Rinnai CHS199100HIN Commercial Hybrid Water Heating System

Product's Documents

Below are documents related to this product, you can read online or download:
Installation Instruction Other Documents
  • Commercial Water Heating Solutions - RE/REP/CU/RSC - (English) Download
  • Demand Duo Compatibility Bms Gateway - CHS199-H/CHS398-H - (English) Download
Specification
  • Spec Sheet: Demand Duo H Series - (English) Download
  • Series Pump Change Technical Bullets - CHS160-H/CHS199-H/CHS130-H - (English) Download
CHS199100HIN photo

Installation and Operation Manual

This is the main product document for model CHS199100HIN. Additionally, the document applies to other Rinnai models: CHS160100HIP, CHS160100HIN, CHS16080HIN, CHS13080HIN, CHS13080HIP, CHS16080HIP, CHS19980HIN, CHS19980HIP

The file format is pdf, 56 pages, you can download this manual here .

background
Demand DuoH-Series Installation and Operation Manual
CHS13080HiN . ........ 80 Gallon, 130,000 BTU
CHS13080HiP . ........ 80 Gallon, 130,000 BTU
CHS16080HiN . ........ 80 Gallon, 160,000 BTU
CHS16080HiP . ........ 80 Gallon, 160,000 BTU
CHS19980HiN . ........ 80 Gallon, 199,000 BTU
CHS19980HiP . ........ 80 Gallon, 199,000 BTU
CHS160100HiN . ...... 100 Gallon, 160,000 BTU
CHS160100HiP . ...... 100 Gallon, 160,000 BTU
For Indoor Commercial Applications Only:
Single Tankless H-Series Demand Duo
This product is NOT intended for residential applications.
background
Demand DuoH-Series Installation and Operation Manual 2
If the informaon in these instrucons is not followed exactly, a
re or explosion may result causing property damage, personal
injury, or death.
Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers
instrucons.
If you cannot reach your gas supplier, call the re department.
Installaon and service must be performed by a trained and qualied professional, service
agency or the gas supplier.
WARNING WARNING
background
READ AND SAVE THESE INSTRUCTIONS
1. Welcome ....................................................................................................................... 4
2. Safety ............................................................................................................................ 5
2.1 Safety Symbols ....................................................................................................... 5
2.2 Safety Precautions .................................................................................................. 5
3. About ............................................................................................................................ 7
3.1 Components ............................................................................................................ 7
3.2 Specifications .......................................................................................................... 8
3.3 Dimensions ............................................................................................................. 10
4. Installation ..................................................................................................................... 12
4.1 Installation Guidelines ............................................................................................. 12
4.2 What You Will Need ................................................................................................ 13
4.3 Choose an Installation Location............................................................................... 13
5. Venting .......................................................................................................................... 17
5.1 Venting Requirements ............................................................................................. 17
5.2 Select a Vent Type .................................................................................................. 19
6. System Plumbing .......................................................................................................... 37
6.1 Pressure Relief Valve Requirements ....................................................................... 37
6.2 Temperature-PRV Requirements ............................................................................ 37
6.3 Typical Installations ................................................................................................. 38
6.4 Piping Diagram for Basic Installations ..................................................................... 40
6.5 Piping Diagram for Multiple Unit Installations........................................................... 41
6.6 Connect the Water Heater to the Water Supply ....................................................... 42
7. Gas and Power Supply .................................................................................................. 43
7.1 Connect the Gas Supply.......................................................................................... 43
7.2 Connect Electricity................................................................................................... 46
7.3 Pump Controller ...................................................................................................... 48
8. Post-Installation Checklist.............................................................................................. 49
9. Maintenance .................................................................................................................. 50
10.1 Replacement Parts ................................................................................................ 51
10.2 Service/Maintenance Log ...................................................................................... 53
10. Warranty ...................................................................................................................... 54
background
Demand DuoH-Series Installation and Operation Manual 4
Thank you for purchasing Rinnais Demand
DuoH-Series Commercial Hybrid Water
Heating System. This manual provides
information on the installation, operation, and
maintenance of Rinnais Demand DuoH-Series
Commercial Hybrid Water Heating System. Read
this manual completely before installing or
operating the system.
This manual is a supplement to the
Installation and Operation Manual for
Condensing Tankless Water Heaters; refer to
the tankless water heater installation and
operation manual for complete water heater
details, including:
Parameter Settings (High Altitude
Adjustment, Vent Length Adjustment, and
more)
Temperature Controller Installation
Performance Data
Diagnostic Codes
A trained and qualified professional must
install the system, inspect it, and leak test it
before use. The warranty may be voided due
to any improper installation.
The trained and qualified professional should
have skills such as:
Gas line sizing
Connecting gas lines, water lines, valves,
and electricity
Knowledge of applicable national, state,
and local codes
Installing venting through a wall or roof
Training in installation of tankless water
heaters. Training on Rinnai Tankless
Water Heaters is accessible at
www.trainingevents.rinnai.us.
Read all instructions in this manual before
installing the system. The system must be
installed according to the exact instructions in
this manual.
Proper installation is the responsibility of the
installer.
When installation is complete, leave this
manual with the system or give the manual
directly to the consumer.
You must read the entire manual to
properly operate the water heater and to
have regular maintenance performed.
Keep this manual for future reference.
As when using any appliance generating
heat, there are certain safety precautions
you should follow. See the Safety
Precautions section for detailed safety
precautions.
Be sure your water heater is installed by a
trained and qualified professional.
If installing in the state of Massachusetts,
you must read the Massachusetts State
Gas Regulations section in the tankless
water heater installation and operation
manual (supplied with tankless water
heater).
For Your Records
Dealer Name:
Dealer Phone #:
Purchase Date:
Tank Serial #:
System Serial #:
Tank Serial
Number Label
System Serial
Number Label
background
Demand DuoH-Series Installation and Operation Manual 5
This manual contains the following important
safety symbols. Always read and obey all safety
messages.
This is the safety alert symbol. This
symbol alerts you to potential hazards
that can kill or hurt you and others.
Indicates an imminently
hazardous situation which,
if not avoided, will result in personal injury or
death.
Indicates a potentially
hazardous situation
which, if not avoided, could result in minor or
moderate injury. It may also be used to alert
against unsafe practices.
DANGER
CAUTION
Indicates a potentially
hazardous situation
which, if not avoided, could result in personal
injury or death.
WARNING
WARNING
Before operating, smell all around the
appliance area for gas. Be sure to smell next
to the floor because some gas is heavier than
air and will settle on the floor.
Keep the area around the appliance clear and
free from combustible materials, gasoline, and
other flammable vapors and liquids.
Combustible construction refers to adjacent
walls and ceiling and should not be confused
with combustible or flammable products and
materials. Combustible and/or flammable
products and materials should never be stored
in the vicinity of this or any gas appliance.
Always check the water temperature before
entering a shower or bath.
To protect yourself from harm, before
performing maintenance:
Turn off the electrical power supply by
unplugging the power cord or by turning off
the electricity at the circuit breaker. (The
On/Offbutton on the temperature control-
ler does not control the electrical power.)
Turn off the gas at the gas valve, usually
located immediately before the water heat-
er.
Turn off the incoming water supply. This
can be done at the isolation valve
immediately before the water heater or by
turning off the water supply to the building.
Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, do not try to
repair it; call a licensed professional. Force or
attempted repair may result in a fire or explo-
sion.
Do not use this appliance if any part has been
under water. Immediately call a
trained and qualified professional to inspect
the appliance and to replace any part of the
control system and any gas control which has
been under water.
Do not use substitute materials. Use only
parts certified for the appliance.
Should overheating occur or the gas supply
fail to shut off, turn off the manual gas control
valve to the appliance.
Do not use an extension cord or an adapter
plug with this appliance.
Any alteration to the appliance or its controls
can be dangerous and will void the warranty.
If a water heater is installed in a closed water
supply system, such as one having a
backflow preventer in the cold water supply
line, means shall be provided to control
thermal expansion. Contact the water
supplier or local plumbing inspector on how to
control thermal expansion.
Topics in this section
Safety Symbols
Safety Precautions
background
Demand DuoH-Series Installation and Operation Manual 6
Only trained and qualified professionals are
permitted to adjust parameter settings.
Proper venting is required for the safe
operation of this appliance.
Flammable liquids such as cleaning solvents,
aerosols, paint thinners, adhesives, gasoline
and propane must be handled and stored with
extreme care. These flammable liquids emit
flammable vapors and when exposed to an
ignition source can result in a fire hazard or
explosion. Flammable liquids should not be
used or stored in the vicinity of this or any
other gas appliance.
DO NOT operate the water heater without the
front panel installed. The front panel should
only be removed for service/maintenance or
replacing internal components.
BURN HAZARD. Hot exhaust and vent may
cause serious burns. Keep away from the
water heater. Keep small children and animals
away from the water heater.
Hot water outlet pipes leaving the water heater
can be hot to touch.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of
this or any other appliance.
Install the vent system per local and national
codes.
Do not install this water heater above 10,200 ft
(3,109 m).
Do not obstruct combustion air to the water
heater.
Failure to properly vent this appliance can
result in death, personal injury and/or property
damage.
Rinnai recommends that every home have a
carbon monoxide (CO) alarm inside or directly
outside each bedroom or sleeping area. Check
batteries monthly and replace them annually.
DO NOT adjust the
internal gas valve. The
design is such that
adjustment is not required. Warranty will be
voided if the internal gas valve is adjusted.
WARNING
Keep the air intake location free of chemicals
such as chlorine or bleach that produce
fumes. These fumes can damage
components and reduce the life of your
appliance.
Make sure the water heater and its water
lines are protected from freezing. Damage
due to freezing is not covered by the
warranty.
FLAMMABLE
Flammable Vapors
WARNING
FOR YOUR SAFETY
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this
or any other appliance.
Hot water can be
dangerous, especially for
infants or children, the
elderly, or infirm.
There is hot water scald
potential if the thermostat
is set too high.
Water temperatures over
125ºF (51ºC) can cause
severe burns or scalding
resulting in death.
Hot water can cause first degree burns with
exposure for as little as:
3 seconds at 140ºF (60ºC)
20 seconds at 130ºF (54ºC)
8 minutes at 120ºF (48ºC)
Test the temperature of the water before placing
a child in the bath or shower.
Do not leave a child or an infirm person in the
bath unsupervised.
