Mitsubishi 1886268 20000 BTU Dual-Zone Mini Split System 9+9 with Wall Mount Indoor Unit, 20 SEER, 12.7 EER, Wireless Remote Controller, AHRI Certified, cETLus Certification, DC Inverter Technology

User Manual - Page 6

For 1886268.

PDF File Manual, 24 pages, Read Online | Download pdf file

1886268 photo
Loading ...
Loading ...
Loading ...
En-5
3-2. PIPE CONNECTION
1)Applyathincoatofrefrigerationoil(G)tothearedendsofthepipesandthe
pipe connections of the outdoor unit.
2) Align the center of the pipe with that of the pipe connections of the outdoor unit,
thenhandtightenthearenut3to4turns.
3)Tightenthearenutwithatorquewrenchasspeciedinthetable.
• Over-tightening maycause damage to the arenut, resultingin refrigerant
leakage.
• Besuretowrapinsulationaroundthepiping.Directcontactwiththebarepiping
may result in burns or frostbite.
3-3. INSULATION AND TAPING
1)Coverpipingjointswithpipecover.
2)Foroutdoorunitside,surelyinsulateeverypipingincludingvalves.
3) Using piping tape (E), apply taping starting from the entry of outdoor unit.
• Stoptheendofpipingtape(E)withtape(withadhesiveagentattached).
• Whenpipinghavetobearrangedthroughaboveceiling,closetorwherethe
temperature and humidity are high, wind additional commercially sold insulation
topreventcondensation.
WARNING
When installing the unit, securely
connect the refrigerant pipes before
starting the compressor.
CAUTION
When there are the ports which are
not used, make sure their nuts are
tightened securely.
Fig. 1 Fig. 2 Fig. 3
Fig. 4 Fig. 5 Fig. 6
TiltedUnevenBurred
Good
No good
Burr
Copper pipe
Spare reamer
Pipe cutter
Smooth all
around
Evenlength
all around
Inside is shin-
ing without any
scratches.
B
Flare nut
Die
Copper pipe
Clutch type
Flaring tool
Wing nut type
Copper
pipe
Pipe diameter
[inch (mm)]
B
[inch (mm)]
A [inch (mm)] Tightening torque
Clutch type tool for R410A Clutch type tool for R22 Wing nut type tool for R22 ft-Ib N•m kgf•cm
1/4 (ø6.35) 21/32 (17)
0 to 0.02
(0 to 0.5)
0.04 to 0.06
(1.0 to 1.5)
0.06 to 0.08
(1.5 to 2.0)
10 to 13 13.7 to 17.7 140 to 180
3/8 (ø9.52) 7/8 (22) 25 to 30 34.3 to 41.2 350 to 420
1/2 (ø12.7) 1-1/32 (26)
0.08 to 1.0
(2.0 to 2.5)
36 to 42 49.0 to 56.4 500 to 575
5/8 (ø15.88) 1-5/32 (29) 54 to 58 73.5 to 78.4 750 to 800
3-1. FLARING WORK
1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)
2)Completelyremoveallburrsfromthecutcrosssectionof
pipe. (Fig. 3)
• Aimthecopperpipedownwardwhileremovingburrsto
preventburrsfromdroppinginthepipe.
3)Removearenutsattachedtoindoorandoutdoorunits,
thenputthemonpipehaving completedburrremoval.
(Notpossibletoputthemonafteraringwork.)
4)Flaringwork (Fig.4,5).Firmly holdcopperpipe in the
dimension shown in the table. Select A inch (mm) from
the table according to the tool selected.
5)Check
• ComparethearedworkwithFig.6.
• Ifareisnotedtobedefective,cutoffthearedsection
anddoaringworkagain.
4-1.PURGINGPROCEDURESANDLEAKTEST
1)Removeserviceportcapofstopvalveonthesideoftheoutdoorunitgaspipe.
(Thestopvalvesarefullyclosedandcoveredincapsintheirinitialstate.)
2)Connectgaugemanifoldvalveandvacuumpumptoserviceportofstopvalve
on the side of the outdoor unit gas pipe.
3)Runthevacuumpump.(Vacuumizeformorethan15minutes.)
4)Check thevacuum withgauge manifold valve,then closegauge manifold
valve,andstopthevacuumpump.
5)Leaveasitisforoneortwominutes.Makesurethepointerofgaugemanifold
valveremainsinthesameposition.Conrmthatpressuregaugeshows-14.7
psi[Gauge](-0.101MPa).
6)Removegaugemanifoldvalvequicklyfromserviceportofstopvalve.
7)Fullyopenallstopvalvesonthegaspipeandtheliquidpipe.Operatingwithout
fully opening lowers the performance and this causes trouble.
8)Referto1-2.,andchargetheprescribedamountofrefrigerantifneeded.Be
sure to charge slowly with liquid refrigerant. Otherwise, composition of the
refrigerant in the system may be changed and affect performance of the air
conditioner.
9)Tightencapofserviceporttoobtaintheinitialstatus.
10
)Leaktest
3. FLARING WORK AND PIPE CONNECTION
4. PURGINGPROCEDURES,LEAKTEST,ANDTESTRUN
Stopvalve
forGAS
Stopvalvecap
(Torque 19.6 to
29.4N•m,200
to300kgf•cm)
Gaugemanifold
valve(forR410A)
Compound pressure
gauge (for R410A)
–0.101MPa
(–760mmHg)
Handle
Low
HandleHigh
Vacuumpump
(for R410A)
*Close
*Open
Hexagonalwrench
*4 to 5 turns
Stopvalve
forLIQUID
Pressure gauge
(for R410A)
Precautions when us-
ingthecontrolvalve
Whenattachingthecontrolvalve
totheserviceport,valvecoremay
deform or loosen if excess pres-
sure is applied. This may cause
gasleak.
Serviceport
Charge hose
(for R410A)
Body
Close
Open
Control
valve
A
Whenattachingthecontrolvalveto
theserviceport,makesurethatthe
valvecoreisinclosedposition,and
then tighten part A. Do not tighten
partAorturnthebodywhenvalve
core is in open position.
Serviceportcap
(Torque 13.7 to
17.7N•m,140 to
180kgf•cm)
Charge hose
(for R410A)
BH79A325H03_en.indd 5 2018/08/06 13:12:25
Loading ...
Loading ...
Loading ...