English
15
20.0 Priming the pump / manual dosing
‘Pump Ovrde’ allows you to ll the inlet and outlet tubes with dosing solution before
rst use (removing any air in the tubes), and to manually dose the tank if required.
Always ensure the inlet dosing tube reaches to the bottom of the pH stock solution
container. Ensure the outlet dosing tube is above the highest water line so that pH
stock solution drips into the tank/reservoir.
NOTE: If priming the pump, temporarily move the outlet dosing tube so it runs into the
pH stock solution container (if not already xed in place). This will avoid adding pH stock
solution to your tank/reservoir unintentionally.
Press ‘menu’.
Press ‘’ to nd ‘Pump Ovrde’. Press ‘enter’ to select.
Press ‘’ to manually operate the pump. Release
the button to stop the pump when you see the stock
solution begins to drip from the outlet dosing tube
into the tank. Press ‘menu’ to exit.
If the outlet dosing tube was temporarily moved in step 1,
place it back, so pH solution will drip into the tank/reservoir.
CHANGING STOCK SOLUTION: If you are changing from pH Up to pH Down, or vice versa, you
MUST ush the dosing tube with water FIRST to avoid a chemical reaction in the tube.
1
2
3
21.0 Set the mode
Use ‘mode’ to select the pH controller function. ‘Monitor’ mode shows the current
solution pH reading. It is the factory default setting. ‘Control’ mode allows the pH
controller to dose pH stock solution to the set values. Dosing will NOT occur when:
The pH controller is in ‘monitor’ mode
The pH controller is in an alarm state
If the pH controller senses dosing is not having an effect on the system (after
15 dose cycles)
The solution temperature is above 50 °C / 122 °F, or below 0 °C / 32 °F
To set ‘monitor’ mode:
Press ‘menu’.
Press ‘’ to select ‘Mode’. Press ‘enter’.
Press ‘’ or ‘’ to select ‘monitor’, then press
‘enter’ to save the mode. Press ‘menu’ to exit.
To set ‘control’ mode:
Press ‘menu’.
Press ‘’ to select ‘Mode’. Press ‘enter’.
Press ‘’ or ‘’ to select ‘control’, then press
‘enter’ to save the mode. Press ‘menu’ to exit.
The display will show a countdown before the pump
can start. This is the ‘Pump start delay’, which is set
to these times: 15Sec when exiting the menu with
control mode enabled; 60Sec if power off/on occurs.
1
1
2
2
3
3