DANGER
background
Demand DuoH-Series Installation and Operation Manual 7
Figure 1: Components
Gas Flex Line
Flare Nut
Adapter
(Supplied but
not installed)
Pump
Electric Conduit
Dirt Leg
Gas Swivel
DuoSmart
Digital Controller
Front Cover
Topics in this section
Components
Specifications
Dimensions
background
Demand DuoH-Series Installation and Operation Manual 8
Appliance Type
Commercial Hybrid Water Heating System Consisting of Condensing Tankless
Water Heater, Insulated Storage Tank, Pump and Controller
Model CHS199100Hi CHS160100Hi CHS19980Hi CHS16080Hi CHS13080Hi
Minimum Gas Consumption Btu/hr (kW/hr) 15,000 (4.3)
Maximum Gas Consumption Btu/hr (kW/hr) 199,000 (58.3) 160,000 (46.9) 199,000 (58.3) 160,000 (46.9) 130,000 (38.1)
Tank Volume 119 Gallons (450 Liters) 80 Gallons (303 Liters)
First Hour Delivery at 100°F Rise
1
317 Gallons
(1,200 Liters)
271 Gallons
(1,026 Liters)
290 Gallons
(1,098 Liters)
244 Gallons
(924 Liters)
209 Gallons
(791 Liters)
Product Weight 431 lb (195 kg) 429 lb (195kg) 307 lb (139 kg) 305lb (138 kg) 305lb (138 kg)
Sound Level 49 dB 48 dB 49 dB 48 dB 48dB
Installation Type Internal (Indoor) Commercial Applications
Category Category IV
Ignition System Direct Electronic Ignition
Water Supply Pressure 150 PSI (Maximum)
Temperature Setting 98°F (37°C) to 185°F (85°C)
98°F (37°C) to
140°F (60°C)
3
Electrical Data
Normal 265 W 223 W 265 W 233 W 219 W
Standby 44 W 44 W 44 W 44 W 44 W
Freeze Protection 148 W 148 W 148 W 148 W 148 W
Max Current 5.5 A 5.5 A 5.5 A 5.5 A 5.5 A
Fuse Tankless Water Heater Engine: 10 Amps, Controller: 10 Amps
Gas Supply Pressure
2
Natural 3.5 - 10.5 in. w.c.
Propane 8.0 - 13.5 in. w.c.
By-Pass Flow Control Electronic
Connections
Gas Supply Inlet: 3/4 in. MNPT Hot Water Outlet: 1-1/2 in. MNPT
Cold Water Inlet: 1-1/2 in. MNPT
Electric Connections
Appliance: AC 120 Volts, 60Hz.
Integrated Temperature Controller: DC 12 Volts (Digital)
Water Temperature Control Simulation Feed Forward and Feedback
ENERGY STAR® Certified (Tankless engine) Yes
Complies with South Coast Air Quality
Management District 14 ng/J or 20 ppm NOx
Emission Levels
Yes
1
First Hour Delivery Rating is a theoretical calculation based on 70% usable tank capacity (Tank Capacity x .70 + (recovery) = First Hour Delivery
Rating
2
The maximum gas supply pressure must not exceed the value specified by the manufacturer.
3
Temperature limit of 185°F can be achieved using optional MCC-91 controller.
Rinnai products are continually being updated and improved; therefore, specifications are subject to change without prior not ice.
Table 1: Specifications
background
Demand DuoH-Series Installation and Operation Manual 9
Product
Number
Gas
Type
Input
U.S. Gallon / HR Liters / HR at Temperature Rise Indicated
Tank
Capacity
°F 30°F 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F 120°F 130°F 140°F
BTU/HR kW °C 17°C 22°C 28°C 33°C 39°C 44°C 50°C 56°C 61°C 67°C 72°C 78°C
CHS199100Hi
NG/
LP
199,000 58
119 Gals. GPH 780 585 468 390 334 292 260 234 213 195 180 167
450 Liters LPH 2,953 2,214 1,771 1,476 1,264 1,105 984 886 806 738 681 632
CHS160100Hi
NG/
LP
160,000 58
119 Gals. GPH 627 470 376 314 269 235 209 188 171 157 145 134
450 Liters LPH 2,374 1,780 1,424 1,187 1,017 890 791 712 647 593 548 509
CHS19980Hi
NG/
LP
199,000 58
80 Gals. GPH 780 585 468 390 334 292 260 234 213 195 180 167
303 Liters LPH 2,953 2,214 1,771 1,476 1,264 1,105 984 886 806 738 681 632
CHS16080Hi
NG/
LP
160,000 58
80 Gals. GPH 627 470 376 314 269 235 209 188 171 157 145 134
303 Liters LPH 2,374 1,780 1,424 1,187 1,017 890 791 712 647 593 548 509
CHS13080Hi
NG/
LP
130,000 58
80 Gals. GPH 509 382 306 255 218 191 170 153 139 127 118 109
303 Liters LPH 1,929 1446 1,157 964 827 723 643 579 526 482 445 413
Table 2: Recovery Capacity / Input
background
Demand DuoH-Series Installation and Operation Manual 10
RIGHT
TOP
FRONT
LEFT
Measurements below are
shown in inches (mm).
LEFT
RIGHT
Models
CHS199100Hi
CHS160100Hi
Figure 2: Dimensions
34.77 (883)
Ø 28.30 (718)
31.67 (804) Gas
34.84 (885) Vent
40.21 (1,021)
24.94
(633) T&P
30.88 (784) PRV
34.07 (865)
Condensate
3.40 (86)
Drain
4.20 (107)
1-1/2 in.
MNPT Cold
34.24 (869) PRV
56.74 (1,441) T&P
35.31 (897) Gas
69.40 (1,762)
71.10 (1,805) 1-1/2 in. MNPT Hot
background
Demand DuoH-Series Installation and Operation Manual 11
RIGHT
TOP
FRONT
LEFT
Models
CHS19980Hi
CHS16080Hi
CHS13080Hi
Measurements below
are shown in inches
(mm).
Figure 3: Dimensions
31.86 (809)
Ø 24.25 (616)
27.31 (694) Gas
30.59 (777) Vent
36 (914)
29.04 (738)
Condensate
29.04 (704) PRV
16.58
(421)
T&P
31.73 (806) Gas
54.28 (1,379) T&P
30.76 (781)
PRV
62.69 (1,592)
64.71 (1,643)
1-1/2 in. MNPT Hot
4.19 (106)1-1/2 in.
MNPT Cold
3.54 (90)
Drain
background
Demand DuoH-Series Installation and Operation Manual 12
THIS SECTION IS INTENDED FOR THE
INSTALLER
Installer qualifications: A trained and qualified
professional must install the appliance,
inspect it, and leak test the Demand Duo
before use. The warranty may be voided due
to any improper installation. The trained and
qualified professional should have skills such
as: Gas sizing; Connecting gas lines, water
lines, valves, and electricity; Knowledge of
applicable national, state, and local codes;
Installing venting through a wall or roof; and
training in installation of tankless water
heaters. Training for Rinnai Tankless Water
Heaters is accessible online at
www.trainingevents.rinnai.us.
This water heater is suitable for combination
water heating and space heating and not
suitable for space heating applications only.
The installation must conform with local
codes or, in the absence of local codes, with
the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, or the Natural Gas and Propane
Installation Code, CSA B149.1.
The appliance, when installed, must be
electrically grounded in accordance with local
codes or, in the absence of local codes, with
the National Electrical Code, ANSI/NFPA 70,
or the Canadian Electrical Code, CSA C22.1.
When installing the Demand Duo, follow these
guidelines:
DO NOT install the Demand DuoCom-
mercial Hybrid Water Heating System out-
doors.
DO NOT install the water heater in an area
where water leakage of the unit or connec-
tions will result in damage to the area adja-
cent to the appliance or to lower floors of
the structure. When such locations cannot
be avoided, it is required that a suitable
drain pan, adequately drained, be installed
under the water heater. The pan must not
restrict combustion air flow.
DO NOT install the water heater in an area
with negative air pressure.
DO NOT obstruct the flow of combustion
and ventilation air.
DO NOT use this appliance in an applica-
tion such as a pool or spa heater that uses
chemically treated water. This appliance is
suitable for filling large or whirlpool spa tubs
with potable water.
DO NOT use substitute parts that are not
authorized for this appliance.
Topics in this section
Installation Guidelines
What You Will Need
Choose an Installation Location
The appliance and its main gas valve must be
disconnected from the gas supply piping sys-
tem during any pressure testing of that sys-
tem at test pressures in excess of 1/2 psi (3.5
kPa) (13.84 in W.C.). For system testing at
pressures less than or equal to 1/2 psi (3.5
kPa) (13.84 in W.C.) the appliance must be
isolated from the gas supply piping by closing
its individual manual shutoff valve.
You must follow the installation instructions
and those in the venting section for adequate
combustion air and exhaust.
If a water heater is installed in a closed water
supply system, such as one having a back-
flow preventer in the cold water supply line,
means shall be provided to control thermal
expansion. Contact the water supplier or local
plumbing inspector on how to control thermal
expansion.
Should overheating occur or the gas supply
fail to shut off, turn off the manual gas control
valve to the appliance.
Combustion air must be free of chemicals,
such as chlorine or bleach, that produce
fumes. These fumes can damage compo-
nents and reduce the life of your appliance.
background
Demand DuoH-Series Installation and Operation Manual 13
Carefully unpack your system package and verify
the following contents are included.
If any items are damaged or missing, contact
your local dealer/distributor or call Rinnai
Customer Care at 1-800-621-9419. Do not
attempt to use any item that appears damaged.
Items included with system:
Rinnai Demand DuoCommercial Hybrid
Water Heating System
Temperature and Pressure Relief Valve
(pre-installed on tank)
Pressure Relief Valve (pre-installed on the
tankless water heater)
Installation and Operation Manual (this
manual)
Installation and Operation Manual for
Tankless Water Heater
2 in. PVC Vent Screens (x2) and Vent
Screen Screws
Gas Flex/Union
To avoid danger of
suffocation, keep
plastic bags away from babies, small children
and pets. Do not use these bags in cribs, beds,
carriages, or playpens. The bags are not a toy.
WARNING
Threading machine with heads and oiler
Core drill with diamond head
Torch set
Copper tubing cutter
Steel pipe cutter
Heat tape
5/8 in. ID PVC flexible tubing
Electrical wire
Concrete wall anchors
Optional pipe cover
PVC glue/cement and primer
2 conductor 22 AWG wire for controller
Single gang electrical box
Wire nuts
Unions and drain valves
Drain pan
Earthquake strap
When selecting an installation location, you must
ensure that clearances will be met and that the
vent length will be within required limits. Consider
the installation environment, water quality, and
need for freeze protection. Requirements for the
gas line, water lines, electrical connection, and
condensate disposal can be found in their
respective installation sections in this manual.
This section provides information on the
importance of water quality to the Rinnai
Tankless Water Heater. The information is
intended to serve as general guidelines only and
is not a complete list of water quality guidelines.
Consideration of care for your water heater
should include evaluation of water quality. The
water must be potable, free of corrosive chemi-
cals, sand, dirt, or other contaminants. It is up to
the installer to ensure the water does not
contain corrosive chemicals or elements that can
affect or damage the Rinnai Commercial Hybrid
Water Heating System. Water that contains
chemicals exceeding the levels below can dam-
age the Rinnai Tankless Water Heater. Replace-
ment of components due to water quality dam-
age is not covered by the warranty.
