69
FlexFit Pro
Outdoor Dip Switches
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description
OFF ---- ---- ---- ---- ---- ---- ---- Manually forced operation invalid(default)
ON ---- ---- ---- ---- ---- ---- ---- Manually forced operation valid
---- OFF ---- ---- ---- ---- ---- ---- Manually forced heating(default)
---- ON ---- ---- ---- ---- ---- ---- Manually forced cooling
---- ---- OFF ---- ---- ---- ---- ---- Normal standby cost(default)
---- ---- ON ---- ---- ---- ---- ---- Low stand by power cost
---- ---- ---- OFF ---- ---- ---- ---- Water heater or heating only
---- ---- ---- ON ---- ---- ---- ---- Unit as air conditioner (default)
---- ---- ---- ---- OFF ---- ---- ---- Central control(default)
---- ---- ---- ---- ON ---- ---- ---- BMS
---- ---- ---- ---- ---- OFF ---- ---- Refrigerant R410A(default)
---- ---- ---- ---- ---- ON ---- ---- Refrigerant R32
---- ---- ---- ---- ---- ---- OFF Defrost automatic(default)
---- ---- ---- ---- ---- ---- ON Defrost by time
---- ---- ---- ---- ---- ---- ---- OFF Not for base station
---- ---- ---- ---- ---- ---- ---- ON Base station application(default)
SW8: Dip switch setting
SW6 (1-ON, 0-OFF) Unit
address
for central
control
SW6-1 SW6-2 SW6-3 SW6-4 SW6-5 SW6-6 SW6-7 SW6-8
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 0 2
0 0 0 0 0 0 1 1 3
0 0 0 0 0 1 0 0 4
0 0 0 0 0 1 0 1 5
0 0 0 0 0 1 1 0 6
0 0 0 0 0 1 1 1 7
---- ---- ---- ---- ---- ---- ---- ---- ----
1 1 1 1 1 1 1 1 255
SW8 Denation
01U24LP2VHA
21U36LP2VHA
51U48LP2VHA