Fuel Consumption
Shown below are the estimated fuel supply requirements.
NOTE: ft³/hr and m³/hr values are for vapor fuels and Gal/hr
is for liquid propane.
Power Connections
Compare this illustration with the generator to familiarize
yourself with the location of these connections.
Series 80000 NG Fuel Consumption
Full Load 1/2 Load No Load
BTU/hr 1,190,000 780,000 370,000
ft³/hr 1190 780 370
m³/hr 33.7 22.1 10.5
Series 100000 NG Fuel Consumption
Full Load 1/2 Load No Load
BTU/hr 1,400,000 880,000 370,000
ft³/hr 1400 880 370
m³/hr 39.6 24.9 10.5
Series 150000 NG Fuel Consumption
Full Load 1/2 Load No Load
BTU/hr 1,970,000 1,105,000 290,000
ft³/hr 1970 1105 290
m³/hr 55.8 31.3 8.2
Series 130000 LP Fuel Consumption
Full Load 1/2 Load No Load
BTU/hr 1,757,500 1,650,000 437,500
Gal/hr 19.3 11.2 4.8
B
C
A
A - Power Connection - Power connection to transfer
switch.
B - Neutral Connection - Connect to transfer switch neutral.
C - Ground Connection - Connect to transfer switch
ground.
Ground the generator per applicable codes, standards, and
regulations. There are two generator GND lug locations.
The location shown by (C, above) should suffice for most
applications. The second generator GND lug is located
on the frame. This should ONLY be used for a ground rod
located at the generator, if required by local codes.
For system connections such as remote start, e-stops,
and controller inputs and outputs, refer to the connection
diagrams on the following pages.
For power output connection, use 75°C (167°F) wire
rated for ambient temperature of 40°C (104°F) per
NEC Tables 310.15(B)(16) and 310.15(B)(2)(a).
For utility circuit connection, use #14 AWG minimum
600 volt, 167-194°F (75-90°C) wire.
For transfer switch communication, use #18 AWG
twisted pair conductors, no greater than 200 ft (60 m)
in length, 600 volt, 167-194°F (75-90°C) wire.
Series 125000 LP Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 1,787,500 1,000,000 412,500
ft³/hr 715 400 165
m³/hr 20.2 11.3 4.7
Gal/hr 19.5 10.9 4.5
Series 80000 LP Fuel Consumption
Full Load 1/2 Load No Load
BTU/hr 765,000 445,000 162,500
ft3/hr 306 178 65
m3/hr 8.7 5.0 1.8
Gal/hr 8.4 4.9 1.8
Series 200000 NG Fuel Consumption
Full Load 1/2 Load No Load
BTU/hr 2,469,000 1,358,000 371,000
ft³/hr 2469 1358 371
m³/hr 69.9 38.5 10.5