Pipe wrenches (x2)
Phillips Head screwdriver
Adjustable pliers
Wire cutters
Gloves
Safety glasses
Level
Soap or gas leak detector solution
Approved venting
Teflon tape (recommended) or pipe com-
pound
Pipe insulation
Hammer drill with concrete bits
Saw
background
Demand DuoH-Series Installation and Operation Manual 14
1. Choose the right hand truck to support the
weight and size of the water heater. Refer to
section “3.2 Specificationsin this manual for
specific weights and dimensions.
2. Use proper lifting techniques to load the
water heater onto the hand truck:
Position the water heater onto the hand
truck so the weight is evenly balanced
and the tank is touching the rails of the
hand truck.
Secure the water heater to the hand
truck:
Position STRAP A around the
tankless unit as illustrated below.
Position STRAP B around the base
of the tank below the lower
enclosure. Do not add strap around
the exhaust or vent connection.
Contaminant Maximum Level
Total Hardness Up to 200 mg/L
Aluminum * Up to 0.2 mg/L
Chlorides * Up to 250 mg/LL
Copper * Up to 1.0 mg/L
Dissolved Carbon Dioxide
(CO2)
Up to 15.0 mg/L
Iron * Up to 0.3 mg/L
Manganese * Up to 0.05 mg/L
pH * 6.5 to 8.5
TDS (Total Dissolved Solids) * Up to 500 mg/L
Zinc * Up to 5 mg/L
* Source: Part 143 National Secondary Drinking
Water Regulations
Air surrounding the water heater, venting, and
vent termination(s) is used for combustion and
must be free of any compounds that cause
corrosion of internal components. These include
corrosive compounds that are found in aerosol
sprays, detergents, bleaches, cleaning solvents,
oil based paints/varnishes, and refrigerants. The
air in beauty shops, dry cleaning stores, photo
processing labs, and storage areas for pool
supplies often contains these compounds.
Therefore, it is recommended to install as a direct
vent (use outside air for combustion). In
applications utilizing room air where there are
high levels of particulates, Rinnai offers a room
air screen.
The water heater, venting, and vent termination
(s) should not be installed in any areas where the
air may contain these corrosive compounds.
If you install this water heater in an area that is
known to have hard water or that causes scale
build-up, the water must be treated and may
require a more frequent flushing schedule.
This water heater includes a service indicator
(Service Soon, SS). When selected in the
parameter settings, an SS code will display on
the controller indicating that it is time to flush and
service the water heater. Scale build-up is
caused by hard water and can be accelerated if
the water heater is set at a temperature above
120°F.
Rinnai offers Southeastern Filtrations
ScaleCutter Water Conditioning Systemthat
offers superior lime scale prevention and
corrosion control by feeding a blend of control
compounds into the cold water supply.
Lower
Enclosure
Strap A
Strap B
Figure 4: Transport
Table 3: Water Quality Guidelines
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or ay
other appliance.
Flammable liquids such as cleaning solvents,
aerosols, paint thinners, adhesives, gasoline
and propane must be handled and stored with
extreme care. These flammable liquids emit
flammable vapors and when exposed to an igni-
tion source can result in a fire hazard or explo-
sion. Flammable liquids should not be used or
stored in the vicinity of this or any other gas ap-
pliance.
background
Demand DuoH-Series Installation and Operation Manual 15
Location Clearance
Top 2 in. (51 mm)
(0 in. from vent components)
** Clearance for servicing the
anode rods is 54 in. (137 cm)
from the top of the water
heater.
Bottom
(Ground)
0 in.
Front 6 in. (152 mm)
* Clearance for servicing is 24
in. (610 mm) in front of water
heater.
Back 0 in.
Sides (Left and
Right)
0 in.
0 in. Minimum
0 in. Minimum
0 in. Minimum
*6 in. Minimum
Door
** 12 in. Minimum
IMPORTANT
Product installed in the state of California
must be braced, anchored, or otherwise
secured to avoid motion or falling during an
earthquake. Contact the California Office of
the State Architect located at 1102 Q Street,
Suite 5100, Sacramento, CA 95811 for
instructions.
1. Loosen screws along the perimeter of the
plastic enclosures.
2. Remove plastic enclosures.
3. Position straps around the tank per the re-
quirements of California Office of the State
Architect. DO NOT POSITION THE STRAPS
OVER PIPE, FITTINGS or WIRE.
4. Replace the plastic enclosures. Modification
of the plastic enclosures may be necessary
to fit the enclosures over the earthquake
straps.
5. Replace the screws around the perimeter of
the plastic enclosures.
STRAP
Plastic
Enclosure
(Side)
Plastic
Enclosure
(Bottom)
STRAP
Figure 5: Clearances
Figure 6: Earthquake Strapping
Table 4: Clearances
background
Demand DuoH-Series Installation and Operation Manual 16
The water heater is not exposed to
corrosive compounds in the air.
The water heater location complies with
the required clearances.
The planned combustion air and exhaust
termination locations meet the required
clearances.
The water supply does not contain
chemicals or exceed total hardness that
will damage the heat exchanger.
A standard 3 prong 120 VAC, 60 Hz
properly grounded wall outlet or other 120
VAC, 60 Hz source is available.
The installation must conform with local
codes or, in the absence of local codes,
with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or the Natural Gas and
Propane Installation Code, CSA B149.1.
Use this checklist to ensure you have selected
the correct location for the water heater.
background
Demand DuoH-Series Installation and Operation Manual 17
When installed as direct vent, refer to the
Tankless Water Heater Installation and
Operation Manual for a complete list of
approved vent manufacturers and products.
You must use vent components that are
certified and listed with the water heater
model.
Avoid dips or sags in horizontal vent runs by
installing supports per the vent
manufacturers instructions.
Support horizontal vent runs every four feet
and all vertical vent runs every six feet or in
accordance with local codes.
Venting should be as direct as possible with
a minimum number of pipe fittings.
Engineered vent systems must be firmly
pressed together so that the gaskets form an
air tight seal.
The vent piece connected to the water heater
must be secured with one self-tapping screw.
When installed as Non-Direct Vent (Room
Air), the venting must be Category IV and of
a type listed by a national recognized testing
agency or PVC (when allowed by local code).
WARNING
DO NOT use cellular core PVC/CPVC.
DO NOT use Radel or galvanized materi-
al to vent this appliance.
DO NOT cover non-metallic vent pipe
and fittings with thermal insulation.
DO NOT combine vent components from
different manufacturers.
DO NOT reduce the vent diameter.
DO NOT connect the venting system with
an
existing vent or chimney.
DO NOT common vent with the vent pipe
of any other manufacturers water heater
or appliance.
IMPORTANT
For venting information not specified in this
section, refer to the Installation and Operation
Manual for Condensing Tankless Water
Heaters (supplied with each tankless water
heater). This manual includes complete
venting information, including approved vent
manufacturers and terminations.
Topics in this section
Venting Requirements
Select a Vent Type
IMPORTANT
If it becomes necessary to access an
enclosed vent system for service or
repairs, Rinnai is not responsible for any
costs or difficulties in accessing the vent
system. The warranty does not cover
obtaining access to a vent system in an
enclosed environment.
If the vent system is to be enclosed, it is
suggested that the design of the enclosure
shall permit inspection of the vent system.
The design of such enclosure shall be
deemed acceptable by the installer or the
local inspector.
Refer to the instructions of the vent system
manufacturer for component assembly in-
structions.
background
Demand DuoH-Series Installation and Operation Manual 18
1. Install the water heater.
2. Determine the
termination method
horizontal or vertical
, concentric, or twin
pipes, etc.
3. Determine proper location for wall or roof
penetration for each termination.
4. Install termination assembly as described in
this manual or in the vent manufacturers
installation instructions.
5. Install air and vent piping from water heater
to termination.
6. Slope horizontal exhaust run towards the
water heater 1/4 in per foot. DO NOT slope
combustion air pipe
towards water heater.
7. Install vent supports and brackets allowing
for movement from expansion, or as per
vent manufacturers
instructions or local code requirements.
8. Install vent screen (supplied with water heat-
er) on PVC combustion air and exhaust ter-
mination elbows as
illustrated below.
Press vent screen inside of termination
piece/elbow.
Secure vent screen to the elbow with
screw provided.
Check to determine whether local codes
supersede the following clearances:
Avoid termination locations near a dryer
vent.
Avoid termination locations near
commercial cooking exhaust.
Avoid termination locations near any air
inlets.
You must install a vent termination at least
12 in above the ground or anticipated
snow level.
The vent for this appliance shall not terminate:
Over public walkways.
Near soffit vents or crawl space vents or
other area where condensate or vapor
could create a nuisance or hazard or
cause property damage.
Where condensate or vapor could cause
damage or could be detrimental to the
operation of regulators pressure relief
valves, or other equipment.
Listed below are important considerations for
locating vent termination under a soffit
(ventilated or unventilated or eave vent; or to a
deck or porch):
Do not install vent termination under a
soffit vent such that exhaust can enter the
soffit vent.
Install vent termination such that exhaust
and rising moisture will not collect under
eaves. Discoloration to the exterior of the
building could occur if installed too close.
Do not install the vent termination too
close under the soffit where it could
present recirculation of exhaust gases
back into the combustion air part of the
termination.
Figure 7: Vent Screen Assembly
background
Demand DuoH-Series Installation and Operation Manual 19
Three types of venting options are available:
Concentric Pipe
Combustion air and exhaust vent directly through
a single concentric connection. Hot exhaust exits
through the interior tube, while combustion air
enters through the outer layer.
Exhaust
Exhaust
Combustion
air
Combustion
air
Combustion
air
Combustion
air
Exhaust
Direct Vent
Non-Direct (Room Air) Vent
Multiple water heaters sharing a combustion air
header and a separate exhaust header that vents
directly through separate penetrations to
Combustion Air
Exhaust
Exhaust
Room Air
For Combustion
Twin Pipe
Combustion air and exhaust vent directly
through separate penetrations.
Room air is used for combustion while exhaust vents to the outside.
Multiple water heaters using room air for
combustion while sharing an exhaust
header that vents directly to the outside.
