Tripp Lite SMART1000RM1U SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, Network Card Option, USB, DB9, 6 Outlets, 1U Rack/Vertical

Owner's Manual - Page 12

For SMART1000RM1U. Also, The document are for others Tripp Lite models: AGSM5060, AGSM8269, AG-0011, AG-0006, AG-0007

PDF File Manual, 48 pages, Read Online | Download pdf file

SMART1000RM1U photo
Loading ...
Loading ...
Loading ...
12
Charge Rate
Setting (when
External Batteries
are connected)
Charge Rate
Setting (when
External Batteries
are not connected)
Basic Operation
Accessory Slot: remove the small cover panel from this slot to install
optional accessories to remotely monitor and control your UPS. Refer to
your accessory’s manual for installation instructions. Visit www.tripplite.com
for compatible SNMP, network management and connectivity products.
Power Sensitivity Adjustment: this dial is normally set fully counter-
clockwise, which enables the UPS to provide maximum protection against
waveform distortions in its AC input. When such distortion occurs, the UPS
will normally switch to providing sine wave power from its battery reserves
for as long as the distortion is present. In areas with poor utility power or
where the UPS input power comes from a backup generator, chronic
waveform distortion could cause the UPS to switch to battery too frequently,
draining its battery reserves. You may be able to reduce how often your UPS
switches to battery due to moderate waveform distortion by experimenting
with different settings for this dial. As the dial is turned clockwise, the UPS
becomes more tolerant of variations in its input power’s AC waveform.
Note: The further the dial is adjusted clockwise, the greater the degree of waveform
distortion the UPS will allow to pass to connected equipment. When experimenting
with different settings for this dial, operate connected equipment in a safe test mode
so that the effect on the equipment of any waveform distortions in the UPS output can
be evaluated without disrupting critical operations.
External Battery Connector (Select Models Only): use to connect
Tripp Lite external battery packs for additional runtime. Visit www.tripplite.
com/products/battery-finder/ to find a compatible battery pack. Refer to
instructions available with the battery pack for complete connection
information and safety warnings.
Battery Charge Level Switch (Select Models Only):
controls the UPS system’s battery charge rate. If you
connect any external batteries, set the Battery Charge
Level Switch to the down position. This will increase your
UPS charger output so the additional batteries charge
faster.
Note: the switch to the right of the Battery Charge Level Switch is
inactive and will not affect UPS operation regardless of its position.
CAUTION! DO NOT set the Battery Charge Level Switch
to the down position without an external battery
connected. There is a risk of damaging the UPS’s
internal battery system.
Input Breaker(s) (all models): protect your electrical circuit from
overcurrent draw from the UPS load. If these breakers trip, remove some of
the load, then reset them by pressing the breaker(s) in.
Output Breaker (select models): your UPS features one or more breakers
that protect your UPS from output overload. If one or more breakers trip,
remove some of the load on the circuit(s), then reset them by pressing the
breaker switch(es) in.
Ground Screw: use this to connect any equipment that requires a chassis
ground.
17-06-249-932406.indb 12 6/20/2017 4:49:19 PM
Loading ...
Loading ...
Loading ...