Tripp Lite 9PX1500GRT-L Eaton 9PX 1500VA 1350W 208V Online Double-Conversion UPS - C14 input, 8 C13, Outlets, Lithium-ion Battery, Cybersecure Network Card Option, 2U Rack/Tower

Users Guide - Page 27

For 9PX1500GRT-L. Also, The document are for others Tripp Lite models: 9PX1500RT-L, 9PX2200RT-L, 9PX3000RT-L, 9PX2200GRT-L, 9PX3000GRT-L, 9PXEBM48RT-L, 9PXEBM72RT-L

PDF File Manual, 52 pages, Read Online | Download pdf file

9PX1500GRT-L photo
Loading ...
Loading ...
Loading ...
Eaton 9PX Lithium-Ion P-164001006—Rev 01 21
33..99 CCoonnnneeccttiioonn wwiitthh aa HHoottsswwaapp MMBBPP MMoodduullee (( OOppttiioonnaall AAcccceessssoorryy))
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected
loads.
9PX 2000RT-L
MBP-120
LOAD
15
28
1 82 43
5 6
9 1011
7
29
33 34 35 36
9PX 3000RT-L
MBP-130
LOAD
15
28
1 82 43
5 6
9 1011
7
29
33 34 35 36
1. Connect the input
36
on the
HotSwap MBP module to the
AC-power source.
2. Connect the UPS input cable
1
to
the “UPS Input socket”
35
on the
HotSwap MBP module.
3. Connect the UPS outlet
5
to the
“UPS Output”
34
on the HotSwap
MBP module (using the cable
28
supplied for G models).
These cables and the connectors
are marked in red.
4. Connect the equipment to the
outlets
29
on the HotSwap MBP
module. These outlets differ,
depending on the version of the
HotSwap MBP module.
Caution: when using HotSwap
MBP, do not use UPS outlets to
directly power equipment. As
operating the bypass switch
33
will cut supply voltage to the
equipment.
* 9PX 1500RT-L: To connect to MBP-115,
follow the same procedure as for the
9PX 2000RT / 9PX 3000RT.
Connection with a Hotswap MBP Module ( Optional Accessory)
Loading ...
Loading ...