1745
Users Manual
10
Table 4. 1745 Power Quality Logger - Controls and Indicators (cont)
Item Name Description
5
Connector for Flexi
Set or current
clamps
Flexi sets or current clamps are detected
automatically at power-up. If you change the
current probe type, be sure to remove and
restore power so the Logger will detect the
new current probe.
Nominal ranges for the Flexi Set are 15 A,
150 A, 1500 A, and 3000 A AC. Nominal
input for current clamps is 0.5 V.
6
RS232 interface port The serial RS232 interface is used to
communicate with a PC. The Logger is
connected to the PC’s serial port (or a
modem for remote communication) using
the interface cable. Use a USB adapter if
necessary.
7
Logging Status LED
Yellow blinking = Logging job not set up yet,
or waiting for start time or START button.
Green blinking = logging is in progress
Steady green = Logging session is finished.
Data are ready to upload to a PC.
8 Channel LEDs The logging channel LEDs indicate
whether the applied voltages are within the
nominal range set using the PQ Log
software.
Red = Overload
Green = OK
Yellow = Underload
(There is no detection for the current input)