the unit and the utility room wall. Never use a
room, closet, or alcove as a return air chamber.
Checking Duct Static
Refer to your furnace rating plate for the maximum ESP
(external duct static) rating.
Total external static refers to everything external to the
furnace cabinet. Cooling coils, lters, ducts, grilles,
registers must all be considered when reading your total
external static pressure. The supply duct pressure must be
read between the furnace and the cooling coil. This reading
is usually taken by removing the “A” shaped block o
plate from the end on the coil; drilling a test hole in it and
reinstalling the block o plate. Take a duct static reading
at the test hole. Tape up the test hole after your test is
complete. The negative pressure must be read between
the lter and the furnace blower.
Too much external static pressure will result in insucient
air that can cause excessive temperature rise. This can

31
cause limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed as
follows:
1. With clean lters in the furnace, use a manometer to
measure the static pressure of the return duct at the
inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct.
(Positive Pressure)
3. The dierence between the two numbers is .4” w.c.
EXAMPLE:
-1
0
1 2
3
Difference is 4
Static reading from return duct = -.1” w.c.
Static reading from supply duct = .3” w.c.
Total external static pressure on this system = .4” w.c.
NOTE: Both readings may be taken simultaneously
and read directly on the manometer if so
desired. If an air conditioner coil or Electronic
Air Cleaner is used in conjunction with the
furnace, the readings must also include theses
components, as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum
listed on the furnace rating plate, check for closed
dampers, registers, undersized and/or oversized poorly laid
out duct work.
The temperature rise of the furnace must be within the
temperature rise range listed on the furnace rating plate.
Checking Static Pressure (80% Furnace Shown, 90% Similar)
Figure 42
WARNING
Edges of sheet metal holes may be sharp. Use gloves as
a precaution when removing sheet metal from return air
openings.
Bottom Return Air Opening [Upflow Models]
The bottom return air opening on upow models utilizes
a “lance and cut” method to remove sheet metal from the
duct opening in the base pan. To remove, simply press
out the lanced sections by hand to expose the metal strips
retaining the sheet metal over the duct opening. Using
tin snips, cut the metal strips and remove the sheet metal
covering the duct opening. In the corners of the opening,
cut the sheet metal along the scribe lines to free the duct
anges. Using the scribe line along the duct ange as a
guide, unfold the duct anges around the perimeter of the
opening using a pair of seamer pliers or seamer tongs.
NOTE: Airflow area will be reduced by
approximately 18% if duct flanges are not
unfolded. This could cause performance issues
and noise issues.
CUT FOUR CORNERS
AFTER REMOVING SHEET
METAL
CUT USING TIN SNIPS
PRESS OUT BY HAND
SCRIBE LINES OUTLINING
DUCT FLANGES
Duct Flange Cut Outs
Figure 43

32
When the furnace is used in connection with a cooling unit,
the furnace should be installed in parallel with or on the
upstream side of the cooling unit to avoid condensa tion
in the heating element. With a parallel ow arrange ment,
the dampers or other means used to control the ow of
air must be adequate to prevent chilled air from entering
the furnace and, if manually operated, must be equipped
with means to prevent operation of either unit unless the
damper is in the full heat or cool position.
When the furnace is installed without a cooling coil, it is
recommended that a removable access panel be provided
in the outlet air duct. This opening shall be accessible when
the furnace is installed and shall be of such a size that the
heat exchanger can be viewed for visual light inspection
or such that a sampling probe can be inserted into the air
stream. The access panel must be made to prevent air
leaks when the furnace is in operation.
When the furnace is heating, the temperature of the return
air entering the furnace must be between 55°F and 100°F.
Filters - Read This Section Before Installing
The Return Air Duct work
Filters must be used with this furnace. Discuss lter
maintenance with the building owner. Filters do not ship
with this furnace, but must be provided, sized and installed
externally by the installer. Filters must comply with UL900
or CAN/ULCS111 standards. Damage or repairs due to
the installation of the furnace without lters is not covered
under the warranty.
On upow units, guide dimples locate the side return cutout
locations. Use a straight edge to scribe lines connecting
the dimples. Cut out the opening on these lines. NOTE: An
undersized opening will cause reduced airow.
Refer to the Filter Sizing Chart to determine lter area
requirements.
Filter Sizing Charts
Model Minimum Recommended Filter Size
*R9S960403AN
1 - 16 X 25 Side or 1 - 14 X 24 Bottom Return
*R9S960603BN
1 - 16 X 25 Side or Bottom Return
*R9S960803BN 1 - 16 X 25 Side or Bottom Return
*R9S960804CN 1 - 16 X 25 Side or Bottom Return
*R9S960805CN 2 - 16 X 25 Side or 1 - 20 X 25 Bottom Return
*R9S961005CN 2 - 16 X 25 Side or 1 - 20 X 25 Bottom Return¹
*R9S961205DN 2 - 16 X 25 Side or 1 - 24 X 24 Bottom Return¹
*D9S960403BN 2 - 10 X 20 or 1 - 14 X 25 Top Return
*D9S960603BN 2 - 10 X 20 or 1 - 14 X 25 Top Return
*D9S960804CN 2 - 14 X 20 or 1 - 16 X 25 Top Return
*D9S961005CN 2 - 14 X 20 or 1
- 20 X 25 Top Return
*D9S961205DN 2 - 14 X 20 or 1 - 24 X 24 Top Return
Filter Sizing Chart
Larger filters may be used, filters may also be centrally located.
¹ = use 2 - 16 X 25 filters and two side returns or 20 X 25 filter on
bottom return or combination side & bottom if furnace is connected to
a cooling unit over 4 tons nominal capacity
Model Minimum Recommended Filter Size
*R9S920403AN 1 - 16 X 25 Side or 1 - 14 X 24 Bottom Return
*R9S920603BN 1 - 16 X 25 Side or Bottom Return
*R9S920803BN 1 - 16 X 25 Side or Bottom Return
*R9S920804CN 1 - 16 X 25 Side or Bottom Return
*R9S920805CN 2 - 16 X 25 Side or 1 - 20 X 25 Bottom Return
*R9S921004CN 1 - 16 X 25 Side or Bottom Return
*R9S921005CN 2 - 16 X 25 Side or 1 - 20 X 25 Bottom Return¹
*R9S921205DN 2 - 16 X 25 Side or 1 - 24 X 24 Bottom Return¹
Filter Sizing Chart
Larger filters may be used, filters may also be centrally located.
¹ = use 2 - 16 X 25 filters and two side returns or 20 X 25 filter on
bottom return or combination side & bottom if furnace is
connected to a cooling unit over 4 tons nominal capacity
Change filters before occupants
take ownership of a new home!
Consider installing an air cleaner with deep-pleated media
lter at the time of furnace installation. A deep-pleated
lter with a MERV rating of 8 (minimum) will often provide
better ltration to protect equipment and the air distribution
system than a standard 1” lter and often has lower static
pressure loss than a 1” lter. Also a deep-pleated lter
will typically require less frequent replacement intervals.
Avoid using highly restrictive 1” lters which produce static
pressure loss greater than .25” W.C. In some installations
the minimum lter size required (consult lter sizing chart
above) will not lend itself to a lter installation on the side
of the furnace. The installation of a centrally installed air
cleaner cabinet or a return duct lter installation may oer
more practicality.
Clean Comfort™ brand MERV 11 air cleaners have
5¼” media lters and are available in the following
congurations. Consult your distributor for information on
our complete line of IAQ Clean Comfort™ products.
Depending on the installation and/or customer preference,
diering lter arrangements can be applied. Filters can
be installed in the central return register or a side panel
external lter rack kit (upows). As an alternative a media
air lter or electronic air cleaner can be used as the
requested lter.

33
The following gures show possible lter locations:
AIR FLOW
SIDE RETURN
EXTERNAL FILTER
RACK KIT
(EITHER SIDE)
Possible Upright Upflow
Figure 44
AIR FLOW
CENTRAL
RETURN
GRILLE
FILTER
SUPPORT
BRACKET
(Field Supplied)
Possible Upright Counterflow Filter Locations
Figure 47
Horizontal Installations
Filters must be installed in either the central return register
or in the return air duct work.
STARTUP PROCEDURE & ADJUSTMENT
Furnace must have a 115 VAC power supply properly
connected and grounded. Proper polarity must be
maintained for correct operation. In addition to the following
start-up and adjustment items, refer to further information
in Operational Checks section.
Furnace Cabinet
Check that all furnace cabinet sealing components are in
place (plugs, grommets, gaskets). NOTE: If the furnace
bottom panel has not been removed for a return duct
connection, all perforations must be sealed with duct
sealant compound or other suitable method to prevent air
leakage. For optimal performance verify that all do gaskets
are properly in place and replace as needed to prevent air
leakage.
Drain Trap Priming
The drain trap must be primed prior to furnace startup.
To prime, ll both sides of the drain trap with water. This
ensures proper furnace drainage upon startup and prohibits
the possibility of ue gases escaping through the drain
system.
Furnace Operation
Purge gas lines of air prior to startup. Be sure not purge
lines into an enclosed burner compartment. Follow
NFPA 54, National Fuel Gas Code 8.1 for proper purging
methods. In Canada, follow approved purging methods in
B149.1-15.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector,
or other approved method. Verify that all required kits
(propane gas, high altitude, etc.) have been appropriately
installed.
NOTE: This furnace is equipped with a control
board that is capable of monitoring for R-32
refrigerant leaks in the indoor evaporator coil.
Please verify that the R-32 sensor wire is plugged
in to the furnace control board before startup,
if applicable. If furnace is not paired with an R-32
Refrigeration system, the default settings in the
furnace control board will need to be changed.
Please see the R-32 section for additional
information.
Furnace Startup
1. Close the manual gas shuto valve external to the
furnace.
2. Turn o the electrical power to the furnace.
3. Set the room thermostat to the lowest possible
setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition
device which automatically lights the burner. Do
not try to light the burner by hand.
5. Move the furnace gas valve manual control to the
OFF position.
6. Wait ve minutes then smell for gas. Be sure check
near the oor as some types of gas are heavier than
air.

