Tripp Lite PDUV15 1.4kW Single-Phase 120V Basic PDU, 14 NEMA 5-15R Outlets, NEMA 5-15P Input, 15 ft. 4.57 m Cord, 0U Vertical

Owner's Manual - Page 2

For PDUV15. Also, The document are for others Tripp Lite models: PDUMV15, PDUMV20, PDUV20

PDF File Manual, 12 pages, Read Online | Download pdf file

PDUV15 photo
Loading ...
2
1B
1A
3
4
5
PDUMV15 and
PDUV15
PDUV20 and PDUMV20
PDUV20 and PDUMV20
1C
3
2
Installation
1A
Zero U Rack Configuration.Attachthethreemountingclips
suppliedwiththePDUtotherackenclosureusingtheincluded
hardware.Themountingclipsshouldbeattachedalonga
verticalplaneatequidistantpointswhichroughlycorrespond
tothecenterandendsofthePDU.Theexactmounting
configurationmayvarydependingontherackandenclosure.If
possible,usepre-existingmountingpointswithinthe
enclosure.
1B
Wall or Under-Counter Configuration.Attachthethree
mountingclipssuppliedwiththePDUtoawallorsimilarflat,
securesurfaceusingtheincludedhardware.Themounting
clipsshouldbeattachedalongaverticalorhorizontalplaneat
equidistantpointswhichroughlycorrespondtothecenterand
endsofthePDU.Ifpossible,usepre-existingmountingpoints.
WARNING: Do not attempt to mount the PDU with the
outlets facing downward; the mounting clips are not
designed to support the weight of the PDU in that manner.
1C
Zero U Rack Configuration (Mounting Buttons). Attachthe
includedmountingbuttonstothePDU.PositionthePDUas
desiredintherackenclosure,alignthebuttonswiththerack
mountingslots,andslidethePDUintoposition.
Note: Regardless of configuration, the user must determine the
fitness of hardware and procedures before mounting. The PDU
and included hardware are designed for common rack and rack
enclosure types and may not be appropriate for all
applications.
2
Attach the PDU to the mounting clips.Usinganassistant,
placearearcornerofthePDUontheinsideedgeofthe
mountingclips,pivotthePDUtowardthealternateinsideedge
andsnapintoplace.
3
Attach the input plug of the PDU to a grounded outlet.
Inserttheplugdirectlyintoagroundedoutletthatdoesnot
shareacircuitwithaheavyelectricalload(suchasanair
conditionerorrefrigerator).
4
Attach equipment to the PDU.Donotexceedtheloadrating
ofthePDU.ThetotalelectricalcurrentusedbythePDUwill
bedisplayedonthedigitalmeterinamperes.
5
Optional Installation (Models PDUV20 & PDUMV20).The
PDUincludesanadapterthatconvertstheL5-20Pinputplug
toa5-20Pinputplug.Theadapterisoptional;thePDUwill
workproperlywithoutconnectingtheadapter.