6
Basic Operation
Storage & Service
Specifications
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Battery Replacement Door: Under normal conditions, the original battery
in your UPS will last several years. Battery replacement should be performed
only by qualified service personnel. Refer to “Battery Warnings” in the Safety
section.
Storage
Turn your UPS OFF: first engage the ON/Standby Switch and release it to place your UPS in
the “Standby” mode, then disconnect the UPS power cord from the wall outlet. If you plan
on storing your UPS for an extended period of time, recharge the UPS batteries once every
three months. Follow steps #1 and #3 in the Quick Installation section and allow the UPS to
charge from 4 to 6 hours. If you leave your UPS batteries discharged for an extended period of
time, they will suffer permanent loss of capacity.
Service
If returning your UPS for service, contact your local Tripp Lite dealer or distributor. They will
refer you to a service center. Please carefully pack the UPS using the ORIGINAL PACKING
MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem.
If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.
Smart INT
450
Smart INT
700
Smart INT
1000
Smart INT
1500
Output Capacity (VA/Watts): 450/280 700/425 1000/680 1500/940
Battery Runtime (Half Load/Full Load) Minutes:
19/5 20/6 23/8 25/10
Battery Recharge Time: 2-4 hrs.
Approvals: UL, CE
Input Voltage (230V); Input Frequency (50/60 Hz, Auto-Selecting); On-Line Input Voltage Range
(151-274 volts); Voltage-Regulated Output Voltage Range (230V +6%/-15%); On-Battery Output
Voltage Range (230V ± 5%); Output Waveform Line Mode (filtered sinewave); Output Waveform
Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards);
AC Noise Attenuation (>40 dB); AC TVSS Protection Modes (H to N, H to G, N to G).