34
7. If you smell gas after ve minutes, immediately follow
the safety instructions in the Safety Considerations
on page 2 of this manual. If you do not smell gas
after ve minutes, move the furnace gas valve
manual control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shuto valve external to the
furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room
temperature.
12. After the burners are lit, set the thermostat to desired
temperature.
Gas Heat Sequence of Operation
Call for Heat
• On a call for heat, the thermostat contacts close &
the control board receives 24 VAC on the W terminal.
• The control board microcomputer runs its self-check
routine.
• The control veries the limit switch is closed (24 VAC
on Pin 8 of the 12 Pin connector).
• The control veries that pressure switch circuit is
open (0 VAC on Pin 5).
• The control module performs a gas valve circuitry
check to verify gas valve relay state and presence of
voltage at the valve.
• The system will energize the Induced draft blower.
• The pre-purge period begins once the pressure
switch is detected closed (24 VAC on Pin 5).
• After the completion of pre-purge, the control will
energize the igniter.
• After completion of the ignitor warm-up period:
• The gas valve is energized.
• The ignitor is de-energized as soon as ame is
sensed.
• After 30 seconds the indoor blower is energized on
heating speed.
• When the thermostat is satised:
• The gas valve is de-energized.
• The inducer remains energized for the post purge
period (15 seconds).
• The indoor blower runs for the selected o delay
period (90 seconds by default, adjustable from 30 –
180 seconds).
Heating Mode Speed Selection
To change the main blower speed in HEATING mode,
follow the following steps:
1. Press left or right button till LED displays “gA1” (for
single stage HEATING). Press center button and
LED will display the selected speed number as Fxx
(xx: Blower speed number).
2. The control shall rotate available speed number
every time Left/Right switches are pressed. Table
below shows the available speeds for Low & High
heat mode.
3. When the center switch is pressed, the current
displayed speed shall be selected, and control shall
apply the newly selected speed in next heating call.
NOTE: Always refer to the Heating Chart to
choose from available heating speeds
THERMOSTAT CALL AVAILABLE SPEEDS
W/W1
F01
F03
F04
F02 (DEFAULT)
Heating Speed Table for 1 Stage IFC
Continuous Fan Mode Speed Selection
To change the main blower speed in circulation mode,
follow the following steps:
1. Press the left or right switch until LED displays “FSd”.
Press the center switch and LED will display the
selected speed number as Fxx (xx: Blower speed
number from 1 to 9). F01 is the default speed for
circulation.
2. The control will rotate available speed number every
time left/right switches are pressed. All 9 speeds are
available for circulation.
3. When the center switch is pressed, the current
displayed speed will be selected, and control will
immediately apply that speed setting.
THERMOSTAT
CALL
AVAILABLE
SPEEDS
G
F01
F02
F03
(DEFAULT)
F04
F05
F06
F07
F08
F09
Circulation Speed Table
Cooling Mode Sequence of Operation
Low Stage Cooling Mode Sequence:
On a call for low stage cooling, the Y/Y1 or Y/Y1 and G
thermostat contacts close signaling the furnace control
board with 24 VAC on Y/Y1 or Y/Y1 and G terminals.
• The 7-Segment will display the cool mode:1 A C
• The compressor and condenser fan are energized.
• The circulator fan is energized at low cool speed
after a cool on delay. The electronic air cleaner will
also be energized.

35
• After the thermostat is satised, the compressor
is de-energized and the Cool Mode Fan O Delay
period begins.
• Following the Cool Mode Fan O Delay period, the
cool circulator and air cleaner relay are de-energized.
2nd Stage Cooling Mode Sequence:
On a call for 2nd stage cooling, the Y2 or Y2 and G
thermostat contacts close signaling the furnace control
board with 24 VAC on Y2 or Y2 and G terminals.
• The 7-Segment will display the cool mode: 2 A C
• The compressor and condenser fan are energized.
• The circulator fan is energized at cool speed after a
cool on delay. The electronic air cleaner will also be
energized.
• After the thermostat is satised, the compressor
is de-energized and the Cool Mode Fan O Delay
period begins.
• Following the Cool Mode Fan O Delay period, the
cool circulator and air cleaner relay are de-energized
Cooling Mode Speed Selection
To change the main blower speed in COOLING mode,
follow the following steps:
1. Press the left or right switch until LED displays “AC1”
(for single stage COOLING) or “AC2” (for two-stage
COOLING). Press the center switch and LED will
display the selected speed number as Fxx (xx:
Blower speed number from 1 to 9).
2. The control will rotate available speed number every
time left/right switches are pressed. All 9 speeds are
available for both Single and Two Stage cooling.
3. When the center switch is pressed, the current
displayed speed will be selected, and control will
apply the newly selected speed in next cooling call.
THERMOSTATCALL AVAILABLESPEEDS
Y/Y1
F01
F02
F03
F04(DEFAULT)
F05
F06
F07
F08
F09
Single-Stage Cooling Speed Table for 2 Stage IFC
THERMOSTATCALL AVAILABLESPEEDS
Y2
F01
F02
F03
F04
F05(DEFAULT)
F06
F07
F08
F09
Two-Stage Cooling Speed Table for 2 Stage IFC
Furnace Shutdown
1. Set the thermostat to the lowest setting. The
integrated control will close the gas valve and
extinguish ame. Following a 15 second delay, the
induced draft blower will be de-energized. After
the blower o delay time expires, the blower de-
energizes.
2. Remove the burner compartment door and move
the furnace gas valve manual control to the OFF
position.
3. Close the manual gas shuto valve external to the
furnace.
4. Replace the burner compartment door.
GAS SUPPLY PRESSURE MEASUREMENT
Gas Pressure Test
The line pressure supplied to the gas valve must be within
the range specied below. The supply pressure can be
measured at the gas valve inlet pressure tap or at a hose
tting installed in the gas piping drip leg. The supply
pressure must be measured with the burners operating.
To measure the gas supply pressure, use the following
procedure.
1. Turn OFF gas to furnace at the manual gas shuto
valve external to the furnace.
2. Connect a calibrated manometer (or appropriate gas
pressure gauge) at either the gas valve inlet pressure
tap or the gas piping drip leg. See White-Rodgers
36J22 gas valve gure for location of inlet pressure
tap.
OUTLET
INLET
Gas Valve ON/OFF Selector Switch
Outlet Pressure
Inlet Pressure
Regulator
Cover Screw
White-Rodgers Model 36J22
Figure 48

36
NOTE: If measuring gas pressure at the drip leg, a
field-supplied hose barb fitting must be installed
prior to making the hose connection. If using the
inlet pressure tap on the White-Rodgers 36J22 gas
valve, then use the 36G/J Valve Pressure Check Kit,
Part No. 0151K00000S.
3. Turn ON the gas supply and operate the furnace and
all other gas consuming appliances on the same gas
supply line.
4. Measure furnace gas supply pressure with burners
ring. Supply pressure must be within the range
specied in the Inlet Gas Supply Pressure table.
Gas Range No minal
Natural 3.2 - 3.8" w.c. 3.5" w.c.
Propane 9.7 - 10.3" w.c. 10.0" w.c.
Manifold Gas Pressure
If supply pressure diers from table, make the necessary
adjustments to pressure regulator, gas piping size, etc.,
and/or consult with local gas utility.
5. Turn OFF gas to furnace at the manual shuto valve
and disconnect manometer. Reinstall plug before
turning on gas to furnace.
6. Turn OFF any unnecessary gas appliances stated in
step 3.
Mode
10.0
Gas Manifold Pressure Measurement and
Adjustment
Only small variations in gas pressure should be made by
adjusting the gas valve pressure regulator. The manifold
pressure must be measured with the burners operating.
To measure and adjust the manifold pressure, use the
following procedure.
1. Turn OFF gas to fur nace at the manual gas shuto
valve external to the furnace.
2. Turn o all electrical power to the system.
3. Outlet pressure tap connections:
White-Rodgers 36J22 valve: Back outlet pressure
test screw (inlet/outlet pressure tap) out one turn
(counterclockwise, not more than one turn).
4. Attach a hose and manometer to the outlet pressure
tap (White-Rodgers valve).
5. Turn ON the gas supply.
6. Turn on power and close thermostat “R” and “W”
contacts to provide a call for heat.
7. Measure the gas manifold pressure with burners
ring. Adjust manifold pressure using the Manifold
Gas Pressure table shown on this page.
8. Remove regulator cover screw from the outlet
pressure regulator adjust tower and turn screw
clockwise to increase pressure or counterclockwise
to decrease pressure. Replace regulator cover
screw.
9. Turn o all electrical power and gas supply to the
system.
10. Remove the manometer hose from the hose barb
tting or outlet pressure tap.
11. Replace outlet pressure tap: White-Rodgers 36J22
valve: Turn outlet pressure test screw in to seal
pressure port (clockwise, 7 in-lb minimum).
12. Turn on electrical power and gas supply to the
system.
13. Close thermostat contacts “R” and “W” to energize
the valve.
Using a leak detection solution or soap suds, check for
leaks at outlet or screw (White-Rodgers valve). Bubbles
forming indicate a leak. SHUT OFF GAS AND REPAIR ALL
LEAKS IMMEDIATELY!
NOTE: For gas to gas conversion, consult your
dealer for appropriate conversion.
CAUTION
To prevent unreliable operation or equipment damage, the
inlet gas supply pressure must be as specified on the unit
rating plate with all other household gas fired appliances
operating.
Gas Input Rate Measurement (Natural Gas Only)
The actual gas input rate to the furnace must never be
greater than that specied on the unit rating plate. To
measure natural gas input using the gas meter, use the
following procedure.

