INSTALLATION - 3791477B059/A
e
positioned on the appliance.
Do not remove this plate for any reason.
The appliance must be connected to ground
using a wire that is at least 20 mm longer than
the other wires.
Terminal block connection
Arrange the cables in an orderly manner to
avoid overlapping or contact with any jumpers.
The cables must be of the correct length to
avoid build-up/twisting inside the terminal box.
The appliance can work in the following modes:
Fixed connection
Fit the power line with an all-pole circuit breaker
with a contact separation distance sufficient to
provide complete disconnection in category III
overvoltage conditions, pursuant to installation
regulations.
For the Australian/New Zealand market:
The circuit breaker incorporated in the fixed
connection must comply with AS/NZS 3000.
220-240 V 1N~
3 x 6 mm ²
three-core cable
220-240 V 2~
3 x 6 mm ²
three-core cable
220-240 V 3~
4 x 4 mm ²
four-core cable
380-415 V 2N~
4 x 4 mm ²
four-core cable
380-415 V 3N~
5 x 1.5 mm ²
five-core cable
4-zone models only
380-415 V 3N~
5 x 2.5 mm ²
five-core cable
5-zone models only
The values indicated refer to the cross-
section of the internal lead.
The power cables are sized taking into
account the coincidence factor (in
compliance with standard EN 60335-
2-6).
Always use the supplied jumper for
each connection, if any. The connection
between terminals 4 and 5 must always
be made.