TESTING AND INSPECTION
Start-up Checklist
Turn on main power to indoor and outdoor units.
Verify the system is not displaying an error code on the indoor unit or Wired Programmable
Controller display.
Press the ON button on the
Wired Programmable
Controller.
Verify the Wired Programmable Controller Controller display turns ON.
Press the Mode button to Cooling.
Adjust the room setpoint to bring the system on in cooling mode. The system should start
cooling mode within 3-5 minutes.
Verify the outdoor fan and compressor are operating.
Verify the indoor fan is operating.
Verify the indoor discharge air is cooling the room.
Press the Mode button to Heating.
Adjust the room setpoint to bring the system on in heating mode. The system should start
heating mode within 3-5 minutes.
Verify the outdoor fan and compressor are operating.
Verify the indoor fan is operating.
Verify the indoor discharge air is heating the room.
Press the OFF button on the Wired Programmable Controller.
Verify Wired Programmable Controller display turns OFF and the system shuts OFF.
Test the Drain Piping.
Verify condensate water drains smoothly. As shown in the figure, add approximately
1 quart of water slowly into the drain pan. The condensate pump should turn on and
drain the water through the condensate drain pipe to a safe location. Verify there are no
leaks
in the condensate pipe and connections.