37
SUPPLY
AIR
RETURN
AIR
Temperature Rise Measurement
Figure 50
OPERATIONAL CHECKS
The burner ames should be inspected with the burner
compartment door installed. Flames should be stable,
quiet, soft, and blue (dust may cause orange tips but
they must not be yellow). Flames should extend directly
outward from the burners without curling, oating, or lifting
o. Flames must not impinge on the sides of the heat
exchanger ring tubes.
SAFETY CIRCUIT DESCRIPTION
A number of safety circuits are employed to ensure safe
and proper furnace operation. These circuits serve to
control any potential safety hazards and serve as inputs
in the monitoring and diagnosis of abnormal function.
These circuits are continuously monitored during furnace
operation by the integrated control module.
Do not bypass safety devices.
WARNING
Integrated Control Module
The integrated control module is an electronic device
which, if a potential safety concern is detected, will take the
necessary precautions and provide diagnostic information
through an LED.
Primary Limit
The primary limit control is located on the partition panel
and monitors heat exchanger compartment temperatures.
It is a normally-closed (electrically), automatic reset,
temperature-activated sensor. The limit guards against
overheating as a result of insucient conditioned air
passing over the heat exchanger.
1. Turn OFF the gas supply to all other gas-burning
appliances except the furnace.
2. While the furnace is operating at high re rate, time
and record one complete revolution of the gas meter
dial, measuring the smallest quantity, usually the dial
that indicates 1/2 cu. ft. per revolution. You will use
this number to calculate the quantity of gas in cubic
ft. if the furnace would consume if it ran steadily for
one hour (3600 seconds).
3. If the 1/2 cu. ft. dial was used, multiply your number x 2.
EXAMPLE: If it took 23 seconds to complete one
revolution of the 1/2 ft. dial (23 x 2 = 46).
This tells us that at this rate, it would take 46 seconds to
consume one cu. ft. of gas. 3600 / 46 = 78.
This tells us that in one hour, the furnace would consume
78 cu. ft. of gas.
The typical value range for 1 cu. ft. of natural gas is around
1000 BTU. Check with your gas utility, if possible. In this
example, the furnace is consuming 78,000 BTUH.
NOTE: The final manifold pressure cannot vary by
more than ± 0.3” w.c. for Natural and + 0.5” for LP
from the specified setting. Consult your local
gas supplier if additional input rate adjustment is
required.
4. Turn ON gas to and relight all other appliances
turned o in step 1. Be certain that all appliances
are functioning properly and that all pilot burners are
operating.
Temperature Rise
Temperature rise must be within the range specied on the
unit rating plate. An incorrect temperature rise may result
in condensing in or overheating of the heat exchanger.
An airow and temperature rise table is provided in the
Specication Sheet applicable to your model. Determine
and adjust temperature rise as follows:
1. Operate furnace with burners ring for approximately
ten minutes. Ensure all registers are open and all
duct dampers are in their nal (fully or partially open)
position.
2. Place thermometers in the return and supply ducts
as close to the furnace as possible. Thermometers
must not be inuenced by radiant heat by being able
to “see” the heat exchanger.
3. Subtract the return air temperature from the supply
air temperature to determine the air temperature rise.
Allow adequate time for thermometer readings to
stabilize.
4. Adjust temperature rise by adjusting the circulator
blower speed. Increase blower speed to reduce
temperature rise. Decrease blower speed to increase
temperature rise. Refer to Startup Procedure and
Adjustment - Circulator Blower Speeds for speed
changing details.

38
Auxiliary Limit
The auxiliary limit controls are located on or near the
circulator blower and monitors blower compartment
temperatures. They are a normally closed (electrically),
manual reset sensors. These limits guard against
overheating as a result of insucient conditioned air
passing over the heat exchanger.
Rollout Limit
The rollout limit controls are mounted on the burner/
manifold assembly and monitor the burner ame. They are
normally closed (electrically), manual reset sensors. These
limits guard against burner ames not being properly drawn
into the heat exchanger.
Pressure Switches
The pressure switches are normally-open (closed during
operation) negative air pressure-activated switches. They
monitor the airow (combustion air and ue products)
through the heat exchanger via pressure taps located on
the induced draft blower and the coil front cover. These
switches guard against insucient airow (combustion
air and ue products) through the heat exchanger and/or
blocked condensate drain conditions.
Flame Sensor
The ame sensor is a probe mounted to the burner/
manifold assembly which uses the principle of ame
rectication to determine the presence or absence of ame.
MAINTENANCE
Annual Inspection
The furnace should be inspected by a qualied installer, or
service agency at least once per year. This check should
be performed at the beginning of the heating season.
This will ensure that all furnace components are in proper
working order and that the heating system functions
appropriately. Pay particular attention to the following
items. Repair or service as necessary.
• Flue pipe system. Check for blockage and/or
leakage. Check the outside termination and the
connections at and internal to the furnace.
• Heat exchanger. Check for corrosion and/or buildup
within the heat exchanger passageways.
• Burners. Check for proper ignition, burner ame, and
ame sense.
• Drainage system. Check for blockage and/or
leakage. Check hose connections at and internal to
furnace.
• Wiring. Check electrical connections for tightness
and/or corrosion. Check wires for damage.
• Filters.
• R-32 Sensor Wire. Check R-32 sensor wire
connection for tightness and check wire for damage.
FILTERS
Filter Maintenance
Improper lter maintenance is the most common cause of
inadequate heating or cooling performance. Filters should
be cleaned (permanent) or replaced (disposable) every two
months or as required. When replacing a lter, it must be
replaced with a lter of the same type and size.
Filter Removal
Depending on the installation, diering lter arrangements
can be applied. Filters can be installed in either the central
return register or a side panel external lter rack (upow
only). A media air lter or electronic air cleaner can be used
as an alternate lter. Follow the lter sizes given in the
Recommended Minimum Filter size table to ensure proper
unit performance.
To remove lters from an external lter rack in an upright
upow installation, follow the directions provided with
external lter rack kit.
Horizontal Unit Filter Removal
Filters in horizontal installations are located in the central
return register or the ductwork near the furnace.
To remove:
1. Turn OFF electrical power to furnace.
2. Remove lter(s) from the central return register or
ductwork.
3. Replace lter(s) by reversing the procedure for
removal.
4. Turn ON electrical power to furnace.
Media Air Filter or Electronic Air Cleaner
Removal
Follow the manufacturer’s directions for service.
Burners
Visually inspect the burner ames periodically during the
heating season. Turn on the furnace at the thermostat and
allow several minutes for ames to stabilize, since any
dislodged dust will alter the ames normal appearance.
Flames should be stable, quiet, soft, and blue (dust may
cause orange tips but they must not be yellow). They
should extend directly outward from the burners without
curling, oating, or lifting o. Flames must not impinge on
the sides of the heat exchanger ring tubes.
Induced Draft and Circulator Blowers
The bearings in the induced draft blower and circulator
blower motors are permanently lubricated by the
manufacturer. No further lubrication is required. Check
motor windings for accumulation of dust which may cause
overheating. Clean as necessary.

39
Burner Flame
Condensate Trap and Drain System
(Qualified Servicer Only)
Annually inspect the drain tubes, drain trap, and eld-
supplied drain line for proper condensate drainage. Check
drain system for hose connection tightness, blockage, and
leaks. Clean or repair as necessary.
Flame Sensor (Qualified Servicer Only)
Under some conditions, the fuel or air supply can create a
nearly invisible coating on the ame sensor. This coating
acts as an insulator causing a drop in the ame sense
signal. If the ame sense signal drops too low the furnace
will not sense ame and will lock out. The ame sensor
should be carefully cleaned by a qualied servicer using
emery cloth or steel wool. Following cleaning, the ame
sense signal should be as indicated in the Specications
Sheet.
Flue Passages (Qualified Servicer Only)
The heat exchanger ue passageways should be
inspected at the beginning of each heating season.
BEFORE LEAVING AN INSTALLATION
• Cycle the furnace with the thermostat at least three
times. Verify cooling and fan only operation.
• Review the Owner’s Manual with the homeowner
and discuss proper furnace operation and
maintenance.
• Leave literature packet near furnace.
REPAIR AND REPLACEMENT PARTS
• When ordering any of the listed functional parts, be
sure to provide the furnace model, manufacturing,
and serial numbers with the order.
• Although only functional parts are shown in the parts
list, all sheet metal parts, doors, etc. may be ordered
by description.
• Parts are available from your distributor.
Functional Parts List-
Gas Valve Blower Motor
Gas Manifold Blower Wheel
Natural Gas Orice Blower Mounting Bracket
Propane Gas Orice Blower Cuto
Igniter Blower Housing
Flame Sensor Pressure Switch
Rollout Limit Switch Door Switch
Primary Limit Switch Auxiliary Limit Switch
Coil Front Cover Integrated Control Module
Transformer Door Switch
Induced Draft Blower
Heat Exchanger with Recuperator Coil

