Tripp Lite by Eaton SmartOnline Series User Guide 614-21325—Rev 01 45
Table 15. Electrical Input Connections
Catalog Number (UPS)
Input Connection Input cable
SU750RTXLCD2U / SU750RTXLCD2UN
5–15P
Attached line cord 8ft / 2.4mSU1000RTXLCD2U / SU1000RTXLCD2UN
SU1500RTXLCD2U / SU1500RTXLCDN
SU2200RTXLCD2U / SU2200RTXLCDN
5–20P
Attached line cord 8ft / 2.4m
SU3000RTXLCD2U / SU3000RTXLCD2UN
L5–30P
Attached line cord 8ft / 2.4m
SUINT1000LCD2U
IEC-C14
6ft / 1.8m
SUINT1500LCD2U
SUINT2200LCD2U
IEC-C20 L6-20P to C19 jumper provided
6ft / 1.8m
SUINT3000LCD2U
Table 16. Electrical Output
All Models Normal Mode Efficiency Mode Battery Mode
Voltage Regulation ±1% ±2%
Efficiency
89.9% for 750 LV models
90.3% for 1.K LV models
90.2% for 1K SUINT models
90% for 1.5K LV models
91% for 1.5K SUINT models
91.4% for 2K LV models
93% for 2K SUINT models
94% for 3K SUINT models
95.3% for 750 LV models
95.8% for 1K LV models
96% for 1K SUINT models
95.8% for 1.5K LV models
96.5% for 1.5K SUINT models
96.8% for 2K LV models
98% for 2K SUINT models
97.2% for 3K LV models
98% for 3K SUINT models
83% for 750 LV models
83% for 1K LV models
87.5% for 1K SUINT models
84% for 1.5K LV models
87.5% for 1.5K SUINTmodels
86% for 2K LV models
90% for 2K SUINT models
86% for 3K LV models
89% for 3K SUINT models
Frequency Regulation
Sync with line ±5% of nominal line frequency (outside this
range: ±0.5% of auto-selected nominal frequency)
±0.5% of auto-selected
nominal frequency
Nominal Output
[100V] [110V] [120V] [125V] (LV models)
[200V] [208V] [220V] [230V] [240V] (SUINT models)
Frequency 50 or 60 Hz, autosensing follows the input frequency
Output Overload
Online mode:
102%~130% :12s
130%~150% :2s
>150% :shutdown after 300ms
Percent is based on nominal Watt/VA.
Transfer behavior can change (see output mode setting on page 14)
Battery mode:
102%~130% :12s
>130% :2s
Overload warning then transfer to stop output
Output Overload ( Bypass
Mode )
102%~110% :Overload warning
110%~130% :shutdown after 5mins
130%~150% :shutdown after 15s
Model Specifications