FLUKE BT521ANG Advanced Battery Analyzer with angled test probes

User Manual for the Fluke BT521ANG Advanced Battery Analyzer with angled test probes - Page 30

For BT521ANG.

PDF File Manual, 66 pages, Read Online | Download pdf file

BT521ANG photo
Loading ...
Loading ...
Loading ...
BT521
Users Manual
3-4
Create a Profile
The Product provides these options to create a profile:
Create by default: Uses system default data to create each profile.
Copy from template: Copies data from an existing template.
String+1: Copies data from the previous profile and increases 1 to the value of
Battery string.
Note
The “Copy from template” option is available only after templates are
downloaded the from PC software.
To create a profile in Sequence mode:
1. On the measurement screen of Sequence mode, push the Profile softkey.
The Profile info menu shows on the display.
2. Push the New softkey. The Select the Way to Create menu shows on the display.
hsz004.jpg
hsz012.jpg
3. Use and L to select Create by default, Copy from template, or String+1.
4. Push the Create softkey.
The New Profile menu shows on the display.
5. When necessary, push the Edit softkey, and then use the arrow keys and softkeys to
edit the field values.
6. Push the Done softkey to exit the edit status.
7. Push the Start softkey to enter the measurement screen.
Note
When the same battery string is tested periodically, Fluke recommends
that the same profile name is used. In this way, test data can be archived
and the data trend can be viewed easier.
After test of one battery string is completed in a system, the String+1
function lets you easily switch to the next battery string without the need of
repeated data input.