40
1 STAGE STATUS CODES
1 STAGE STATUS CODES
STATUS MENU
Main Menu Option Menu
Active Alarm menu
Er r Exx
( xx: code numbers )
Last 10 Faults
F10 Exx
( xx: code numbers )
Code Release Number
Cr
CR Number
Reset to Factory Default
r Fd yes, no
Blower Speed for Continous Fan Mode
FSd Fxx
( xx: Blower Speed Number F01,
F02.. )
Blower Speed for 1st Stage Compressor
Mode
AC1 Fxx
( xx: Blower Speed Number F01,
F02.. )
Blower Speed for 2nd Stage Compressor
Mode
AC2 Fxx
( xx: Blower Speed Number F01,
F02.. )
Cool On Delay
Cnd
Delay, Seconds
Default set at 7 Secs,
Adjustments can be made in 7
Secs increments from 0 to 35
Secs
Cool Off Delay
Cf d
Delay, Seconds
Default set at 65 Secs,
Adjustments can be made in 5
Secs increments from 0 to 120
Secs
Blower Speed for Gas Heat Mode
gAF Fxx
( xx: Blower Speed Number F01,
F02.. )
Gas Heat On Delay
gnd
Delay, Seconds
Default set at 30 Secs,
Adjustments can be made in 5
Secs increments from 5 to 30
Secs
Gas heat Off Delay
gFd
Delay, Seconds
Default set at 90 Secs,
Adjustments can be made in 30
Secs increments from 30 to 180
Secs
Automatic Heat Staging - For Two Stage
Control
AHS
no, 10, 20, 30,
60, AUt
Refer to Section " CHANGING
HEATING MODE SETTING"
A2L Function Verification
A2u yes, no
Refer to the R-32 Information
Section
A2L Function Enabled
A2E yes, no
Refer to the R-32 Information
Section
Menu Description
LED Display
Notes
Idle
I dL
Continous Fan
FAn
Compressor Cooling, Low Stage
1 AC
Compressor Cooling, High Stage
2 AC
Gas heat - Single Stage Control
gH
OEM test Mode
EOL
Mode
Main
Menu

41
1 STAGE TROUBLESHOOTING CODES
Symptom
LED
Status
Fault Description Corrective Actions
Normal operation
I dL
Normal operation None
Locate and correct gas interruption
Check front cover pressure switch operation and verify
proper drainage (hose, wiring, contact operation),
correct if necessary
Replace or realign igniter
Check flame sense signal, clean sensor if coated or
oxidized
Check flue piping for blockage, proper length, elbows,
and termination
Verify proper induced draft blower performance
Pressure switch circuit is closed at start
of heating cycle
Pressure switch contacts sticking
Short in pressure switch circuit wiring
Pressure switch circuit is not closed
Pressure switch hose blocked pinched,
or connected improperly
Inspect flue and/or inlet air piping for blockage, proper
length, elbows, and termination
Check drain system, correct as necessary
Check induced draft blower performance, correct as
necessary
Incorrect pressure switch set point or
malfunctioning switch contacts
Check pressure switch operation, replace as needed
Loose or improperly connected wiring Tighten or correct wiring connection
Primary limit circuit is open
Check filters and ductwork for blockage Clean filters or
remove obstruction
Insufficient conditioned air over the heat
exchanger
Check circulator blower speed and performance
Blocked filters, restrictive ductwork,
improper circulator blower speed, or
failed circulator blower motor
Correct speed or replace blower motor if necessary
Loose or improperly connected wiring in
high limit circuit
Tighten or correct wiring connection
Flame sensed with no call for heat Correct short at flame sensor or in flame sensor wiring
Short to ground in flame sense circuit
Lingering burner flame Slow closing gas
valve
Induced draft blower
and circulator blower
runs continuously
No furnace operation
EE4
Check for lingering or lazy flame Verify proper operation
of gas valve
Induced draft blower
runs continuously with
no furnace operation
EE2
Inspect pressure switch hose, repair/replace if
necessary
Blocked flue and/or inlet air pipe, blocked
drain system or weak induced draft
blower
Circulator blower runs
continuously
No furnace operation
EE3
Furnace fails to
operate
EE0
Furnace lockout due to an excessive
number of ignition “retries” (3 total)
Failure to establish flame
Loss of flame after establishment
Furnace fails to
operate
EE1
Replace low stage pressure switch Repair short in
wiring

42
1 STAGE TROUBLESHOOTING CODES
Symptom
LED
Status
Fault Description Corrective Actions
Open fuse Replace fuse
Short in low voltage wiring Locate and correct short in low voltage wiring
Flame sense micro amp signal is
minimal
Flame sensor is coated/oxidized
Flame sensor incorrectly positioned in
burner fame
Check inlet air piping for blockage, proper length,
elbows, and termination
Compare current gas pressure to rating plate and adjust
as needed
Problem with igniter circuit
Check and correct wiring from integrated control
module to igniter
Improperly connected or shorted igniter
Poor unit ground
Igniter relay fault on integrated control
module
Check igniter output from control, replace if necessary
Polarity of 115 volt AC is reversed Correct polarity, check and correct wiring if necessary
Poor unit ground Verify proper ground, correct if necessary
Gas valve is not energized when it
should be
Check wiring in gas valve circuit
External Gas Valve Error Replace integrated control board
Gas valve is energized when it should
not be
Check wiring in gas valve circuit
Internal gas valve error Replace integrated control board
Furnace fails to
operate.
No 115 power to furnace or no 24 volt
power to integrated control module.
Restore high voltage power to furnace and integrated
control module.
Blown fuse or tripped circuit breaker
Correct condition which caused fuse to open, replace
fuse
Integrated control module is non-
functional
Replace non-functional integrated control module.
Furnace fails to
operate
E10
Grounding fault
Poor neutral connection
Verify neutral wire connection to furnace & continuity to
ground source
Furnace fails to
operate
EEb
Furnace fails to
operate
EEC
None
Integrated control
module LED display
provides no signal
Furnace fails to
operate
EEL
Diagnose and replace shorted igniter as needed Verify
and correct unit ground wiring if needed
Furnace fails to
operate
EEA
No furnace operation
EE5
Normal furnace
operation
EE6
Clean flame sensor if coated or oxidized Inspect for
proper flame sensor alignment
Lazy burner flame due to improper gas
pressure or combustion air

43
Symptom
LED
Status
Fault Description Corrective Actions
Furnace fails to
operate
E11
Open roll out switch
Check for correct gas pressure Check for correct
burner alignment
Check for and correct burner restriction
Furnace fails to
operate
EEn
Ignitor Open
Check for Ignitor wiring.
Replace Damaged Ignitor
Furnace fails to
operate
EEJ
Inducer relay Error Replace integrated control board
Twinning feature not
working
EEH
TWIN Error
Check for wiring connections.
Replace integrated control board
Furnace fails to
operate
EEE
Internal Faults or IRQ Loss in Control
Board
Replace integrated control board
Furnace fails to
operate and goes
to hard lockout
EbL
Main blower motor is consuming
very little current after heat on
delay, below an expected value
Check for loose motor wiring connections.
Verify if the blower motor is burnt, replace
blower motor if found burnt
Furnace fails to
operate and goes
to hard lockout
EbU
Main blower motor is consuming
too much current during inducer
pre-purge, above an expected
value.
Verify wiring connections to and from motor
are not loose.
Verify that line
voltage wires to the control
and the main blower motor are not reversed
at the control.
Furnace stops heating
and only the fan is
operating
EAF
Furnace has lost communication with the
R-32 sensor and the furnace is in
mitigation mode.
Verify wire connection to R-32 sensor is not loose.
Verify that the R-32 sensor wire is not damaged.
Replace R-32 Sensor.
Furnace stops heating
and only the fan is
operating
EAL
R-32 sensor has detected a refrigerant
leak and furnace is in mitigation mode.
Investigate the indoor coil for a refrigerant leak.
Furnace will resume normal operation once a leak is not
detected and the 5 minute delay period is over.
Furnace stops heating
and only the fan is
operating
EAS
R-32 sensor has detected a fault and the
furnace is in mitigation mode.
Investigate the R-32 sensor.
Replace the R-32 sensor.
Furnace stops heating
and only the fan is
operating
Ear
A2L relay in the furnace control board
has detected a fault and the furnace is in
mitigation mode.
Investigate A2L relay.
Cycle power on the furnace.
Replace integrated control board.
Furnace may not be paired with an R-32 cooling unit.
Refer to the R-32 Information Section.
1 STAGE TROUBLESHOOTING CODES
To View & Clear Fault Codes
• Press either the Left or Right switch until L 6 F is displayed.
• Press the center switch to view stored faults.
• Press and hold the center switch for 5 to 30 seconds.
• All stored faults will be erased, and the display will ash - - - three times and return to L 6 F.