Direct Vent (Concentric Pipe and Twin Pipe)
1
Non-Direct Vent (Room Air)
2
Common Vent (Indoor Units Only. Direct Vent and Non-Direct/Room Air Vent)
3
Figure 8
Figure 9
Figure 10
Figure 11 Figure 12
background
Demand DuoH-Series Installation and Operation Manual 20
Canadian Installaons
(CSA B149.1)
U.S. Installaons
(ANSI Z223.1 /NFPA 54)
Ref Descripon Direct Vent (Indoor Unit) Direct Vent (Indoor Unit)
A Clearance above grade, veranda, porch, deck, or balcony 12 in. (30 cm) 12 in. (30 cm)
B Clearance to window or door that may be opened 36 in. (91 cm) 12 in. (30 cm)
C Clearance to permanently closed window * *
D
Vercal clearance to venlated sot, located above the terminal within a
horizontal distance of 2  (61 cm) from the center line of the terminal
* *
E Clearance to unvenlated sot * *
F Clearance to outside corner * *
G Clearance to inside corner * *
H
Clearance to each side of center line extended above meter/regulator
assembly
* *
I Clearance to service regulator vent outlet
Above a regulator within 3 
(91 cm) horizontally of the vercal
center line of the regulator vent
outlet to a maximum vercal
distance of 15  (4 m)
*
J
Clearance to non-mechanical air supply inlet to building or the
combuson air inlet to any other appliance
36 in. (91 cm) 12 in. (30 cm)
K Clearance to a mechanical air supply inlet 6  (1.83 m)
3  (91 cm) above if within
10  (3 m) horizontally
L
Clearance above paved sidewalk or paved driveway located on public
property
7  (2.13 m) [1] *
M Clearance under veranda, porch, deck, or balcony 12 in. (30 cm) [2] *
Figure 13: Direct Vent Termination Clearances (For Concentric and Twin Pipe)
Direct Vent (Concentric Pipe and Twin Pipe)
1
AIR SUPPLY INLET
VENT TERMINAL
AREA WHERE TERMINAL
IS NOT PERMITTTED
X
V
SNOW
TERMINATION
Clearance in
Ref. A also
applies to
anticipated
snow line
Clearance to opposite wall is 24 in. (60 cm).
[1] A vent shall not terminate directly above a sidewalk or paved driveway that
is located between two single family dwellings and serves both dwellings.
[2] Permied only if veranda, porch, deck, or balcony is fully open on a mini-
mum of two sides beneath the oor.
Clearances are in accordance with local installaon codes and the
requirements of the gas supplier. (Dégagement conforme aux codes
dinstallaon locaux et aux exigences du foumisseur de gaz.)
background
Demand DuoH-Series Installation and Operation Manual 21
All terminations (horizontal and/or vertical)
must terminate 12 in. (0.30 m) above grade or
anticipated snow level.
12 in. (0.30 m)
Between terminals at same level
60 in. (1.52 m)
Between terminals at different levels
Note: 24 in. (0.61 m)
to wall or parapet
Combustion air and exhaust vent directly through
a single concentric connection. Hot exhaust exits
through the interior tube, while combustion air
enters through the outer layer.
Combustion
air
Exhaust
Concentric Pipe Termination Clearances
Direct Vent (Concentric Pipe)
1
Concentric Pipe Overview
Combustion
air
Inside
Corner
12 in.
(0.30 m)
12 in.
(0.30 m)
60 in. (1.52 m)
vertically
between
terminals
Figure 14
Figure 15
Figure 16
Figure 17
background
Demand DuoH-Series Installation and Operation Manual 22
Concentric
Vent
Concentric Pipe Installation Instructions
Direct Vent (Concentric Pipe)
1
Concentric Vent Maximum Equivalent Length
Vent Sizes 2 in. X 4 in. 3 in. X 5 in.
Vent Lengths
65  (20 m) 150  (46 m)
45° elbow is equivalent to 3  (1 m)
90° elbow is equivalent to 6  (2 m)
Concentric Pipe Example Vent Applications
Horizontal Wall
Terminations
2 in. x 4 in.
3 in. x 5 in.
Vertical Roof
Terminations
2 in. x 4 in. and
3 in. x 5 in.
Concentric Pipe Maximum Vent Length
1. Remove and discard screw from concentric
flue connection.
2. Remove exhaust adapter ring (discard
for concentric venting configurations).
3. Install the concentric vent. Ensure it is
properly seated.
4. Secure the vent pipe to the concentric flue
connection with the supplied screw.
IMPORTANT
Install the venting termination according to
the diagrams and instructions in this manual.
Slope the venting 1/4 in. per foot toward the
appliance according to the vent
manufacturers installation instructions.
Dispose of condensate per local codes.
Figure 18
Figure 19
Figure 20
Figure 21
background
Demand DuoH-Series Installation and Operation Manual 23
Twin Pipe Termination Clearances
Direct Vent (Twin Pipe)
1
Combustion air and exhaust vent directly through
separate penetrations.
Twin Pipe Overview
Exhaust
Combuson
air
For illustration purposes only. Listed equivalent length is based on worst case scenario of 3 X 90°
elbows or 18 equivalent ft.
Twin Pipe Vertical Termination
of Multiple Water Heaters
12 in. (0.30 m) minimum
12 in. (0.30 m)
minimum above
combustion air
opening
Roof
12 in. (0.30 m)
above grade or
anticipated snow
level
12 in. (0.30 m)
minimum
Combustion
Air
Exhaust
Figure 22
Figure 23
Intake
Ground/Grade/Snow Level
60 in.
min
Indicates area in
which intake
cannot be located.
12 in.
min
12 in.
min
12 in.
min
12 in.
min
12 in.
min
Intake
Exhaust
Intake
background
Demand DuoH-Series Installation and Operation Manual 24
Twin Pipe Installation Instructions
DO NOT apply PVC glues, solvents, or clean-
ers to the water heaters combustion air or
exhaust gasket connections. Failure to cor-
rectly assemble the components according to
these instructions may result in property dam-
age, personal injury, or death.
WARNING
The water heater is equipped with a 2 in. (51
mm) pipe connection. With the use of a pipe
reducer, installers can use a 3 in. (76 mm) pipe
for the combustion air and exhaust.
1. Remove and discard the screw from the
combustion air vent connection.
Combustion Air
Vent Pipe
Supplied
screw
Exhaust Vent Pipe
Supplied
screw
Direct Vent (Twin Pipe)
1
2. Remove and discard the combustion
air vent cap.
3. Install the combustion air vent pipe.
Ensure it is properly seated.
Secure the combustion air vent pipe to the
combustion air vent connection with the
supplied screw.
4. Install the exhaust vent pipe. Ensure it is
properly seated.
Secure the exhaust vent pipe to the exhaust
adapter ring with the supplied screw.
Figure 24
Figure 25
Figure 26
Figure 27
background
Demand DuoH-Series Installation and Operation Manual 25
2 in. or 3 in.
PVC/CPVC
IPEX / Royal
Concentric
Side Wall
Termination
Configuration
2 in. or 3 in.
PVC/CPVC
IPEX /Royal
Concentric
Vertical
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC or
ABS Snorkel
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC or
ABS Standard
upside down
"U" Vertical Ter-
mination Con-
figuration
2 in. or 3 in.
Schedule 40
PVC/CPVC or
ABS
Elbow or Tee
Side Wall
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC or
ABS Tee
Vertical
Termination
Configuration
2 in. or 3 in.
PVC Low
Profile
Termination
Configuration
This configuration requires the use
of a Concentric Vent Termination
Exhaust and
combuson air
MUST NOT be
brought
together into
a single PVC
pipe using a
pipe ng.
Twin Pipe Maximum Equivalent Length Table
Vent Sizes 2 in. (51 mm) 3 in. (76 mm)
Vent Lengths 65  (20 m) 150  (46 m)
45° elbow is equivalent to 3  (1 m)
90° elbow is equivalent to 6  (1.83 m)
WARNING
Twin Pipe Example Vent Applications
Twin Pipe Maximum Vent Length
Direct Vent (Twin Pipe)
1
Slope horizontal exhaust 1/4 in. per foot towards the water heater. DO NOT slope combustion air pipe
towards the water heater.
Exhaust
Combuson
Air
Single
Pipe
This configuration requires the use
of a Concentric Vent Termination
background
Demand DuoH-Series Installation and Operation Manual 26
Canadian Installaons
(CSA B149.1)
U.S. Installaons
(ANSI Z223.1 /NFPA 54)
Ref Descripon
Other than direct vent
(Outdoor unit and/or Room Air)
Other than direct vent
(Outdoor unit and/or Room Air)
A Clearance above grade, veranda, porch, deck, or balcony 12 in. (30 cm) 12 in. (30 cm)
B Clearance to window or door that may be opened 36 in. (91 cm)
4  (1.2 m) below or to side of opening;
1  (300 mm) above opening
C Clearance to permanently closed window * *
D
Vercal clearance to venlated sot, located above the
terminal within a horizontal distance of 2  (61 cm) from
the center line of the terminal
* *
E Clearance to unvenlated sot * *
F Clearance to outside corner * *
G Clearance to inside corner * *
H
Clearance to each side of center line extended above
meter/regulator assembly
* *
I Clearance to service regulator vent outlet
Above a regulator within 3  (91 cm)
horizontally of the vercal center line of
the regulator vent outlet to a maximum
vercal distance of 15  (4 m)
*
J
Clearance to non-mechanical air supply inlet to building or
the combuson air inlet to any other appliance
36 in. (91 cm)
4  (1.2 m) below or to side of opening;
1  (300 mm) above opening
K Clearance to a mechanical air supply inlet 6  (1.83 m)
3  (91 cm) above if within 10
(3 m) horizontally
L
Clearance above paved sidewalk or paved driveway located
on public property
7  (2.13 m) [1] *
M Clearance under veranda, porch, deck, or balcony 12 in. (30 cm) [2] *
Figure 28: Room Air Termination Clearances
Non-Direct Vent (Room Air)
2
AIR SUPPLY INLET
VENT TERMINAL
AREA WHERE TERMINAL
IS NOT PERMITTTED
X
V
SNOW
TERMINATION
Clearance in
Ref. A also
applies to
anticipated
snow line
Clearance to opposite wall is 24 in. (60 cm).
[1] A vent shall not terminate directly above a sidewalk or paved driveway that
is located between two single family dwellings and serves both dwellings.
[2] Permied only if veranda, porch, deck, or balcony is fully open on a mini-
mum of two sides beneath the oor.
Clearances are in accordance with local installaon codes and the
requirements of the gas supplier. (Dégagement conforme aux codes
dinstallaon locaux et aux exigences du foumisseur de gaz.)
background
Demand DuoH-Series Installation and Operation Manual 27
60 in.
12 in.
12 in.
(0.30 m)
Inside
Corner
Exhaust Termination Clearances for Internal (Indoor) Room Air Applications
Non-Direct Vent (Room Air)
2
(1.52 m) vercally between terminals
Installation of Non-Direct Vent (Room Air) must use listed category IV venting.
All terminations (horizontal and/or vertical) must terminate 12 in. above grade or anticipated
snow level.
NOTE
Figure 29
background
Demand DuoH-Series Installation and Operation Manual 28
For applications containing corrosive indoor air,
this appliance must be installed as direct vent.
DO NOT use room air in applications where
combustion air contains acid forming chemicals
such as sulfur, fluorine and chlorine. These
chemicals have been found to cause rapid
damage and decay and can become toxic when
used as combustion air in gas appliances. Such
chemicals can be found in, but not limited to
bleach, ammonia, cat litter, aerosol sprays,
cleaning solvents, varnish, paint and air
fresheners. Do not store these products or similar
products in the vicinity of this water heater.
Unconfined Space
An unconfined space is defined in National Fuel
Gas Code, ANSI Z223.1/NFPA 54 as a space
whose volume is not less than 50 cubic feet per
1000 Btu/hr (4.8 m3 per kW per hour) of the
aggregate input rating of all appliances installed
in that space. Rooms communicating directly with
the space in which the appliances are installed,
through openings not furnished with doors, are
considered a part of the unconfined space.If the
unconfined spacecontaining the appliance(s) is
in a building with tight construction, additional
outside air may be required for proper operation.
