● Install an ELB in the power source.
If ELB is not used, it will cause electric shock or
fire at the worst.
● The tightening torque of each screw shall be as
Keep the above tightening torque when wiring work.
Power Source Wiring is fundamental
according to this method.
NOTE:
Supply the power source of outdoor units and indoor
units respectively.
(1) Power Source Wiring:
() In the case that a conduit tube for field-
wiring is not used, fix rubber bushes
with
adhesive on the panel.
● Install main switch and ELB for each system
separately. Select the high response type ELB that
is
acted
within
0.1
second.
● Separate the control wiring between outdoor unit
CHV6-36URBM
CHV6-48URBM
CHV6-60URBM
Model
Power Source
200V ~ 60Hz
Distribution Box or Pull Box
Tabe 61
follows.
M4: 0.7 to 1.0 ft.·lbs (1.0 to 1.3 N·m)
M5: 1.5 to 1.8 ft.·lbs (2.0 to 2.5 N·m)
M6: 3.0 to 3.7 ft.·lbs (4.0 to 5.0 N·m)
M8: 6.6 to 8.1 ft.·lbs (9.0 to 11.0 N·m)
M10: 13.3 to 17.0 ft.·lbs (18.0 to 23.0 N·m)
208/230V ~ 60Hz
208/230V ~ 60Hz
a
nd indoor unit more than approximately 1-3132 to 2-38 in.
(50 to 60mm) from power supply wiring. Do not use a
coaxial cable.
0
0
0
0
Ground Wiring (O.U.)
Ground Wiring (O.U.)