44
AIRFLOW TABLES
NOTE:
FURNACE MODEL
Y2 Y1
1. F04 is Default Speed for Y/Y1
*D9S961005CN F06 F01 2. F05 is Default Speed for Y2
*D9S961205DN F04 F05 3. F01 is Default Speed for G
4. For a single-stage outdoor unit, the Y connec�on from the thermostat can be connected to the Y/Y1 or Y2 connec�on on the
furnace control module. A call for cooling will energize that connec�on on the furnace control module. The desired cooling fan
speed should be adjusted for the furnace control module connec�on used (Y1 or Y2) to provide the correct cooling airflow.
RECOMMENDED AIRFLOW SPEEDS FOR CONNECTIO
N
WITH 2 STAGE OUTDOOR MODELS
*D9S96
0.1 0.2 0.3 0.4
CFM CFM CFM CFM CFM Watts CFM Watts CFM Watts CFM Watts
F01 632 574 510 448 388 80 332 85 277 89 234 93
F02 727 677 623 565 510 101 455 106 403 111 351 116
F03 878 839 797 751 701 146 653 151 607 157 561 162
F04^ 948 910 870 828 785 169 739 175 693 181 652 187
F05 1106 1076 1044 1010 974 243 939 250 899 256 860 263
F06 1156 1125 1096 1063 1028 268 996 276 960 282 927 290
F07 1237 1205 1174 1145 1115 317 1081 324 1050 332 1016 341
F08 1334 1306 1275 1249 1220 385 1194 391 1163 398 1136 408
F09 1382 1354 1327 1302 1276 418 1246 424 1219 432 1190 439
F01 771 698 632 560 491 104 428 110 372 115 307 119
F02 1197 1150 1102 1057 1014 254 968 262 926 272 877 279
F03 1309 1264 1224 1180 1141 318 1098 325 1058 334 1018 343
F04^ 1138 1091 1043 993 949 227 901 235 853 243 805 249
F05 944 884 824 774 716 151 660 158 605 163 554 169
F06 963 907 852 803 745 160 689 166 639 173 587 179
F07 1332 1289 1245 1200 1160 327 1120 335 1081 343 1036 353
F08 1366 1319 1277 1235 1192 347 1154 354 1117 363 1074 371
F09 1468 1436 1393 1359 1323 418 1285 427 1248 436 1210 445
F01 873 778 682 630 578 90 490 94 419 100 347 105
F02 1442 1386 1335 1280 1221 288 1157 297 1110 307 1054 316
F03 1643 1588 1534 1478 1415 339 1357 350 1299 361 1246 375
F04^ 1600 1555 1505 1460 1412 375 1364 384 1309 395 1260 403
F05 1338 1269 1206 1133 1063 211 999 220 934 229 861 239
F06 1796 1744 1691 1638 1584 430 1532 441 1473 453 1422 462
F07 1874 1823 1775 1729 1675 482 1621 492 1567 500 1512 517
F08 1798 1754 1719 1672 1627 500 1585 510 1546 520 1497 530
F09 1991 1947 1900 1854 1808 573 1759 585 1707 592 1655 606
F01 1176 1107 1037 969 891 184 825 194 753 201 692 207
F02 1773 1721 1671 1621 1571 465 1521 474 1470 485 1421 495
F03 1709 1658 1607 1556 1503 426
1451 436 1399 445 1349 455
F04^ 1651 1597 1542 1491 1437 392 1384 401 1332 410 1278 421
F05 1467 1409 1352 1307 1240 297 1182 306 1124 315 1063 325
F06 1834 1785 1738 1691 1643 513 1593 522 1545 532 1502 543
F07 1924 1881 1836 1796 1750 583 1701 592 1652 602 1606 614
F08 2028 1994 1937 1899 1863 683 1814 690 1769 702 1724 713
F09 2193 2145 2106 2076 2032 844 1998 852 1945 862 1903 874
F01 1187 1101 1013 931 847 165 764 174 677 180 604 186
F02 1973 1916 1864 1810 1756 502 1702 513 1650 525 1590 536
F03 1918 1859 1807 1748 1696 463 1643 476 1591 486 1531 497
F04^ 1835 1776 1720 1657 1602 414 1544 425 1483 436 1428 447
F05 1236 1152 1073 990 919 181 834 190 749 198 679 204
F06 1521 1459 1391 1327 1253 271 1187 281 1116 291 1053 302
F07 1673 1609 1549 1493 1430 345 1362 354 1305 365 1242 375
F08 2033 1981 1929 1878 1822 541 1771 553 1716 565 1669 578
F09 2257 2201 2151 2099 2057 704 2008 719 1959 732 1906 742
*D9S960403B*
Y/Y1, Y2, G
*D9S960603B*
Y/Y1, Y2, G
*D9S960804C*
Y/Y1, Y2, G
*D9S961005C*
Y/Y1, Y2, G
*D9S961205D*
Y/Y1, Y2, G
FAN & COOLING AIFLOW
MODEL
THERMOSTAT
CALL
TAP #
EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
0.5
0.6
0.7
0.8

45
AIRFLOW TABLES
0.6 0.7 0.8
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
F01^^
632 N/A 574 N/A 510 N/A 448 N/A 388 N/A 332 277 234
F02^
727 48 677 51 623 54 565 60 510 65 455 403 351
F03
878 41 839 42 797 45 751 47 701 51 653 607 561
F04
948 38 910 39 870 41 828 43 785 45 739 693 652
F01^^
771 N/A 698 N/A 632 N/A 560 N/A 491 N/A 428 372 307
F02^
1197 45 1150 46 1102 48 1057 50 1014 53 968 926 877
F03
1309 41 1264 42 1224 44 1180 45 1141 47 1098 1058 1018
F04
1138 47 1091 49 1043 51 993 54 949 56 901 853 805
F01^^
873 N/A 778 N/A 682 N/A 630 N/A 578 N/A 490 419 347
F02^
1442 49 1386 51 1335 53 1280 56 1221 58 1157 1110 1054
F03
1643 43 1588 45 1534 46 1478 48 1415 50 1357 1299 1246
F04
1600 44 1555 46 1505 47 1460 49 1412 50 1364 1309 1260
F01^^
1176 N/A 1107 N/A 1037 N/A 969 N/A 891 N/A 825 753 692
F02^
1773 50 1721 52 1671 53 1621 55 1571 57 1521 1470 1421
F03^^
1709 52 1658 54 1607 55 1556 57 1503 59 1451 1399 1349
F04
1651 54 1597 56 1542 58 1491 60 1437 62 1384 1332 1278
F01^^
1187 N/A 1101 N/A 1013 N/A 931 N/A 847 N/A 764 677 604
F02^
1973 54 1916 56 1864 57 1810 59 1756 61 1702 1650 1590
F03
1918 56 1859 57 1807 59 1748 61 1696 63 1643 1591 1531
F04
1835 58 1776 60 1720 62 1657 64 1602 67 1544 1483 1428
NOTE:
HEATING AIRFLOW
TEMP
RANGE
0.1
0.2
0.3
0.4
0.5
35-65
W/W1 35-65
^DEFAULT & RECOMMENDED
45-75
W/W1 40-70
W/W1 40-70
^^NOT RECOMMENDED FOR HEATING
W/W1
W/W1
MODEL TSTAT CALL TAP #
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
*D9S960403B*
*D9S960603B*
*D9S960804C*
*D9S961005C*
*D9S961205D*
*D9S96