Outside air openings should be sized the same
as for a confined space.
This water heater requires adequate combus-
tion air for ventilation and dilution of flue gas-
es. Failure to provide adequate combustion
air can result in unit failure, fire, explosion,
serious bodily injury or death. Use the follow-
ing methods to ensure adequate combustion
air is available for correct and safe operation
of this water heater.
WARNING
Combustion Air
Non-Direct Vent (Room Air)
2
Combustion air must be free of corrosive
chemicals. Do not provide combustion air
from corrosive environments. Appliance
failure due to corrosive air is not covered by
warranty.
IMPORTANT
If ducts are used, the cross sectional area of
the duct must be greater than or equal to the
required free area of the openings to which
they are connected.
NOTE
Confined Space
A confined space is defined in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 as "a space
whose volume is less than 50 cubic feet per
1000 Btu/hr (4.8 m3 per kW per hour) of the ag-
gregate input rating of all appliances installed in
that space." Examples include a small room,
closet, alcove, utility room, etc. A confined space
must have two combustion air openings. Size
the combustion air openings based on the BTU
input for all gas utilization equipment in the
space and the method by which combustion air
is supplied.
Using Indoor Air For Combustion:
When using air from other room(s) in the build-
ing, the total volume of the room(s) must be of
adequate volume (Greater than 50 cubic feet per
1000 Btu/hr). Combustion air openings between
joining rooms must have at least 1 square inch
of free area for each 1000 Btu/hr, but not less
than 100 square inches each.
Using Outdoor Air For Combustion
Outdoor air can be provided to a confined space
through two permanent openings, one com-
mencing within 12 in. (0.30 m) of the top and
one commencing within 12 in. (0.30 m) of the
bottom, of the confined space. The openings
shall communicate to the outside by one of two
ways.
When communicating directly with the outdoors
through horizontal ducts, each opening shall
have a minimum free area of 1 in
2
/2000 Btu/hr
(1100 mm
2
/kW) of total input rating of all appli-
ances in the confined space.
background
Demand DuoH-Series Installation and Operation Manual 29
WARNING
TO PREVENT POSSIBLE PERSONAL INJURY
OR DEATH DUE TO ASPHYXIATION,
COMMON VENTING WITH OTHER
MANUFACTURERS INDUCED DRAFT
APPLIANCES IS NOT ALLOWED.
Location
To maintain proper circulation of combustion air
two permanent openings (one upper, one lower)
must be positioned in confined spaces. The up-
per shall be within 12 in. (0.30 m) of the top of
the confined space and the lower opening shall
be within 12 in. (0.30 m) of the bottom of the
confined space. Openings must be positioned as
to never be obstructed.
Louvers and Grills
When sizing the permanent opening considera-
tion must be taken for the design of the louvers
or grills to maintain the required free area re-
quired for all gas utilizing equipment in the
space. If the free area of the louver or grill de-
sign is not available, assume wood louvers will
have 25% free area and metal louvers or grills
will have 75% free area. Under no circumstance
should the louver, grill or screen have openings
smaller than 1/4 in.
Free Area = Height x Length x % Free Area
Wood: 18 in. x 24 in. x 0.25 = 108 in.
2
Metal: 18 in. x 24 in. x 0.75 = 324 in.
2
Non-Direct Vent (Room Air)
2
Combustion Air (Continued)
24 in.
(600 mm)
18 in.
(450 mm)
Combustion air provided to the appliance
should not be taken from any area of the
structure that may produce a negative
pressure (i.e. exhaust fans, powered
ventilation fans).
IMPORTANT
Figure 30
background
Demand DuoH-Series Installation and Operation Manual 30
Exhaust
Vent termination per ANSI Z223.1/NFPA 54. For
clearances not specified in ANSI Z223.1/NFPA 54,
clearances are in accordance with local installation
codes and the requirements of the gas supplier.
Non-Direct Vent (Room Air)
2
Figure 31
background
Demand DuoH-Series Installation and Operation Manual 31
1. Remove and discard screw from combustion
air vent connection.
2. Remove and discard the combustion air
vent cap.
3. Install the combustion air vent pipe. Ensure it
is properly seated.
Secure the combustion air vent pipe to the
combustion air vent connection with the
supplied screw.
4. Place the vent screen or room air screen
inside elbow and secure with the supplied
screw. Use the room air screen for
environments where room air is dusty.
5. Install the exhaust vent pipe. Ensure it is
properly seated.
Secure the exhaust vent pipe to the exhaust
adapter ring with the supplied screw.
Combustion Air Vent
Pipe
Supplied
screw
Supplied
screw
Supplied
screw
Exhaust Vent Pipe
Non-Direct Vent (Room Air) Installation
Instructions
Non-Direct Vent (Room Air)
2
Elbow
Vent
Screen
2 in. vent screen supplied with water
heater.
Room air screen is available as an
accessory.
NOTE
Glue elbow to the combustion air PVC vent pipe
per manufacturers instructions.
Figure 32
Figure 33
Figure 34
Figure 35
Figure 36
background
Demand DuoH-Series Installation and Operation Manual 32
2 in. or 3 in.
Schedule 40
PVC/CPVC
Snorkel
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC
Standard
Upside Down
"U" Vertical
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC
Elbow or Tee
Side Wall
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC
Tee Vertical
Termination
Configuration
Non-Direct Vent (Room Air) Example Vent Applications
Non-Direct Vent (Room Air) Maximum Vent Length
Non-Direct Vent (Room Air)
2
Room Air Maximum Equivalent Length Table
Vent Sizes 2 in. (51 mm) 3 in. (76 mm) 2 in. (51 mm) Ubbink Flex
Vent Lengths 65 ft (20 m) 150 ft (46 m) 50 ft (15 m)
45° elbow is equivalent to 3 ft (1 m)
90° elbow is equivalent to 6 ft (2 m)
Slope horizontal exhaust 1/4 in. per foot towards the water heater.
PP Flex Venting
B-Vent Pipe
4 in. (102 mm)
Ubbink flexible venting
approved for vertical
non-direct vent (room
air) applications only.
Refer to the flex vent
manual for further
details.
background
Demand DuoH-Series Installation and Operation Manual 33
When installing Common Vent, follow these
guidelines:
Vent system must be supported according to
the vent manufactures installation
instructions.
Venting should be as direct as possible with
a minimum number of fittings.
The common vent system must only be
installed by a trained and qualified
professional.
Common Vent Termination Clearances
Vent termination per ANSI Z223.1/NFPA 54.
For clearances not specified in ANSI Z223.1/
NFPA 54, clearances are in accordance with
local installation codes and the requirements
of the gas supplier.
Common venting allows multiple Rinnai Tankless
Water Heaters to share the same vent system.
Rinnai water heaters can only be common vented
with Schedule 40 PVC/CPVC or with the Rinnai
certified common vent system.
Example: Rinnai Common Venting
Example: Schedule 40 PVC/CPVC
Common Vent
DO NOT obstruct combustion air flow or
exhaust gas flow in the venting system.
DO NOT install the water heater in an area
with negative air pressure.
DO NOT combine the common vent system
with existing vents, chimneys, or vent pipes
connected to other water heaters, boilers or
appliances.
DO NOT common vent different Rinnai
models in a single common vent system.
DO NOT use cellular core PVC/CPVC,
Radel or galvanized materials.
DO NOT combine vent components from
different manufacturers.
WARNING
DO NOT slope the combustion air pipe to-
ward unit. Failure to comply with this warn-
ing could result in property damage, person-
al injury, or death.
DO NOT apply PVC/CPVC glues, solvents,
or cleaners to the tankless water heaters
intake or exhaust gasket connections. Fail-
ure to correctly assemble the components
according to these instructions may result in
property damage, personal injury, or death.
Common Vent
(Indoor Units Only. Direct Vent and
Non-Direct/Room Air Vent)
3
General Guidelines
Use only the materials listed in this manual
for vent, air intake pipe, and fittings. Failure
to comply with this warning could result in
property damage, personal injury, or death.
When cutting vent components, ensure that
the cuts are straight.
Chamfer and deburr all edges before in-
stalling the components.
Vent joints must not leak. Confirm gas tight
connections of every vent joint.
Before operating the water heater(s), ensure
vent system is clean and free of debris.
Figure 37
background
Demand DuoH-Series Installation and Operation Manual 34
For the table below:
Header is the main vent pipe into which sev-
eral vents connect
Vent Length is the distance from the end of
the header to the vent termination.
Maximum vent length starts at the end of the
header system.
Use 10 ft (3 m) as equivalent vent length for
90° elbows.
Header
Vent Length
Common Vent Maximum Equivalent Vent Length
Rinnai Common Vent System or Schedule 40 PVC/CPVC
Water Heater
Model
# Water
Heaters
Max
System
BTU/HR
HEADER DIAMETER
3 in. 4 in. 6 in.
3 in.
Vent
Diameter
4 in.
Vent
Diameter
6 in.
Vent
Diameter
6 in.
Vent
Diameter
2 398,000 65
150
150
150
CU199i
(REU-N3237FFC-US)
3 597,000
4 796,000 65
5 995,000
6 1,194,000
7 1,393,000
70
8 1,592,000
CU160i
(REU-N2530FFC-US)
2 320,000 90  150
150
150
3 480,000
100
4 640,000 65
5 800,000
6 960,000
RU130i
(REU-N2024FF-US)
2 260,000 90  150
150
150
3 390,000
100
4 520,000 65
5 650,000
6 780,000
Figure 38
background
Demand DuoH-Series Installation and Operation Manual 35
Manufacturer Phone Web Site
Ubbink 800-621-9419 www.rinnai.us
790096
790095
CVent Roof Termination 6 in.
CVent Roof Termination 4in.
5
790125 CVent Roof Termination 3 in.
5
790094
790093
90124
CVent Wall Terminal Kit 6 in.
CVent Wall Terminal Kit 6 in.
CVent Wall Terminal Kit 6 in.
5
780061
780060
Intake Rain Cap 6 in.
Intake Rain Cap 4 in.
N/A
790098
790097
Exhaust Flue Rain Cap 6 in.
Exhaust Flue Rain Cap 4 in.
N/A
Diagram
Horizontal
Vertical
Equivalent
Length (ft)
Tee
10
90° Elbow
10
45° Elbow
5
Product
Descripon
Horizontal
Vertical
Equivalent
Length (ft)
Diagram
Part Number
Product
Description
Rinnai Common Vent Terminations (Ubbink C-Vent)
Various 3 in., 4 in. and 6 in. Schedule 40 PVC/CPVC Terminations
background
Demand DuoH-Series Installation and Operation Manual 36
When installing PVC/CPVC Common Vent,
follow these guidelines:
Avoid sharp bends or tees in the vent
system. These vent components create
additional restrictions that could reduce
performance of the water heaters.
