TP-7092 2/2166 Section 4 Scheduled Maintenance
4.4 Air Cleaner Service
Risk of fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
WARNING
Servicing the air cleaner. A sudden backfire can cause
severe injury or death. Do not operate the generator set with
the air cleaner removed.
4.4.1 Air Cleaner, 14 kW Models
The engine has a replaceable high-density paper air
cleaner element. See Figure 4-8.
1
2
3
4
5
6
586536
1. Cover knob
2. Air cleaner cover
3. Element cover nut
4. Element cover
5. Air cleaner element
6. Air cleaner base
Figure 4-8 Air Cleaner Components
Check for a buildup of dirt and debris around the air
cleaner system. Keep this area clean. Also check for
loose or damaged components. Replace all bent or
damaged air cleaner components.
Note: Operating the engine with loose or damaged air
cleaner components could allow unfiltered air
into the engine causing premature wear and
failure.
Air Cleaner Service
Use the following procedure to replace the paper
element at the intervals specified in the service
schedule. Replace the paper element more often under
extremely dusty or dirty conditions.
1. Press the OFF button on the generator set
controller.
2. Disconnect the utility power to the generator set.
3. Disconnect the generator set engine starting
battery, negative (- ) lead first.
4. Loosen the cover retaining knob and remove the
cover.
5. Remove the element cover nut, element cover, and
the paper element.
Note: Do not wash the paper element or clean it
with pressurized air, as this will damage the
element.
6. Replace the element if it is dirty, bent, or damaged.
7. Check the air cleaner base. Make sure it is secure
and not bent or damaged. Also check the element
cover for damage and fit. Replace all damaged air
cleaner components. Remove any loose dirt or
debris from the air cleaner base. Wipe the base
carefully so that no dirt drops into the intake throat.
Check the condition of the rubber seal on the air
cleaner stud and replace the seal if necessary.
8. Reinstall the paper element, element cover,
element cover nut, and the air cleaner cover.
Secure the cover with the cover retaining knob.
9. Reconnect the utility power to the generator set.
10. Reconnect the generator set engine starting
battery, negative (- ) lead last.