46
AIRFLOW TABLES
NOTE:
FURNACE MODEL
Y2 Y1
*R9S921205DN F08 F05
RECOMMENDED AIRFLOW SPEEDS FOR CONNECTION
WITH 2 STAGE OUTDOOR MODELS
1. F04 is Default Speed for Y/Y1
2. F05 is Default Speed for Y2
3. F01 is Default Speed for G
4. For a single-stage outdoor unit, the Y connec�on from the thermostat can be connected to the Y/Y1 or Y2
connec�on on the furnace control module. A call for cooling will energize that connec�on on the furnace control
module. The desired cooling fan speed should be adjusted for the furnace control module connec�on used (Y1 or
Y2) to provide the correct cooling airflow.
*R9S92
0.1 0.2 0.3 0.4
CFM CFM CFM CFM CFM Watts CFM Watts CFM Watts CFM Watts
F01 610 559 513 467 419 84 368 89 316 95 285 98
F02 925 887 852 818 787 181 754 187 720 192 685 200
F03 846 808 772 737 703 149 667 155 630 161 594 167
F04^ 781 739 701 663 625 129 586 133 547 139 508 144
F05 1038 1003 970 940 909 232 879 239 849 245 820 251
F06 1106 1072 1041 1011 981 271 953 278 926 285 898 291
F07 1215 1180 1151 1121 1095 336 1066 343 1043 352 1017 361
F08 1238 1210 1180 1153 1126 360 1099 368 1073 376 1047 383
F09 1319 1299 1273 1246 1220 429 1194 436 1169 444 1146 455
F01 723 663 604 539 476 93 404 99 347 104 291 110
F02 1052 1010 962 920 875 181 829 189 785 198 740 206
F03 1125 1084 1042 1003 964 211 918 218 875 227 834 237
F04^ 1206 1166 1129 1091 1054 249 1012 258 977 267 947 277
F05 901 854 809 758 703 136 653 145 604 151 552 159
F06 948 900 855 810 762 149 708 156 662 164 608 172
F07 1273 1237 1206 1169 1128 286 1094 294 1057 302 1020 311
F08 1365 1321 1292 1251 1219 331 1184 341 1152 349 1120 358
F09 1426 1387 1360 1326 1292 374 1257 383 1226 392 1193 400
F01 718 662 611 551 486 99 419 104 358 111 300 115
F02 1373 1341 1307 1279 1253 410 1226 414 1197 420 1172 428
F03 1309 1265 1232 1192 1162 324 1129 332 1093 337 1057 347
F04^ 1233 1194 1165 1131 1097 309 1070 317 1039 324 1008 330
F05 874 828 791 750 703 147 655 153 602 157 547 164
F06 950 908 865 826 786 168 739 175 689 181 638 188
F07 1097 1056 1019 988 952 236 921 243 880 248 842 255
F08 1166 1127 1092 1060 1027 268 994 276 960 281 926 286
F09 1407 1373 1338 1308 1282 424 1253 431 1229 438 1203 446
F01 804 740 670 586 501 93 407 98 347 103 0 0
F02 1422 1375 1332 1288 1245 271 1200 281 1154 290 1108 299
F03 1502 1455 1410 1365 1322 304
1278 314 1237 325 1195 335
F04^ 1567 1519 1476 1441 1402 339 1360 349 1319 361 1278 371
F05 1347 1299 1253 1205 1157 238 1111 245 1063 255 1013 263
F06 1692 1648 1609 1567 1529 406 1490 416 1451 428 1413 440
F07 1772 1728 1689 1652 1614 456 1574 462 1534 474 1498 486
F08 1793 1753 1720 1679 1643 470 1604 479 1562 489 1524 500
F09 1875 1833 1797 1759 1727 529 1686 539 1652 552 1616 563
F01 869 782 684 575 482 100 395 104 331 110 122 58
F02 1823 1776 1720 1679 1642 409 1597 424 1553 442 1504 456
F03 1778 1729 1690 1648 1605 398 1558 412 1497 425 1449 439
F04^ 1722 1660 1609 1553 1507 350 1455 369 1402 383 1350 395
F05 1498 1442 1388 1332 1278 264 1215 277 1154 290 1090 301
F06 1634 1583 1536 1489 1440 325 1387 339 1330 351 1275 365
F07 1925 1879 1836 1795 1752 471 1711 489 1664 503 1621 521
F08 1993 1941 1899 1852 1813 508 1778 525 1741 545 1693 560
F09 2216 2172 2131 2087 2046 663 2011 681 1973 697 1935 717
F01 809 740 669 603 536 98 449 105 377 110 319 115
F02 1754 1707 1673 1640 1604 487 1568 493 1538 505 1509 514
F03 1648 1620 1586 1552 1515 426 1480 435 1449 442 1412 454
F04^ 1558 1517 1479 1441 1403 368 1366 378 1330 386 1295 396
F05 1303 1255 1210 1167 1125 241 1081 250 1041 260 999 271
F06 1406 1362 1321 1281 1240 283 1197 291 1157 301 1118 311
F07 1445 1403 1363 1324 1287 307 1247 315 1208 325 1167 336
F08 1778 1743 1700 1669 1634 508 1600 518 1568 530 1542 544
F09 1824 1785 1747 1714 1680 536 1647 548 1617 559 1585 568
F01 906 813 717 613 519 103 439 109 368 114 0 0
F02 1871 1818 1769 1720 1667 435 1614 446 1565 459 1511 468
F03 1831 1782 1729 1679 1624 413 1571 424 1520 437 1465 449
F04^ 1653 1596 1538 1480 1422 324 1362 335 1306 346 1247 357
F05 1496 1437 1376 1315 1250 259 1189 269 1126 279 1056 288
F06 1640 1587 1527 1471 1414 314 1357 324 1294 336 1235 347
F07 1955 1937 1909
1860 1813 513 1765 527 1712 541 1662 553
F08 2086 2039 1991 1944 1896 574 1855 588 1810 593 1763 607
F09 2222 2178 2133 2088 2043 683 1998 699 1954 711 1910 727
F01 1056 962 866 772 666 130 574 136 501 143 429 150
F02 2096 2050 2005 1948 1899 532 1848 545 1800 559 1755 575
F03 2023 1973 1927 1877 1829 488 1781 501 1731 515 1680 532
F04^ 1946 1900 1848 1795 1741 441 1689 455 1637 470 1584 485
F05 1231 1151 1078 992 913 171 812 181 725 189 651 196
F06 1503 1440 1382 1318 1251 256 1179 270 1108 281 1039 293
F07 1704 1646 1586 1532 1473 328 1412 340 1346 357 1284 372
F08 1831 1775 1720 1668 1610 388 1560 401 1511 413 1457 430
F09 2222 2173 2125 2078 2029 607 1980 622 1933 636 1884 652
*R9S920804C*
Y/Y1, Y2, G
*R9S920805C*
Y/Y1, Y2, G
*R9S921004C*
Y/Y1, Y2, G
*R9S921005C*
Y/Y1, Y2, G
*R9S921205D*
Y/Y1, Y2, G
*R9S920403A*
Y/Y1, Y2, G
*R9S920603B*
Y/Y1, Y2, G
*R9S920803B*
Y/Y1, Y2, G
FAN & COOLING AIFLOW
MODEL
THERMOSTAT
CALL
TAP #
EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
0.5
0.6
0.7
0.8

47
AIRFLOW TABLES
0.6 0.7 0.8
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
F01^^ 610
56
559
N/A
513
N/A
467
N/A
419
N/A
368 316 285
F02^ 925
37
887
38
852
40
818
42
787
43
754 720 685
F03 846
40
808
42
772
44
737
46
703
49
667 630 594
F04 781
44
739
46
701
49
663
51
625
55
586 547 508
F01^^
723 N/A 663 N/A 604 N/A 539 N/A 476 N/A 404 347 291
F02^
1052 49 1010 51 962 53 920 56 875 58 829 785 740
F03
1125 45 1084 47 1042 49 1003 51 964 53 918 875 834
F04
1206 42 1166 44 1129 45 1091 47 1054 48 1012 977 947
F01^^
718 N/A 662 N/A 611 N/A 551 N/A 486 N/A 419 358 300
F02^
1373 50 1341 51 1307 52 1279 53 1253 54 1226 1197 1172
F03
1309 52 1265 54 1232 55 1192 57 1162 59 1129 1093 1057
F04
1233 55 1194 57 1165 59 1131 60 1097 62 1070 1039 1008
F01^^
804 N/A 740 N/A 670 N/A 586 N/A 501 N/A 407 347 N/A
F02^
1422 48 1375 50 1332 51 1288 53 1245 55 1200 1154 1108
F03
1502 45 1455 47 1410 48 1365 50 1322 52 1278 1237 1195
F04
1567 44 1519 45 1476 46 1441 47 1402 49 1360 1319 1278
F01^^
869 N/A 782 N/A 684 N/A 575 N/A 482 N/A 395 331 122
F02^
1823 37 1776 38 1720 40 1679 41 1642 41 1597 1553 1504
F03
1778 38 1729 39 1690 40 1648 41 1605 42 1558 1497 1449
F04
1722 40 1660 41 1609 42 1553 44 1507 45 1455 1402 1350
F01^^
809 N/A 740 N/A 669 N/A 603 N/A 536 N/A 449 377 319
F02^
1754 49 1707 50 1673 51 1640 52 1604 53 1568 1538 1509
F03
1648 52 1620 53 1586 54 1552 55 1515 56 1480 1449 1412
F04
1558 55 1517 56 1479 58 1441 59 1403 61 1366 1330 1295
F01^^
906 N/A 813 N/A 717 N/A 613 N/A 519 N/A 439 368 N/A
F02^
1871 46 1818 47 1769 48 1720 50 1667 51 1614 1565 1511
F03
1831 47 1782 48 1729 49 1679 51 1624 52 1571 1520 1465
F04^^
1653 52 1596 53 1538 55 1480 58 1422 60 1362 1306 1247
F01^^
1056 N/A 962 N/A 866 N/A 772 N/A 666 N/A 574 501 429
F02^
2096 49 2050 50 2005 51 1948 52 1899 54 1848 1800 1755
F03
2023 51 1973 52 1927 53 1877 54 1829 56 1781 1731 1680
F04^^
1946 53 1900 54 1848 55 1795 57 1741 59 1689 1637 1584
NOTE:
^DEFAULT & RECOMMENDED
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
MODEL TSTAT CALL TAP #
W/W1 30-60
*R9S920603B* W/W1 35-65
^^NOT RECOMMENDED FOR HEATING
*R9S921005C* W/W1
*R9S920803B* W/W1
*R9S921004C* W/W1
*R9S920804C* W/W1
*R9S920805C* W/W1
35-65
*R9S921205D* W/W1 35-65
HEATING AIRFLOW
35-65
25-55
35-65
TEMP
RANGE
0.1
0.2
0.3
0.4
0.5
35-65
*R9S920403A*
*R9S92

