10
2. Remote Condensing Unit
NOTICE
• The remote condensing unit is intended for outdoor use. Normal operating ambient
temperature must be within -20°F to 122°F (-29°C to 50°C). Operation of the
remote condensing unit, for extended periods, outside of this normal temperature
range may affect icemaker performance.
• Maximum line set length is 66 feet. No refrigerant charge adjustment is necessary.
• The maximum vertical distance between the remote condensing unit and icemaker
is 33feet above or 10 feet below the icemaker. These distances are measured
tting to tting. See Fig. 1.
• If the vertical distance between the remote condensing unit and the icemaker is
greater than 20 feet (not to exceed 33 feet), an "S" oil-trap (5/8" OD copper tubing)
must be installed in the suction line. The "S" oil-trap must be located halfway
between the icemaker and remote condensing unit. This ensures sufficient oil
return to the compressor.
The remote condensing unit must be positioned in a permanent site under the following
guidelines:
• A rm and at site.
• A dry and well ventilated area with 24" (61 cm) clearance in both front and rear for proper
air circulation and ease of maintenance and/or service should they be required. See Fig. 2.
Fig. 1
Fig. 2
Min. 24" (61 cm) Clearance
Air
Air
24"
(61 cm)
24"
(61 cm)
Icemaker
Remote Condensing
Unit
Suction Line
"S" Oil-Trap
Service Loop
Max. 33 Feet
Max.
16.5
Feet
Max.
16.5
Feet
Bin
Icemaker
Service
Loop
Max. 10 Feet
Remote Condensing
Unit
Bin