The MaxiCharger AC Wallbox Home can also be wired for higher amperages. Consult
all applicable codes for breaker and wire sizing requirements. The field-wiring terminal
is rated to 105 °C and accepts a maximum of 6 AWG (16 mm²) wire.
Circuit Rating
Max Load
Estimated Range
per Hour
NEMA Plug-in
Hardwire
70 A 50 A Up to 45 miles/72 km
No Yes
2. For NEMA plug-in installation, determine the purchased plug type, either a NEMA 6-50
or 14-50 plug.
3. Ensure the electrical panel supports a 240 V dedicated circuit with a new, dedicated, and
non-GFCI two-pole circuit breaker, in accordance with local codes and ordinances.
4. The recommended installation height is between 51 and 67 inches (1300 and 1700 mm).
For NEMA plug-in installation, the NEMA outlet should be located at least 18 inches (460
mm) from the ground adjacent to the position where the charger will be mounted.
5. The NEMA plug-in version requires an outdoor-rated and weather-resistant electrical
outlet, and the hardwire version requires and outdoor-rated and weather-resistant
hardwired installation.