PVC combustion air and exhaust should
terminate with elbow or tee pointing down.
This will stop unwanted moisture from
entering the vent system.
Fire rated penetrations shall be firestopped.
Contact your vent supplier or local firestop
manufacturer for appropriate firestop
methods.
Examine all vent components for damage
prior to installation.
PVC/CPVC vent systems must be free to
expand and contract. Refer to the vent
manufacturers installation instructions for
appropriate support methods.
PVC/CPVC venting must include unrestricted
vent movement through walls, ceilings, and
roof penetrations.
Use only PVC/CPVC primer and cement
approved for use by the vent manufacturer.
Keep solvents away from heat, sparks,
flames and all other sources of ignition.
Do not solder, cut or weld until all vapors
have dissipated.
PVC solvents are heavier than air causing
them to settle at low points of the system.
Before using PVC solvent
Disconnect power to the water heater.
Remove the front cover of the water
heater.
Ensure areas around the water heater
and PVC venting are all well ventilated.
Allow all vapors to dissipate before
applying power to the system or
introducing any other source of ignition.
PVC solvents (primer
and glue) can be
extremely flammable. Vapors may cause a
flash fire or explosion resulting in property
damage, personal injury or death.
WARNING
DO NOT
DO NOT mix vent pipe, fittings or joining
methods from different vent manufacturers.
DO NOT attempt to repair damaged vent.
Damaged vent components must be re-
placed.
DO NOT use short radius elbows in the com-
mon vent system.
ACCEPTABLE ACCEPTABLE
90° Elbows, Long
Sweep
90° Elbows, Short
Sweep
HEADER VENT
PVC/CPVC Common Vent Installation
Refer to vent manufacturers installation in-
structions for proper joint assembly proce-
dures and products.
PVC/CPVC common venting should include a
condensate drain and trap between the head-
er and vent length. Condensate trap must
include a loop that can hold 6 in. (15 cm) of
water. See PVC/CPVC Common Vent Instal-
lationillustration on this page.
NOT ACCEPTABLE
90° Elbows,
Close Turn
Figure 39
background
Demand DuoH-Series Installation and Operation Manual 37
Water discharged from the pressure relief valve
could cause severe burns instantly or death from
scalds.
WARNING
An approved pressure relief valve (preinstalled) is
required by the American National Standard
(ANSI Z21.10.3) for all water heating systems
and shall be accessible for servicing.
DO NOT
Do not plug the relief valve and do not install
any reducing fittings or other restrictions in the
relief line. The relief line should allow for
complete drainage of the valve and the line.
Do not place any other type valve or shutoff
device between the relief valve and the water
heater.
Install the Temperature-Pressure Relief (T&P)
Valve according to these instructions.
The tank portion of this system is provided with a
combination T&P relief valve. For safe operation
of the water heater, the relief valve(s) must not be
removed from its designated point of installation
or plugged.
An approved T&P relief valve is required by the
American National Standard (ANSI Z21.10.3) for
all water heating systems, and shall be
accessible for servicing.
DO NOT
Do not plug the T&P relief valve and do not
install any reducing fittings or other restrictions
in the relief line. The relief line should allow for
complete drainage of the T&P relief valve and
the line.
Do not place any other type valve or shut off
device between the relief valve and the water
heater.
Do not pipe T&P relief valve, pressure relief
valve, and/or condensate drain together into a
common pipe.
MUST DO
The T&P valve must comply with the standard
for Relief Valves and Automatic Gas Shutoff
Devices for Hot Water Supply Systems ANSI
Z21.22 and /or the standard Temperature,
Pressure, Temperature and Pressure Relief
Valves and Vacuum Relief Valves, CAN1-4.4.
Topics in this section
Pressure Relief Valve Requirements
Temperature - PRV Requirements
Connect the Water Heater to the Water
Supply
Typical Installations
Piping Diagram for Basic Installations
Piping Diagram for Multiple Unit Installations
The relief valve is installed near the tankless
hot water outlet.
INFORMATION
If a relief valve discharges periodically, this may
be due to thermal expansion in a closed water
supply system. Contact the water supplier or
local plumbing inspector on how to correct this
situation. Do not plug the relief valve.
MUST DO
The relief valve must comply with the standard
for Relief Valves and Automatic Gas Shutoff
Devices for Hot Water Supply Systems ANSI
Z21.22 and /or the standard Temperature,
Pressure, Temperature and Pressure Relief
Valves and Vacuum Relief Valves, CAN1-4.4.
The pressure relief valve must be rated up to
150 psi and to at least the maximum Btu/hr of
the appliance.
The discharge from the pressure relief valve
should be piped to the ground or into a drain
system per local codes.
The pressure relief valve must be manually
operated once a year to check for correct oper-
ation.
background
Demand DuoH-Series Installation and Operation Manual 38
Water connections to the Commercial Hybrid
System should follow all state and local plumbing
codes.
If this is a standard installation, refer to section
“6.5 Piping Diagram for Basic Installations.
1. Use of this layout should provide a trouble-
free installation for the life of the water heater.
Before making the plumbing connections,
locate the COLD water inlet and the HOT
water outlet.
The COLD water inlet is a 1-1/2 in. MNPT
fitting on the lower portion of the tank
below the tankless unit.
The HOT water outlet is a 1-1/2 in. MNPT
fitting located at the top of the tank. Install
a shut-off valve close to the water heater
in the cold water line. It is recommended
that unions be installed in the cold and
hot water lines so that the water heater
can be easily disconnected, if servicing is
required.
2. When assembling the hot and cold piping,
use a good food grade pipe joint compound,
and ensure all fittings are tight. It is
imperative that open flame is not applied to
the inlet and outlet fittings, as heat will
damage or destroy the plastic lined fittings.
This will result in premature failure of the
fittings, which is not covered by the
warranty.
DO NOT OPERATE THIS WATER HEATER
UNLESS IT IS COMPLETELY FULL OF
WATER. To prevent damage to the water heater,
all air must be relieved from the system and a hot
water fixture must be flowing water before the
water heater is plugged in and turned on. To
ensure safe and effective operation of the water
heater, use the following filling procedure. To fill
the water heater:
1. Ensure the drain valve located at the bottom
of the tank is closed.
2. Open the nearest hot water fixture in the
plumbing system.
3. Open the cold water supply valve to the water
heater.
4. Keep the hot water fixture open until the tank
is filled and constant flow is obtained at the
fixture.
5. Check water heater connections and
plumbing system for damage or leaks. Repair
if needed.
NOTICE
DO NOT OPERATE THIS WATER HEATER
UNLESS IT IS COMPLETELY FULL OF
WATER.
The T&P relief valve must be rated up to 150
psi and to at least the maximum Btu/hr of the
appliance.
The discharge from the T&P relief valve should
be piped to the ground or into a drain system
to prevent exposure or possible burn hazards
to humans or other plant or animal life. Follow
local codes. Water discharged from the relief
valve could cause severe burns instantly,
scalds, or death.
The T&P relief valve must be manually operat-
ed once a year to check for correct operation.
Condensate can form in the vent of high
efficiency direct vent appliances. Without proper
drainage, condensate will damage the heat ex-
changer. Refer to Rinnai Tankless Water Heater
Installation and Operation Manual for condensate
guidelines.
To prevent condensate damage, follow these
instructions.
DO NOT
Do not connect the condensate drain pipe di-
rectly to the rain sewer.
Do not connect the condensate drain line with
an air conditioning evaporator coil drain.
Do not pipe condensate drain, temperature-
pressure relief valve, and/or pressure relief
valve together into a common pipe.
Do not install an external condensate trap.
The tankless water heater has an integrated
condensate trap.
MUST DO
Use only venting that is approved and identi-
fied as acceptable for your particular model.
background
Demand DuoH-Series Installation and Operation Manual 39
Slope the venting toward the appliance
according to the vent manufacturers
installation instructions.
All condensate must drain and be disposed of
according to local codes.
Use only corrosion resistant materials for the
condensate drain lines such as PVC pipe or
plastic hose.
The condensate drain pipe (along its entire
length) must be at least the same diameter as
the drain line, (1/2 inch NPT).
The end of the condensate drain pipe should
be open to the atmosphere. The end should
not be under water or other substances.
To minimize freezing of the condensate, run
the condensate drain line through an interior
wall or between insulation and an interior wall.
Ensure that condensate drain, PRV, and T&P
relief valve are piped separately to their own
dedicated drain lines.
Dispose of condensate per local codes.
INFORMATION
Water heaters have an integrated condensate
collector.
The condensate drain pipe should be as short
as possible and have a downward pitch.
If the condensate drain gets blocked, a
diagnostic code will display on the controller. If
this occurs, the condensate drain must be
cleaned.
The condensate trap will automatically prime
(self-prime) during operation of the unit as
condensate forms. Condensate draining from
the unit indicates that the trap is full and that
there is no blockage in the condensate drain. It
is not necessary to add water to the
condensate trap.
A condensate neutralizer kit (Part Number:
804000074) is available from Rinnai. The kit
allows condensate to flow through neutralizing
media that raises the pH of the condensate to
a level that will help prevent corrosion of the
drain and public sewer system.
A condensate line must be installed to the 1/2 in.
PVC elbow located at the left side of the lower
enclosure.
Condensate line must pitch toward the drain.
Air gap must be installed on the condensate line
to enable the condensate to drain.
CORRECT
Pipe open to
atmosphere
Pipe submerged
in water
NOT
CORRECT
Water
Level
Water
Level
The end of the condensate drain pipe should
be open to the atmosphere. The end should
not be under water or other substances.
EXTERNAL TRAP
NOT REQUIRED
DO NOT
DO NOT connect the condensate drain line
with an air conditioning evaporator coil drain.
Water heaters have an integrated
condensate trap. DO NOT install an external
condensate trap.
Condensate Drain
(1/2 in. PVC)
Figure 40
background
Demand DuoH-Series Installation and Operation Manual 40
A Hot Water Outlet *
B Hot Water Outlet Valve *
C Cold and Hot Unions *
D
Temperature-Pressure Relief
Valve
E
Operation Unit / Temperature
Control
F
Temperature-Pressure Relief
Valve Discharge Pipe
(do not cap, plug, or reduce)
*
G
Pressure Relief Valve Discharge
Pipe (do not cap, plug, or re-
*
H
Condensate Discharge Pipe
(Must include air gap)
*
I Drain Pan *
J
Vent pipe (PVC Room Air shown
for illustration purposes, see
venting section for other options)
*
K Gas Control Valve *
L Gas Union *
M Drip Leg (Sediment Trap) *
N Cold Water Supply Valve *
O Cold Water Supply *
P Thermal Expansion Tank *
Q Non-Tempered Supply Line *
R Thermostatic Mixing Valve *
S Purge Line *
T Check Valve *
* Field Supplied
Mixing Valve Installation
Hot Water
Supply
A
B
C
D
O
N
P
J
E
I
F
M
L
K
R
Q
S
G
H
D
Figure 41
Figure 42
Cold Water Supply
T
background
Demand DuoH-Series Installation and Operation Manual 41
Commercial Hybrid Single Unit Circulation
Note:
Installation must conform to applicable code and all requirements listed in the installation manual. Balancing valves, equivalent piping, pressure
gauges, and temperature gauges are to be used as necessary to ensure proper flow between units.
