FLUKE 1744 Three Phase Power Quality Logger Memobox

User Manual for the Fluke 1744 Three Phase Power Quality Logger Memobox - Page 33

For 1744.

PDF File Manual, 80 pages, Read Online | Download pdf file

1744 photo
Loading ...
Loading ...
Loading ...
Power Quality Logger
Using the Logger
17
Connect the Logger as follows:
Note
(Delta) or Υ (Wye) measurements
The 1744/1743 Logger is prepared for logging in 3-phase 4-wire
(Wye) systems (P-N), or 3-phase 3-wire (Delta) systems (P-P). Please
note the different types of connection and configuration in the PQ Log
software.
1. Connect all required measuring leads.
2. If you want to supply the Logger from an extra outlet, use the
supplied line power adapter. The power supply leads can also be
connected in parallel to the voltage test leads, but the voltage is
limited to 660 V RMS ac.
3. Connect the current clamp set or Flexi Set to the Logger.
4. Connect the current sensor to the conductor under test.
5. Connect the dolphin clips to the test leads. For 3-phase, 4-wire
systems, connect the N-test lead first, and then the other phases.
1.888.610.7664 sales@GlobalTestSupply.com
Fluke-Direct.com