Hoshizaki KMS2000MLJ KMS-2000MLJ 30" Serenity Series Cuber Ice Machine

Instruction Manual - Page 19

For KMS2000MLJ.

PDF File Manual, 36 pages, Read Online | Download pdf file

KMS2000MLJ photo
Loading ...
Loading ...
Loading ...
19
E. Installation of the Remote Condensing Unit
WARNING
• Installation must be performed by properly trained and EPA-certied service
personnel.
• Power supply and ground wire to the icemaker are supplied from the remote
condensing unit. For details, see "II.F. Electrical Connection."
1. Setup
1) Secure the legs to the remote condensing
unit with the 16 bolts and nuts provided.
See Fig. 13.
2) The legs have 8 mounting holes. Secure
the legs with 8 bolts (not included).
Nut
Fig. 13
Bolt with
Split Lock
Washer and
Flat Washer
2. Line Set
NOTICE
The icemaker, remote condensing unit, and line set must contain the same type
of refrigerant. Mixing of refrigerants will result in improper operation and possible
damage to equipment.
The maximum line set length is 66 feet and no refrigerant charge adjustment is necessary.
NOTICE! Do not exceed maximum line set length.
Line Set Size and Length for SRK-20J(3) Remote Condensing Units
Model
Liquid
Line
Suction
Line
Factory Line Set
Lengths (ft) Maximum Line Set Length (ft)
KMS-2000MLJ 1/2" OD 3/4" OD 25, 35, and 55 66
The maximum vertical distance between the remote condensing unit and icemaker is
33feet above or 10 feet below the icemaker. These distances are measured tting to tting.
See Fig. 14. NOTICE! Do not exceed maximum vertical distance.
• If the vertical distance between the remote condensing unit and the icemaker is greater
than 20 feet (not to exceed 33 feet), an "S" oil-trap (3/4" OD tubing) must be installed
in the suction line. The "S" oil-trap must be located halfway between the icemaker and
remote condensing unit. This ensures sufficient oil return to the compressor.
Loading ...
Loading ...
Loading ...