Description Green “PROTECTED” LED Alarm
Line Mode On Off
Battery Mode Flashes every 10 seconds Off
Battery Low Glows solid every 1 second Sounds every 1 second
Line Mode Overload Alert* On Sounds every 0.5 second
Battery Mode Overload Alert** Flashes Sounds every 0.5 second
Line Mode Overload Fault* Off Continuously sounds
Battery Mode Overload Fault** Off UPS will shut down
Replace Battery On Sounds every 1 minute
Fault Condition Off Continuously sounds
*Line Mode Overload Alert Condition - 110%±10%, goes to fault after 5 minutes; Overload Fault
Condition - 120%±10%, goes to fault immediately
**Battery Mode Overload Alert Condition - 110%±10%, shuts down in 5 seconds; Battery Mode Overload
Fault Condition - 120%±10%, shuts down immediately