List of event codes
Information – 194
61FWarningBattery State Of Charge below
limit
Battery State Of Charge OK-
620WarningBattery State Of Health below limitBattery State Of Health OKCheck battery
628WarningBattery voltage low warningBattery voltage OKCheck battery
62AWarningBattery voltage high warningBattery voltage OKCheck battery
62CWarningBatterycharge current low
warning
Batterycharge current OKCheck battery
62EWarningBatterycharge current high
warning
Batterycharge current OKCheck battery
630WarningBattery discharge current low
warning
Battery discharge current OKCheck battery
632WarningBattery discharge current high
warning
Battery discharge current OKCheck battery
634WarningBattery temperature low warningBattery temperature OKCheck battery
636WarningBatterytemperature high warningBatterytemperature OKCheck battery
638WarningBattery BMS failureBattery BMS OKCheck battery
639WarningBattery temperature unbalancedBatterytemperature OKCheck battery
63DWarningBattery warningBattery OKCheck battery
700WarningInverter limitationNo current limitationReduce output load
701WarningInverter fuse faultInverter fuse OKService required
70AWarningInverter thermal overloadNo power overloadReduce output load
70CWarningInverter voltage too lowInverter voltage OKService required
70DWarningInverter voltage too highInverter voltage OKService required
801WarningLoad not poweredLoad powered-
803WarningOutput breaker openOutput breaker closed-
806WarningEmergency power OFFNo emergency OFF-
808WarningPower overloadNo power overloadReduce output load
80DWarningInternal configuration failureInternal configuration OKService required
80EWarningOverload pre-alarmNo overload pre-alarmReduce output load
810WarningOverload alarmNo overloadReduce output load
814WarningFirmware watchdog resetFirmware watchdog OKService required
816WarningCompatibility failureCompatibility OKService required
817WarningOutput over currentNo output over currentReduce output load
818WarningOutput frequency out of rangeOutput frequency in rangeService required