48
AIRFLOW TABLES
NOTE:
FURNACE MODEL
Y2 Y1
*R9S960805CN F02 F05
*R9S961205DN F08 F05
RECOMMENDED AIRFLOW SPEEDS FOR CONNECTION
WITH 2 STAGE OUTDOOR MODELS
1. F04 is Default Speed for Y/Y1
2. F05 is Default Speed for Y2
3. F01 is Default Speed for G
4. For a single-stage outdoor unit, the Y connec�on from the thermostat can be connected to the Y/Y1 or Y2 connec�on on the furnace
control module. A call for cooling will energize that connec�on on the furnace control module. The desired cooling fan speed should be
adjusted for the furnace control module connec�on used (Y1 or Y2) to provide the correct cooling airflow.
*R9S96
0.1 0.2 0.3 0.4
CFM CFM CFM CFM CFM Watts CFM Watts CFM Watts CFM Watts
F01 705 661 617 564 509 103 455 108 405 115 362 120
F02 1079 1055 1027 994 965 256 935 264 906 271 863 277
F03 915 881 846 814 780 174 737 180 695 186 652 193
F04^ 887 855 823 790 751 164 705 170 666 176 608 183
F05 1135 1106 1078 1049 1021 281 994 290 965 299 933 306
F06 1189 1163 1138 1111 1085 321 1059 331 1032 341 1001 349
F07 1266 1243 1218 1197 1172 372 1148 383 1123 394 1099 400
F08 1313 1288 1261 1239 1215 403 1189 412 1165 422 1143 432
F09 1342 1324 1305 1280 1263 440 1239 452 1216 463 1193 473
F01 758 696 636 572 512 104 460 110 412 115 354 121
F02 1218 1178 1140 1100 1060 275 1016 284 977 292 937 299
F03 1164 1123 1084 1042 1003 249 960 258 920 268 871 276
F04^ 1121 1083 1041 996 953 230 906 236 861 245 818 252
F05 902 851 801 746 689 145 637 153 585 158 542 164
F06 960 917 864 812 764 164 708 171 661 179 614 184
F07 1273 1240 1207 1171 1128 309 1089 318 1051 327 1012 336
F08 1335 1301 1266 1228 1192 347 1154 356 1118 365 1078 373
F09 1427 1390 1362 1327 1297 408 1260 414 1224 423 1193 434
F01 715 658 589 524 465 93 412 99 360 104 279 108
F02 1415 1385 1355 1322 1291 394 1255 403 1219 407 1186 417
F03 1388 1360 1325 1291 1259 375 1223 385 1191 393 1157 403
F04^ 1290 1252 1215 1182 1143 311 1107 319 1071 329 1032 337
F05 916 867 817 767 710 147 657 154 608 159 563 166
F06 985 940 892 842 797 169 746 176 693 184 649 190
F07 1118 1078 1037 992 952 222 910 230 863 239 822 247
F08 1191 1153 1114 1074 1034 255 993 264 951 272 911 281
F09 1471 1440 1409 1377 1347 427 1314 436 1283 446 1247 456
F01 1019 952 878 796 706 138 619 144 542 150 485 157
F02 1791 1743 1700 1663 1626 472 1583 487 1538 499 1489 510
F03 1625 1559 1512 1468 1425 359
1370 369 1325 385 1271 395
F04^ 1537 1490 1447 1403 1354 326 1301 337 1247 347 1190 357
F05 1289 1234 1180 1122 1058 217 991 226 917 234 840 242
F06 1431 1375 1329 1283 1227 276 1169 285 1108 295 1043 304
F07 1836 1784 1741 1703 1664 496 1628 515 1585 528 1537 540
F08 1919 1890 1846 1807 1771 566 1735 585 1694 600 1650 613
F09 1952 1921 1885 1843 1804 590 1769 611 1731 629 1691 643
F01 1029 959 890 811 727 149 647 157 579 163 511 170
F02 1814 1766 1722 1679 1637 486 1595 502 1555 517 1511 531
F03 1893 1844 1803 1763 1723 541 1685 556 1641 569 1604 588
F04^ 1738 1680 1637 1596 1554 437 1510 452 1469 465 1420 477
F05 1193 1135 1087 1016 950 198 880 208 805 217 738 225
F06 1421 1369 1323 1272 1222 283 1168 295 1108 306 1045 318
F07 1582 1536 1491 1445 1404 358 1358 370 1309 382 1255 395
F08 1962 1919 1889 1851 1816 601 1780 620 1743 638 1702 655
F09 2068 2024 1986 1947 1912 692 1873 709 1837 726 1797 744
F01 1008 934 855 779 702 142 628 148 557 155 493 161
F02 2026 1981 1929 1901 1858 659 1819 677 1773 685 1733 701
F03 1921 1879 1840 1791 1751 577 1705 588 1656 604 1610 617
F04^ 1804 1755 1710 1664 1619 490 1574 502 1526 514 1479 524
F05 1475 1421 1369 1314 1260 307 1207 317 1152 326 1097 337
F06 1626 1578 1522 1475 1427 381 1353 390 1328 401 1283 412
F07 1693 1639 1588 1542 1491 422 1437 432 1390 442 1340 453
F08 1775 1723 1674 1629 1580 472 1529 485 1484 497 1435 508
F09 2161 2122 2084 2048 2010 739 1973 755 1940 776 1914 796
F01 1118 1035 952 860 750 149 663 156 590 165 519 171
F02 2143 2095 2047 2002 1954 619 1891 632 1850 647 1802 663
F03 2025 1977 1930 1897 1848 539 1798 553 1750 567 1703 583
F04^ 1906 1877 1828 1778 1726 474 1674 487 1622 501 1568 515
F05 1220 1145 1070 995 907 177 811 187 725 194 651 201
F06 1684 1620 1561 1499 1438 345 1378 358 1318 371 1259 383
F07 1766 1712 1666
1612 1558 387 1506 401 1450 412 1395 425
F08 1863 1807 1754 1698 1642 432 1587 445 1532 459 1476 472
F09 2454 2396 2347 2296 2250 889 2202 905 2157 922 2113 941
*R9S961205D*
Y/Y1, Y2, G
*R9S960804C*
Y/Y1, Y2, G
*R9S960805C*
Y/Y1, Y2, G
*R9S961005C*
Y/Y1, Y2, G
*R9S960403A*
Y/Y1, Y2, G
*R9S960603B*
Y/Y1, Y2, G
*R9S960803B*
Y/Y1, Y2, G
FAN & COOLING AIFLOW
MODEL
THERMOSTAT
CALL
TAP #
EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
0.5
0.6
0.7
0.8

49
AIRFLOW TABLES
0.6 0.7 0.8
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
F01^^ 705
50
661
54
617
N/A
564
N/A
509
N/A
455 405 362
F02^ 1079
33
1055
34
1027
35
994
36
965
37
935 906 863
F03 915
39
881
40
846
42
814
44
780
46
737 695 652
F04 887
40
855
42
823
43
790
45
751
47
705 666 608
F01^^
758 N/A 696 N/ A 636 N/A 572 N/A 512 N/A 460 412 354
F02^
1218 44 1178 45 1140 47 1100 48 1060 50 1016 977 937
F03
1164 46 1123 47 1084 49 1042 51 1003 53 960 920 871
F04
1121 48 1083 49 1041 51 996 54 953 56 906 861 818
F01^^
715 N/A 658 N/ A 589 N/A 524 N/A 465 N/A 412 360 279
F02^
1415 50 1385 51 1355 52 1322 54 1291 55 1255 1219 1186
F03
1388 51 1360 52 1325 54 1291 55 1259 57 1223 1191 1157
F04
1290 55 1252 57 1215 59 1182 60 1143 62 1107 1071 1032
F01^^
1019 N/A 952 N/A 878 N/A 796 N/A 706 N/A 619 542 485
F02^
1791 40 1743 41 1700 42 1663 43 1626 44 1583 1538 1489
F03
1625 44 1559 46 1512 47 1468 48 1425 50 1370 1325 1271
F04
1537 46 1490 48 1447 49 1403 51 1354 53 1301 1247 1190
F01^^
1029 N/A 959 N/A 890 N/A 811 N/A 727 N/A 647 579 511
F02^
1814 39 1766 40 1722 41 1679 42 1637 43 1595 1555 1511
F03
1893 38 1844 39 1803 39 1763 40 1723 41 1685 1641 1604
F04
1738 41 1680 42 1637 43 1596 45 1554 46 1510 1469 1420
F01^^
1008 N/A 934 N/A 855 N/A 779 N/A 702 N/A 628 557 493
F02^
2026 44 1981 45 1929 46 1901 47 1858 48 1819 1773 1733
F03
1921 46 1879 47 1840 48 1791 50 1751 51 1705 1656 1610
F04
1804 49 1755 51 1710 52 1664 53 1619 55 1574 1526 1479
F01^^
1118 N/A 1035 N/A 952 N/A 860 N/A 750 N/A 663 590 519
F02^
2143 50 2095 51 2047 52 2002 53 1954 55 1891 1850 1802
F03
2025 53 1977 54 1930 55 1897 56 1848 58 1798 1750 1703
F04^^
1906 56 1877 57 1828 58 1778 60 1726 62 1674 1622 1568
HEATING AIRFLOW
25-55
30-60
35-65W/W1
*R9S960603B* W/W1
*R9S960803B* W/W1
*R9S960804C* W/W1
*R9S960805C* W/W1
*R9S961005C* W/W1
*R9S961205D*
35-65
25-55
TEMP
RANGE
25-55W/W1
35-65
*R9S960403A*
MODEL TSTAT CALL
^^NOT RECOMMENDED FOR HEATING
NOTE:
TAP #
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.1
0.2
0.3
0.4
0.5
^DEFAULT & RECOMMENDED
*R9S96

