22
Install an ELB in the power source.
If ELB is not used, it will cause electric shock or
fire at the worst.
The tightening torque of each screw shall be as
Keep the above tightening torque when wiring work.
Power Source Wiring is fundamental
according to this method.
NOTE:
Supply the power source of outdoor units and indoor
units respectively.
(1) Power Source Wiring:
() In the case that a conduit tube for field-
wiring is not used, fix rubber bushes
with
adhesive on the panel.
Install main switch and ELB for each system
separately. Select the high response type ELB that
is
acted
within
0.1
second.
Separate the control wiring between outdoor unit

CHV6-36URBM

CHV6-48URBM

CHV6-60URBM

Model
Power Source
200V ~ 60Hz
Distribution Box or Pull Box
Tabe 61  
follows.
M4: 0.7 to 1.0 ft.·lbs (1.0 to 1.3 N·m)
M5: 1.5 to 1.8 ft.·lbs (2.0 to 2.5 N·m)
M6: 3.0 to 3.7 ft.·lbs (4.0 to 5.0 N·m)
M8: 6.6 to 8.1 ft.·lbs (9.0 to 11.0 N·m)
M10: 13.3 to 17.0 ft.·lbs (18.0 to 23.0 N·m)
208/230V ~ 60Hz
208/230V ~ 60Hz
a
nd indoor unit more than approximately 1-3132 to 2-38 in.
(50 to 60mm) from power supply wiring. Do not use a
coaxial cable.


0


0
0
0
Ground Wiring (O.U.)
Ground Wiring (O.U.)