Table of Parameters and Factory Settings
Parameter
Function
Set Range
Default
Parameter
Function
Set Range
Default
Set
Setpoint
-20°C / -5°F
C3H
Product
Temp. High
Temp. Alarm
C3L~40.0°C /
104°F
-17.2°C /
1°F
PAS
Password
00~99
15
C3L
Product
Temp. Low
Temp. Alarm
-40.0°C/-
40°F~C3H
-28.8°C /
-20°F
E1
Lowest set
-30°C / -22°F
-30°C / -22°F
C4
Hysteresis
0.1~20.0°C /
0.1°C /
point limit
Alarm
0.2~36.0°F
0.18°F
E2
Higher set
point limit
-10.0°C / 14°F
-10.0°C / 14°F
C5
Start-up
Temp. Alarm
delay
00~99 min
60 min
E3
Temp.
Hysteresis
0.1
~20.0°C /
0.2
~36.0°F
-15.7°C / 3.6°F
C6
Temp. Alarm
Delay
00~99 min
3 min
E40
Turning On
delay time
00 ~10 min.
3 min.
C7
Turn off
Relay
Alarm
00=do not alarm /
01= alarm
01
E41
Comp. start
delay time
00 ~10 min.
3 min.
C8
The alarm
relay closed
after
silencing
alarm relay
switch
00=open /
01=close
00
E5
Offset on Air
Temperature
-10.0~10.0°C / -
18.0~18.0°F
2.0°C / 3.6°F
C9
Restart
time after
buzzer is
muted
00=do not start /
01 ~30 min=restart
time
10 min
E6
Offset on
Product
Temp.
-10.0~10.0°C / -
18.0~18.0°F
0.0°C / 32°F
C10
Comp.
Force stop
time
01~99 min
99 min