Tripp Lite SMART700RT1U 700VA 420W 120V Line-Interactive UPS - 4 NEMA 5-15R Outlets, Network Card Option, USB, DB9, 1U Rack/Tower

Owner's Manual for SmartPro Line-Interactive Single-Phase 1U UPS Systems with Pure Sine Wave Output Models: SMART700RT1U, SMART750RT1U, SMART1000RT1U, SMC1000RT1U, SMART1500RT1U, SMC1500RT1U - Multiple Languages - Page 30

For SMART700RT1U. Also, The document are for others Tripp Lite models: SMART750RT1U, SMART1000RT1U, SMC1000RT1U, SMART1500RT1U, SMC1500RT1U

PDF File Manual, 92 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
30
12 Technical Specifications
Model SMART700RT1U SMART750RT1U SMART1000RT1U SMC1000RT1U SMART1500RT1U SMC1500RT1U
Nominal Voltage
and Input Range
100V~, 120V~, 127V~, 80V-162V (High Sensitivity)
70V-162V (Low Sensitivity)
Nominal Input
Frequency and
Tolerance
50 Hz (-4/+20 Hz for High Sensitivity; -10/+20 Hz for Low Sensitivity)
60 Hz (-4/+10 Hz)
Nominal Output
Voltage
120V~ in Line Mode and 120V~ in Battery Mode
Nominal Output
Frequency
50 Hz (-4/+20 Hz for High Sensitivity; -10/+20 Hz for Low Sensitivity)
60 Hz (-4/+10 Hz)
Output Voltage
Regulation in Line
Mode
120V~ (-16%/+16%)
Output voltage
regulation in Battery
Mode:
120V~ (-10%/+6%)
Nominal output
power in W / VA:
420W/700VA @
120V~/127V~
350W/583VA
100V~
600W/750VA @
120V~/127V~
500W/625VA @
100V~
770W/1000VA @
120V ~/127V~
641W/833VA @
100V~
600W/1000VA @
120V ~ /127V~
500W/833VA @
100V~
1100W/1440VA @
120V ~/127V~
825W/1080VA
(100V~)
1100W/1440VA @
120V ~/127V~
825W/1083VA
(100V~)
Output Voltage
Waveform
Sinusoidal in Line Mode and in Battery Mode
Maximum Output
Current @ P.F.
5.83A @ 100V~
5.84A @ 120V~
5.52A @ 127V~
6.25A @ 100V~
6.25A @120V~
5.91A @127V~
8.33A @ 100V~
8.34A @120V~
7.88A @ 127V~
8.33A @ 100V~
8.34A @120V~
7.88A @ 127V~
10.8A @ 100V~
12A @ 120V~
11.34A @ 127V~
10.8A @ 100V~
12A @ 120V~
11.34A @ 127V~
P.F. = 0.6 P.F. = 0.8 P.F. = 0.8 P.F. = 0.6 P.F. = .76 P.F. = .76
Efficiency with
Nominal Load
98%
Maximum Operating
Altitude at 100% of
Nominal Power
3280 ft. (1000 m)
Online Overload
Capability
<120% 5 minutes; <150% 1 minute; >=150% 10 seconds
Overload Capacity
in Battery Mode
<120% 10 seconds; >=120% 1 second
Current Limitation 10A 10A 15A 15A 15A 15A
Autonomy Time at
Full Load
3 minutes @ 420W 3 minutes @600W 3 minutes @ 770W 3 minutes @ 770W
2 minutes @
1100W
2 minutes @
1100W
Battery Recharge
Time
6 hours @ recharge to 90% with 50% R-load discharging
Transfer Time 6-8 milliseconds typical (<10 milliseconds max)
Outlets
4x 5-15R outlets
with battery backup,
regulation, surge
4x 5-15R outlets
with battery backup,
regulation, surge
5x 5-15R outlets
with battery backup,
regulation and
surge
4x 5-15R outlets
with battery backup,
regulation and
surge
5x 5-15R outlets
with battery backup,
regulation and
surge
5x 5-15R outlets
with battery backup,
regulation and
surge
Maximum Input
Current
6.01A
6.01A
5.69A
6.44A
6.44A
6.09A
8.59A
8.60A
8.12A
8.59A
8.60A
8.12A
10.8A
12.0A
11.34A
10.8A
12.0A
11.34A
Loading ...