Condensate piping shall be CPVC or PVC material and shall not be smaller than the drain connection on the appliance.
Components of condensate drainage shall be CPVC or PVC material. All components shall be selected for the pressure and temperature rating of
the installation.
Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with
an approved method as dictated by local codes.
Condensate must be disposed of according to local codes.
Building Hot Water Supply Line
Condensate Drain Line
Pipe T&P to Open Drain
Building Circulation
Pump
Gas Supply
Building Hot Water
Return Line (Optional)
Cold Water Supply
Tank
T&P
Tankless
PRV
Figure 43
background
Demand DuoH-Series Installation and Operation Manual 42
Notes:
Installation must conform to applicable code and all requirements listed in the installation manual. Balancing valves, equivalent piping, pressure gag-
es, and temperature gages are to be used as necessary to ensure proper flow between units.
Condensate piping shall be CPVC or PVC material and shall not be smaller than the drain connection on the appliance.
Components of the condensate drainage shall be CPVC or PVC material. All components shall be selected for the pressure and temperature rating of
the installation.
Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with
an approved method as dictated by local codes.
Condensate must be disposed of according to local codes.
HOT WATER SUPPLY LINE
CONDENSATE
DRAIN LINE
PIPE EACH T&P AND PRV TO OPEN DRAIN
BUILDING CIRCULATION PUMP AND
HOT WATER RETURN LINE
(OPTIONAL)
COLD WATER
SUPPLY
GAS SUPPLY
Additional units can be installed as illustrated.
Figure 44
background
Demand DuoH-Series Installation and Operation Manual 43
1. Install a manual gas control valve in the gas
supply line to the water heater. A union can
be used on the connection above the shut off
valve for the future servicing or disconnection
of the water heater (Figure 45 on the follow-
ing page).
2. Check the type of gas and gas supply pres-
sure before connecting the water heater. If
the water heater is not of the gas type that
the building is supplied with, DO NOT con-
nect the water heater. Contact the dealer for
the proper water heater to match the gas
type.
3. Check the gas supply pressure immediately
upstream at a location provided by the gas
company. Supplied gas pressure must be
within the limits shown in the Section “3.2
Specificationswith all gas appliances oper-
ating.
A licensed professional must install the gas
supply.
Turn off 120V power supply.
Turn off the gas.
Gas is flammable. Do not smoke or provide
other ignition sources while working with
gas.
Do not turn on the water heater or gas until
all fumes are gone.
WARNING
To connect the gas supply, follow the instructions
below:
3/4 in. MNPT Gas Connection
on Bottom of Water Heater
Topics in this section
Connect the Gas Supply
Connect Electricity
Pump Controller
Figure 45
Figure 46
The gas swivel and gas
flex line can move in
multiple directions for
installation.
background
Demand DuoH-Series Installation and Operation Manual 44
5. Before placing the appliance in operation, all
joints including the heater must be checked for
gas tightness by means of soap, gas leak
detector solution, or an equivalent
nonflammable solution, as applicable. (Since
some leak test solutions, including soap and
water, may cause corrosion or stress cracking,
the piping shall be rinsed with water after
testing, unless it has been determined that the
leak test solution is non-corrosive.)
6. Use approved connectors to connect the water
heater to the gas line. Purge the gas line of
any debris before connection to the water
heater.
7. Any compound used on the threaded joint of
the gas piping must be chemically compatible
and mechanically suitable to be used in
liquified petroleum gas (LPG/Propane)
applications.
8. The gas supply line shall be gas tight, sized,
and so installed as to provide a supply of gas
sufficient to meet the maximum demand of the
heater and all other gas consuming appliances
at the location without loss of pressure. If in
doubt about the size of the gas line, refer to
the tankless water heater installation and
operation manual.
9. Perform a leak and pressure test prior to
operating the water heater. If a leak is
detected, do not operate the water heater until
the leak is repaired.
Gas
Valve
Union
Figure 47
background
Demand DuoH-Series Installation and Operation Manual 45
Flare Side
3/4 NPT
Side
36 in. Gas Flex
3/4 NPT
Field
Connection
Flare Side
3/4 NPT Side
1. Remove Gas Flare Adapter from the end of
the Gas Flex Hose Assembly.
2. Apply a pipe sealant approved for gas to
the 3/4 NPT side of the Gas Flare Adapter.
3. Thread the 3/4 NPT side of the Gas Flare
Adapter into the field connection gas
supply (Figure 49).
NOTE
DO NOT apply sealant to the parallel
threads on the flare side of the Gas Flare
Adapter.
4. Thread the flare side of the 36 in. Gas Flex
into the flare side of the Gas Flare
Adapter (Figure 50).
6. Leak test ALL gas fittings and assembly
using a leak test solution, soap and water,
or an equivalent nonflammable solution.
7. If leak is identified at the flex connection,
gradually tighten fitting until leak stops.
DO NOT connect gas flex directly to pipe
threads of gas supply pipe or appliance. Install
Gas Flex using only the Gas Flare Adapter
provided.
Flare Side
36 in. Gas Flex
5. Use a backer wrench to tighten all
connections to the recommended torque
value of 62 lbs-ft.
Figure 49
Figure 50
Figure 51
Figure 48
background
Demand DuoH-Series Installation and Operation Manual 46
WARNING
Do not use an extension cord or adapter plug with this appliance.
The water heater must be electrically grounded in accordance with local codes and ordinances or, in
the absence of local codes, in accordance with the National Electrical Code, ANSI/NFPA No. 70.
The water heater is equipped with a three-prong (grounding) plug for your protection against shock
hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut
or remove the grounding terminal from this plug. This appliance includes an integrated junction box
for hard wire or three-prong plug.
When connecting the power supply, follow these guidelines:
Do not rely on the gas or water piping to ground the water heater. Ground locations are provided
inside the water heater and inside the provided junction box.
The water heater requires 120 VAC, 60 Hz power from a properly grounded circuit.
When using the 6 ft (1.8 m) power cord (included with controller), plug it into the provided 3 prong
120 VAC, 60 Hz properly grounded outlet or hard wire to the integrated junction box.
The Tankless Water Heater wiring diagram is located on the inside of the water heater front cover.
The controller wiring diagram is located on the inside front cover of the controller.
B W R
Bl Bl
B R W G
B W G
B - Black
R - Red
W - White
G - Green
Bl - Blue
Figure 52
Do no connect power to the com-
mercial hybrid system prior to
completing installation and the
system has been filled with water.
ATTENTION
Displays set
temperature
background
Demand DuoH-Series Installation and Operation Manual 47
3. Remove the desired knockout along the
perimeter of the electric box for conduit
installation (Figure 55).
2. Remove the two screws around the outlet
cover. Remove the outlet cover and
prewired outlet (Figure 54).
4. Install conduit into the knockout opening
and pull the green, white and black wires
into the box.
5. Strip the green, white, and black field sup-
plied wires 1/2 in. Make sure the conductors
are completely bare (Figure 56).
6. Match the wire colors, then grip the wire
firmly and push the conductor into open
port of the push in connector (Figure 57).
1. Locate the electric conduit on the side of
the water heater (Figure 53).
Use only one conductor per port. Verify
conductor is fully inserted to the back of
the connector.
NOTE
Figure 53
Figure 54
Figure 55
Figure 56
Figure 57
background
Demand DuoH-Series Installation and Operation Manual 48
The system controller maintains communication between the tank and tankless via the tankless
communication cable to effectively control the tank temperature based on the selected temperature on
the tankless unit.
The system controller will energize (120V) the pump when the tank temperature drops. When the tank
temperature returns to the selected set temperature, the system controller will de-energize the pump
and remain in standby until the tank temperature drops again.
When power is supplied, the system controller will maintain pump
operation. If system is not in use for an extended period of time,
disconnect power from the system.
ATTENTION
Tank Recovery Pump
Activated
Tankless Flow Rate has
dropped below 2.5 GPM
Slow flash indicates
controller is active with
no errors
Power supply is
working correctly
Figure 58
Displays set
temperature
background
Demand DuoH-Series Installation and Operation Manual 49
The water heater is not subject to corrosive
compounds in the air.
The water supply does not contain
chemicals or exceed total hardness that will
damage the heat exchanger.
Clearances from the water heater unit are
met.
Clearances from the vent termination / air
intake are met.
Ensure you have used the correct venting
products for the model installed and that you
have completely followed the venting
manufacturers installation instructions and
these installation instructions.
Verify that the vent system does not exceed
the maximum length for the number of
elbows used.
Purge the water line of all debris and air by
closing the hot isolation valve and opening
the cold isolation valve and its drain. Debris
will damage the water heater. Use a
bucket or hose if necessary.
Ensure that hot and cold water lines are not
crossed to the unit and are leak free.
A manual gas control valve has been placed
in the gas line to the water heater.
Ensure that a pressure relief valve is
installed with a rating that exceeds the BTU
input of the water heater model. Refer to
the rating plate on the side of the water
heater for BTU input.
Clean the inlet water filter by closing the
cold and hot water inlet isolation (shut-off)
valves. Put a bucket under the filter at the
bottom of the water heater to catch any
water that is contained inside the unit.
Unscrew the water filter. Rinse the filter to
remove any debris. Install the filter and open
the isolation valves.
Check the gas lines and connections for
leaks.
Confirm that the gas inlet pressure is within
limits.
Confirm that the water heater is rated for the
gas type supplied.
Confirm that the electricity is supplied from a
120 VAC, 60 Hz power source, is in a
properly grounded circuit, and turned on.
Verify the temperature controller is
functioning properly.
Confirm parameter settings are set
appropriately for the altitude.
Verify the system is functioning correctly by
connecting your manometer to the gas
pressure test port on the water heater.
Operate all gas appliances in the home or
facility at high fire. The inlet gas pressure at
the water heater must not drop below that
listed on the rating plate.
DO NOT introduce toxic chemicals such as
those used for boiler water treatment to the
potable water used for space heating.
If the water heater is not needed for
immediate use, then drain the water from the
heat exchanger.
Install the front panel.
Explain to the customer the importance of not
blocking the vent termination or air intake.
Explain to the customer the operation of the
water heater, safety guidelines, maintenance,
and warranty.
The installation must conform with local
codes or, in the absence of local codes, with
the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, or the Natural Gas and Propane
Installation Code, CSA B149.1.
Leave this manual and the Rinnai
Tankless Water Heater manual taped to
the water heater, or give both manuals
directly to the consumer.
background
Demand DuoH-Series Installation and Operation Manual 50
Anodes
The storage tank is equipped with two magnesi-
um anodes designed to extend the life of the stor-
age tank. Slowly consumed over time, the anode
protects the glass-lined tank from corrosion. It is
strongly recommended to inspect the anodes
every two (2) years. If more than half of the an-
odes has been consumed, they should be re-
placed. Instructions on how to change the anodes
can be obtained from the manufacturer.
