Eaton 9PX Lithium-Ion P-164001006—Rev 01 9
Table 6. User Settings (Continued)
Submenu
Available settings Default settings
LCD
Modify LCD screen brightness and
contrast to be adapted to room light
conditions.
Audible alarm
Mode: [Enabled] [Disabled on battery]
[Always disabled] Enable or disable
the buzzer if an alarm occurs. Level:
[High] [Low]
[Enabled] [High]
Protected
access
[Enabled] [Disabled] Password is: 0577 [Disabled]
In/Out settings
Output voltage
100V] [110V] [120V] [125V]
[200V] [208V] [220V] [230V] [240V]
[120V]
[208V]
Output
frequency
Mode: [Normal] [Converter] [Marine]
Frequency can be changed in
Frequency [Converter] mode In [Marine]
mode output frequency follows input
frequency
[Normal]
Output mode
Mode: [Industrial] [IT] [Custom]
Overload: [Inv>Stop] [Inv>BP]
[Inv>BP>Inv]
Short-circuit: [Inv>Stop] [Inv>BP]
[Inv>BP>Inv]
[IT] [Inv>BP>Inv] [Inv>Stop]
Input volt
hysteresis
Sets input voltage hysteresis from [1]
to |10V]
[10V]
High Efficiency
mode
[Enabled] [Disabled] Power the output
from Bypass for high efficiency
[Disabled]
Bypass settings
[Volt low]
[Volt high]
[Qualify]
[Hz synch]
[Unsynch]
[80V] LV; [160V] HV;
[144V] LV; [276V] HV;
[In spec];
[5%];
[Half cycle]
Load segments
[Auto start delay]
[Auto shutdown delay]
UPS: [0s]; Group1: [3s]; Group2: [6s] UPS:
[Disabled];
Group1: [Disabled]; Group2: [Disabled]
Overload
prealarm
[10%] [102%] Load % when
overload alarm occurs
[102%]
On/Off Settings
Start/Restart
[Cold start] [Auto restart] [Auto start]
[Start on bypass]
[Cold start] [Auto restart] are Enabled
[Auto start] [Start on bypass] are Disabled
Forced reboot
[Enabled] [Disabled]
[Timer] [10s] [180s]
When mains recover during a
shutdown sequence: If set to Enabled,
shutdown sequence will complete and
wait 10 seconds prior to restart, If set
[Enabled]
[10s]
User Settings