Tripp Lite BP96V NEW series 96V Extended Battery Module EBM

Eaton Tripp Lite SmartOnline Series Tower UPS Advanced User Guide - Page 48

For BP96V NEW.

PDF File Manual, 52 pages, Read Online | Download pdf file

BP96V NEW photo
Loading ...
Loading ...
Loading ...
42 Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01
Table 14. UPS and BP Weights and Dimensions (Continued)
Description
Weights (lb/kg)
Dimensions (inch/mm) W x H x D
BP48V
54 / 24.5 6.3 x 9.9 x 17.0 / 160 x 252 x 434
BP96V
107.4 / 48.7 8.4 x 13.6 x 16.2 / 214 x 346 x 412
Table 15. Electrical Input
Catalog Number (UPS)
Default Input
(Voltage/Max Current)
Input Nominal Voltages Input Voltage Window at
Rated Load
SU700XLCD 120V / 6.5A
100V, 110V, 120V, 125V
100–144V
SU1000XLCD
120V / 9.0A
SU1500XLCD 120V / 12A
SU2200XLCD 120V / 16A
SU3000XLCD 120V / 24A
Nominal Frequency 50/60Hz auto-sensing
Frequency Range 40-70Hz before transfer to battery
Bypass Voltage Range
-20% / +15% of nominal value (default)
Noise Filtering Input EMC filter
Table 16. Electrical Input Connections
Catalog Number (UPS)
Input Connection Input cable
SU700XLCD
5–15P
Attached line cord 8ft / 2.4m
SU1000XLCD
SU1500XLCD
SU2200XLCD 5–20P
Attached line cord 8ft / 2.4m
SU3000XLCD L5–30P
Attached line cord 8ft / 2.4m
Table 17. Electrical output
Catalog Number (UPS)
Normal Mode
Efficiency Mode Battery Mode
Voltage Regulation
±2% ±3%
Efficiency
SU700XLCD
86% 93% 79.5%
SU1000XLCD
87% 93% 82%
SU1500XLCD
86% 93% 82%
SU2200XLCD
88% 93% 84%
SU3000XLCD
89% 93% 84%
Frequency Regulation
Sync with line ±5% of nominal line frequency (outside this
range: ±0.5% of auto-selected nominal frequency)
±0.5% of auto-selected
nominal frequency
Model Specifications
Loading ...
Loading ...