The longevity of the storage tank can be reduced
when a water softener is introduced to fight hard
water. Sodium salts added by a softener can
make the water extremely conductive; therefore,
the anodes are consumed at a faster rate. In such
conditions, the anodes should be inspected on a
yearly basis.
In certain conditions, the anodes may react with
the water, producing discolored or smelly water.
The most common complaint is hot water that
smells like rotten eggs. This is the result of the
reaction between the anode and hydrogen sul-
phide gas dissolved in the water, which is com-
mon in well systems. This issue can usually be
eliminated or reduced by changing the magnesi-
um anodes to aluminum anodes and by
chlorinating the storage tank and plumbing sys-
tem. If the problem continues, special filtration
equipment may be required. Under no circum-
stances are the anodes to be removed from the
water heater on a permanent basis.
Removal of the anodes will lead to premature
failure of the water heater and will void the
warranty.
Storage Tank
Drain a pail of water through the drain valve at
least once a year. This will remove excess sedi-
ment from the bottom of the tank. This sediment,
if allowed to accumulate, will reduce the efficien-
cy and the life of the tank.
Draining the Storage Tank
To completely drain the storage tank:
1. Turn the power OFFto the system by un-
plugging power to the system. (The system
will not be fully shut down by simply pressing
the power button on the controller)
2. Close the cold water supply manual shut-off
valve.
3. Connect one end of a garden hose to the
storage tank drain valve and put the other
end next to a free-flowing drain.
4. Open the drain valve by turning the knob
counter clockwise
5. Open a hot water faucet to allow air into the
system.
Cold Water
Supply Valve
Drain Valve
Topics in this section
Replacement Parts
Service/Maintenance Log
Anode Replacement
Procedure
1. Remove plastic caps.
2. With 1-1/8 in. socket
wrench, remove the
anode.
Figure 59
Figure 60
background
Demand DuoH-Series Installation and Operation Manual 51
ITEM
NO.
PART
NUMBER
DESCRIPTION
1
CU199iN/CU199iP
CU160iN/CU160iP
RINNAI SENSEI TANKLESS
2 109000741 LEFT COVER
3 109000740 RIGHT COVER
4 109000732 FRONT COVER
5 104000297 PUMP UNION KIT
6 107000387 CONDENSATE PIPE (PVC)
7 107000308 1-1/2 IN DIELECTRIC NIPPLE
8 107000309 1 IN DIELECTRIC NIPPLE
9 107000472 FVMX-6LS 1 IN MALE T&P 500KBTU/HR
10 107000257 CHECK VALVE
11 107000375 PRV PIPE (45 DEG)
12 105000322 SENSEI CONTROLLER ASSEMBLY
13 105000225 THERMISTOR, 3/4MNPT, 10K OHM
14 107000452 PRV CONNECTION ASSEMBLY
15 107000260 HEX NIPPLE, 3.4 IN
16 107000458 PUMP
17 107000311 TANK CLEANOUT FLANGE GASKET
18 107000312 HAND HOLE CLEANOUT COVER
19 109000633 CLEANOUT BOLTS 5/16IN-18 X 1 IN
20 107000255
FLEX, LENGTH 12 IN, 3/4 NPSH X 3/4
NPSH
21 107000401 TANK, 119 GALLON W/BRACKETS
22 107000398 TUBE, 43.95 X 3/4 NPSH X 3/4 NPSH
23 107000185 90° FEM X MALE ELBOW, 3/4IN
24 107000284 HOT, COLD, PRV VALVE KIT
25 107000314 ANODE ROD, MAGNESIUM
26 107000315 BRASS DRAIN VALVE 3/4 X 2-3/4
27 105000337 ELECTRICAL ASSEMBLY
28 106000165 DIRT LEG 3/4 IN
29 106000164 GAS SWIVEL
30 106000166 GAS FLEX HOSE
background
Demand DuoH-Series Installation and Operation Manual 52
ITEM
NO.
PART
NUMBER
DESCRIPTION
1
CU199iN/CU199iP
CU160iN/CU160iP
RU130iN/RU130iP
RINNAI SENSEI TANKLESS
2 109000741 LEFT COVER
3 109000740 RIGHT COVER
4 109000732 FRONT COVER
5 104000297 PUMP UNION KIT
6 107000387 CONDENSATE PIPE (PVC)
7 107000308 1-1/2 IN DIELECTRIC NIPPLE
8 107000309 1 IN DIELECTRIC NIPPLE
9 107000472 FVMX-6LS 1 IN MALE T&P 500KBTU/HR
10 107000257 CHECK VALVE
11 107000375 PRV PIPE (45 DEG)
12 105000322 SENSEI CONTROLLER ASSEMBLY
13 105000225 THERMISTOR, 3/4MNPT, 10K OHM
14 107000452 PRV CONNECTION ASSEMBLY
15 107000260 HEX NIPPLE, 3.4 IN
16 107000458 PUMP
17 107000311 TANK CLEANOUT FLANGE GASKET
18 107000312 HAND HOLE CLEANOUT COVER
19 109000633 CLEANOUT BOLTS 5/16IN-18 X 1 IN
20 107000255 FLEX, LENGTH 12 IN, 3/4 NPSH X 3/4 NPSH
21 107000253 TANK, 80 GALLON W/BRACKETS
22 107000398 TUBE, 43.95 X 3/4 NPSH X 3/4 NPSH
23 107000185 90° FEM X MALE ELBOW, 3/4IN
24 107000284 HOT, COLD, PRV VALVE KIT
25 107000314 ANODE ROD, MAGNESIUM
26 107000315 BRASS DRAIN VALVE 3/4 X 2-3/4
27 105000337 ELECTRICAL ASSEMBLY
28 106000165 DIRT LEG 3/4 IN
29 106000164 GAS SWIVEL
30 106000166 GAS FLEX HOSE
background
Demand DuoH-Series Installation and Operation Manual 53
Date Service / Maintenance Completed
background
Demand DuoH-Series Installation and Operation Manual 54
Limited Warranty for Demand Duo H-Series
What Is Covered?
The Rinnai Standard Limited Warranty covers any defects in materials or workmanship when the
product is installed and operated according to Rinnai written installation instructions, subject to the terms
within this Limited Warranty document. This Limited Warranty applies only to products that are installed
correctly in the United States and Canada. Improper installation may void this Limited Warranty. In order
for this warranty to apply, it is required that you use a trained and qualified professional who has
attended a Rinnai installation training class before installing this water heater. This Limited Warranty
coverage as set out in the table below extends to the original purchaser and subsequent owners, but
only while the product remains at the site of the original installation. This Limited Warranty only extends
to the first / original installation of the product and terminates if the product is moved or reinstalled at a
new location.
*The heat exchanger warranty will be 8 years or 12,000 operation hours, whichever occurs first.
Notes:
From date of purchase, period of coverage is reduced to 8 years or 12,000 operation hours,
whichever occurs first, if the Rinnai water heater temperature settings exceeds 160°F (71°C).
The integrated controller has a 1 year warranty on parts.
What Will Rinnai Do?
Rinnai will repair or replace the covered product or any part or component that is defective in materials
or workmanship as set forth in the above table. Rinnai will pay reasonable labor charges associated with
the repair or replacement of any such part or component during the term of the labor warranty period. All
repair parts must be genuine Rinnai parts. All repairs or replacements must be performed by a licensed
professional who is properly trained to do the type of repair.
Replacement of the product may be authorized by Rinnai only at its sole discretion. Rinnai does not
authorize any person or company to assume for it any obligation or liability in connection with the
replacement of the product. If Rinnai determines that repair of a product is not possible, Rinnai may
replace the product with a comparable product at Rinnais sole discretion. The warranty claim for
product parts and labor may be denied if a component or product returned to Rinnai is found to be free
of defects in material or workmanship; damaged by improper installation, use or operation; or damaged
during return shipping.
How Do I Get Service?
You must contact a trained and qualified professional for the repair of a product under this Limited
Warranty. For the name of a trained and qualified professional, please contact your place of purchase,
visit the Rinnai website (www.rinnai.us), call Rinnai at 1-800-621-9419 or write to Rinnai at 103
International Drive, Peachtree City, Georgia 30269.
Proof of purchase is required to obtain warranty service. You may show proof of purchase with a dated
sales receipt, or by registering within 30 days of purchasing the product. To register your Rinnai
Tankless Water Heater, please visit www.rinnai.us. For those without internet access, please call 1-866-
RINNAI1 (746-6241). Receipt of Registration by Rinnai will constitute proof-of-purchase for this product.
Registration of product installed in new home construction may be verified with a copy of the closing
papers provided by the initial home buyer. However, Registration is not necessary in order to validate
this Limited
Warranty.
Item Warranty Coverage
Heat Exchanger* 8 Years
Storage Tank 6 Years
All Other Parts and Components
5 Years
Reasonable Labor
1 Year
background
Demand DuoH-Series Installation and Operation Manual 55
What Is Not Covered?
This Limited
Warranty does not cover any failures or operating difficulties due to the following:
There is no warranty coverage on product installed in a closed loop application, commonly associated
with space heating only applications.
This Limited
Warranty does not apply to any product whose serial number or manufacture date has
been defaced.
This Limited
Warranty does not cover any product used in an application that uses chemically treated
water such as a pool or spa heater.
Limitation on Warranties
No one is authorized to make any other warranties on behalf of Rinnai America Corporation. Except as
expressly
provided herein, there are no other warranties, expressed or implied, including, but not limited to
warranties of
merchantability or fitness for a particular purpose, which extend beyond the description of the warranty
herein.
Any implied warranties of merchantability and fitness arising under state law are limited in duration to the
period of coverage provided by this Limited Warranty, unless the period provided by state law is less.
Some states do not allow limitations on how long an implied Limited
Warranty lasts, so the above
limitation may not apply to you.
Rinnai shall not be liable for indirect, incidental, special, consequential or other similar damages that
may arise,
including lost profits, damage to person or property, loss of use, inconvenience, or liability arising from
improper
installation, service or use. Some states do not allow the exclusion or limitation of incidental or
consequential damages, so the above limitation may not apply to you.
This Limited Warranty gives you specific legal rights, and you may also have other rights which vary
from state to state.
www.rinnai.us/warranty
Accident, abuse, or misuse
Alteration of the product or any component part
Misapplication of this product
Improper installation (such as but not limited to)
Product being installed in a corrosive envi-
ronment
Condensate damage
Improper venting
Incorrect gas type
Incorrect gas or water pressure
Absence of a drain pan under the appliance
Improper maintenance (such as but not limited
to scale build-up, freeze damage, or vent
blockage)
Incorrect sizing
Any other cause not due to defects in materials
or workmanship
Problems or damage due to fires, flooding,
electrical surges, freezing or any acts of God
Any damage caused by poor water quality
Operating the water heater with anything other
than potable water at all times
Force majeure
background
04/2020
100000684