Page 11
VIII / Utilizing your KwiKool System
In contrast to conventional air conditioners, which circulate air conditioning capacity evenly
to an entire floor, KwiKool systems are designed for cooling an area with a high concentra-
tion of heat load, usually from electrical or computer equipment. Understanding the capabili-
ties of your KwiKool can help you avoid problems. For example, if you add heat-generating
equipment to the room after purchasing a KwiKool system, you may be short of the
necessary cooling capacity. Your KwiKool system offers an effective affordable solution for
many applications. It can also provide spot cooling for workers or process cooling within a
large space without the use of condenser ducting, such as a warehouse factory, or produc-
tion areas. If the system is used in this manner, the cold air supply must be within 5 feet of
the person or equipment being cooled, since the hot ambient air will mix with the cool air
very quickly. Your KwiKool system is specifically designed to adapt to today’s high tech
environments such as telecommunication or computer rooms and is equipped with the
necessary controls to maintain those special environments. Call your nearest KwiKool
Distributor or 1-800-594-5665 for help or for questions about other applications.
VII / Maintenance
Air Filters - Your KwiKool unit comes from the factory with filters installed on the
evaporator inlet to prevent dust and debris from entering the system and circulating in
the conditioned space, factory installed filters are a disposable type and must be
periodically checked and replaced based on the air quality of your conditioned space.
Failure to maintain the filters will cause restricted air flow and low overall unit
performance. The air filter is located on the front of your KwiKool unit below the
control, release the 2 slotted fasteners on the access door to open.
Conditioned Air Supply Drive Belts - Your KwiKool KIB120 models moves air
over the evaporator coil to remove heat and moisture from the conditioned space by
way of a motor attached to a blower wheel, this wheel turns by way of a pulley and belt
system. Inspect/adjust these belts every 60 days of operation, replace as needed.
Failure to maintain the drive belts will cause low performance, coil freezing or in
extreme cases damage to the blower/motor in the event of a belt breaking. Located in
the left side evaporator access door as you face the control panel. When adjusting the
belts, adjust them from the base of the motor. Do NOT adjust the sheave (pulley).
B.
A.
Positioning of Unit - Do not place your KwiKool unit in direct sunlight, The unit
should be positioned so that the output of the unit can be focused as close to the heat
generating equipment as possible with the front grill fully exposed. Do not block the
front of the unit, since this will cause a restriction in the airflow and can cause low
performance and/or evaporator coil freezing.