7. Installation
AC Input and Output Maximum Current & Power Cable Configuration
Note: Use copper wire with temperature resistance up to 105°C.
Small-Frame Units (30U) including Battery Module(s)
30kVA 60kVA 90kVA*
Installation Breaker Size Recommended 200A 200A 200A
Max Current (A) 57 114 171
Power and Ground Cable (mm²) 95 95 95
Fixation Torque Force (N·m) 2.26 2.26 2.26
* 90kVA without Battery Modules in Small Frame. Requires external battery installation.
Medium-Frame Units (42U) including Battery Module(s)
30kVA 60kVA 90kVA
Installation Breaker Size Recommended 250A 250A 250A
Max Current (A) 57 114 171
Power and Ground Cable (mm²) 120 120 120
Fixation Torque Force (N·m) 2.26 2.26 2.26
Large Frame (42U) without Battery Modules
30kVA 60kVA 90kVA 120kVA 150kVA 180kVA 210kVA
Installation Breaker Size Recommended 400A 400A 400A 400A 400A 400A 400A
Max Current (A) 57 114 171 228 285 342 399
Power and Ground Cable (mm²) 300 300 300 300 300 300 300
Fixation Torque Force (N·m) 2.26 2.26 2.26 2.26 2.26 2.26 2.26
DC Input Maximum Current and Power Cable Configuration
Small Frame (30U) including Battery Module(s)
Nominal Battery Voltage +/-240VDC
30kVA 60kVA 90kVA*
External Battery Breaker Recommended 100A 200A 300A
Power and Ground Cable (mm²) 25 95 150
Fixation Torque Force (N·m) 2.26 2.26 2.26
* 90kVA without Battery Modules in Small Frame. Requires external battery installation.
Medium Frame (42U) including Battery Module(s)
30kVA 60kVA 90kVA
External Battery Breaker Recommended 100A 200A 300A
Power and Ground Cable (mm²) 25 95 150
Fixation Torque Force (N·m) 2.26 2.26 2.26
Large Frame (42U) without Battery Modules
30kVA 60kVA 90kVA 120kVA 150kVA 180kVA 210kVA
External Battery Breaker Recommended 100A 200A 300A 400A 500A 600A 700A
Power and Ground Cable (mm²) 25 95 150 240 120 x 2 150 x 2 240 x 2
Fixation Torque Force (N·m) 2.26 2.26 2.26 2.26 2.26 2.26 2.26