50
WIRING DIAGRAM *R9S92 / *R9S96 / *D9S96
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple
power sources may be present. Failure to do so may cause property
damage, personal injury or death.
ERROR CODE STATUS
READ CODES FROM LEFT TO RIGHT
SEVEN SEGMENT DISPLAY
Seg#3 Seg#2 Seg#1
INTERNAL FAULTS OR IRQ LOSS E E E
LOCKOUT DUE TO EXCESSIVE RETRIES RECYCLE E E0
PRESSURE SWITCH STUCK CLOSED E E1
PRESSURE SWITCH OPEN E E2
OPEN HIGH LIMIT SWITCH EE3
FLAME DETECTED WHEN NO FLAME SHOULD BE PRESENT E E4
OPEN FUSE EE5
LOW FLAME SIGNAL EE6
IGNITOR RELAY FAULT EEL
REVERSED LINE POLARITY OR GROUNDING ERROR EEA
INTERNAL GAS VALVE ERROR EEb
EXTERNAL GAS VALVE ERROR EEC
OPEN ROLLOUT SWITCH E11
IGNITOR OPEN EEn
INDUCER RELAY ERROR E EJ
ERROR CODE STATUS
READ CODES FROM LEFT TO RIGHT
SEVEN SEGMENT DISPLAY
Seg#3 Seg#2 Seg#1
TWIN ERROR EEH
GROUNDING ERROR E10
LOW CIRCULATOR CURRENT EbL
CIRCULATOR CURRENT UNEXPECTED EbU
A2L COMMUNICATION ALARM EAF
A2L LEAKAGE ALARM EAL
A2L INTERNAL ALARM EAS
A2L RELAY ALARM EAr
N
JUNCTION
BOX
L
DISCONNECT
GND
WH
BK
GND
GR
GR
GND
RD
24
VAC
115
VAC
BK
BR
WH
PK
RD
LIMIT
CONTROL
AUXILIARY
AUTO RESET
PK
40 VA
TRANSFORMER
G
C
SENSOR
FLAME
1 ROLL OUT SWITCH
SOME UNITS MAY HAVE
PU
RD
WH
YL
LIMIT CONTROL
AUTO RESET PRIMARY
WH
1
BK
PK
RD
L
N
DOOR OPEN)
(OPEN WHEN
DOOR SWITCH
COMPARTMENT
BLOWER
BLOWER
CIRCULATOR
CONNECTOR
2 CIRCUIT
GND
IGNITER
SURFACE
HOT
2
BLOWER
DRAFT
INDUCED
BK
BLOWER COMPARTMENT
ECM MOTOR
HARNESS
BK
BURNER COMPARTMENT
1
2
3
4
5
6
7
8
9
10
11
12
EAC-H
XFMR-H
CIRC-H
LINE-H
E20
E39
E2
E1
E15
E8
E5
E4
E3
E7
E6
LEFT
CENTER
RIGHT
SW331313 SW1
R223
SW2
6
R226
RD
YL
RD
YL
YL
BK
BK
BK
WH
WH
WH
GY
BL
GR
PU
PU
NEUT2
NEUT1
CIRC-N
EAC-N
HUM-N
XFMR-N
LINE-N
RD
1
2
RD
BK
BK
WH
WH
WH
5
2
1
4
3
RD
BK
OR
BL
YL
RD
BL
OR
BK
YL
T1
T2
T3
T4
T5
COM
RD
YL
PU
TWIN
24V HUM
E21
E24
W/W1
R
Y/Y1
GC
Y2
GND
WH
GND
1
2
5V
A2L
ALARM
SPARE
VT-
OUT
VT-
IN
YL
ID BLOWER
PRESSURE
SWITCH
BR
GAS
VALVE
C
HI
NO
C
GY
FRONT COVER
PRESSURE
SWITCH
GY
GY
0140F20003-B
TO 115 VAC/ 1
/60 HZ
POWER SUPPLY WITH
OVERCURRENT
PROTECTION DEVICE
NOTES:
1. MANUFACTURER'S SPECIFIED REPLACEMENT
PARTS MUST BE USED WHEN SERVICING.
2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED
WITH THE FURNACE MUST BE REPLACED IT MUST
BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST
105
˚
C. USE COPPER CONDUCTORS ONLY.
3. UNIT MUST BE PERMANENTLY GROUNDED AND
CONFORM TO N.E.C. AND LOCAL CODES.
4. TO RECALL THE LAST 6 FAULTS, MOST RECENT
TO LEAST RECENT, DEPRESS SWITCH FOR MORE
THAN 2 SECONDS WHILE IN STANDBY
(NO THERMOSTAT INPUTS)
5. WHEN THIS FURNACE IS PAIRED WITH NON R-32
REFRIGERANT SYSTEMS, DEFAULT SETTINGS
WILL NEED TO BE CHANGED. REFER TO
INSTALLATION MANUAL FOR FURTHER
INSTRUCTIONS.
WIRE
COLOR:
YL
WH
BL
BK
RD
OR
PK
GY
TN
GR
BR
YELLOW
WHITE
BLUE
BLACK
RED
ORANGE
BROWN
PINK
GRAY
TAN
GREEN
PURPLE
VIOLET
COLOR
DESIGNATION:
PU
VT
SWITCH (PRESSURE)
FIELD SPLICE
FIELD GROUND
EQUIPMENT GROUND
PROTECTION DEVICE
PLUG CONNECTION
SWITCH (TEMPERATURE)
JUNCTION
OVERCURRENT
TERMINAL
IGNITER
HIGH VOLTAGE (115V)
HIGH VOLTAGE FIELD
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
WARNING: DISCONNECT
POWER BEFORE
SERVICING. WIRING
TO UNIT MUST BE
PROPERLY POLARIZED
AND GROUNDED
NO
C
A2L MODE IS ENABLED BY
DEFAULT
REFER TO INSTALLATION MANUAL
FOR FURTHER INSTRUCTIONS.
A2L SENSOR
CONNECTOR

51
SPECIAL INSTRUCTIONS FOR PRODUCTS INSTALLED IN THE STATE OF
MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where
the side wall exhaust vent termination is less than seven
(7) feet above nished grade in the area of the venting,
including but not limited to decks and porches, the following
requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE
DETECTORS. At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing
plumber or gastter shall observe that a hard wired
carbon monoxide detector with an alarm and battery
back-up is installed on the oor level where the gas
equipment is to be installed. In addition, the installing
plumber or gastter shall observe that a battery
operated or hard wired carbon monoxide detector
with an alarm is installed on each additional level of
the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall
be the responsibility of the property owner to secure
the services of qualied licensed professionals for the
installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented
gas fueled equipment is installed in a crawl space or
an attic, the hard wired carbon monoxide detector
with alarm and battery back-up may be installed on
the next adjacent oor level.
b. In the event that the requirements of this subdivision
can not be met at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30)
day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in
accordance with the above provisions shall comply
with NFPA 720 and be ANSI/UL 2034 listed and IAS
certied.
3. SIGNAGE. A metal or plastic identication plate shall
be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade
directly in line with the exhaust vent terminal for the
horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print size no less
than one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the
side wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon monoxide
detectors and signage installed in accordance with the
provisions of 248 CMR 5.08(2)(a)1 through 4.
EXEMPTIONS
The following equipment is exempt from 248 CMR 5.08(2)
(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure used
in whole or in part for residential purposes.
VENT/FLUE
TEE
COMBUSTION
AIR INTAKE.
DISTANCE BETWEEN
COMBUSTION AIR
INTAKE AND GRADE
DISTANCE BETWEEN
VENT AND GRADE
c. MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side
wall horizontally vented gas equipment provides
a venting system design or venting system
components with the equipment, the instructions
provided by the manufacturer for installation of the
equipment and the venting system shall include:
3. Detailed instructions for the installation of the venting
system design or the venting system components and;
4. A complete parts list for the venting system design or
venting system.
d. MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does
not provide the parts for venting the ue gases, but
identies “special venting systems”, the following
requirements shall be satised by the manufacturer:
5. The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
6. The “special venting systems” shall be Product
Approved by the Board, and the instructions for that
system shall include a parts list and detailed installation
instructions.
e. A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists
for venting instructions, and/or all venting design
instructions shall remain with the appliance or
equipment at the completion of the installation.

52
START-UP CHECKLIST
Furnace
ELECTRICAL
Line Voltage (Measure L1 to N and N to Ground Voltage) L - N
N - G
Secondary Voltage (Measure Transformer Output Voltage) R - C
Blower Amps
BLOWER EXTERNAL STATIC PRESSURE
Return Air Sta�c Pressure IN. W.C.
Supply Air Sta�c Pressure IN. W.C.
Total External Sta�c Pressure (Ignoring +/- from the reading above, add total here) IN. W.C.
TEMPERATURES
Return Air Temperature (Dry bulb / Wet bulb) DB °F WB °F
DB °F WB °F
Hea�ng Supply Air Temperature DB °F
Temperature Rise DB °F
Delta T (Differenc
e between Supply and Return Temperatures) DB °F
GAS PRESSURES
Gas Inlet Pressure IN. W.C.
Gas Manifold Pressure (Low Fire) IN. W.C.
Gas Manifold Pressure (High Fire) IN. W.C.
Gas Type (NG) = Natural Gas / (LP) = Liquid Propane
Addi�onal Checks
Check wire rou�ngs for any rubbing
Check for kinked pressure switch tubing.
Check flue elbow for alignment and clamp �ghtness.
Check screw �ghtness on blower wheel.
Check factory wiring and wire c
onnec�ons.
Check product for proper clearances as noted by installa�on instruc�ons
°F to °C formula: (°F - 32) divided by 1.8 = °C °C to °F formula: (°C mul�plied by 1.8) + 32 = °F
Model Number
Serial Number
Cooling Supply Air Temperature (Dry bulb / Wet bulb)
Check R-32 sensor wire is connected properly (if applicable)

53
THIS PAGE LEFT INTENTIONALLY BLANK.

54
THIS PAGE LEFT INTENTIONALLY BLANK.

55
THIS PAGE LEFT INTENTIONALLY BLANK.

56
19001 Kermier Rd. Waller, TX 77484
www.goodmanmfg.com • www.amana-hac.com
© 2023 Daikin Comfort Technologies Manufacturing, L.P.
is a registered trademark of Maytag Corporation or its related companies and is used under
license. All rights reserved.
CUSTOMER FEEDBACK
We are very interested in all product comments.
Please ll out the feedback form on one of the following links:
Goodman
®
Brand Products: (http://www.goodmanmfg.com/about/contact-us).
Amana
®
Brand Products: (http://www.amana-hac.com/about-us/contact-us).
You can also scan the QR code on the right for the product brand
you purchased to be directed to the feedback page.
GOODMAN
®
BRAND
AMANA
®
BRAND
GOODMAN
®
BRAND
AMANA
®
BRAND
PRODUCT REGISTRATION
Thank you for your recent purchase. Though not required to get the protection of
the standard warranty, registering your product is a relatively short process, and
entitles you to additional warranty protection, except that failure by California and
Quebec residents to register their product does not diminish their warranty rights.
The duration of warranty coverages in Texas and Florida diers in some cases.
For Product Registration, please register as follows:
Goodman
®
Brand products: (https://www.goodmanmfg.com/product-registration).
Amana
®
Brand products: (http://www.amana-hac.com/product-registration).
You can also scan the QR code on the right for the product brand
you purchased to be directed to the Product Registration page.